Heat Load Estimation MS1525 Design

Download as pdf or txt
Download as pdf or txt
You are on page 1of 10

M01 - HEAT LOAD CALCULATION

Project 31 Storeys Office Job No 9001 Revision 0


2
Location LG1 - Food Court Floor Area 8,072 Ft User SW
DESIGN CONDITIONS DESIGN NOTES
ITEM AREA / QUANTITY SUN GAIN / FACTOR BTU/H Design Time 12 PM Month June at latitude0 N 1) Design air bypass factor = 0
TEMP DIFF 2) Design Off-Coil Temp. = Dewpoint Temp.
SOLAR GAIN - EXTERNAL WINDOWS Glass 1/4" type Tinted Grey 3) No infiltration to cooling space
2
Glass N 0 Ft x 103 x 0.41 0 - shaded Yes 4) No duct heat gain
2
Glass NE 0 Ft x 66 x 0.41 0
2
Glass E 0 Ft x 18 x 0.41 0 Wall Material Heavy Weight Brick
2
Glass SE 0 Ft x 18 x 0.41 0 - thickness 4''
2
Glass S 0 Ft x 18 x 0.41 0 SUMMARY
2
Glass SW 0 Ft x 18 x 0.41 0 Roof Material 2'' Insulated Metal Sheet Grand Total Heat : 630,523 Btu/hr
2
Glass W 0 Ft x 18 x 0.41 0 : 52.5 RT
2
Glass NW 0 Ft x 66 x 0.41 0 Partition Heavy Weight Brick Load per Unit Area : 78 Btu/hr.ft2
2
Skylight 0 Ft x 283 x 0.41 0 - thickness 4'' Total Sensible Heat : 408,637 Btu/hr
Overhead ceiling Yes GSHR : 0.65
SOLAR & TRANS. GAIN - EXTERNAL WALLS & ROOF Ceiling below floor slab No
2
Wall N 0 Ft x 16 x 0.57 0 Space height clearance 12.0 Ft Without Bypass,
2
Wall NE 0 Ft x 41 x 0.57 0 Air Flow : 14,689 CFM
2
Wall E 0 Ft x 43 x 0.57 0 Occupant Factory Heavy Work : 1.82 CFM/Ft2
2
Wall SE 0 Ft x 23 x 0.57 0 : 280 CFM/RT
2 o
Wall S 0 Ft x 17 x 0.57 0 Room DB Temp. 75 F Air Changes : 9.1 Times/Hr
2
Wall SW 0 Ft x 19 x 0.57 0 Room RH 55 % Outdoor Air : 7.6 %
2
Wall W 0 Ft x 23 x 0.57 0
2
Wall NW 0 Ft x 22 x 0.57 0
2
Roof - Sun 0 Ft x 35 x 0.13 0 Conditions FDB FWB %RH GR/LB
Outdoor (OA) 93.0 82.0 148.9
TRANS. GAIN - EXTERNAL WINDOWS & INTERNAL PARTITIONS Room (RM) 75.0 55 71.5
2
All Glass 0 Ft x 18 x 1.10 0 Difference 18.0 77.4
2
Partition 0 Ft x 18 x 0.46 0
2
Floor slab above (exc. roof) 8,072 Ft x 18 x 0.27 39,230 SUPPLY AIR
2
Floor slab below 8,072 Ft x 18 x 0.57 82,819 OUTDOOR AIR
Ventilation 125 Pax x 5 CFM/Pax = 625
2 2
INTERNAL SENSIBLE LOAD 8,072 Ft x 0.06 CFM/Ft = 484
People 125 persons x 530
Btu/hr.person 66,250 Duct infiltration 0.0 % = 0
Power Ft8,072 1.2 W/Ft2 x 3.41
Btu/hr.W 33,031
Lights Ft8,072 1.2 W/Ft2 x 3.41
Btu/hr.W 33,031 OUTDOOR AIR THRU APPARATUS = 1,109 CFMOA
Other Sensible Heat Gains 20,000 W x 3.41
Btu/hr.W 68,200
SUB TOTAL 322,560 OFF-COIL TEMPERATURE & SUPPLY AIR QUANTITY
Safety Factor 20 % 64,512 SHR 387,072 RSH = 0.70
ROOM SENSIBLE HEAT (RSH) 387,072 550,572 RTH
o
Off-Coil Temp. = 50.6 F DP 54.8 Gr/lb
INTERNAL LATENT LOAD
o
People 125 persons x 930 Btu/hr.person 116,250 Allowable Temp. Rise = 24.4 F
Other Latent Heat Gains 20,000 Btu/hr 20,000
o
SUB TOTAL 136,250 On-Coil Temp. = 76.4 F 77.3 Gr/lb (w/o bypass OA mixture)
Safety Factor 20 % 27,250
ROOM LATENT HEAT (RLH) 163,500 Supply Air 387,072 RSH = 14,689 CFMSA
o
1.08 x 24.4 F Dehum. Rise
ROOM TOTAL HEAT (RTH) 550,572
SUPPLY / BYPASS AIR QUANTITY (for bypass air design application only)
OUTDOOR AIR HEAT Required? No
o
Sensible : 1,109 CFM x 18 F
x 1.08 21,565
Latent : 1,109 CFM x 77 GR/LB
x 0.68 58,386
Return Air or Blow-thru Fan HP 0

