Cooling Load Calculation
Cooling Load Calculation
Cooling Load Calculation
Estmated By
Date
Coustomer
Location
Room
Classification
AHU Tag No SYSTEM-2
Item Sun gain Factor
Solar gain glass
North 0.0 39 0.56
South 0.0 14 0.56
West 0.0 158 0.56
East 0.0 158 0.56
NW 0.0 148 0.56
NE 0.0 148 0.56
SW 0.0 66 0.56
SE 0.0 66 0.56
Solar and trans gain-walls&roof 0.36
North 2754.6 12.0 0.37
South 2754.6 26.0 0.37
West 3701.4 41.0 0.37
East 3701.4 31.0 0.37
NW 0.0 32.0 0.37
NE 0.0 24.0 0.37
SW 0.0 36.0 0.37
SE 0.0 28.0 0.37
Roof -Sun 14805.8 40.0 0.48
Roof -Sun-Insulated 40.0 0.20
Roof -Shaded 17.0 0.48
Transmission gain-except walls & roof
All glass 0.0 20.0 1.13
Partition 0.0 15.0 0.36
Ceiling 15.0 0.36
Floor 14805.8 15.0 0.42
Infiltration and Outside air
Infiltration 20.0 1.08
Outsideair 3000 20.0 1.08 0.10
Internal Heat
People 200 345 0
Lights 14806 1.5 3.413
Equipment 100.00 1 3413
Appliances 1 3413
Coffe Urn 0
Food Warmer 0
0 0
Motor BKW 0.00 1 3413
Room sensible heat-sub total
2%Duct leakage& 2%R.A.Heat Regain + 4%Safety 10%
Room Sensible Heat Total
Room Latent Heat
Infiltration
outsideair 3000 73.5 0.68 0.10
People 200 435
Appilances 1 3413
Coffe Urn 0
Food Warmer 0
0 0
Vap.Trans 33313 0.029
Room Latent Heat Sub-Total
Duct leakage& R.A.Heat Regain + Safety 10%
Room Latent Heat Total
Room Total Heat (Sensible + Latent)
Outside Air Heat
air qty temp diff const 1 - bf
Sensible 3000 20.0 1.08 0.90
hum diff const
Latent 3000 73.5 0.68 0.90
Grand Total Heat SubTotal
Heat gain% +leak gain%+ hp pump%+dehumpiplos% 10%
Re- heat
GRAND TOTAL HEAT
HP & tons 167.1371545399
Sensible heat factor
Indicated adp 'f
Selected adp 'F
Dehumidifier rise (1-bf)*(rm temp -adp)
Dehumidified air qty (Cfm) S.heat/(1.08*deh.rise)
318.15
340.58
U Factor
Wall
Partition
Glass
ying Heat Load Estimate for SUMMER
CONDITION DB 'F WB 'F RH
OUTSIDE 95.0 81.0
ROOM 75.0 50%
DIFFERENCE 20.0
JULY & MAY 10DEG
GLASS, WALL & PARTITION AREAS (ft2)
GLASS WALLS PARTNS
Btu/hr NORTH 2754.6
SOUTH 2754.6
- WEST 3701.4
EAST 3701.4
NW 0.0
NE 0.0
- SW 0.0
- SE
- OTHER DATA TO BE FILLED 0.0
- AREA 14,805.76 sft The ADP Table
ROOF HEIGHT 13 ft FOR 75.0 & 50%RH
12,230 FALSE CEILING HT. 26 ft SHR
26,499 NO OF F.A.CHANGES 15 PER HR. 1
56,151 NO. OF PEOPLE 200 0.03 0.92
42,456 Steam 0 0.84
- Brewer 0 0.78
- 0 0.74
- 0 0.71
- LIGHTING LOAD 1.5 W/S. FT 0.69
284,271 EQUIPMENT LOAD 100.0 KW 0.66
- DIVERSITY FACTOR 1 0.64
- SH PER PERSON 345 Btu/hr
LH PER PERSON 435 Btu/hr
BPF 0.1
- CFM/PERSON 10
- EXHAUST 0
94,165 FLOOR GAIN 0 (1 if fl. gain exists else 0)
ROOF(0)/CEILING(1) 1
- ROOF (1 if Roof provided Insulation else 0)
6,480 PARTITIONS (1 if Mod.Partitions exists else 0)
