Transformers
Transformers
Transformers
The impedance, voltage regulation, efficiency, and similar calculations for three-
phase transformers are done on a per-phase basis.
WYE-WYE CONNECTION
This connection is shown below.
Both the unbalance problem and the third-harmonic problem can be solved using one
of two techniques:
1) Solidly ground the neutrals of the transformers, especially the primary winding's
neutral. This connection permits the additive third-harmonic components to cause a
current flow in the neutral instead of building up large voltages. The neutral also
provides a return path for any current imbalances in the load.
The -connected tertiary windings need not even be brought out of the transformer
case, but they often are used to supply lights and auxiliary power within the substation
where it is located. The tertiary windings must be large enough to handle the
circulating currents, so they are usually made about one-third the power rating of the
two main windings.
One or the other of these correction techniques must be used any time a Y-Y
transformer is installed. In practice, very few Y - Y transformers are used, since the
same jobs can be done by one of the other types of three-phase transformers.
WYE-DELTA CONNECTION
This connection is shown in the following figure.
This arrangement does have one problem, though. Because of the connection, the
secondary voltage is shifted 30° relative to the primary voltage of the transformer.
The fact that a phase shift has occurred can cause problems in paralleling the
secondaries of two transformer banks together. The phase angles of transformer
secondaries must be equal if they are to be paralleled, which means that attention
must be paid to the direction of the 30° phase shift occuring in each transformer bank
to be paralleled together.
Notice that, the connection shown in the previous figure will cause the secondary
voltage to be lagging if the system phase sequence is abc (positive sequence). If the
system phase sequence is acb (negative sequence), then the secondary voltage will be
leading the primary voltage by 30°.
This connection has the same advantages and the same phase shift as the Y-
transformer. The connection shown in the previous figure makes the secondary
voltage lag the primary voltage by 30 0 , as before.
DELTA-DELTA CONNECTION.
This connection is shown in the figure below.
In this connection:
V LP VP and V LS VS , thus: