This document summarizes the heat load calculation for a 31-storey office building located in LG1 - Food Court with a floor area of 8,072 square feet. The total heat load is calculated to be 630,523 BTU/hr or 52.5 tons. When accounting for a safety factor of 20%, the total sensible heat load is 387,072 BTU/hr. The supply air quantity required is calculated based on maintaining an off-coil temperature of 50.6°F dew point temperature and allowing a maximum temperature rise of 24.4°F.
This document summarizes the heat load calculation for a 31-storey office building located in LG1 - Food Court with a floor area of 8,072 square feet. The total heat load is calculated to be 630,523 BTU/hr or 52.5 tons. When accounting for a safety factor of 20%, the total sensible heat load is 387,072 BTU/hr. The supply air quantity required is calculated based on maintaining an off-coil temperature of 50.6°F dew point temperature and allowing a maximum temperature rise of 24.4°F.
This document summarizes the heat load calculation for a 31-storey office building located in LG1 - Food Court with a floor area of 8,072 square feet. The total heat load is calculated to be 630,523 BTU/hr or 52.5 tons. When accounting for a safety factor of 20%, the total sensible heat load is 387,072 BTU/hr. The supply air quantity required is calculated based on maintaining an off-coil temperature of 50.6°F dew point temperature and allowing a maximum temperature rise of 24.4°F.
This document summarizes the heat load calculation for a 31-storey office building located in LG1 - Food Court with a floor area of 8,072 square feet. The total heat load is calculated to be 630,523 BTU/hr or 52.5 tons. When accounting for a safety factor of 20%, the total sensible heat load is 387,072 BTU/hr. The supply air quantity required is calculated based on maintaining an off-coil temperature of 50.6°F dew point temperature and allowing a maximum temperature rise of 24.4°F.
2 Location LG1 - Food Court Floor Area 8,072 Ft User SW DESIGN CONDITIONS DESIGN NOTES ITEM AREA / QUANTITY SUN GAIN / FACTOR BTU/H Design Time 12 PM Month June at latitude0 N 1) Design air bypass factor = 0 TEMP DIFF 2) Design Off-Coil Temp. = Dewpoint Temp. SOLAR GAIN - EXTERNAL WINDOWS Glass 1/4" type Tinted Grey 3) No infiltration to cooling space 2 Glass N 0 Ft x 103 x 0.41 0 - shaded Yes 4) No duct heat gain 2 Glass NE 0 Ft x 66 x 0.41 0 2 Glass E 0 Ft x 18 x 0.41 0 Wall Material Heavy Weight Brick 2 Glass SE 0 Ft x 18 x 0.41 0 - thickness 4'' 2 Glass S 0 Ft x 18 x 0.41 0 SUMMARY 2 Glass SW 0 Ft x 18 x 0.41 0 Roof Material 2'' Insulated Metal Sheet Grand Total Heat : 630,523 Btu/hr 2 Glass W 0 Ft x 18 x 0.41 0 : 52.5 RT 2 Glass NW 0 Ft x 66 x 0.41 0 Partition Heavy Weight Brick Load per Unit Area : 78 Btu/hr.ft2 2 Skylight 0 Ft x 283 x 0.41 0 - thickness 4'' Total Sensible Heat : 408,637 Btu/hr Overhead ceiling Yes GSHR : 0.65 SOLAR & TRANS. GAIN - EXTERNAL WALLS & ROOF Ceiling below floor slab No 2 Wall N 0 Ft x 16 x 0.57 0 Space height clearance 12.0 Ft Without Bypass, 2 Wall NE 0 Ft x 41 x 0.57 0 Air Flow : 14,689 CFM 2 Wall E 0 Ft x 43 x 0.57 0 Occupant Factory Heavy Work : 1.82 CFM/Ft2 2 Wall SE 0 Ft x 23 x 0.57 0 : 280 CFM/RT 2 o Wall S 0 Ft x 17 x 0.57 0 Room DB Temp. 75 F Air Changes : 9.1 Times/Hr 2 Wall SW 0 Ft x 19 x 0.57 0 Room RH 55 % Outdoor Air : 7.6 % 2 Wall W 0 Ft x 23 x 0.57 0 2 Wall NW 0 Ft x 22 x 0.57 0 2 Roof - Sun 0 Ft x 35 x 0.13 0 Conditions FDB FWB %RH GR/LB Outdoor (OA) 93.0 82.0 148.9 TRANS. GAIN - EXTERNAL WINDOWS & INTERNAL PARTITIONS Room (RM) 75.0 55 71.5 2 All Glass 0 Ft x 18 x 1.10 0 Difference 18.0 77.4 2 Partition 0 Ft x 18 x 0.46 0 2 Floor slab above (exc. roof) 8,072 Ft x 18 x 0.27 39,230 SUPPLY AIR 2 Floor slab below 8,072 Ft x 18 x 0.57 82,819 OUTDOOR AIR Ventilation 125 Pax x 5 CFM/Pax = 625 2 2 INTERNAL SENSIBLE LOAD 8,072 Ft x 0.06 CFM/Ft = 484 People 125 persons x 530 Btu/hr.person 66,250 Duct infiltration 0.0 % = 0 Power Ft8,072 1.2 W/Ft2 x 3.41 Btu/hr.W 33,031 Lights Ft8,072 1.2 W/Ft2 x 3.41 Btu/hr.W 33,031 OUTDOOR AIR THRU APPARATUS = 1,109 CFMOA Other Sensible Heat Gains 20,000 W x 3.41 Btu/hr.W 68,200 SUB TOTAL 322,560 