Three-Phase To Two-Phase/One-Phase Conversion Using TWO TRANSFORMERS (Scott Connection)
Three-Phase To Two-Phase/One-Phase Conversion Using TWO TRANSFORMERS (Scott Connection)
Three-Phase To Two-Phase/One-Phase Conversion Using TWO TRANSFORMERS (Scott Connection)
5a
AIM:
1) To obtain balanced two-phase supply from three-phase supply by Scott arrangement of two transformers.
2) To perform load test at unity power factor for both balanced and unbalanced loads and compare the test results
with predictions.
3) To obtain single-phase supply from three-phase supply by Scott arrangement and perform load test at unity
power factor.
THEORY:
Consider the Scott connection of two single-phase transformers with turns ratio N1:N2 as shown in figure 1.
The phase diagram of line voltages on the primary side, VAB, VBC, VCA form an equilateral triangle.
Let,
This voltage VAM is across (3/2)*N1 turns. Therefore, the primary voltage (across N1 turns) of teaser transformer is
given by,
Hence, from equations (4) and (8) we can see that, for a balanced three-phase supply on the primary side, the voltages
on the secondary side of the transformers are equal in magnitude but 90 degrees out of phase. Therefore we got a
balanced two-phase supply from balanced three-phase supply using Scott connection.
If the secondary load currents are Ia and Ib , then the primary currents can be obtained as follows,
The Phasor diagrams for balanced and unbalanced unity power factor load are shown in figure 2. Note that for balanced
load, the two secondary currents are equal (Ia=Ib) in magnitude and the three primary currents are also equal (IA=IB=IC)
in magnitude.
To get single-phase voltage supply, short negative polarity side of teaser transformer and positive polarity of main
transformer on secondary side and take the voltage across positive polarity of teaser transformer and negative polarity
of main transformer on secondary side. This single phase voltage is given by,
Substituting equation (14) in equations (9), (10), (11) and (12) we can get the currents on primary side.
PROCEDURE:
1)
2)
3)
4)
5)
6)
7)
8)
9)
10)
Perform polarity test of the two single-phase transformers and find the polarities.
Connect the circuit as shown in the figure 1 for three-phase to two-phase conversion.
The three-phase balanced supply should be given to the circuit through auto-transformer and switch S1.
With switch S2 open, close S1 to supply rated voltage on primary side. Note down the voltages on primary
and secondary sides of teaser and main transformers.
Start with balanced load on the secondary side (ZL1=ZL2). Close S2 and take all the ammeter and voltmeter
readings. (Note that for balanced load the two secondary currents are equal and the three primary currents are
equal. Else, it implies that the load is unbalanced).
Now keep unbalanced load on secondary side and take all the voltmeter and ammeter readings. Repeat this for
3 more sets of unbalanced load.
Verify the results with theoretical predictions and draw Phasor diagrams.
For three-phase to single-phase conversion, short the negative polarity side of teaser transformer and positive
polarity side of main transformer in the previous circuit. Note the load is kept across positive polarity side of
teaser and negative polarity side of main transformer. (Note that the single-phase voltage is higher than the
secondary voltage in two-phase conversion (equation 13) and connect the load accordingly. If necessary
connect two loads in series to maintain the rated voltage of load greater than or equal to single-phase voltage.)
Keep load at some value and note down all the voltmeter and ammeter readings.
Verify the results with theoretical predictions and draw Phasor diagrams.