GRAND TOTAL HEAT (GTH) 630,523

20/6/2012 20:21 CONFIDENTIAL


M01 - HEAT LOAD CALCULATION

Project 31 Storeys Office Job No 9001 Revision 0


2
Location GF-Lettable Floor Area 10,991 Ft User SW
DESIGN CONDITIONS DESIGN NOTES
ITEM AREA / QUANTITY SUN GAIN / FACTOR BTU/H Design Time 4 PM Month Sep/Mar at latitude0 N 1) Design air bypass factor = 0
TEMP DIFF 2) Design Off-Coil Temp. = Dewpoint Temp.
SOLAR GAIN - EXTERNAL WINDOWS Glass 1/4" type Tinted Grey 3) No infiltration to cooling space
Glass N Ft2 x 15 x 0.41 0 - shaded Yes 4) No duct heat gain
2
Glass NE 830 Ft x 15 x 0.41 5,069
Glass E Ft2 x 15 x 0.41 0 Wall Material Light Weight Block
2
Glass SE 0 Ft x 15 x 0.41 0 - thickness 4''
Glass S Ft2 x 15 x 0.41 0 SUMMARY
2
Glass SW 830 Ft x 148 x 0.41 50,016 Roof Material 2'' Insulated Metal Sheet Grand Total Heat : 618,004 Btu/hr
Glass W Ft2 x 209 x 0.41 0 : 51.5 RT
2
Glass NW 738 Ft x 148 x 0.41 44,472 Partition Light Weight Block Load per Unit Area : 56 Btu/hr.ft2
2
Skylight 0 Ft x 125 x 0.41 0 - thickness 4'' Total Sensible Heat : 530,691 Btu/hr
Overhead ceiling Yes GSHR : 0.86
SOLAR & TRANS. GAIN - EXTERNAL WALLS & ROOF Ceiling below floor slab Yes
2
Wall N 0 Ft x 29 x 0.47 0 Space height clearance 12.0 Ft Without Bypass,
2
Wall NE 526 Ft x 31 x 0.47 7,664 Air Flow : 26,129 CFM
2
Wall E Ft x 31 x 0.47 0 Occupant Office Work : 2.38 CFM/Ft2
2
Wall SE 1,291 Ft x 38 x 0.47 23,057 : 507 CFM/RT
2 o
Wall S Ft x 33 x 0.47 0 Room DB Temp. 75 F Air Changes : 11.9 Times/Hr
2
Wall SW 526 Ft x 55 x 0.47 13,597 Room RH 55 % Outdoor Air : 4.5 %
2
Wall W Ft x 49 x 0.47 0
2
Wall NW 600 Ft x 31 x 0.47 8,742
2
Roof - Sun Ft x 73 x 0.13 0 Conditions FDB FWB %RH GR/LB
Outdoor (OA) 93.0 82.0 148.9
TRANS. GAIN - EXTERNAL WINDOWS & INTERNAL PARTITIONS Room (RM) 75.0 55 71.5
2
All Glass 2,398 Ft x 18 x 1.10 47,480 Difference 18.0 77.4
2
Partition 2,711 Ft x 18 x 0.39 19,031
2
Floor slab above (exc. roof) 10,991 Ft x 18 x 0.27 53,416 SUPPLY AIR
2
Floor slab below 10,991 Ft x 18 x 0.39 77,157 OUTDOOR AIR
Ventilation 102 Pax x 5 CFM/Pax = 510
2 2
INTERNAL SENSIBLE LOAD 10,991 Ft x 0.06 CFM/Ft = 659
People 102 persons x 250
Btu/hr.person 25,500 Duct infiltration 0.0 % = 0
2
Power Ft10,991 0.9 W/Ft x 3.41
Btu/hr.W 34,481
2
Lights Ft10,991 1.4 W/Ft x 3.41
Btu/hr.W 52,096 OUTDOOR AIR THRU APPARATUS = 1,169 CFMOA
Other Sensible Heat Gains W x 3.41
Btu/hr.W 0
SUB TOTAL 461,778 OFF-COIL TEMPERATURE & SUPPLY AIR QUANTITY
Safety Factor 10 % 46,178 SHR 507,956 RSH = 0.95
ROOM SENSIBLE HEAT (RSH) 507,956 533,718 RTH
o
Off-Coil Temp. = 57.0 F DP 69.6 Gr/lb
INTERNAL LATENT LOAD
o
People 102 persons x 210 Btu/hr.person 21,420 Allowable Temp. Rise = 18.0 F
Other Latent Heat Gains 2,000 Btu/hr 2,000
o
SUB TOTAL 23,420 On-Coil Temp. = 75.8 F 75.0 Gr/lb (w/o bypass OA mixture)
Safety Factor 10 % 2,342
ROOM LATENT HEAT (RLH) 25,762 Supply Air 507,956 RSH = 26,129 CFMSA
o
1.08 x 18.0 F Dehum. Rise
ROOM TOTAL HEAT (RTH) 533,718
SUPPLY / BYPASS AIR QUANTITY (for bypass air design application only)
OUTDOOR AIR HEAT Required? No
o
Sensible : 1,169 CFM x 18 F
x 1.08 22,734
Latent : 1,169 CFM x 77 GR/LB
x 0.68 61,551
Return Air or Blow-thru Fan HP 0