OFF-COIL TEMPERATURE & SUPPLY AIR QUANTITY Safety Factor 20 % 64,512 SHR 387,072 RSH = 0.70 ROOM SENSIBLE HEAT (RSH) 387,072 550,572 RTH o Off-Coil Temp. = 50.6 F DP 54.8 Gr/lb INTERNAL LATENT LOAD o People 125 persons x 930 Btu/hr.person 116,250 Allowable Temp. Rise = 24.4 F Other Latent Heat Gains 20,000 Btu/hr 20,000 o SUB TOTAL 136,250 On-Coil Temp. = 76.4 F 77.3 Gr/lb (w/o bypass OA mixture) Safety Factor 20 % 27,250 ROOM LATENT HEAT (RLH) 163,500 Supply Air 387,072 RSH = 14,689 CFMSA o 1.08 x 24.4 F Dehum. Rise ROOM TOTAL HEAT (RTH) 550,572 SUPPLY / BYPASS AIR QUANTITY (for bypass air design application only) OUTDOOR AIR HEAT Required? No o Sensible : 1,109 CFM x 18 F x 1.08 21,565 Latent : 1,109 CFM x 77 GR/LB x 0.68 58,386 Return Air or Blow-thru Fan HP 0
GRAND TOTAL HEAT (GTH) 630,523
20/6/2012 20:21 CONFIDENTIAL
M01 - HEAT LOAD CALCULATION
Project 31 Storeys Office Job No 9001 Revision 0
2 Location GF-Lettable Floor Area 10,991 Ft User SW DESIGN CONDITIONS DESIGN NOTES ITEM AREA / QUANTITY SUN GAIN / FACTOR BTU/H Design Time 4 PM Month Sep/Mar at latitude0 N 1) Design air bypass factor = 0 TEMP DIFF 2) Design Off-Coil Temp. = Dewpoint Temp. SOLAR GAIN - EXTERNAL WINDOWS Glass 1/4" type Tinted Grey 3) No infiltration to cooling space Glass N Ft2 x 15 x 0.41 0 - shaded Yes 4) No duct heat gain 2 Glass NE 830 Ft x 15 x 0.41 5,069 Glass E Ft2 x 15 x 0.41 0 Wall Material Light Weight Block 2 Glass SE 0 Ft x 15 x 0.41 0 - thickness 4'' Glass S Ft2 x 15 x 0.41 0 SUMMARY 2 Glass SW 830 Ft x 148 x 0.41 50,016 Roof Material 2'' Insulated Metal Sheet Grand Total Heat : 618,004 Btu/hr Glass W Ft2 x 209 x 0.41 0 : 51.5 RT 2 Glass NW 738 Ft x 148 x 0.41 44,472 Partition Light Weight Block Load per Unit Area : 56 Btu/hr.ft2 2 Skylight 0 Ft x 125 x 0.41 0 - thickness 4'' Total Sensible Heat : 530,691 Btu/hr Overhead ceiling Yes GSHR : 0.86 SOLAR & TRANS. GAIN - EXTERNAL WALLS & ROOF Ceiling below floor slab Yes 2 Wall N 0 Ft x 29 x 0.47 0 Space height clearance 12.0 Ft Without Bypass, 2 Wall NE 526 Ft x 31 x 0.47 7,664 Air Flow : 26,129 CFM 2 Wall E Ft x 31 x 0.47 0 Occupant Office Work : 2.38 CFM/Ft2 2 Wall SE 1,291 Ft x 38 x 0.47 23,057 : 507 CFM/RT 2 o Wall S Ft x 33 x 0.47 0 Room DB Temp. 75 F Air Changes : 11.9 Times/Hr 2 Wall SW 526 Ft x 55 x 0.47 13,597 Room RH 55 % Outdoor Air : 4.5 % 2 Wall W Ft x 49 x 0.47 0 2 Wall NW 600 Ft x 31 x 0.47 8,742 2 Roof - Sun Ft x 73 x 0.13 0 Conditions FDB FWB %RH GR/LB Outdoor (OA) 93.0 82.0 148.9 TRANS. GAIN - EXTERNAL WINDOWS & INTERNAL PARTITIONS Room (RM) 75.0 55 71.5 2 All Glass 2,398 Ft x 18 x 1.10 47,480 Difference 18.0 77.4 2 Partition 2,711 Ft x 18 x 0.39 19,031 2 Floor slab above (exc. roof) 10,991 Ft x 18 x 0.27 53,416 SUPPLY AIR 2 Floor slab below 10,991 Ft x 18 x 0.39 77,157 OUTDOOR AIR Ventilation 102 Pax x 5 CFM/Pax = 510 2 2 INTERNAL SENSIBLE LOAD 10,991 Ft x 0.06 CFM/Ft = 659 People 102 persons x 250 Btu/hr.person 25,500 Duct infiltration 0.0 % = 0 2 Power Ft10,991 0.9 W/Ft x 3.41 Btu/hr.W 34,481 2 Lights Ft10,991 1.4 W/Ft x 3.41 Btu/hr.W 52,096 OUTDOOR AIR THRU APPARATUS = 1,169 CFMOA Other Sensible Heat Gains W x 3.41 Btu/hr.W 0 SUB TOTAL 461,778 OFF-COIL TEMPERATURE & SUPPLY AIR QUANTITY Safety Factor 10 % 46,178 SHR 507,956 RSH = 0.95 ROOM SENSIBLE HEAT (RSH) 507,956 533,718 RTH o Off-Coil Temp. = 57.0 F DP 69.6 Gr/lb INTERNAL LATENT LOAD o People 102 persons x 210 Btu/hr.person 21,420 Allowable Temp. Rise = 18.0 F Other Latent Heat Gains 2,000 Btu/hr 2,000 o SUB TOTAL 23,420 On-Coil Temp. = 75.8 F 75.0 Gr/lb (w/o bypass OA mixture) Safety Factor 10 % 2,342 ROOM LATENT HEAT (RLH) 25,762 Supply Air 507,956 RSH = 26,129 CFMSA o 1.08 x 18.0 F Dehum. Rise ROOM TOTAL HEAT (RTH) 533,718 SUPPLY / BYPASS AIR QUANTITY (for bypass air design application only) OUTDOOR AIR HEAT Required? No o Sensible : 1,169 CFM x 18 F x 1.08 22,734 Latent : 1,169 CFM x 77 GR/LB x 0.68 61,551 Return Air or Blow-thru Fan HP 0
GRAND TOTAL HEAT (GTH) 618,004
20/6/2012 20:21 CONFIDENTIAL
M01 - HEAT LOAD CALCULATION
Project 31 Storeys Office Job No 9001 Revision 0