CEILING 14806 (1 if Mod.Ceiling Panels exists else 0)
69,000 PRE-COOLING COIL 0 (1 if Pre-cooling/TFA exists else 0)
75,798 ADP&SHR 0 (1 if ADP & SHR revised else 0)
341,300 Motor bkw IF ADP & SHR REVISED,CONSIDER FOL
- SHR 0.85 REV. ESHR
ADP 49.00 REV. ADP
- TR 133.71 REV. TR
- Dehumd. CFM 42539 REV. AIR QTY CFM
- Reheat,KW N/A RE- HEAT IN KWTO INCREASE ADP
1,008,349
66,705 FRESH AIR REQUIREMENT
1,075,054 NOS CFM/PER ACH
PEOPLE 200 15
- EXHAUST
14,996 NO. OF A/CHANGES
87,000 TOTAL FRESH AIR
- Ventilation cfm/ft2 14806 0.2
PRE-COOLING COIL
- DB 'F WB 'F RH
- LEV. COND 56.0 55.9 99.5
71,016 INSIDE 69.0 58.9 1
173,012
17,301 DIFF. -13.0
190,314
1,265,367 1. SUPPLY AIR TEMP. ( ROOM O/L AIR)
Trm-( RSH/(1.08 x (De. CFM+CFMoa))
* If above is too high. Determine supply CFM
58,320 for desired diff. By supply air qty. formula
2. ENTERING DRY BULB TEMPERATURE
134,964 ( CFM oa x Toa)+(CFMra X Trm)/CFMsa)
1,458,652 3. ENTERING AIR MOISTURE CONTENT
145,865 (CFM oa*Woa+CFM ra*Wrm)/CFM da
N/A 4. LEAVING DRY BULB TEMPERATURE
1,604,517 ( Tadp + (BF(Tedb - T adp)))
133.71 5. SUPPLY AIR CFM
0.85 ( RSH/1.08 X (Trm-Tsa)
49 From psychrometric chart T ewb =
51 T lwb =
23 # when bypassing a mixture of OA & RA use supply CFM, when
42,539 bypassing RA only, use deh. CFM
TH GR/LB
138.4
64.9
0.0 73.5
U' FACTORS
WALL 0.360 11.4 34.2
GLASS 0.560 15.96 13.68
ALL GLASS 1.130 27.36 47.88
PARTITION 0.360
M.PARTN 0.150
CEILING 0.424
M.CLG.PANL 0.150
FLOOR 0.424
ROOF 0.510
sts else 0)
NET (CFM)
3000
0
0
3000
G COIL
TH GR/LB
23.8 66.7
25.6 58.2
-1.8 8.5
53.14 0F
23.40
76.32 0F
79.23 Gr./lb
51.32 0F
45539.32 0F
F
0
F
0
Cooling and Dehumidifying Heat Load Est
Estmated By
Date
Coustomer
Location
Room
Classification
AHU Tag No SYSTEM-2
Item Sun gain Factor
Solar gain glass April
North 0.0 39 13 0.56
South 0.0 14 14 0.56
West 0.0 158 163 0.56
East 0.0 158 163 0.56
NW 0.0 148 130 0.56
NE 0.0 148 130 0.56
SW 0.0 66 94 0.56
SE 0.0 66 94 0.56
Solar and trans gain-walls&roof 0.36
North 0.0 12.0 0.37
South 0.0 26.0 0.37
West 0.0 41.0 0.37
East 0.0 31.0 0.37
NW 0.0 32.0 0.37
NE 0.0 24.0 0.37
SW 0.0 36.0 0.37
SE 0.0 28.0 0.37
Roof -Sun 40.0 0.48
Roof -Sun-Insulated 295.9 40.0 0.20
Roof -Shaded 17.0 0.48
Transmission gain-except walls & roof
All glass 0.0 20.0 1.13
Partition 677.9 15.0 0.36
Ceiling 295.9 15.0 0.36
Floor 295.9 15.0 0.42
Infiltration and Outside air
Infiltration 20.0 1.08
Outsideair 0 20.0 1.08
Internal Heat
People 9 255 0
Lights 296 1.5 3.413
Equipment 0.25 1 3413
Appliances 1 3413
Coffe Urn 0
Food Warmer 0
0 0
Motor BKW 0.00 1 3413
Room sensible heat-sub total
2%Duct leakage& 2%R.A.Heat Regain + 4%Safety