GRAND TOTAL HEAT (GTH) 618,004

20/6/2012 20:21 CONFIDENTIAL


M01 - HEAT LOAD CALCULATION

Project 31 Storeys Office Job No 9001 Revision 0


2
Location 1FL-Lettable & 2FL-Lettable Floor Area 8,721 Ft User SW
DESIGN CONDITIONS DESIGN NOTES
ITEM AREA / QUANTITY SUN GAIN / FACTOR BTU/H Design Time 4 PM Month Sep/Mar at latitude0 N 1) Design air bypass factor = 0
TEMP DIFF 2) Design Off-Coil Temp. = Dewpoint Temp.
SOLAR GAIN - EXTERNAL WINDOWS Glass 1/4" type Tinted Grey 3) No infiltration to cooling space
Glass N Ft2 x 15 x 0.41 0 - shaded Yes 4) No duct heat gain
2
Glass NE 830 Ft x 15 x 0.41 5,069
Glass E Ft2 x 15 x 0.41 0 Wall Material Light Weight Block
2
Glass SE 0 Ft x 15 x 0.41 0 - thickness 4''
Glass S Ft2 x 15 x 0.41 0 SUMMARY
2
Glass SW 830 Ft x 148 x 0.41 50,016 Roof Material 2'' Insulated Metal Sheet Grand Total Heat : 549,641 Btu/hr
Glass W Ft2 x 209 x 0.41 0 : 45.8 RT
2
Glass NW 738 Ft x 148 x 0.41 44,472 Partition Light Weight Block Load per Unit Area : 63 Btu/hr.ft2
2
Skylight 0 Ft x 125 x 0.41 0 - thickness 4'' Total Sensible Heat : 479,874 Btu/hr
Overhead ceiling Yes GSHR : 0.87
SOLAR & TRANS. GAIN - EXTERNAL WALLS & ROOF Ceiling below floor slab Yes
2
Wall N 0 Ft x 29 x 0.47 0 Space height clearance 12.0 Ft Without Bypass,
2
Wall NE 526 Ft x 31 x 0.47 7,664 Air Flow : 24,024 CFM
2
Wall E Ft x 31 x 0.47 0 Occupant Office Work : 2.75 CFM/Ft2
2
Wall SE 1,291 Ft x 38 x 0.47 23,057 : 524 CFM/RT
2 o
Wall S Ft x 33 x 0.47 0 Room DB Temp. 75 F Air Changes : 13.8 Times/Hr
2
Wall SW 526 Ft x 55 x 0.47 13,597 Room RH 55 % Outdoor Air : 3.9 %
2
Wall W Ft x 49 x 0.47 0
2
Wall NW 600 Ft x 31 x 0.47 8,742
2
Roof - Sun Ft x 73 x 0.13 0 Conditions FDB FWB %RH GR/LB
Outdoor (OA) 93.0 82.0 148.9
TRANS. GAIN - EXTERNAL WINDOWS & INTERNAL PARTITIONS Room (RM) 75.0 55 71.5
2
All Glass 2,398 Ft x 18 x 1.10 47,480 Difference 18.0 77.4
2
Partition 3,874 Ft x 18 x 0.39 27,195
2
Floor slab above (exc. roof) 8,721 Ft x 18 x 0.27 42,384 SUPPLY AIR
2
Floor slab below 8,721 Ft x 18 x 0.39 61,221 OUTDOOR AIR
Ventilation 81 Pax x 5 CFM/Pax = 405
2 2
INTERNAL SENSIBLE LOAD 8,721 Ft x 0.06 CFM/Ft = 523
People 81 persons x 250
Btu/hr.person 20,250 Duct infiltration 0.0 % = 0
2
Power Ft8,721 0.9 W/Ft x 3.41
Btu/hr.W 27,360
2
Lights Ft8,721 1.4 W/Ft x 3.41
Btu/hr.W 41,337 OUTDOOR AIR THRU APPARATUS = 928 CFMOA
Other Sensible Heat Gains W x 3.41
Btu/hr.W 0
SUB TOTAL 419,844 OFF-COIL TEMPERATURE & SUPPLY AIR QUANTITY
Safety Factor 10 % 41,984 SHR 461,828 RSH = 0.96
ROOM SENSIBLE HEAT (RSH) 461,828 482,739 RTH
o
Off-Coil Temp. = 57.2 F DP 70.1 Gr/lb
INTERNAL LATENT LOAD
o
People 81 persons x 210 Btu/hr.person 17,010 Allowable Temp. Rise = 17.8 F
Other Latent Heat Gains 2,000 Btu/hr 2,000
o
SUB TOTAL 19,010 On-Coil Temp. = 75.7 F 74.5 Gr/lb (w/o bypass OA mixture)
Safety Factor 10 % 1,901
ROOM LATENT HEAT (RLH) 20,911 Supply Air 461,828 RSH = 24,024 CFMSA
o
1.08 x 17.8 F Dehum. Rise
ROOM TOTAL HEAT (RTH) 482,739
SUPPLY / BYPASS AIR QUANTITY (for bypass air design application only)
OUTDOOR AIR HEAT Required? No
o
Sensible : 928 CFM x 18 F
x 1.08 18,045
Latent : 928 CFM x 77 GR/LB
x 0.68 48,856
Return Air or Blow-thru Fan HP 0

GRAND TOTAL HEAT (GTH) 549,641

20/6/2012 20:21 CONFIDENTIAL


M01 - HEAT LOAD CALCULATION

Project 31 Storeys Office Job No 9001 Revision 0


2
Location 3FL Fitness Centre Floor Area 13,486 Ft User SW
DESIGN CONDITIONS DESIGN NOTES
ITEM AREA / QUANTITY SUN GAIN / FACTOR BTU/H Design Time 4 PM Month Sep/Mar at latitude0 N 1) Design air bypass factor = 0
TEMP DIFF 2) Design Off-Coil Temp. = Dewpoint Temp.
SOLAR GAIN - EXTERNAL WINDOWS Glass 1/4" type Tinted Grey 3) No infiltration to cooling space
Glass N Ft2 x 15 x 0.41 0 - shaded Yes 4) No duct heat gain
2
Glass NE 830 Ft x 15 x 0.41 5,069
Glass E Ft2 x 15 x 0.41 0 Wall Material Light Weight Block
2
Glass SE 0 Ft x 15 x 0.41 0 - thickness 4''
Glass S Ft2 x 15 x 0.41 0 SUMMARY
2
Glass SW 830 Ft x 148 x 0.41 50,016 Roof Material 2'' Insulated Metal Sheet Grand Total Heat : 962,292 Btu/hr
Glass W Ft2 x 209 x 0.41 0 : 80.2 RT
2
Glass NW 738 Ft x 148 x 0.41 44,472 Partition Light Weight Block Load per Unit Area : 71 Btu/hr.ft2
2
Skylight 0 Ft x 125 x 0.41 0 - thickness 4'' Total Sensible Heat : 712,014 Btu/hr
Overhead ceiling Yes GSHR : 0.74
SOLAR & TRANS. GAIN - EXTERNAL WALLS & ROOF Ceiling below floor slab Yes
2
Wall N 0 Ft x 29 x 0.47 0 Space height clearance 12.0 Ft Without Bypass,
2
Wall NE 526 Ft x 31 x 0.47 7,664 Air Flow : 31,110 CFM
2
Wall E Ft x 31 x 0.47 0 Occupant Factory Heavy Work : 2.31 CFM/Ft2
2
Wall SE 1,291 Ft x 38 x 0.47 23,057 : 388 CFM/RT
2 o
Wall S Ft x 33 x 0.47 0 Room DB Temp. 75 F Air Changes : 11.5 Times/Hr
2
Wall SW 526 Ft x 55 x 0.47 13,597 Room RH 55 % Outdoor Air : 6.6 %
2
Wall W Ft x 49 x 0.47 0
2
Wall NW 600 Ft x 31 x 0.47 8,742
2
Roof - Sun Ft x 73 x 0.13 0 Conditions FDB FWB %RH GR/LB
Outdoor (OA) 93.0 82.0 148.9
TRANS. GAIN - EXTERNAL WINDOWS & INTERNAL PARTITIONS Room (RM) 75.0 55 71.5
2
All Glass 2,398 Ft x 18 x 1.10 47,480 Difference 18.0 77.4
2
Partition 3,874 Ft x 18 x 0.39 27,195
2
Floor slab above (exc. roof) 13,486 Ft x 18 x 0.27 65,542 SUPPLY AIR
2
Floor slab below 13,486 Ft x 18 x 0.39 94,672 OUTDOOR AIR
Ventilation 125 Pax x 10 CFM/Pax = 1,250
2 2
INTERNAL SENSIBLE LOAD 13,486 Ft x 0.06 CFM/Ft = 809
People 125 persons x 530
Btu/hr.person 66,250 Duct infiltration 0.0 % = 0
2
Power Ft13,486 0.9 W/Ft x 3.41
Btu/hr.W 42,308
2
Lights Ft13,486 1.4 W/Ft x 3.41
Btu/hr.W 63,922 OUTDOOR AIR THRU APPARATUS = 2,059 CFMOA
Other Sensible Heat Gains W x 3.41
Btu/hr.W 0
SUB TOTAL 559,987 OFF-COIL TEMPERATURE & SUPPLY AIR QUANTITY
Safety Factor 20 % 111,997 SHR 671,984 RSH = 0.83
ROOM SENSIBLE HEAT (RSH) 671,984 813,884 RTH
o
Off-Coil Temp. = 55.0 F DP 64.6 Gr/lb
INTERNAL LATENT LOAD
o
People 125 persons x 930 Btu/hr.person 116,250 Allowable Temp. Rise = 20.0 F
Other Latent Heat Gains 2,000 Btu/hr 2,000
o
SUB TOTAL 118,250 On-Coil Temp. = 76.2 F 76.6 Gr/lb (w/o bypass OA mixture)
Safety Factor 20 % 23,650
ROOM LATENT HEAT (RLH) 141,900 Supply Air 671,984 RSH = 31,110 CFMSA
o
1.08 x 20.0 F Dehum. Rise
ROOM TOTAL HEAT (RTH) 813,884
SUPPLY / BYPASS AIR QUANTITY (for bypass air design application only)
OUTDOOR AIR HEAT Required? No
o
Sensible : 2,059 CFM x 18 F
x 1.08 40,030
Latent : 2,059 CFM x 77 GR/LB
x 0.68 108,378
Return Air or Blow-thru Fan HP 0