2 Location 1FL-Lettable & 2FL-Lettable Floor Area 8,721 Ft User SW DESIGN CONDITIONS DESIGN NOTES ITEM AREA / QUANTITY SUN GAIN / FACTOR BTU/H Design Time 4 PM Month Sep/Mar at latitude0 N 1) Design air bypass factor = 0 TEMP DIFF 2) Design Off-Coil Temp. = Dewpoint Temp. SOLAR GAIN - EXTERNAL WINDOWS Glass 1/4" type Tinted Grey 3) No infiltration to cooling space Glass N Ft2 x 15 x 0.41 0 - shaded Yes 4) No duct heat gain 2 Glass NE 830 Ft x 15 x 0.41 5,069 Glass E Ft2 x 15 x 0.41 0 Wall Material Light Weight Block 2 Glass SE 0 Ft x 15 x 0.41 0 - thickness 4'' Glass S Ft2 x 15 x 0.41 0 SUMMARY 2 Glass SW 830 Ft x 148 x 0.41 50,016 Roof Material 2'' Insulated Metal Sheet Grand Total Heat : 549,641 Btu/hr Glass W Ft2 x 209 x 0.41 0 : 45.8 RT 2 Glass NW 738 Ft x 148 x 0.41 44,472 Partition Light Weight Block Load per Unit Area : 63 Btu/hr.ft2 2 Skylight 0 Ft x 125 x 0.41 0 - thickness 4'' Total Sensible Heat : 479,874 Btu/hr Overhead ceiling Yes GSHR : 0.87 SOLAR & TRANS. GAIN - EXTERNAL WALLS & ROOF Ceiling below floor slab Yes 2 Wall N 0 Ft x 29 x 0.47 0 Space height clearance 12.0 Ft Without Bypass, 2 Wall NE 526 Ft x 31 x 0.47 7,664 Air Flow : 24,024 CFM 2 Wall E Ft x 31 x 0.47 0 Occupant Office Work : 2.75 CFM/Ft2 2 Wall SE 1,291 Ft x 38 x 0.47 23,057 : 524 CFM/RT 2 o Wall S Ft x 33 x 0.47 0 Room DB Temp. 75 F Air Changes : 13.8 Times/Hr 2 Wall SW 526 Ft x 55 x 0.47 13,597 Room RH 55 % Outdoor Air : 3.9 % 2 Wall W Ft x 49 x 0.47 0 2 Wall NW 600 Ft x 31 x 0.47 8,742 2 Roof - Sun Ft x 73 x 0.13 0 Conditions FDB FWB %RH GR/LB Outdoor (OA) 93.0 82.0 148.9 TRANS. GAIN - EXTERNAL WINDOWS & INTERNAL PARTITIONS Room (RM) 75.0 55 71.5 2 All Glass 2,398 Ft x 18 x 1.10 47,480 Difference 18.0 77.4 2 Partition 3,874 Ft x 18 x 0.39 27,195 2 Floor slab above (exc. roof) 8,721 Ft x 18 x 0.27 42,384 SUPPLY AIR 2 Floor slab below 8,721 Ft x 18 x 0.39 61,221 OUTDOOR AIR Ventilation 81 Pax x 5 CFM/Pax = 405 2 2 INTERNAL SENSIBLE LOAD 8,721 Ft x 0.06 CFM/Ft = 523 People 81 persons x 250 Btu/hr.person 20,250 Duct infiltration 0.0 % = 0 2 Power Ft8,721 0.9 W/Ft x 3.41 Btu/hr.W 27,360 2 Lights Ft8,721 1.4 W/Ft x 3.41 Btu/hr.W 41,337 OUTDOOR AIR THRU APPARATUS = 928 CFMOA Other Sensible Heat Gains W x 3.41 Btu/hr.W 0 SUB TOTAL 419,844 OFF-COIL TEMPERATURE & SUPPLY AIR QUANTITY Safety Factor 10 % 41,984 SHR 461,828 RSH = 0.96 ROOM SENSIBLE HEAT (RSH) 461,828 482,739 RTH o Off-Coil Temp. = 57.2 F DP 70.1 Gr/lb INTERNAL LATENT LOAD o People 81 persons x 210 Btu/hr.person 17,010 Allowable Temp. Rise = 17.8 F Other Latent Heat Gains 2,000 Btu/hr 2,000 o SUB TOTAL 19,010 On-Coil Temp. = 75.7 F 74.5 Gr/lb (w/o bypass OA mixture) Safety Factor 10 % 1,901 ROOM LATENT HEAT (RLH) 20,911 Supply Air 461,828 RSH = 24,024 CFMSA o 1.08 x 17.8 F Dehum. Rise ROOM TOTAL HEAT (RTH) 482,739 SUPPLY / BYPASS AIR QUANTITY (for bypass air design application only) OUTDOOR AIR HEAT Required? No o Sensible : 928 CFM x 18 F x 1.08 18,045 Latent : 928 CFM x 77 GR/LB x 0.68 48,856 Return Air or Blow-thru Fan HP 0
GRAND TOTAL HEAT (GTH) 549,641
20/6/2012 20:21 CONFIDENTIAL
M01 - HEAT LOAD CALCULATION
Project 31 Storeys Office Job No 9001 Revision 0
2 Location 3FL Fitness Centre Floor Area 13,486 Ft User SW DESIGN CONDITIONS DESIGN NOTES ITEM AREA / QUANTITY SUN GAIN / FACTOR BTU/H Design Time 4 PM Month Sep/Mar at latitude0 N 1) Design air bypass factor = 0 TEMP DIFF 2) Design Off-Coil Temp. = Dewpoint Temp. SOLAR GAIN - EXTERNAL WINDOWS Glass 1/4" type Tinted Grey 3) No infiltration to cooling space Glass N Ft2 x 15 x 0.41 0 - shaded Yes 4) No duct heat gain 2 Glass NE 830 Ft x 15 x 0.41 5,069 Glass E Ft2 x 15 x 0.41 0 Wall Material Light Weight Block 2 Glass SE 0 Ft x 15 x 0.41 0 - thickness 4'' Glass S Ft2 x 15 x 0.41 0 SUMMARY 2 Glass SW 830 Ft x 148 x 0.41 50,016 Roof Material 2'' Insulated Metal Sheet Grand Total Heat : 962,292 Btu/hr Glass W Ft2 x 209 x 0.41 0 : 80.2 RT 2 Glass NW 738 Ft x 148 x 0.41 44,472 Partition Light Weight Block Load per Unit Area : 71 Btu/hr.ft2 2 Skylight 0 Ft x 125 x 0.41 0 - thickness 4'' Total Sensible Heat : 712,014 Btu/hr Overhead ceiling Yes GSHR : 0.74 SOLAR & TRANS. GAIN - EXTERNAL WALLS & ROOF Ceiling below floor slab Yes 2 Wall N 0 Ft x 29 x 0.47 0 Space height clearance 12.0 Ft Without