Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Three-Phase To Two-Phase/One-Phase Conversion Using TWO TRANSFORMERS (Scott Connection)

Download as pdf or txt
Download as pdf or txt
You are on page 1of 13

Experiment No.

5a

THREE-PHASE TO TWO-PHASE/ONE-PHASE CONVERSION USING


TWO TRANSFORMERS (Scott Connection)
INTRODUCTION:
Phase conversion from three to two phase is needed in special cases, such as in supplying 2-phase electric arc
furnaces. Scott connection of two-single phase transformers is employed for conversion of a three-phase system to two
phase system or vice-versa. Rating of one transformer should be 15% greater than that of the other, but in practical two
identical transformers are used for interchangeability and spares. The connection scheme, known as Scott connections
is as shown in the figure 1, 50% tap of one transformer (Main transformer) is connected to 86.6% tap of the other
transformer (Teaser transformer). The secondaries for balanced supply system have equal number of turns.

AIM:
1) To obtain balanced two-phase supply from three-phase supply by Scott arrangement of two transformers.
2) To perform load test at unity power factor for both balanced and unbalanced loads and compare the test results
with predictions.
3) To obtain single-phase supply from three-phase supply by Scott arrangement and perform load test at unity
power factor.

THEORY:
Consider the Scott connection of two single-phase transformers with turns ratio N1:N2 as shown in figure 1.
The phase diagram of line voltages on the primary side, VAB, VBC, VCA form an equilateral triangle.
Let,

The secondary voltage of the main transformer is given by,

The voltage VAM is given by,

This voltage VAM is across (3/2)*N1 turns. Therefore, the primary voltage (across N1 turns) of teaser transformer is
given by,

Hence, the secondary voltage of the teaser transformer is given by,

Hence, from equations (4) and (8) we can see that, for a balanced three-phase supply on the primary side, the voltages
on the secondary side of the transformers are equal in magnitude but 90 degrees out of phase. Therefore we got a
balanced two-phase supply from balanced three-phase supply using Scott connection.
If the secondary load currents are Ia and Ib , then the primary currents can be obtained as follows,

The Phasor diagrams for balanced and unbalanced unity power factor load are shown in figure 2. Note that for balanced
load, the two secondary currents are equal (Ia=Ib) in magnitude and the three primary currents are also equal (IA=IB=IC)
in magnitude.
To get single-phase voltage supply, short negative polarity side of teaser transformer and positive polarity of main
transformer on secondary side and take the voltage across positive polarity of teaser transformer and negative polarity
of main transformer on secondary side. This single phase voltage is given by,

Since, Va and Vb are 90 degrees apart.


In case of single-phase configuration, the secondary currents of teaser and main transformer are same i.e.,

Substituting equation (14) in equations (9), (10), (11) and (12) we can get the currents on primary side.

PROCEDURE:
1)
2)
3)
4)
5)

6)
7)
8)

9)
10)

Perform polarity test of the two single-phase transformers and find the polarities.
Connect the circuit as shown in the figure 1 for three-phase to two-phase conversion.
The three-phase balanced supply should be given to the circuit through auto-transformer and switch S1.
With switch S2 open, close S1 to supply rated voltage on primary side. Note down the voltages on primary
and secondary sides of teaser and main transformers.
Start with balanced load on the secondary side (ZL1=ZL2). Close S2 and take all the ammeter and voltmeter
readings. (Note that for balanced load the two secondary currents are equal and the three primary currents are
equal. Else, it implies that the load is unbalanced).
Now keep unbalanced load on secondary side and take all the voltmeter and ammeter readings. Repeat this for
3 more sets of unbalanced load.
Verify the results with theoretical predictions and draw Phasor diagrams.
For three-phase to single-phase conversion, short the negative polarity side of teaser transformer and positive
polarity side of main transformer in the previous circuit. Note the load is kept across positive polarity side of
teaser and negative polarity side of main transformer. (Note that the single-phase voltage is higher than the
secondary voltage in two-phase conversion (equation 13) and connect the load accordingly. If necessary
connect two loads in series to maintain the rated voltage of load greater than or equal to single-phase voltage.)
Keep load at some value and note down all the voltmeter and ammeter readings.
Verify the results with theoretical predictions and draw Phasor diagrams.