GRAND TOTAL HEAT (GTH) 962,292

20/6/2012 20:21 CONFIDENTIAL


M01 - HEAT LOAD CALCULATION

Project 31 Storeys Office Job No 9001 Revision 0


2
Location 5FL-16FL Floor Area 13,613 Ft User SW
DESIGN CONDITIONS DESIGN NOTES
ITEM AREA / QUANTITY SUN GAIN / FACTOR BTU/H Design Time 4 PM Month Dec at latitude0 N 1) Design air bypass factor = 0
TEMP DIFF 2) Design Off-Coil Temp. = Dewpoint Temp.
SOLAR GAIN - EXTERNAL WINDOWS Glass 1/4" type Tinted Grey 3) No infiltration to cooling space
Glass N Ft2 x 14 x 0.41 0 - shaded Yes 4) No duct heat gain
2
Glass NE 1,160 Ft x 14 x 0.41 6,612
Glass E Ft2 x 14 x 0.41 0 Wall Material Light Weight Block
2
Glass SE 0 Ft x 14 x 0.41 0 - thickness 4''
Glass S Ft2 x 81 x 0.41 0 SUMMARY
2
Glass SW 1,160 Ft x 195 x 0.41 92,100 Roof Material 2'' Insulated Metal Sheet Grand Total Heat : 776,862 Btu/hr
Glass W Ft2 x 184 x 0.41 0 : 64.7 RT
2
Glass NW 738 Ft x 83 x 0.41 24,940 Partition Light Weight Block Load per Unit Area : 57 Btu/hr.ft2
2
Skylight 0 Ft x 109 x 0.41 0 - thickness 4'' Total Sensible Heat : 668,915 Btu/hr
Overhead ceiling Yes GSHR : 0.86
SOLAR & TRANS. GAIN - EXTERNAL WALLS & ROOF Ceiling below floor slab Yes
2
Wall N 0 Ft x 29 x 0.47 0 Space height clearance 12.0 Ft Without Bypass,
2
Wall NE 733 Ft x 30 x 0.47 10,335 Air Flow : 33,328 CFM
2
Wall E Ft x 31 x 0.47 0 Occupant Office Work : 2.45 CFM/Ft2
2
Wall SE 1,549 Ft x 41 x 0.47 29,849 : 515 CFM/RT
2 o
Wall S Ft x 53 x 0.47 0 Room DB Temp. 75 F Air Changes : 12.2 Times/Hr
2
Wall SW 733 Ft x 63 x 0.47 21,704 Room RH 55 % Outdoor Air : 4.4 %
2
Wall W Ft x 47 x 0.47 0
2
Wall NW 600 Ft x 30 x 0.47 8,460
2
Roof - Sun Ft x 69 x 0.13 0 Conditions FDB FWB %RH GR/LB
Outdoor (OA) 93.0 82.0 148.9
TRANS. GAIN - EXTERNAL WINDOWS & INTERNAL PARTITIONS Room (RM) 75.0 55 71.5
2
All Glass 3,058 Ft x 18 x 1.10 60,548 Difference 18.0 77.4
2
Partition 3,874 Ft x 18 x 0.39 27,195
2
Floor slab above (exc. roof) 13,613 Ft x 18 x 0.27 66,159 SUPPLY AIR
2
Floor slab below 13,613 Ft x 18 x 0.39 95,563 OUTDOOR AIR
Ventilation 127 Pax x 5 CFM/Pax = 635
2 2
INTERNAL SENSIBLE LOAD 13,613 Ft x 0.06 CFM/Ft = 817
People 127 persons x 250
Btu/hr.person 31,750 Duct infiltration 0.0 % = 0
2
Power Ft13,613 0.9 W/Ft x 3.41
Btu/hr.W 42,707
2
Lights Ft13,613 1.4 W/Ft x 3.41
Btu/hr.W 64,524 OUTDOOR AIR THRU APPARATUS = 1,452 CFMOA
Other Sensible Heat Gains W x 3.41
Btu/hr.W 0
SUB TOTAL 582,448 OFF-COIL TEMPERATURE & SUPPLY AIR QUANTITY
Safety Factor 10 % 58,245 SHR 640,693 RSH = 0.95
ROOM SENSIBLE HEAT (RSH) 640,693 672,230 RTH
o
Off-Coil Temp. = 57.2 F DP 70.1 Gr/lb
INTERNAL LATENT LOAD
o
People 127 persons x 210 Btu/hr.person 26,670 Allowable Temp. Rise = 17.8 F
Other Latent Heat Gains 2,000 Btu/hr 2,000
o
SUB TOTAL 28,670 On-Coil Temp. = 75.8 F 74.9 Gr/lb (w/o bypass OA mixture)
Safety Factor 10 % 2,867
ROOM LATENT HEAT (RLH) 31,537 Supply Air 640,693 RSH = 33,328 CFMSA
o
1.08 x 17.8 F Dehum. Rise
ROOM TOTAL HEAT (RTH) 672,230
SUPPLY / BYPASS AIR QUANTITY (for bypass air design application only)
OUTDOOR AIR HEAT Required? No
o
Sensible : 1,452 CFM x 18 F
x 1.08 28,223
Latent : 1,452 CFM x 77 GR/LB
x 0.68 76,410
Return Air or Blow-thru Fan HP 0