IA
THREE
PHASE
SUPPLY IB
a2
V1
Ib
b1
b2
ZL1
T1/2
0.5
Va
a1
T1/2
IC
A1
0.866T1
0.866
Ia
ZL2
Vb
V2
A2
A
a2
1.15 Ia
Ib
Ia
Ib
0.58 Ia
0.58 Ia
a1
C
b2
b1
Ib
A
1.15Ia
IA
0.58 Ia
IC
a2
Ib
Ia
n
Ib
a1
Ib B
IB
b2
b1
0.58 Ia
Fig. 2: Phasor diagrams (a) Balanced unity power factor load and (b) Unbalanced load
Experiment No. 5b
THREE PHASE CONNECTION OF SINGLE-PHASE TRANSFORMERS
(Vector Groups)
Introduction
Advantages of dealing with three-phase power instead of single-phase power are well known. The
requirements of three-phase transmission/distribution system make it necessary to employ three-phase
voltage transformation at the sending end as well as the receiving end. Three single-phase transformers are
often used for this purpose instead of a single three-phase unit. This reduces the cost of spare and also
installation/transportation becomes easier. The single-phase transformers may be connected in different
ways to suit specific requirements. For equal transformation ratio of the phase windings (i.e. the individual
single-phase units), the ratio of the line voltages and their phase relations depend on the mode of connection
of the transformers.
Objective
The main objectives of the experiment are listed below:
1. To connect three single-phase transformers in (a) Star/star, (b) Star/delta, (c) Delta/star, (d)
Delta/delta, and to obtain the no-load line voltage ratios and phase relations for each connection.
2. To study the voltage and/or current waveforms for different connections.
3. To obtain triple-frequency components of exciting currents, or triple-frequency induced voltages
that appear owing to different phase connections.
Theory
From an economic point of view, a transformer is designed to operate in the saturation region of the
magnetic core. This makes the exciting current non-sinusoidal [1, 2]. The exciting current contains the
fundamental and all odd harmonics, third one being the predominant one. Thus, for all practical purposes,
harmonics greater than third can be neglected. This section describes how these harmonics are generated in
various connections and ways to limit their effect. The ratio of line quantities and phase relations for each
connection is also described.
A1
A2
In
Vn
A1
n B1
C1
C2
V2
b1
Vph1
V1
a2
a2
a1
b2
c1
b2
B2
Iph2
c2
c2
A2
a2
30
b2
c2
C2
B2
A2 a2
b2
c2
C2
B2
Star/delta connection: Consider the system shown in Fig. 3(a). The primary windings are connected in star
and the neutral point of the supply is available. The secondary windings are connected in delta. To start with,
let us consider that the secondary delta is not closed (say, one arm is open). If the neutral of the primary star
is connected to the system ground, the exciting currents of the three phases are given as
As the exciting current is non-sinusoidal, the flux in the core and hence the induced voltages in both
the windings will be sinusoidal.
Next, consider the case when the neutral of the primary is kept isolated and the secondary continues
to be open delta. The third harmonic currents cannot flow in the primary windings; hence the primary
currents are essentially sinusoidal. The flux will be non-sinusoidal because of nonlinear B-H characteristics
of the magnetic core, and it contains third harmonic components (higher order harmonics neglected as
before). This will induce third harmonic voltage in the windings. The phase voltages are therefore nonsinusoidal, containing the fundamental and third harmonic voltages.
v a = 2V
ph1sin t
+ 2V ph3 sin 3t
v 0 = v a + vb + vc = 3 2V ph3 sin 3t
The voltage across the open delta is the sum of the three third harmonic voltages induced in the secondary
windings. Now, under this condition, if the delta is closed then the net third harmonic voltage will give rise
to a third harmonic current which will circulate in the delta connected windings. This will partly provide the
missing third harmonic component of the primary exciting current and consequently the flux and induced
voltage will be close to sinusoidal [2].
It can be seen from the emf phasor diagram that if the transformers are connected in Yd11 and A2
and a2 are joined, the following conditions hold
A1
a2
A2
a2
V1
V1
Vph1
In
Vn
C
B
C2
A1
n B1
C1
B2
a1
V2
n
c1 b1
c2
b2
b2
c2
a2
A2
n
C2
B2
c2
b2
Star/star connection (Fig. 3(b)): Similar to the Star/delta connection with no neutral and open delta, the
triple frequency components of the excitation currents are suppressed thereby causing large triple frequency
components in flux variation. Triple frequency component will be present in the phase voltages of both the
windings, but these will not appear in the line voltages. For such connections the ratio of line voltages of
primary and secondary is N1 N 2 : 1 . The neutral point voltage will be
v 0 = 3 2V ph3 sin 3t
With the neutral connection (4 wire system), the triple frequency components will disappear from the
induced voltages in all the windings as the exciting currents of the primary will contain all the harmonics.