Room Sensible Heat Total
Room Latent Heat
Infiltration
outsideair 0 73.5 0.68
People 9 255
Appilances 1.00 1 3413
Coffe Urn 0
Food Warmer 0
0 0
Vap.Trans 592 0.029
Room Latent Heat Sub-Total
Duct leakage& R.A.Heat Regain + Safety
Room Latent Heat Total
Room Total Heat (Sensible + Latent)
Outside Air Heat
air qty temp diff const
Sensible 0 20.0 1.08
hum diff const
Latent 0 73.5 0.68
Grand Total Heat SubTotal
Heat gain% +leak gain%+ hp pump%+dehumpiplos%
Re- heat
GRAND TOTAL HEAT
HP & tons
Sensible heat factor
Indicated adp 'f
Selected adp 'F
Dehumidifier rise (1-bf)*(rm temp -adp)
Dehumidified air qty (Cfm) S.heat/(1.08*deh.rise)
midifying Heat Load Estimate for SUMMER
CONDITION DB 'F WB 'F
OUTSIDE 95.0 81.0
ROOM 75.0
DIFFERENCE 20.0
JULY & MAY 10DEG
GLASS, WALL & PARTITION AREAS (ft2)
GLASS WALLS
Btu/hr NORTH
SOUTH
- WEST
- EAST
- NW 0.0
- NE 0.0
- SW 0.0
- SE
- OTHER DATA TO BE FILLED
- AREA 295.90 sft
ROOF HEIGHT 13 ft
- FALSE CEILING HT. 13 ft
- NO OF F.A.CHANGES 15 PER HR.
- NO. OF PEOPLE 9 0.03
- Steam 0
- Brewer 0
- 0
- 0
- LIGHTING LOAD 1.5 W/S. FT
- EQUIPMENT LOAD 1.0 KW
2,367 DIVERSITY FACTOR 1
- SH PER PERSON 255 Btu/hr
LH PER PERSON 255 Btu/hr
- BPF 0.1
3,661 CFM/PERSON 10
EXHAUST 0
1,882 FLOOR GAIN 0 (1 if fl. gain exists else 0)
ROOF(0)/CEILING(1) 1
- ROOF (1 if Roof provided Insulation
0.10 - PARTITIONS (1 if Mod.Partitions exists else
CEILING 296 (1 if Mod.Ceiling Panels exist
2,264 PRE-COOLING COIL 0 (1 if Pre-cooling/TFA exists el
1,515 ADP&SHR 0 (1 if ADP & SHR revised else
853 Motor bkw IF ADP & SHR REVIS
- SHR 0.64 REV. ESHR
ADP 49.00 REV. ADP
- TR 1.96 REV. TR
- Dehumd. CFM 543 REV. AIR QTY CFM
- Reheat,KW N/A RE- HEAT IN KWTO INCREASE
12,541
10% 1,169 FRESH AIR REQUIREMENT
13,710 NOS CFM/PER
PEOPLE 9
- EXHAUST
0.10 - NO. OF A/CHANGES
2,264 TOTAL FRESH AIR
3,413 Ventilation cfm/ft2 296 0.2
PRE-COOLING COIL
- DB 'F WB 'F
- LEV. COND 56.0 55.9
1,262 INSIDE 69.0 58.9
6,938
10% 694 DIFF. -13.0
7,632
21,342 1. SUPPLY AIR TEMP. ( ROOM O/L AIR)
Trm-( RSH/(1.08 x (De. CFM+CFMoa))
1 - bf * If above is too high. Determine supply CFM
0.90 - for desired diff. By supply air qty. formula
2. ENTERING DRY BULB TEMPERATURE
0.90 - ( CFM oa x Toa)+(CFMra X Trm)/CFMsa)
21,342 3. ENTERING AIR MOISTURE CONTENT
10% 2,134 (CFM oa*Woa+CFM ra*Wrm)/CFM da
N/A 4. LEAVING DRY BULB TEMPERATURE
23,477 ( Tadp + (BF(Tedb - T adp)))
2.44547065 1.96 5. SUPPLY AIR CFM
0.64 ( RSH/1.08 X (Trm-Tsa)
49 From psychrometric chart
51
23 # when bypassing a mixture of OA & RA use supply CFM, when
543 bypassing RA only, use deh. CFM
277.30
277.30
RH TH GR/LB
138.4
50% 64.9
0.0 73.5
UIREMENT
ACH NET (CFM)
0
0