GRAND TOTAL HEAT (GTH) 776,862

20/6/2012 20:21 CONFIDENTIAL


M01 - HEAT LOAD CALCULATION

Project 31 Storeys Office Job No 9001 Revision 0


2
Location 10FL Floor Area 10,603 Ft User SW
DESIGN CONDITIONS DESIGN NOTES
ITEM AREA / QUANTITY SUN GAIN / FACTOR BTU/H Design Time 4 PM Month Dec at latitude0 N 1) Design air bypass factor = 0
TEMP DIFF 2) Design Off-Coil Temp. = Dewpoint Temp.
SOLAR GAIN - EXTERNAL WINDOWS Glass 1/4" type Tinted Grey 3) No infiltration to cooling space
Glass N Ft2 x 14 x 0.41 0 - shaded Yes 4) No duct heat gain
2
Glass NE 1,160 Ft x 14 x 0.41 6,612
Glass E Ft2 x 14 x 0.41 0 Wall Material Light Weight Block
2
Glass SE 0 Ft x 14 x 0.41 0 - thickness 4''
Glass S Ft2 x 81 x 0.41 0 SUMMARY
2
Glass SW 1,160 Ft x 195 x 0.41 92,100 Roof Material 2'' Insulated Metal Sheet Grand Total Heat : 674,172 Btu/hr
Glass W Ft2 x 184 x 0.41 0 : 56.2 RT
2
Glass NW 738 Ft x 83 x 0.41 24,940 Partition Light Weight Block Load per Unit Area : 64 Btu/hr.ft2
2
Skylight 0 Ft x 109 x 0.41 0 - thickness 4'' Total Sensible Heat : 589,567 Btu/hr
Overhead ceiling Yes GSHR : 0.87
SOLAR & TRANS. GAIN - EXTERNAL WALLS & ROOF Ceiling below floor slab Yes
2
Wall N 0 Ft x 29 x 0.47 0 Space height clearance 12.0 Ft Without Bypass,
2
Wall NE 733 Ft x 30 x 0.47 10,335 Air Flow : 29,524 CFM
2
Wall E Ft x 31 x 0.47 0 Occupant Office Work : 2.78 CFM/Ft2
2
Wall SE 1,549 Ft x 41 x 0.47 29,849 : 526 CFM/RT
2 o
Wall S Ft x 53 x 0.47 0 Room DB Temp. 75 F Air Changes : 13.9 Times/Hr
2
Wall SW 733 Ft x 63 x 0.47 21,704 Room RH 55 % Outdoor Air : 3.8 %
2
Wall W Ft x 47 x 0.47 0
2
Wall NW 600 Ft x 30 x 0.47 8,460
2
Roof - Sun Ft x 69 x 0.13 0 Conditions FDB FWB %RH GR/LB
Outdoor (OA) 93.0 82.0 148.9
TRANS. GAIN - EXTERNAL WINDOWS & INTERNAL PARTITIONS Room (RM) 75.0 55 71.5
2
All Glass 3,058 Ft x 18 x 1.10 60,548 Difference 18.0 77.4
2
Partition 3,874 Ft x 18 x 0.39 27,195
2
Floor slab above (exc. roof) 10,603 Ft x 18 x 0.27 51,531 SUPPLY AIR
2
Floor slab below 10,603 Ft x 18 x 0.39 74,433 OUTDOOR AIR
Ventilation 99 Pax x 5 CFM/Pax = 495
2 2
INTERNAL SENSIBLE LOAD 10,603 Ft x 0.06 CFM/Ft = 636
People 99 persons x 250
Btu/hr.person 24,750 Duct infiltration 0.0 % = 0
Power Ft10,603 0.9 W/Ft2 x 3.41
Btu/hr.W 33,264
Lights Ft10,603 1.4 W/Ft2 x 3.41
Btu/hr.W 50,257 OUTDOOR AIR THRU APPARATUS = 1,131 CFMOA
Other Sensible Heat Gains 0 W x 3.41
Btu/hr.W 0
SUB TOTAL 515,979 OFF-COIL TEMPERATURE & SUPPLY AIR QUANTITY
Safety Factor 10 % 51,598 SHR 567,577 RSH = 0.96
ROOM SENSIBLE HEAT (RSH) 567,577 592,646 RTH
o
Off-Coil Temp. = 57.2 F DP 70.1 Gr/lb
INTERNAL LATENT LOAD
o
People 99 persons x 210 Btu/hr.person 20,790 Allowable Temp. Rise = 17.8 F
Other Latent Heat Gains 2,000 Btu/hr 2,000
o
SUB TOTAL 22,790 On-Coil Temp. = 75.7 F 74.5 Gr/lb (w/o bypass OA mixture)
Safety Factor 10 % 2,279
ROOM LATENT HEAT (RLH) 25,069 Supply Air 567,577 RSH = 29,524 CFMSA
o
1.08 x 17.8 F Dehum. Rise
ROOM TOTAL HEAT (RTH) 592,646
SUPPLY / BYPASS AIR QUANTITY (for bypass air design application only)
OUTDOOR AIR HEAT Required? No
o
Sensible : 1,131 CFM x 18 F
x 1.08 21,990
Latent : 1,131 CFM x 77 GR/LB
x 0.68 59,536
Return Air or Blow-thru Fan HP 0