IA

THREE
PHASE
SUPPLY IB

a2

V1

Ib

b1
b2

ZL1

T1/2
0.5

Va

a1

T1/2

IC

A1

0.866T1
0.866

Ia

ZL2

Vb
V2
A2

Fig. 1: Connection for load test with Scott connected transformers

A
a2

1.15 Ia

Ib

Ia

Ib

0.58 Ia

0.58 Ia
a1
C

b2

b1

Ib

A
1.15Ia
IA
0.58 Ia
IC

a2

Ib
Ia

n
Ib
a1

Ib B
IB

b2

b1

0.58 Ia

Fig. 2: Phasor diagrams (a) Balanced unity power factor load and (b) Unbalanced load

Experiment No. 5b
THREE PHASE CONNECTION OF SINGLE-PHASE TRANSFORMERS
(Vector Groups)

Introduction
Advantages of dealing with three-phase power instead of single-phase power are well known. The
requirements of three-phase transmission/distribution system make it necessary to employ three-phase
voltage transformation at the sending end as well as the receiving end. Three single-phase transformers are
often used for this purpose instead of a single three-phase unit. This reduces the cost of spare and also
installation/transportation becomes easier. The single-phase transformers may be connected in different
ways to suit specific requirements. For equal transformation ratio of the phase windings (i.e. the individual
single-phase units), the ratio of the line voltages and their phase relations depend on the mode of connection
of the transformers.

Objective
The main objectives of the experiment are listed below:
1. To connect three single-phase transformers in (a) Star/star, (b) Star/delta, (c) Delta/star, (d)
Delta/delta, and to obtain the no-load line voltage ratios and phase relations for each connection.
2. To study the voltage and/or current waveforms for different connections.
3. To obtain triple-frequency components of exciting currents, or triple-frequency induced voltages
that appear owing to different phase connections.

Theory
From an economic point of view, a transformer is designed to operate in the saturation region of the
magnetic core. This makes the exciting current non-sinusoidal [1, 2]. The exciting current contains the
fundamental and all odd harmonics, third one being the predominant one. Thus, for all practical purposes,
harmonics greater than third can be neglected. This section describes how these harmonics are generated in
various connections and ways to limit their effect. The ratio of line quantities and phase relations for each
connection is also described.

A1

A2

In
Vn

A1
n B1
C1

C2

V2

b1

Vph1

V1

a2

a2

a1

b2
c1

b2

B2

Iph2

c2

c2

A2

a2
30

b2

c2

C2

B2
A2 a2
b2
c2
C2

B2

Fig. 3(a) Star-Delta Connection of Three Phase Transformers

Star/delta connection: Consider the system shown in Fig. 3(a). The primary windings are connected in star
and the neutral point of the supply is available. The secondary windings are connected in delta. To start with,
let us consider that the secondary delta is not closed (say, one arm is open). If the neutral of the primary star
is connected to the system ground, the exciting currents of the three phases are given as

ia = 2 I ph1 sin (t ) + 2 I ph3 sin 3(t )

ib = 2 I ph1 sin (t 120) + 2 I ph3 sin 3(t 120)


= 2 I ph1 sin (t 120) + 2 I ph3 sin 3(t )
ic = 2 I ph1 sin (t + 120) + 2 I ph3 sin 3(t + 120)
= 2 I ph1 sin (t + 120) + 2 I ph3 sin 3(t )
Where, I ph1 and I ph3 are the r.m.s. values of the fundamental and the third harmonic phase currents
respectively and is the power factor angle. It can be noted that the fundamental currents in the windings
are phase shifted by 120 from each other, while the third harmonic currents are all in phase (co-phasal). The
neutral line carries the sum of the three third harmonic currents, in, but no fundamental.

in = 3 2 I ph3 sin 3(t )

As the exciting current is non-sinusoidal, the flux in the core and hence the induced voltages in both
the windings will be sinusoidal.
Next, consider the case when the neutral of the primary is kept isolated and the secondary continues
to be open delta. The third harmonic currents cannot flow in the primary windings; hence the primary
currents are essentially sinusoidal. The flux will be non-sinusoidal because of nonlinear B-H characteristics
of the magnetic core, and it contains third harmonic components (higher order harmonics neglected as
before). This will induce third harmonic voltage in the windings. The phase voltages are therefore nonsinusoidal, containing the fundamental and third harmonic voltages.