Bypass, 2 Wall NE 526 Ft x 31 x 0.47 7,664 Air Flow : 31,110 CFM 2 Wall E Ft x 31 x 0.47 0 Occupant Factory Heavy Work : 2.31 CFM/Ft2 2 Wall SE 1,291 Ft x 38 x 0.47 23,057 : 388 CFM/RT 2 o Wall S Ft x 33 x 0.47 0 Room DB Temp. 75 F Air Changes : 11.5 Times/Hr 2 Wall SW 526 Ft x 55 x 0.47 13,597 Room RH 55 % Outdoor Air : 6.6 % 2 Wall W Ft x 49 x 0.47 0 2 Wall NW 600 Ft x 31 x 0.47 8,742 2 Roof - Sun Ft x 73 x 0.13 0 Conditions FDB FWB %RH GR/LB Outdoor (OA) 93.0 82.0 148.9 TRANS. GAIN - EXTERNAL WINDOWS & INTERNAL PARTITIONS Room (RM) 75.0 55 71.5 2 All Glass 2,398 Ft x 18 x 1.10 47,480 Difference 18.0 77.4 2 Partition 3,874 Ft x 18 x 0.39 27,195 2 Floor slab above (exc. roof) 13,486 Ft x 18 x 0.27 65,542 SUPPLY AIR 2 Floor slab below 13,486 Ft x 18 x 0.39 94,672 OUTDOOR AIR Ventilation 125 Pax x 10 CFM/Pax = 1,250 2 2 INTERNAL SENSIBLE LOAD 13,486 Ft x 0.06 CFM/Ft = 809 People 125 persons x 530 Btu/hr.person 66,250 Duct infiltration 0.0 % = 0 2 Power Ft13,486 0.9 W/Ft x 3.41 Btu/hr.W 42,308 2 Lights Ft13,486 1.4 W/Ft x 3.41 Btu/hr.W 63,922 OUTDOOR AIR THRU APPARATUS = 2,059 CFMOA Other Sensible Heat Gains W x 3.41 Btu/hr.W 0 SUB TOTAL 559,987 OFF-COIL TEMPERATURE & SUPPLY AIR QUANTITY Safety Factor 20 % 111,997 SHR 671,984 RSH = 0.83 ROOM SENSIBLE HEAT (RSH) 671,984 813,884 RTH o Off-Coil Temp. = 55.0 F DP 64.6 Gr/lb INTERNAL LATENT LOAD o People 125 persons x 930 Btu/hr.person 116,250 Allowable Temp. Rise = 20.0 F Other Latent Heat Gains 2,000 Btu/hr 2,000 o SUB TOTAL 118,250 On-Coil Temp. = 76.2 F 76.6 Gr/lb (w/o bypass OA mixture) Safety Factor 20 % 23,650 ROOM LATENT HEAT (RLH) 141,900 Supply Air 671,984 RSH = 31,110 CFMSA o 1.08 x 20.0 F Dehum. Rise ROOM TOTAL HEAT (RTH) 813,884 SUPPLY / BYPASS AIR QUANTITY (for bypass air design application only) OUTDOOR AIR HEAT Required? No o Sensible : 2,059 CFM x 18 F x 1.08 40,030 Latent : 2,059 CFM x 77 GR/LB x 0.68 108,378 Return Air or Blow-thru Fan HP 0
GRAND TOTAL HEAT (GTH) 962,292
20/6/2012 20:21 CONFIDENTIAL
M01 - HEAT LOAD CALCULATION
Project 31 Storeys Office Job No 9001 Revision 0
2 Location 5FL-16FL Floor Area 13,613 Ft User SW DESIGN CONDITIONS DESIGN NOTES ITEM AREA / QUANTITY SUN GAIN / FACTOR BTU/H Design Time 4 PM Month Dec at latitude0 N 1) Design air bypass factor = 0 TEMP DIFF 2) Design Off-Coil Temp. = Dewpoint Temp. SOLAR GAIN - EXTERNAL WINDOWS Glass 1/4" type Tinted Grey 3) No infiltration to cooling space Glass N Ft2 x 14 x 0.41 0 - shaded Yes 4) No duct heat gain 2 Glass NE 1,160 Ft x 14 x 0.41 6,612 Glass E Ft2 x 14 x 0.41 0 Wall Material Light Weight Block 2 Glass SE 0 Ft x 14 x 0.41 0 - thickness 4'' Glass S Ft2 x 81 x 0.41 0 SUMMARY 2 Glass SW 1,160 Ft x 195 x 0.41 92,100 Roof Material 2'' Insulated Metal Sheet Grand Total Heat : 776,862 Btu/hr Glass W Ft2 x 184 x 0.41 0 : 64.7 RT 2 Glass NW 738 Ft x 83 x 0.41 24,940 Partition Light Weight Block Load per Unit Area : 57 Btu/hr.ft2 2 Skylight 0 Ft x 109 x 0.41 0 - thickness 4'' Total Sensible Heat : 668,915 Btu/hr Overhead ceiling Yes GSHR : 0.86 SOLAR & TRANS. GAIN - EXTERNAL WALLS & ROOF Ceiling below floor slab Yes 2 Wall N 0 Ft x 29 x 0.47 0 Space height clearance 12.0 Ft Without Bypass, 2 Wall NE 733 Ft x 30 x 0.47 10,335 Air Flow : 33,328 CFM 2 Wall E Ft x 31 x 0.47 0 Occupant Office Work : 2.45 CFM/Ft2 2 Wall SE 1,549 Ft x 41 x 0.47 29,849 : 515 CFM/RT 2 o Wall S Ft x 53 x 0.47 0 Room DB Temp. 75 F Air Changes : 12.2 Times/Hr 2 Wall SW 733 Ft x 63 x 0.47 21,704 Room RH 55 % Outdoor Air : 4.4 % 2 Wall W Ft x 47 x 0.47 0 2 Wall NW 600 Ft x 30 x 0.47 8,460 2 Roof - Sun Ft x 69 x 0.13 0 Conditions FDB FWB %RH GR/LB Outdoor (OA) 93.0 82.0 148.9 TRANS. GAIN - EXTERNAL WINDOWS & INTERNAL PARTITIONS Room (RM) 75.0 55 71.5 2 All Glass 3,058 Ft x 18 x 1.10 60,548 Difference 18.0 77.4 2 Partition 3,874 Ft x 18 x 0.39 27,195 2 Floor slab above (exc. roof) 13,613 Ft x 18 x 0.27 66,159 SUPPLY AIR 2 Floor slab below 13,613 Ft x 18 x 0.39 95,563 OUTDOOR AIR Ventilation 127 Pax x 5 CFM/Pax = 635 2 2 INTERNAL SENSIBLE LOAD 13,613 Ft x 0.06 CFM/Ft = 817 People 127 persons x 250 Btu/hr.person 31,750 Duct infiltration 0.0 % = 0 2 Power Ft13,613 0.9 W/Ft x 3.41 Btu/hr.W 