GRAND TOTAL HEAT (GTH) 674,172

20/6/2012 20:21 CONFIDENTIAL


M01 - HEAT LOAD CALCULATION

Project 31 Storeys Office Job No 9001 Revision 0


2
Location 20FL Floor Area 12,916 Ft User SW
DESIGN CONDITIONS DESIGN NOTES
ITEM AREA / QUANTITY SUN GAIN / FACTOR BTU/H Design Time 4 PM Month Dec at latitude0 N 1) Design air bypass factor = 0
TEMP DIFF 2) Design Off-Coil Temp. = Dewpoint Temp.
SOLAR GAIN - EXTERNAL WINDOWS Glass 1/4" type Tinted Grey 3) No infiltration to cooling space
Glass N Ft2 x 14 x 0.41 0 - shaded Yes 4) No duct heat gain
2
Glass NE 1,160 Ft x 14 x 0.41 6,612
Glass E Ft2 x 14 x 0.41 0 Wall Material Light Weight Block
2
Glass SE 0 Ft x 14 x 0.41 0 - thickness 4''
Glass S Ft2 x 81 x 0.41 0 SUMMARY
2
Glass SW 1,160 Ft x 195 x 0.41 92,100 Roof Material 2'' Insulated Metal Sheet Grand Total Heat : 752,636 Btu/hr
Glass W Ft2 x 184 x 0.41 0 : 62.7 RT
2
Glass NW 738 Ft x 83 x 0.41 24,940 Partition Light Weight Block Load per Unit Area : 58 Btu/hr.ft2
2
Skylight 0 Ft x 109 x 0.41 0 - thickness 4'' Total Sensible Heat : 650,349 Btu/hr
Overhead ceiling Yes GSHR : 0.86
SOLAR & TRANS. GAIN - EXTERNAL WALLS & ROOF Ceiling below floor slab Yes
2
Wall N 0 Ft x 29 x 0.47 0 Space height clearance 12.0 Ft Without Bypass,
2
Wall NE 733 Ft x 30 x 0.47 10,335 Air Flow : 32,440 CFM
2
Wall E Ft x 31 x 0.47 0 Occupant Office Work : 2.51 CFM/Ft2
2
Wall SE 1,549 Ft x 41 x 0.47 29,849 : 517 CFM/RT
2 o
Wall S Ft x 53 x 0.47 0 Room DB Temp. 75 F Air Changes : 12.6 Times/Hr
2
Wall SW 733 Ft x 63 x 0.47 21,704 Room RH 55 % Outdoor Air : 4.2 %
2
Wall W Ft x 47 x 0.47 0
2
Wall NW 600 Ft x 30 x 0.47 8,460
2
Roof - Sun Ft x 69 x 0.13 0 Conditions FDB FWB %RH GR/LB
Outdoor (OA) 93.0 82.0 148.9
TRANS. GAIN - EXTERNAL WINDOWS & INTERNAL PARTITIONS Room (RM) 75.0 55 71.5
2
All Glass 3,058 Ft x 18 x 1.10 60,548 Difference 18.0 77.4
2
Partition 3,874 Ft x 18 x 0.39 27,195
2
Floor slab above (exc. roof) 12,916 Ft x 18 x 0.27 62,772 SUPPLY AIR
2
Floor slab below 12,916 Ft x 18 x 0.39 90,670 OUTDOOR AIR
Ventilation 120 Pax x 5 CFM/Pax = 600
2 2
INTERNAL SENSIBLE LOAD 12,916 Ft x 0.06 CFM/Ft = 775
People 120 persons x 250
Btu/hr.person 30,000 Duct infiltration 0.0 % = 0
Power Ft12,916 0.9 W/Ft2 x 3.41
Btu/hr.W 40,520
Lights Ft12,916 1.4 W/Ft2 x 3.41
Btu/hr.W 61,221 OUTDOOR AIR THRU APPARATUS = 1,375 CFMOA
Other Sensible Heat Gains 0 W x 3.41
Btu/hr.W 0
SUB TOTAL 566,927 OFF-COIL TEMPERATURE & SUPPLY AIR QUANTITY
Safety Factor 10 % 56,693 SHR 623,620 RSH = 0.95
ROOM SENSIBLE HEAT (RSH) 623,620 653,540 RTH
o
Off-Coil Temp. = 57.2 F DP 70.1 Gr/lb
INTERNAL LATENT LOAD
o
People 120 persons x 210 Btu/hr.person 25,200 Allowable Temp. Rise = 17.8 F
Other Latent Heat Gains 2,000 Btu/hr 2,000
o
SUB TOTAL 27,200 On-Coil Temp. = 75.8 F 74.8 Gr/lb (w/o bypass OA mixture)
Safety Factor 10 % 2,720
ROOM LATENT HEAT (RLH) 29,920 Supply Air 623,620 RSH = 32,440 CFMSA
o
1.08 x 17.8 F Dehum. Rise
ROOM TOTAL HEAT (RTH) 653,540
SUPPLY / BYPASS AIR QUANTITY (for bypass air design application only)
OUTDOOR AIR HEAT Required? No
o
Sensible : 1,375 CFM x 18 F
x 1.08 26,729
Latent : 1,375 CFM x 77 GR/LB
x 0.68 72,367
Return Air or Blow-thru Fan HP 0