v a = 2V

ph1sin t

+ 2V ph3 sin 3t

vb = 2V ph1 sin (t 120) + 2Vm3 sin 3(t 120)


vc = 2V ph1 sin (t + 120) + 2V ph3 sin 3(t + 120)
Where, V ph1 and V ph3 are the r.m.s. value of the fundamental and the third harmonic components of phase
voltage respectively. The r.m.s. value of the net phase voltage, Vph is given by
2
2
V ph = V ph
+ V ph
1
3

The line voltage is given by

v ab = v a vb = 2V ph1 sin t 2V ph1 sin (t 120)


Note that although the phase voltages have third harmonic components, the line voltages do not. Therefore,
the ratio of line voltages of primary and secondary is

3 N1 N 2 : 1 , where N1 and N2 are the number of

turns of primary and secondary winding respectively.


The open delta voltage of the secondary is

v 0 = v a + vb + vc = 3 2V ph3 sin 3t
The voltage across the open delta is the sum of the three third harmonic voltages induced in the secondary
windings. Now, under this condition, if the delta is closed then the net third harmonic voltage will give rise
to a third harmonic current which will circulate in the delta connected windings. This will partly provide the
missing third harmonic component of the primary exciting current and consequently the flux and induced
voltage will be close to sinusoidal [2].
It can be seen from the emf phasor diagram that if the transformers are connected in Yd11 and A2
and a2 are joined, the following conditions hold

VC2 Vc2 = V B2 Vc2


VC2 Vb2 > V B2 Vb2

A1

a2

A2

a2
V1

V1

Vph1

In
Vn

C
B

C2

A1
n B1
C1
B2

a1

V2

n
c1 b1

c2

b2

b2
c2

a2

A2

n
C2

B2

c2

b2

Fig. 3(b) Star-Star Connection of Three Phase Transformers

Star/star connection (Fig. 3(b)): Similar to the Star/delta connection with no neutral and open delta, the
triple frequency components of the excitation currents are suppressed thereby causing large triple frequency
components in flux variation. Triple frequency component will be present in the phase voltages of both the
windings, but these will not appear in the line voltages. For such connections the ratio of line voltages of
primary and secondary is N1 N 2 : 1 . The neutral point voltage will be

v 0 = 3 2V ph3 sin 3t
With the neutral connection (4 wire system), the triple frequency components will disappear from the
induced voltages in all the windings as the exciting currents of the primary will contain all the harmonics.
Phase difference between the primary and secondary emfs for the connection is zero i.e., the connection is
Yy0. If A2 and a2 are joined, the following conditions hold

VC2 Vc2 < VC2 Vb2


V B2 Vb2 < V B2 Vc2
Star-star connected transformers are normally provided with a tertiary winding connected in delta. This
winding helps in minimizing the third harmonic content in line currents and stabilizing the neutral of the
fundamental frequency voltage.

I1

A2

A2

a2
A

B1
Vph2

a1
V1
A1 I
ph1
C2

c1

c2

V2

b1

B2

C2

C1

b2

B2

A2

300

N
c2

a2

B2

C2

b2
A2,a2

c2
B2

C2
b2

Fig. 3(c) Delta-Star Connection of Three Phase Transformers


Delta/star connection: The connection and the corresponding phasor diagram for fundamental component of
induced voltages are shown in Fig. 3(c). It is obvious that the ratio of primary line voltage to secondary line
voltage is 1 : 3 N1 N 2 . As explained earlier, triple frequency current in each of the primary windings
being in phase, the delta connection will provide a closed path for these harmonics to flow, and therefore,
they will be absent from the line current. Thus the line magnetizing current will carry only the fundamental
frequency component. As a consequence, r.m.s. values of the line and phase exciting currents will not be
related by

3 . The fundamental component phase current ( I ph1 ) can be related to the line current ( I L ) and

the third harmonic component of phase current ( I ph3 ) by the expression

I ph1

I
= L + I 2ph3
3

Triple frequency current being present, flux variation will almost be sinusoidal and the line and phase
voltages on the secondary side will be related by

3 . For the connection shown in the figure, it can be

observed that the secondary induced e.m.f. lags the primary induced e.m.f. by 30 (Dy1) for the phase
sequence ABC. If A2 and a2 are joined, the following conditions hold