Phase difference between the primary and secondary emfs for the connection is zero i.e., the connection is
Yy0. If A2 and a2 are joined, the following conditions hold
I1
A2
A2
a2
A
B1
Vph2
a1
V1
A1 I
ph1
C2
c1
c2
V2
b1
B2
C2
C1
b2
B2
A2
300
N
c2
a2
B2
C2
b2
A2,a2
c2
B2
C2
b2
3 . The fundamental component phase current ( I ph1 ) can be related to the line current ( I L ) and
I ph1
I
= L + I 2ph3
3
Triple frequency current being present, flux variation will almost be sinusoidal and the line and phase
voltages on the secondary side will be related by
observed that the secondary induced e.m.f. lags the primary induced e.m.f. by 30 (Dy1) for the phase
sequence ABC. If A2 and a2 are joined, the following conditions hold
V B2 Vb2 = V B2 Vc2
VC2 Vc2 < VC2 Vb2
I1
A2
A2
a2
A
B1
a2
b1
V1
V2
A1 I
ph1
C2
B2
C2
C1
b2
a1 Iph2
c2
b2
c1
c2
B2
C2
A2
a2
n
B2
c2
b2
Delta/delta connection: The delta-delta method of connection is shown in Fig. 3(d) along with its e.m.f.
phasor diagram for balanced supply voltage. It can be seen that the (primary to secondary) transformation
ratio for line as well as phase voltage is N1 N 2 : 1 . For the reasons described before, delta-delta connection
will cause the triple frequency currents to circulate, making the resultant flux variation almost sinusoidal.
Owing to circulating triple frequency current, primary line and phase currents will not be related by 3 . It
is clear from the phasor diagram that there is no phase difference between the primary and secondary
induced e.m.f.s and the connection is Dd0. If A2 and a2 are joined, the following will be observed
V12
V2
V1
AC
Pry
Secy
Step III: Using a Digital Storage Oscilloscope (DSO) observe the waveforms of the voltages and
currents mentioned below for different connections. Using Fast Fourier Transform (FFT), find the
percentages of 3rd, 5th and 7th harmonics with respect to the fundamental.
Star/star
(i)
(ii)
(iii)
(iv)
Line voltage, phase voltage and line current of the primary when neutral is not grounded.
Line voltage, phase voltage and line current of the primary when neutral is grounded. Also
observe the current through the neutral-ground connection wire.
Line voltage and phase voltage of the secondary with (a) primary neutral isolated and (b)
primary neutral grounded.
Connect A2 and a2, connect neutral of primary to ground and observe the voltage between
neutrals of the two windings.
Star/delta
(i)
(ii)
(iii)
Line voltage, phase voltage and line current of the primary when neutral is isolated and the
secondary delta is open. Also measure and observe the voltage between the open points of the
delta connected secondary.
Line voltage and phase voltage of the primary, line voltage of the secondary and the current
flowing in the delta of the secondary when the primary neutral is still isolated but the secondary
delta is closed.
Now make the neutral grounded but the secondary delta open. Measure and observe the voltage
between the open points of the delta connected secondary.
Delta/star
(i)
(ii)
Delta/delta:
(i)
(ii)
Discussion
1. Comment on the observed line-voltage ratios for different transformer connections and their
deviations from the name plate information.
2. Comment on the observations on the neutral voltages and currents with star connected primary.
3. Compare the probable third harmonic voltages and currents in a three-limb transformer compared
with those in a three-phase bank of single-phase transformers with similar connections.
Questions
1. What do the polarities of the transformer windings mean?
2. What are the relative merits and demerits of different three phase connections?
3. Supply to one terminal of a delta/star connected transformer fails. What would be the line-to-neutral
and line-to-line voltages on the secondary side?
4. Terminal markings of a three-phase three limb transformer are missing. How could you identify all
the terminals (A1-A2, B1-B2, C1-C2, a1-a2, b1-b2, and c1-c2) of the windings?