GRAND TOTAL HEAT (GTH) 752,636

20/6/2012 20:21 CONFIDENTIAL


M01 - HEAT LOAD CALCULATION

Project 31 Storeys Office Job No 9001 Revision 0


2
Location 17FL-26FL Floor Area 14,025 Ft User SW
DESIGN CONDITIONS DESIGN NOTES
ITEM AREA / QUANTITY SUN GAIN / FACTOR BTU/H Design Time 4 PM Month Dec at latitude0 N 1) Design air bypass factor = 0
TEMP DIFF 2) Design Off-Coil Temp. = Dewpoint Temp.
SOLAR GAIN - EXTERNAL WINDOWS Glass 1/4" type Tinted Grey 3) No infiltration to cooling space
Glass N Ft2 x 14 x 0.41 0 - shaded Yes 4) No duct heat gain
2
Glass NE 1,160 Ft x 14 x 0.41 6,612
Glass E Ft2 x 14 x 0.41 0 Wall Material Light Weight Block
2
Glass SE 0 Ft x 14 x 0.41 0 - thickness 4''
Glass S Ft2 x 81 x 0.41 0 SUMMARY
2
Glass SW 1,160 Ft x 195 x 0.41 92,100 Roof Material 2'' Insulated Metal Sheet Grand Total Heat : 790,197 Btu/hr
Glass W Ft2 x 184 x 0.41 0 : 65.8 RT
2
Glass NW 738 Ft x 83 x 0.41 24,940 Partition Light Weight Block Load per Unit Area : 56 Btu/hr.ft2
2
Skylight 0 Ft x 109 x 0.41 0 - thickness 4'' Total Sensible Heat : 679,466 Btu/hr
Overhead ceiling Yes GSHR : 0.86
SOLAR & TRANS. GAIN - EXTERNAL WALLS & ROOF Ceiling below floor slab Yes
2
Wall N 0 Ft x 29 x 0.47 0 Space height clearance 12.0 Ft Without Bypass,
2
Wall NE 733 Ft x 30 x 0.47 10,335 Air Flow : 33,460 CFM
2
Wall E Ft x 31 x 0.47 0 Occupant Office Work : 2.39 CFM/Ft2
2
Wall SE 1,549 Ft x 41 x 0.47 29,849 : 508 CFM/RT
2 o
Wall S Ft x 53 x 0.47 0 Room DB Temp. 75 F Air Changes : 11.9 Times/Hr
2
Wall SW 733 Ft x 63 x 0.47 21,704 Room RH 55 % Outdoor Air : 4.5 %
2
Wall W Ft x 47 x 0.47 0
2
Wall NW 600 Ft x 30 x 0.47 8,460
2
Roof - Sun Ft x 69 x 0.13 0 Conditions FDB FWB %RH GR/LB
Outdoor (OA) 93.0 82.0 148.9
TRANS. GAIN - EXTERNAL WINDOWS & INTERNAL PARTITIONS Room (RM) 75.0 55 71.5
2
All Glass 3,058 Ft x 18 x 1.10 60,548 Difference 18.0 77.4
2
Partition 3,874 Ft x 18 x 0.39 27,195
2
Floor slab above (exc. roof) 14,025 Ft x 18 x 0.27 68,162 SUPPLY AIR
2
Floor slab below 14,025 Ft x 18 x 0.39 98,456 OUTDOOR AIR
Ventilation 130 Pax x 5 CFM/Pax = 650
2 2
INTERNAL SENSIBLE LOAD 14,025 Ft x 0.06 CFM/Ft = 842
People 130 persons x 250
Btu/hr.person 32,500 Duct infiltration 0.0 % = 0
2
Power Ft14,025 0.9 W/Ft x 3.41
Btu/hr.W 43,999
2
Lights Ft14,025 1.4 W/Ft x 3.41
Btu/hr.W 66,477 OUTDOOR AIR THRU APPARATUS = 1,492 CFMOA
Other Sensible Heat Gains W x 3.41
Btu/hr.W 0
SUB TOTAL 591,338 OFF-COIL TEMPERATURE & SUPPLY AIR QUANTITY
Safety Factor 10 % 59,134 SHR 650,472 RSH = 0.95
ROOM SENSIBLE HEAT (RSH) 650,472 682,702 RTH
o
Off-Coil Temp. = 57.0 F DP 69.6 Gr/lb
INTERNAL LATENT LOAD
o
People 130 persons x 210 Btu/hr.person 27,300 Allowable Temp. Rise = 18.0 F
Other Latent Heat Gains 2,000 Btu/hr 2,000
o
SUB TOTAL 29,300 On-Coil Temp. = 75.8 F 75.0 Gr/lb (w/o bypass OA mixture)
Safety Factor 10 % 2,930
ROOM LATENT HEAT (RLH) 32,230 Supply Air 650,472 RSH = 33,460 CFMSA
o
1.08 x 18.0 F Dehum. Rise
ROOM TOTAL HEAT (RTH) 682,702
SUPPLY / BYPASS AIR QUANTITY (for bypass air design application only)
OUTDOOR AIR HEAT Required? No
o
Sensible : 1,492 CFM x 18 F
x 1.08 28,995
Latent : 1,492 CFM x 77 GR/LB
x 0.68 78,501
Return Air or Blow-thru Fan HP 0

GRAND TOTAL HEAT (GTH) 790,197

20/6/2012 20:21 CONFIDENTIAL


M01 - HEAT LOAD CALCULATION

Project 31 Storeys Office Job No 9001 Revision 0


2
Location 27FL-30FL Floor Area 14,373 Ft User SW
DESIGN CONDITIONS DESIGN NOTES
ITEM AREA / QUANTITY SUN GAIN / FACTOR BTU/H Design Time 4 PM Month Dec at latitude0 N 1) Design air bypass factor = 0
TEMP DIFF 2) Design Off-Coil Temp. = Dewpoint Temp.
SOLAR GAIN - EXTERNAL WINDOWS Glass 1/4" type Tinted Grey 3) No infiltration to cooling space
Glass N Ft2 x 14 x 0.41 0 - shaded Yes 4) No duct heat gain
2
Glass NE 1,160 Ft x 14 x 0.41 6,612
Glass E Ft2 x 14 x 0.41 0 Wall Material Light Weight Block
2
Glass SE 0 Ft x 14 x 0.41 0 - thickness 4''
Glass S Ft2 x 81 x 0.41 0 SUMMARY
2
Glass SW 1,160 Ft x 195 x 0.41 92,100 Roof Material 2'' Insulated Metal Sheet Grand Total Heat : 801,864 Btu/hr
Glass W Ft2 x 184 x 0.41 0 : 66.8 RT
2
Glass NW 738 Ft x 83 x 0.41 24,940 Partition Light Weight Block Load per Unit Area : 56 Btu/hr.ft2
2
Skylight 0 Ft x 109 x 0.41 0 - thickness 4'' Total Sensible Heat : 688,552 Btu/hr
Overhead ceiling Yes GSHR : 0.86
SOLAR & TRANS. GAIN - EXTERNAL WALLS & ROOF Ceiling below floor slab Yes
2
Wall N 0 Ft x 29 x 0.47 0 Space height clearance 12.0 Ft Without Bypass,
2
Wall NE 733 Ft x 30 x 0.47 10,335 Air Flow : 33,892 CFM
2
Wall E Ft x 31 x 0.47 0 Occupant Office Work : 2.36 CFM/Ft2
2
Wall SE 1,549 Ft x 41 x 0.47 29,849 : 507 CFM/RT
2 o
Wall S Ft x 53 x 0.47 0 Room DB Temp. 75 F Air Changes : 11.8 Times/Hr
2
Wall SW 733 Ft x 63 x 0.47 21,704 Room RH 55 % Outdoor Air : 4.5 %
2
Wall W Ft x 47 x 0.47 0
2
Wall NW 600 Ft x 30 x 0.47 8,460
2
Roof - Sun Ft x 69 x 0.13 0 Conditions FDB FWB %RH GR/LB
Outdoor (OA) 93.0 82.0 148.9
TRANS. GAIN - EXTERNAL WINDOWS & INTERNAL PARTITIONS Room (RM) 75.0 55 71.5
2
All Glass 3,058 Ft x 18 x 1.10 60,548 Difference 18.0 77.4
2
Partition 3,874 Ft x 18 x 0.39 27,195
2
Floor slab above (exc. roof) 14,373 Ft x 18 x 0.27 69,853 SUPPLY AIR
2
Floor slab below 14,373 Ft x 18 x 0.39 100,898 OUTDOOR AIR
Ventilation 133 Pax x 5 CFM/Pax = 665
2 2
INTERNAL SENSIBLE LOAD 14,373 Ft x 0.06 CFM/Ft = 862
People 133 persons x 250
Btu/hr.person 33,250 Duct infiltration 0.0 % = 0
Power Ft14,373 0.9 W/Ft2 x 3.41
Btu/hr.W 45,091
Lights Ft14,373 1.4 W/Ft2 x 3.41
Btu/hr.W 68,127 OUTDOOR AIR THRU APPARATUS = 1,527 CFMOA
Other Sensible Heat Gains 0 W x 3.41
Btu/hr.W 0
SUB TOTAL 598,963 OFF-COIL TEMPERATURE & SUPPLY AIR QUANTITY
Safety Factor 10 % 59,896 SHR 658,860 RSH = 0.95
ROOM SENSIBLE HEAT (RSH) 658,860 691,783 RTH
o
Off-Coil Temp. = 57.0 F DP 69.6 Gr/lb
INTERNAL LATENT LOAD
o
People 133 persons x 210 Btu/hr.person 27,930 Allowable Temp. Rise = 18.0 F
Other Latent Heat Gains 2,000 Btu/hr 2,000
o
SUB TOTAL 29,930 On-Coil Temp. = 75.8 F 75.0 Gr/lb (w/o bypass OA mixture)
Safety Factor 10 % 2,993
ROOM LATENT HEAT (RLH) 32,923 Supply Air 658,860 RSH = 33,892 CFMSA
o
1.08 x 18.0 F Dehum. Rise
ROOM TOTAL HEAT (RTH) 691,783
SUPPLY / BYPASS AIR QUANTITY (for bypass air design application only)
OUTDOOR AIR HEAT Required? No
o
Sensible : 1,527 CFM x 18 F
x 1.08 29,692
Latent : 1,527 CFM x 77 GR/LB
x 0.68 80,389
Return Air or Blow-thru Fan HP 0