42,707 2 Lights Ft13,613 1.4 W/Ft x 3.41 Btu/hr.W 64,524 OUTDOOR AIR THRU APPARATUS = 1,452 CFMOA Other Sensible Heat Gains W x 3.41 Btu/hr.W 0 SUB TOTAL 582,448 OFF-COIL TEMPERATURE & SUPPLY AIR QUANTITY Safety Factor 10 % 58,245 SHR 640,693 RSH = 0.95 ROOM SENSIBLE HEAT (RSH) 640,693 672,230 RTH o Off-Coil Temp. = 57.2 F DP 70.1 Gr/lb INTERNAL LATENT LOAD o People 127 persons x 210 Btu/hr.person 26,670 Allowable Temp. Rise = 17.8 F Other Latent Heat Gains 2,000 Btu/hr 2,000 o SUB TOTAL 28,670 On-Coil Temp. = 75.8 F 74.9 Gr/lb (w/o bypass OA mixture) Safety Factor 10 % 2,867 ROOM LATENT HEAT (RLH) 31,537 Supply Air 640,693 RSH = 33,328 CFMSA o 1.08 x 17.8 F Dehum. Rise ROOM TOTAL HEAT (RTH) 672,230 SUPPLY / BYPASS AIR QUANTITY (for bypass air design application only) OUTDOOR AIR HEAT Required? No o Sensible : 1,452 CFM x 18 F x 1.08 28,223 Latent : 1,452 CFM x 77 GR/LB x 0.68 76,410 Return Air or Blow-thru Fan HP 0
GRAND TOTAL HEAT (GTH) 776,862
20/6/2012 20:21 CONFIDENTIAL
M01 - HEAT LOAD CALCULATION
Project 31 Storeys Office Job No 9001 Revision 0
2 Location 10FL Floor Area 10,603 Ft User SW DESIGN CONDITIONS DESIGN NOTES ITEM AREA / QUANTITY SUN GAIN / FACTOR BTU/H Design Time 4 PM Month Dec at latitude0 N 1) Design air bypass factor = 0 TEMP DIFF 2) Design Off-Coil Temp. = Dewpoint Temp. SOLAR GAIN - EXTERNAL WINDOWS Glass 1/4" type Tinted Grey 3) No infiltration to cooling space Glass N Ft2 x 14 x 0.41 0 - shaded Yes 4) No duct heat gain 2 Glass NE 1,160 Ft x 14 x 0.41 6,612 Glass E Ft2 x 14 x 0.41 0 Wall Material Light Weight Block 2 Glass SE 0 Ft x 14 x 0.41 0 - thickness 4'' Glass S Ft2 x 81 x 0.41 0 SUMMARY 2 Glass SW 1,160 Ft x 195 x 0.41 92,100 Roof Material 2'' Insulated Metal Sheet Grand Total Heat : 674,172 Btu/hr Glass W Ft2 x 184 x 0.41 0 : 56.2 RT 2 Glass NW 738 Ft x 83 x 0.41 24,940 Partition Light Weight Block Load per Unit Area : 64 Btu/hr.ft2 2 Skylight 0 Ft x 109 x 0.41 0 - thickness 4'' Total Sensible Heat : 589,567 Btu/hr Overhead ceiling Yes GSHR : 0.87 SOLAR & TRANS. GAIN - EXTERNAL WALLS & ROOF Ceiling below floor slab Yes 2 Wall N 0 Ft x 29 x 0.47 0 Space height clearance 12.0 Ft Without Bypass, 2 Wall NE 733 Ft x 30 x 0.47 10,335 Air Flow : 29,524 CFM 2 Wall E Ft x 31 x 0.47 0 Occupant Office Work : 2.78 CFM/Ft2 2 Wall SE 1,549 Ft x 41 x 0.47 29,849 : 526 CFM/RT 2 o Wall S Ft x 53 x 0.47 0 Room DB Temp. 75 F Air Changes : 13.9 Times/Hr 2 Wall SW 733 Ft x 63 x 0.47 21,704 Room RH 55 % Outdoor Air : 3.8 % 2 Wall W Ft x 47 x 0.47 0 2 Wall NW 600 Ft x 30 x 0.47 8,460 2 Roof - Sun Ft x 69 x 0.13 0 Conditions FDB FWB %RH GR/LB Outdoor (OA) 93.0 82.0 148.9 TRANS. GAIN - EXTERNAL WINDOWS & INTERNAL PARTITIONS Room (RM) 75.0 55 71.5 2 All Glass 3,058 Ft x 18 x 1.10 60,548 Difference 18.0 77.4 2 Partition 3,874 Ft x 18 x 0.39 27,195 2 Floor slab above (exc. roof) 10,603 Ft x 18 x 0.27 51,531 SUPPLY AIR 2 Floor slab below 10,603 Ft x 18 x 0.39 74,433 OUTDOOR AIR Ventilation 99 Pax x 5 CFM/Pax = 495 2 2 INTERNAL SENSIBLE LOAD 10,603 Ft x 0.06 CFM/Ft = 636 People 99 persons x 250 Btu/hr.person 24,750 Duct infiltration 0.0 % = 0 Power Ft10,603 0.9 W/Ft2 x 3.41 Btu/hr.W 33,264 Lights Ft10,603 1.4 W/Ft2 x 3.41 Btu/hr.W 50,257 OUTDOOR AIR THRU APPARATUS = 1,131 CFMOA Other Sensible Heat Gains 0 W x 3.41 Btu/hr.W 0 SUB TOTAL 515,979 OFF-COIL TEMPERATURE & SUPPLY AIR QUANTITY Safety Factor 10 % 51,598 SHR 567,577 RSH = 0.96 ROOM SENSIBLE HEAT (RSH) 567,577 592,646 RTH o Off-Coil Temp. = 57.2 F DP 70.1 Gr/lb INTERNAL LATENT LOAD o People 99 persons x 210 Btu/hr.person 20,790 Allowable Temp. Rise = 17.8 F Other Latent Heat Gains 2,000 Btu/hr 2,000 o SUB TOTAL 22,790 On-Coil Temp. = 75.7 F 74.5 Gr/lb (w/o bypass OA mixture) Safety Factor 10 % 2,279 ROOM LATENT HEAT (RLH) 25,069 Supply Air 567,577 RSH = 29,524 CFMSA o 1.08 x 17.8 F Dehum. Rise ROOM TOTAL HEAT (RTH) 592,646 SUPPLY / BYPASS AIR QUANTITY (for bypass air design application only) OUTDOOR AIR HEAT Required? No o Sensible : 1,131 CFM x 18 F x 1.08 21,990 Latent : 1,131 CFM x 77 GR/LB x 0.68 59,536 Return Air or Blow-thru Fan HP 0
GRAND TOTAL HEAT (GTH) 674,172
20/6/2012 20:21 CONFIDENTIAL
M01 - HEAT LOAD CALCULATION
Project 31 Storeys Office Job No 9001 Revision 0
2 Location 20FL Floor Area 12,916 Ft User SW DESIGN CONDITIONS DESIGN NOTES ITEM AREA / QUANTITY SUN GAIN / FACTOR BTU/H Design Time 4 PM Month Dec at latitude0 N 1) Design air bypass factor = 0 TEMP DIFF 2) Design Off-Coil Temp. = Dewpoint Temp. SOLAR GAIN - EXTERNAL WINDOWS Glass 1/4" type Tinted Grey 3) No infiltration to cooling space Glass N Ft2 x 14 x 0.41 0 - shaded Yes 4) No duct heat gain 2 Glass NE 1,160 Ft x 14 x 0.41 6,612 Glass E Ft2 x 14 x 0.41 0 Wall Material Light Weight Block 2 Glass SE 0 Ft x 14 x 0.41 0 - thickness 4'' Glass S Ft2 x 81 x 0.41 0 SUMMARY 2 Glass SW 1,160 Ft x 195 x 0.41 92,100 Roof Material 2'' Insulated Metal Sheet Grand Total Heat : 752,636 Btu/hr Glass W Ft2 x 184 x 0.41 0 : 62.7 RT 2 Glass NW 738 Ft x 83 x 0.41 24,940 Partition Light Weight Block Load per Unit Area : 58 Btu/hr.ft2 2 Skylight 0 Ft x 109 x 0.41 0 - thickness 4'' Total Sensible Heat : 650,349 Btu/hr Overhead ceiling Yes GSHR : 0.86 SOLAR & TRANS. GAIN - EXTERNAL WALLS & ROOF Ceiling below floor slab Yes 2 Wall N 0 Ft x 29 x 0.47 0 Space height clearance 12.0 Ft Without Bypass, 2 Wall NE 733 Ft x 30 x 0.47 10,335 Air Flow : 32,440 CFM 2 Wall E Ft x 31 x 0.47 0 Occupant Office Work : 2.51 CFM/Ft2 2 Wall SE 1,549 Ft x 41 x 0.47 29,849 : 517 CFM/RT 2 o Wall S Ft x 53 x 0.47 0 Room DB Temp. 75 F Air Changes : 12.6 Times/Hr 2 Wall SW 733 Ft x 63 x 0.47 21,704 Room RH 55 % Outdoor Air : 4.2 % 2 Wall W Ft x 47 x 0.47 0 2 Wall NW 600 Ft x 30 x 0.47 8,460 2 Roof - Sun Ft x 69 x 0.13 0 Conditions FDB FWB %RH GR/LB Outdoor (OA) 93.0 82.0 148.9 TRANS. GAIN - EXTERNAL WINDOWS & INTERNAL PARTITIONS Room (RM) 75.0 55 71.5 2 All Glass 3,058 Ft x 18 x 1.10 60,548 Difference 18.0 77.4 2 Partition 3,874 Ft x 18 x 0.39 27,195 2 Floor slab above (exc. roof) 12,916 Ft x 18 x 0.27 62,772 SUPPLY AIR 2 Floor slab below 12,916 Ft x 18 x 0.39 90,670 OUTDOOR AIR Ventilation 120 Pax x 5 CFM/Pax = 600 2 2 INTERNAL SENSIBLE LOAD 12,916 Ft x 0.06 CFM/Ft = 775 People 120 persons x 250 Btu/hr.person 30,000 Duct infiltration 0.0 % = 0 Power Ft12,916 0.9 W/Ft2 x 3.41 Btu/hr.W 40,520 Lights Ft12,916 1.4 W/Ft2 x 3.41 Btu/hr.W 61,221 OUTDOOR AIR THRU APPARATUS = 1,375 CFMOA Other Sensible Heat Gains 0 W x 3.41 Btu/hr.W 0 SUB TOTAL 566,927 OFF-COIL TEMPERATURE & SUPPLY AIR QUANTITY Safety Factor 10 % 56,693 SHR 623,620 RSH = 0.95 ROOM SENSIBLE HEAT (RSH) 623,620 653,540 RTH o Off-Coil Temp. = 57.2 F DP 70.1 Gr/lb INTERNAL LATENT LOAD o People 120 persons x 210 Btu/hr.person 25,200 Allowable Temp. Rise = 17.8 F Other Latent Heat Gains 2,000 Btu/hr 2,000 o SUB TOTAL 27,200 On-Coil Temp. = 75.8 F 74.8 Gr/lb (w/o bypass OA mixture) Safety Factor 10 % 2,720 ROOM LATENT HEAT (RLH) 29,920 Supply Air 623,620 RSH = 32,440 CFMSA o 1.08 x 17.8 F Dehum. Rise ROOM TOTAL HEAT (RTH) 653,540 SUPPLY / BYPASS AIR QUANTITY (for bypass air design application only) OUTDOOR AIR HEAT Required? No o Sensible : 1,375 CFM x 18 F x 1.08 26,729 Latent : 1,375 CFM x 77 GR/LB x 0.68 72,367 Return Air or Blow-thru Fan HP 0
GRAND TOTAL HEAT (GTH) 752,636
20/6/2012 20:21 CONFIDENTIAL
M01 - HEAT LOAD CALCULATION
Project 31 Storeys Office Job No 9001 Revision 0
2 Location 17FL-26FL Floor Area 14,025 Ft User SW DESIGN CONDITIONS DESIGN NOTES ITEM AREA / QUANTITY SUN GAIN / FACTOR BTU/H Design Time 4 PM Month Dec at latitude0 N 1) Design air bypass factor = 0 TEMP DIFF 2) Design Off-Coil Temp. = Dewpoint Temp. SOLAR GAIN - EXTERNAL WINDOWS Glass 1/4" type Tinted Grey 3) No infiltration to cooling space Glass N Ft2 x 14 x 0.41 0 - shaded Yes 4) No duct heat gain 2 Glass NE 1,160 Ft x 14 x 0.41 6,612 Glass E Ft2 x 14 x 0.41 0 Wall Material Light Weight Block 2 Glass SE 0 Ft x 14 x 0.41 0 - thickness 4'' Glass S Ft2 x 81 x 0.41 0 SUMMARY 2 Glass SW 1,160 Ft x 195 x 0.41 92,100 Roof Material 2'' Insulated Metal Sheet Grand Total Heat : 790,197 Btu/hr Glass W Ft2 x 184 x 0.41 0 : 65.8 RT 2 Glass NW 738 Ft x 83 x 0.41 24,940 Partition Light Weight Block Load per Unit Area : 56 Btu/hr.ft2 2 Skylight 0 Ft x 109 x 0.41 0 - thickness 4'' Total Sensible Heat : 679,466 Btu/hr Overhead ceiling Yes GSHR : 0.86 SOLAR & TRANS. GAIN - EXTERNAL WALLS & ROOF Ceiling below floor slab Yes 2 Wall N 0 Ft x 29 x 0.47 0 Space height clearance 12.0 Ft Without Bypass, 2 Wall NE 733 Ft x 30 x 0.47 10,335 Air Flow : 33,460 CFM 2 Wall E Ft x 31 x 0.47 0 Occupant Office Work : 2.39 CFM/Ft2 2 Wall SE 1,549 Ft x 41 x 0.47 29,849 : 508 CFM/RT 2 o Wall S Ft x 53 x 0.47 0 Room DB Temp. 75 F Air Changes : 11.9 Times/Hr 2 Wall SW 733 Ft x 63 x 0.47 21,704 Room RH 55 % Outdoor Air : 4.5 % 2 Wall W Ft x 47 x 0.47 0 2 Wall NW 600 Ft x 30 x 0.47 8,460 2 Roof - Sun Ft x 69 x 0.13 0 Conditions FDB FWB %RH GR/LB Outdoor (OA) 93.0 82.0 148.9 TRANS. GAIN - EXTERNAL WINDOWS & INTERNAL PARTITIONS Room (RM) 75.0 55 71.5 2 All Glass 3,058 Ft x 18 x 1.10 60,548 Difference 18.0 77.4 2 Partition 3,874 Ft x 18 x 0.39 27,195 2 Floor slab above (exc. roof) 14,025 Ft x 18 x 0.27 68,162 SUPPLY AIR 2 Floor slab below 14,025 Ft x 18 x 0.39 98,456 OUTDOOR AIR Ventilation 130 Pax x 5 CFM/Pax = 650 2 2 INTERNAL SENSIBLE LOAD 14,025 Ft x 0.06 CFM/Ft = 842 People 130 persons x 250 Btu/hr.person 32,500 Duct infiltration 0.0 % = 0 2 Power Ft14,025 0.9 W/Ft x 3.41 Btu/hr.W 43,999 2 Lights Ft14,025 1.4 W/Ft x 3.41 Btu/hr.W 66,477 OUTDOOR AIR THRU APPARATUS = 1,492 CFMOA Other Sensible Heat Gains W x 3.41 Btu/hr.W 0 SUB TOTAL 591,338 OFF-COIL TEMPERATURE & SUPPLY AIR QUANTITY Safety Factor 10 % 59,134 SHR 650,472 RSH = 0.95 ROOM SENSIBLE HEAT (RSH) 650,472 682,702 RTH o Off-Coil Temp. = 57.0 F DP 69.6 Gr/lb INTERNAL LATENT LOAD o People 130 persons x 210 Btu/hr.person 27,300 Allowable Temp. Rise = 18.0 F Other Latent Heat Gains 2,000 Btu/hr 2,000 o SUB TOTAL 29,300 On-Coil Temp. = 75.8 F 75.0 Gr/lb (w/o bypass OA mixture) Safety Factor 10 % 2,930 ROOM LATENT HEAT (RLH) 32,230 Supply Air 650,472 RSH = 33,460 CFMSA o 1.08 x 18.0 F Dehum. Rise ROOM TOTAL HEAT (RTH) 682,702 SUPPLY / BYPASS AIR QUANTITY (for bypass air design application only) OUTDOOR AIR HEAT Required? No o Sensible : 1,492 CFM x 18 F x 1.08 28,995 Latent : 1,492 CFM x 77 GR/LB x 0.68 78,501 Return Air or Blow-thru Fan HP 0
GRAND TOTAL HEAT (GTH) 790,197
20/6/2012 20:21 CONFIDENTIAL
M01 - HEAT LOAD CALCULATION
Project 31 Storeys Office Job No 9001 Revision 0
2 Location 27FL-30FL Floor Area 14,373 Ft User SW DESIGN CONDITIONS DESIGN NOTES ITEM AREA / QUANTITY SUN GAIN / FACTOR BTU/H Design Time 4 PM Month Dec at latitude0 N 1) Design air bypass factor = 0 TEMP DIFF 2) Design Off-Coil Temp. = Dewpoint Temp. SOLAR GAIN - EXTERNAL WINDOWS Glass 1/4" type Tinted Grey 3) No infiltration to cooling space Glass N Ft2 x 14 x 0.41 0 - shaded Yes 4) No duct heat gain 2 Glass NE 1,160 Ft x 14 x 0.41 6,612 Glass E Ft2 x 14 x 0.41 0 Wall Material Light Weight Block 2 Glass SE 0 Ft x 14 x 0.41 0 - thickness 4'' Glass S Ft2 x 81 x 0.41 0 SUMMARY 2 Glass SW 1,160 Ft x 195 x 0.41 92,100 Roof Material 2'' Insulated Metal Sheet Grand Total Heat : 801,864 Btu/hr Glass W Ft2 x 184 x 0.41 0 : 66.8 RT 2 Glass NW 738 Ft x 83 x 0.41 24,940 Partition Light Weight Block Load per Unit Area : 56 Btu/hr.ft2 2 Skylight 0 Ft x 109 x 0.41 0 - thickness 4'' Total Sensible Heat : 688,552 Btu/hr Overhead ceiling Yes GSHR : 0.86 SOLAR & TRANS. GAIN - EXTERNAL WALLS & ROOF Ceiling below floor slab Yes 2 Wall N 0 Ft x 29 x 0.47 0 Space height clearance 12.0 Ft Without Bypass, 2 Wall NE 733 Ft x 30 x 0.47 10,335 Air Flow : 33,892 CFM 2 Wall E Ft x 31 x 0.47 0 Occupant Office Work : 2.36 CFM/Ft2 2 Wall SE 1,549 Ft x 41 x 0.47 29,849 : 507 CFM/RT 2 o Wall S Ft x 53 x 0.47 0 Room DB Temp. 75 F Air Changes : 11.8 Times/Hr 2 Wall SW 733 Ft x 63 x 0.47 21,704 Room RH 55 % Outdoor Air : 4.5 % 2 Wall W Ft x 47 x 0.47 0 2 Wall NW 600 Ft x 30 x 0.47 8,460 2 Roof - Sun Ft x 69 x 0.13 0 Conditions FDB FWB %RH GR/LB Outdoor (OA) 93.0 82.0 148.9 TRANS. GAIN - EXTERNAL WINDOWS & INTERNAL PARTITIONS Room (RM) 75.0 55 71.5 2 All Glass 3,058 Ft x 18 x 1.10 60,548 Difference 18.0 77.4 2 Partition 3,874 Ft x 18 x 0.39 27,195 2 Floor slab above (exc. roof) 14,373 Ft x 18 x 0.27 69,853 SUPPLY AIR 2 Floor slab below 14,373 Ft x 18 x 0.39 100,898 OUTDOOR AIR Ventilation 133 Pax x 5 CFM/Pax = 665 2 2 INTERNAL SENSIBLE LOAD 14,373 Ft x 0.06 CFM/Ft = 862 