V B2 Vb2 < V B2 Vc2


VC2 Vc2 = VC2 Vb2
In the case of 30 lead (Dy11), the relation will be

V B2 Vb2 = V B2 Vc2
VC2 Vc2 < VC2 Vb2

I1

A2

A2

a2
A

B1

a2

b1

V1

V2
A1 I
ph1

C2

B2

C2

C1

b2

a1 Iph2
c2

b2

c1
c2

B2

C2

A2

a2

n
B2

c2

Fig. 3(d) Delta-Delta Connection of Three Phase Transformers

b2

Delta/delta connection: The delta-delta method of connection is shown in Fig. 3(d) along with its e.m.f.
phasor diagram for balanced supply voltage. It can be seen that the (primary to secondary) transformation
ratio for line as well as phase voltage is N1 N 2 : 1 . For the reasons described before, delta-delta connection
will cause the triple frequency currents to circulate, making the resultant flux variation almost sinusoidal.
Owing to circulating triple frequency current, primary line and phase currents will not be related by 3 . It
is clear from the phasor diagram that there is no phase difference between the primary and secondary
induced e.m.f.s and the connection is Dd0. If A2 and a2 are joined, the following will be observed

VC2 Vc2 < VC2 Vb2


V B2 Vb2 < V B2 Vc2
With this connection, large unbalance of loads may be met without difficulty while the closed mesh serves
to damp out third harmonic voltage.

V12

V2

V1
AC

Pry

Secy

Fig. 4. Circuit Diagram for Polarity Test


Procedure
Step I: Refer to Fig. 4 for identification of the corresponding terminals (polarities) of the primary
and the secondary windings. Join one terminal of the primary winding to any one of the terminals of the
secondary winding and apply a small voltage to the primary winding. Measure the voltage V12 between the
remaining two terminals of the windings as well as the secondary terminal voltage V2. If V12 closely equals
the difference between the primary applied voltage V1 and the secondary induced voltage V2, the terminals to
which the voltmeter is connected are the corresponding terminals (or terminals with same polarity). If not
then the secondary terminal joined with primary terminal is to be changed.
Step II: With due regard to the polarities of the windings, connect the primaries and the secondaries
of the transformers in the manner indicated in Fig. 1. For balanced applied voltage note down the readings of
the ammeters and voltmeters and enter them in the appropriate columns of Table 1 and Table 2. In the case
of star connected primary take the readings both with and without neutral connection to the system neutral.

Step III: Using a Digital Storage Oscilloscope (DSO) observe the waveforms of the voltages and
currents mentioned below for different connections. Using Fast Fourier Transform (FFT), find the
percentages of 3rd, 5th and 7th harmonics with respect to the fundamental.

Star/star
(i)
(ii)
(iii)
(iv)

Line voltage, phase voltage and line current of the primary when neutral is not grounded.
Line voltage, phase voltage and line current of the primary when neutral is grounded. Also
observe the current through the neutral-ground connection wire.
Line voltage and phase voltage of the secondary with (a) primary neutral isolated and (b)
primary neutral grounded.
Connect A2 and a2, connect neutral of primary to ground and observe the voltage between
neutrals of the two windings.

Star/delta
(i)

(ii)

(iii)

Line voltage, phase voltage and line current of the primary when neutral is isolated and the
secondary delta is open. Also measure and observe the voltage between the open points of the
delta connected secondary.
Line voltage and phase voltage of the primary, line voltage of the secondary and the current
flowing in the delta of the secondary when the primary neutral is still isolated but the secondary
delta is closed.
Now make the neutral grounded but the secondary delta open. Measure and observe the voltage
between the open points of the delta connected secondary.

Delta/star
(i)
(ii)

Phase and line current and phase voltage of the primary.


Phase and line voltage of the secondary.

Delta/delta:
(i)
(ii)

Line current and phase current of the primary.


Phase current of the secondary.

Discussion
1. Comment on the observed line-voltage ratios for different transformer connections and their
deviations from the name plate information.
2. Comment on the observations on the neutral voltages and currents with star connected primary.
3. Compare the probable third harmonic voltages and currents in a three-limb transformer compared
with those in a three-phase bank of single-phase transformers with similar connections.

Questions
1. What do the polarities of the transformer windings mean?
2. What are the relative merits and demerits of different three phase connections?

3. Supply to one terminal of a delta/star connected transformer fails. What would be the line-to-neutral
and line-to-line voltages on the secondary side?
4. Terminal markings of a three-phase three limb transformer are missing. How could you identify all
the terminals (A1-A2, B1-B2, C1-C2, a1-a2, b1-b2, and c1-c2) of the windings?

You might also like