GRAND TOTAL HEAT (GTH) 801,864

20/6/2012 20:21 CONFIDENTIAL


M01 - HEAT LOAD CALCULATION

Project 31 Storeys Office Job No 9001 Revision 0


2
Location Bistro Floor Area 3,138 Ft User SW
DESIGN CONDITIONS DESIGN NOTES
ITEM AREA / QUANTITY SUN GAIN / FACTOR BTU/H Design Time 4 PM Month Dec at latitude0 N 1) Design air bypass factor = 0
TEMP DIFF 2) Design Off-Coil Temp. = Dewpoint Temp.
SOLAR GAIN - EXTERNAL WINDOWS Glass 1/4" type Tinted Grey 3) No infiltration to cooling space
Glass N Ft2 x 14 x 0.41 0 - shaded Yes 4) No duct heat gain
2
Glass NE 290 Ft x 14 x 0.41 1,653
Glass E Ft2 x 14 x 0.41 0 Wall Material Light Weight Block
2
Glass SE 0 Ft x 14 x 0.41 0 - thickness 4''
Glass S Ft2 x 81 x 0.41 0 SUMMARY
2
Glass SW 290 Ft x 195 x 0.41 23,025 Roof Material 2'' Insulated Metal Sheet Grand Total Heat : 232,518 Btu/hr
Glass W Ft2 x 184 x 0.41 0 : 19.4 RT
2
Glass NW 185 Ft x 83 x 0.41 6,252 Partition Light Weight Block Load per Unit Area : 74 Btu/hr.ft2
2
Skylight 0 Ft x 109 x 0.41 0 - thickness 4'' Total Sensible Heat : 174,095 Btu/hr
Overhead ceiling Yes GSHR : 0.75
SOLAR & TRANS. GAIN - EXTERNAL WALLS & ROOF Ceiling below floor slab Yes
2
Wall N 0 Ft x 29 x 0.47 0 Space height clearance 12.0 Ft Without Bypass,
2
Wall NE 183 Ft x 30 x 0.47 2,580 Air Flow : 7,670 CFM
2
Wall E Ft x 31 x 0.47 0 Occupant Factory Average Work : 2.44 CFM/Ft2
2
Wall SE 387 Ft x 41 x 0.47 7,457 : 396 CFM/RT
2 o
Wall S Ft x 53 x 0.47 0 Room DB Temp. 75 F Air Changes : 12.2 Times/Hr
2
Wall SW 183 Ft x 63 x 0.47 5,419 Room RH 55 % Outdoor Air : 5.6 %
2
Wall W Ft x 47 x 0.47 0
2
Wall NW 600 Ft x 30 x 0.47 8,460
2
Roof - Sun Ft x 69 x 0.13 0 Conditions FDB FWB %RH GR/LB
Outdoor (OA) 93.0 82.0 148.9
TRANS. GAIN - EXTERNAL WINDOWS & INTERNAL PARTITIONS Room (RM) 75.0 55 71.5
2
All Glass 765 Ft x 18 x 1.10 15,147 Difference 18.0 77.4
2
Partition 0 Ft x 18 x 0.39 0
2
Floor slab above (exc. roof) 3,138 Ft x 18 x 0.27 15,251 SUPPLY AIR
2
Floor slab below 3,138 Ft x 18 x 0.39 22,029 OUTDOOR AIR
Ventilation 49 Pax x 5 CFM/Pax = 245
2 2
INTERNAL SENSIBLE LOAD 3,138 Ft x 0.06 CFM/Ft = 188
People 49 persons x 380
Btu/hr.person 18,620 Duct infiltration 0.0 % = 0
Power Ft3,138 0.9 W/Ft2 x 3.41
Btu/hr.W 9,845
Lights Ft3,138 1.4 W/Ft2 x 3.41
Btu/hr.W 14,874 OUTDOOR AIR THRU APPARATUS = 433 CFMOA
Other Sensible Heat Gains 0 W x 3.41
Btu/hr.W 0
SUB TOTAL 150,611 OFF-COIL TEMPERATURE & SUPPLY AIR QUANTITY
Safety Factor 10 % 15,061 SHR 165,672 RSH = 0.82
ROOM SENSIBLE HEAT (RSH) 165,672 201,290 RTH
o
Off-Coil Temp. = 55.0 F DP 64.6 Gr/lb
INTERNAL LATENT LOAD
o
People 49 persons x 620 Btu/hr.person 30,380 Allowable Temp. Rise = 20.0 F
Other Latent Heat Gains 2,000 Btu/hr 2,000
o
SUB TOTAL 32,380 On-Coil Temp. = 76.0 F 75.9 Gr/lb (w/o bypass OA mixture)
Safety Factor 10 % 3,238
ROOM LATENT HEAT (RLH) 35,618 Supply Air 165,672 RSH = 7,670 CFMSA
o
1.08 x 20.0 F Dehum. Rise
ROOM TOTAL HEAT (RTH) 201,290
SUPPLY / BYPASS AIR QUANTITY (for bypass air design application only)
OUTDOOR AIR HEAT Required? No
o
Sensible : 433 CFM x 18 F
x 1.08 8,423
Latent : 433 CFM x 77 GR/LB
x 0.68 22,804
Return Air or Blow-thru Fan HP 0

GRAND TOTAL HEAT (GTH) 232,518

20/6/2012 20:21 CONFIDENTIAL