0
0
E-COOLING COIL
RH TH GR/LB
99.5 23.8 66.7
1 25.6 58.2
-1.8 8.5
51.60 0F
23.40
75.00 0F
64.89 Gr./lb
51.34 0F
542.51 0F
T ewb = F
0
T lwb = F
0
343.73
357.86
ying Heat Load Estimate for SUMMER
CONDITION DB 'F WB 'F RH
OUTSIDE 95.0 81.0
ROOM 75.0 50%
DIFFERENCE 20.0
JULY & MAY 10DEG
GLASS, WALL & PARTITION AREAS (ft2)
GLASS WALLS PARTNS
Btu/hr NORTH 161.4
SOUTH 161.4
- WEST 129.1
EAST 129.1
NW 0.0
NE 0.0
- SW 0.0
- SE
- OTHER DATA TO BE FILLED 581.0
- AREA 215.20 sft The ADP Table
ROOF HEIGHT 13 ft FOR 75.0 & 50%RH
- FALSE CEILING HT. 13 ft SHR
- NO OF F.A.CHANGES 15 PER HR. 1
- NO. OF PEOPLE 6 0.03 0.92
- Steam 0 0.84
- Brewer 0 0.78
- 0 0.74
- 0 0.71
- LIGHTING LOAD 1.5 W/S. FT 0.69
- EQUIPMENT LOAD 1.0 KW 0.66
- DIVERSITY FACTOR 1 0.64
- SH PER PERSON 255 Btu/hr
LH PER PERSON 255 Btu/hr
BPF 0.1
3,138 CFM/PERSON 10
1,162 EXHAUST 0
1,369 FLOOR GAIN 0 (1 if fl. gain exists else 0)
ROOF(0)/CEILING(1) 1
- ROOF (1 if Roof provided Insulation else 0)
70 PARTITIONS (1 if Mod.Partitions exists else 0)
CEILING 215 (1 if Mod.Ceiling Panels exists else 0)
1,646 PRE-COOLING COIL 0 (1 if Pre-cooling/TFA exists else 0)
1,102 ADP&SHR 0 (1 if ADP & SHR revised else 0)
3,003 Motor bkw IF ADP & SHR REVISED,CONSIDER FOL
6,826 SHR 0.87 REV. ESHR
ADP 49.00 REV. ADP
- TR 2.28 REV. TR
- Dehumd. CFM 785 REV. AIR QTY CFM
- Reheat,KW N/A RE- HEAT IN KWTO INCREASE ADP
18,316
1,531 FRESH AIR REQUIREMENT
19,847 NOS CFM/PER ACH
PEOPLE 6 5
- EXHAUST
161 NO. OF A/CHANGES
1,646 TOTAL FRESH AIR
- Ventilation cfm/ft2 215 0.2
PRE-COOLING COIL
- DB 'F WB 'F RH
- LEV. COND 56.0 55.9 99.5
918 INSIDE 69.0 58.9 1
2,725
273 DIFF. -13.0
2,998
22,844 1. SUPPLY AIR TEMP. ( ROOM O/L AIR)
Trm-( RSH/(1.08 x (De. CFM+CFMoa))
* If above is too high. Determine supply CFM
628 for desired diff. By supply air qty. formula
2. ENTERING DRY BULB TEMPERATURE
1,452 ( CFM oa x Toa)+(CFMra X Trm)/CFMsa)
24,924 3. ENTERING AIR MOISTURE CONTENT
2,492 (CFM oa*Woa+CFM ra*Wrm)/CFM da
N/A 4. LEAVING DRY BULB TEMPERATURE
27,417 ( Tadp + (BF(Tedb - T adp)))
2.28 5. SUPPLY AIR CFM
0.87 ( RSH/1.08 X (Trm-Tsa)
49 From psychrometric chart T ewb =
51 T lwb =
23 # when bypassing a mixture of OA & RA use supply CFM, when
785 bypassing RA only, use deh. CFM
TH GR/LB
138.4
64.9
0.0 73.5
U' FACTORS
WALL 0.360 11.4 34.2
GLASS 0.560 15.96 13.68
ALL GLASS 1.130 27.36 47.88
PARTITION 0.360
M.PARTN 0.150
CEILING 0.424
M.CLG.PANL 0.150
FLOOR 0.424
ROOF 0.510
sts else 0)
NET (CFM)
32
0
0
32
G COIL
TH GR/LB
23.8 66.7
25.6 58.2
-1.8 8.5
52.52 0F
23.40
75.79 0F
73.25 Gr./lb
51.33 0F
817.61 0F
F
0
F
0
EU5Q
GS6E
A4HA
6F55
DJHR
CVSL
XPFD
ZZGL
1ZPV
UZLX
Y0ES
YWWH
QNZ3
E6WV
Z