People 133 persons x 250 Btu/hr.person 33,250 Duct infiltration 0.0 % = 0 Power Ft14,373 0.9 W/Ft2 x 3.41 Btu/hr.W 45,091 Lights Ft14,373 1.4 W/Ft2 x 3.41 Btu/hr.W 68,127 OUTDOOR AIR THRU APPARATUS = 1,527 CFMOA Other Sensible Heat Gains 0 W x 3.41 Btu/hr.W 0 SUB TOTAL 598,963 OFF-COIL TEMPERATURE & SUPPLY AIR QUANTITY Safety Factor 10 % 59,896 SHR 658,860 RSH = 0.95 ROOM SENSIBLE HEAT (RSH) 658,860 691,783 RTH o Off-Coil Temp. = 57.0 F DP 69.6 Gr/lb INTERNAL LATENT LOAD o People 133 persons x 210 Btu/hr.person 27,930 Allowable Temp. Rise = 18.0 F Other Latent Heat Gains 2,000 Btu/hr 2,000 o SUB TOTAL 29,930 On-Coil Temp. = 75.8 F 75.0 Gr/lb (w/o bypass OA mixture) Safety Factor 10 % 2,993 ROOM LATENT HEAT (RLH) 32,923 Supply Air 658,860 RSH = 33,892 CFMSA o 1.08 x 18.0 F Dehum. Rise ROOM TOTAL HEAT (RTH) 691,783 SUPPLY / BYPASS AIR QUANTITY (for bypass air design application only) OUTDOOR AIR HEAT Required? No o Sensible : 1,527 CFM x 18 F x 1.08 29,692 Latent : 1,527 CFM x 77 GR/LB x 0.68 80,389 Return Air or Blow-thru Fan HP 0
GRAND TOTAL HEAT (GTH) 801,864
20/6/2012 20:21 CONFIDENTIAL
M01 - HEAT LOAD CALCULATION
Project 31 Storeys Office Job No 9001 Revision 0
2 Location Bistro Floor Area 3,138 Ft User SW DESIGN CONDITIONS DESIGN NOTES ITEM AREA / QUANTITY SUN GAIN / FACTOR BTU/H Design Time 4 PM Month Dec at latitude0 N 1) Design air bypass factor = 0 TEMP DIFF 2) Design Off-Coil Temp. = Dewpoint Temp. SOLAR GAIN - EXTERNAL WINDOWS Glass 1/4" type Tinted Grey 3) No infiltration to cooling space Glass N Ft2 x 14 x 0.41 0 - shaded Yes 4) No duct heat gain 2 Glass NE 290 Ft x 14 x 0.41 1,653 Glass E Ft2 x 14 x 0.41 0 Wall Material Light Weight Block 2 Glass SE 0 Ft x 14 x 0.41 0 - thickness 4'' Glass S Ft2 x 81 x 0.41 0 SUMMARY 2 Glass SW 290 Ft x 195 x 0.41 23,025 Roof Material 2'' Insulated Metal Sheet Grand Total Heat : 232,518 Btu/hr Glass W Ft2 x 184 x 0.41 0 : 19.4 RT 2 Glass NW 185 Ft x 83 x 0.41 6,252 Partition Light Weight Block Load per Unit Area : 74 Btu/hr.ft2 2 Skylight 0 Ft x 109 x 0.41 0 - thickness 4'' Total Sensible Heat : 174,095 Btu/hr Overhead ceiling Yes GSHR : 0.75 SOLAR & TRANS. GAIN - EXTERNAL WALLS & ROOF Ceiling below floor slab Yes 2 Wall N 0 Ft x 29 x 0.47 0 Space height clearance 12.0 Ft Without Bypass, 2 Wall NE 183 Ft x 30 x 0.47 2,580 Air Flow : 7,670 CFM 2 Wall E Ft x 31 x 0.47 0 Occupant Factory Average Work : 2.44 CFM/Ft2 2 Wall SE 387 Ft x 41 x 0.47 7,457 : 396 CFM/RT 2 o Wall S Ft x 53 x 0.47 0 Room DB Temp. 75 F Air Changes : 12.2 Times/Hr 2 Wall SW 183 Ft x 63 x 0.47 5,419 Room RH 55 % Outdoor Air : 5.6 % 2 Wall W Ft x 47 x 0.47 0 2 Wall NW 600 Ft x 30 x 0.47 8,460 2 Roof - Sun Ft x 69 x 0.13 0 Conditions FDB FWB %RH GR/LB Outdoor (OA) 93.0 82.0 148.9 TRANS. GAIN - EXTERNAL WINDOWS & INTERNAL PARTITIONS Room (RM) 75.0 55 71.5 2 All Glass 765 Ft x 18 x 1.10 15,147 Difference 18.0 77.4 2 Partition 0 Ft x 18 x 0.39 0 2 Floor slab above (exc. roof) 3,138 Ft x 18 x 0.27 15,251 SUPPLY AIR 2 Floor slab below 3,138 Ft x 18 x 0.39 22,029 OUTDOOR AIR Ventilation 49 Pax x 5 CFM/Pax = 245 2 2 INTERNAL SENSIBLE LOAD 3,138 Ft x 0.06 CFM/Ft = 188 People 49 persons x 380 Btu/hr.person 18,620 Duct infiltration 0.0 % = 0 Power Ft3,138 0.9 W/Ft2 x 3.41 Btu/hr.W 9,845 Lights Ft3,138 1.4 W/Ft2 x 3.41 Btu/hr.W 14,874 OUTDOOR AIR THRU APPARATUS = 433 CFMOA Other Sensible Heat Gains 0 W x 3.41 Btu/hr.W 0 SUB TOTAL 150,611 OFF-COIL TEMPERATURE & SUPPLY AIR QUANTITY Safety Factor 10 % 15,061 SHR 165,672 RSH = 0.82 ROOM SENSIBLE HEAT (RSH) 165,672 201,290 RTH o Off-Coil Temp. = 55.0 F DP 64.6 Gr/lb INTERNAL LATENT LOAD o People 49 persons x 620 Btu/hr.person 30,380 Allowable Temp. Rise = 20.0 F Other Latent Heat Gains 2,000 Btu/hr 2,000 o SUB TOTAL 32,380 On-Coil Temp. = 76.0 F 75.9 Gr/lb (w/o bypass OA mixture) Safety Factor 10 % 3,238 ROOM LATENT HEAT (RLH) 35,618 Supply Air 165,672 RSH = 7,670 CFMSA o 1.08 x 20.0 F Dehum. Rise ROOM TOTAL HEAT (RTH) 201,290 SUPPLY / BYPASS AIR QUANTITY (for bypass air design application only) OUTDOOR AIR HEAT Required? No o Sensible : 433 CFM x 18 F x 1.08 8,423 Latent : 433 CFM x 77 GR/LB x 0.68 22,804 Return Air or Blow-thru Fan HP 0