Fill-Rite Company warrants the goods manufactured shall be free from defects of materials and workmanship. Specific warranty details for individual
products can be found at fillrite.com.
fillrite.com 2
| H-SERIES FUEL TRANSFER PUMPS INSTALLATION AND OPERATION MANUAL
From initial concept and design through final production, your Fill-Rite fuel transfer pump is built to provide years of trouble-free use. To ensure the safety
of yourself and those around you, it is critical that this manual is read in its entirety prior to attempting to install or operate your new purchase. We strongly
urge that any installer and operator become familiar with the terms, diagrams, and technical data in this manual and pay close attention to warning
symbols and definitions. At Fill-Rite, your satisfaction with our products is paramount. If you have questions or need assistance with your product, please
contact Fill-Rite Technical Support at 1 (800) 720-5192 (M-F, 8am-5pm ET).
Indicates a hazardous situation which, if not avoided, will result in death or serious injury.
Indicates a hazardous situation which, if not avoided, could result in death or serious injury.
Indicates a hazardous situation which, if not avoided, could result in moderate or minor injury.
Fueling Requirements
The Fill-Rite FR1200, FR2400, FR4200, FR4400, FR600 as well as SD1200 and SD600 models are designed and approved for use with the following
flammable and combustible fluids: gasoline and gasoline blends up to 15% or E15, diesel, biodiesel blends up to 20% or B20, kerosene, and mineral spirits.
Please take all necessary precautions when handling flammable liquids.
fillrite.com 3
| H-SERIES FUEL TRANSFER PUMPS INSTALLATION AND OPERATION MANUAL
Safety Information
To ensure a safe installation and proper equipment operation, please read, understand, and adhere to all DANGER/WARNING/CAUTION and other NOTICES.
Never smoke around or near a fuel tank or transfer pump. Open flames or a spark when pumping a flammable liquid will
result in a fire. Improper electrical wiring or installation will result in serious injury or death.
Electrical wiring should ONLY be performed by a licensed electrician in compliance with all local, state, and
national electrical codes (NEC/ANSI/NFPA 30, NFPA 30A, and NFPA 70) as appropriate for the intended use of a
Fill‑Rite fuel transfer pump.
Threaded rigid conduit, sealed fittings, and conductor seal should be used where applicable and as defined by
these codes.
This product must be properly bonded or grounded to avoid the build up of static electricity when handling flammable
products. Static discharge may ignite vapors causing serious injury or death.
Fill-Rite pumps are not suited for use with water or fluids intended for human consumption. Do not use to fuel aircrafts.
To minimize static electricity build up, keep the nozzle in contact with the container being filled at all times during the
filling process. Use only static wire conductive hose when pumping flammable liquid.
Improper mechanical installation or use can result in serious injury or death.
Threaded pipe joints and connections must be sealed with the appropriate sealant or sealant tape to prevent leaks.
All Fill-Rite pump models are equipped with thermal overload protection by which the motor will shut off to prevent heat
damage. If motor is turned off by a thermal overload, turn the switch lever to the OFF position. Once the motor has cooled
sufficiently, turn the switch lever to the ON position to resume fuel transfer.
Some Fill-Rite models will restart automatically if the switch lever is not in the OFF position once the thermal protector
resets. As good practice, always place the switch lever in the OFF position when the motor overheats.
A filter should be used on the pump outlet to avoid contamination into the vehicle or equipment’s fuel tank.
We recommend Fill‑Rite filters for best results.
To prevent fuel storage tanks from shifting or tipping, refer to tank manufacturer’s guidelines on proper anchoring.
fillrite.com 4
| H-SERIES FUEL TRANSFER PUMPS INSTALLATION AND OPERATION MANUAL
Installation
Your Fill-Rite pump is designed to be mounted on a fuel tank via a threaded inlet flange supplied with the pump. Typical installations are shown in Diagram 1
and 2. Your pump features an integral bypass valve to recirculate the fluid when the pump is operating with the nozzle closed.
Do not use additional check valves or foot valves unless they have a proper pressure relief valve built into them.
Please be aware that additional check valves will reduce flow rates.
A pressure-retaining fill cap can be used to reduce fuel loss through evaporation.
Threaded pipe joints and connections must be sealed with the appropriate sealant to prevent leaks.
Use caution to prevent cross-threading during installation which can cause damage to either or both the inlet flange
as well as storage tank bung.
In all tank applications, be sure the tank is properly secured per tank manufacturer’s guidelines.
For stationary fuel tanks, the pump mounts to the tank bung by way of For mobile fuel tanks, the pump mounts to the tank bung by way
the pump inlet flange. Given the different sizes of stationary fuel tanks, of the pump inlet flange.
a custom suction or inlet pipe may be necessary. We recommend 1” NPT For Telescoping Steel Suction Pipe
black iron pipe that is extended to a length of at least 1-2” from the Allow telescoping tube to extend fully to the bottom of the tank.
bottom of the tank, with the bottom of the pipe cut to an angle between
30-45 degrees for improved flow. For Custom or PVC Suction Pipe
To avoid penetrating the tank, we recommend leaving a minimum of 1-2”
A stationary tank must be equipped with a vent cap. (Diagram 1) of the pipe off the bottom of tank. We further recommend cutting the
suction pipe to a 30-45 degree angle for improved flow.
The mobile tank must be equipped with a vent cap. (Diagram 2)
Diagram 1 Diagram 2
Vent Cap
Vent Cap
1-2"
Min.
1-2"
Min.
fillrite.com 5
| H-SERIES FUEL TRANSFER PUMPS INSTALLATION AND OPERATION MANUAL
Installation Procedure
Step 6: Feed wires from power source through NPT opening into junction
†
box. For DC models, use the black cable connector*. For AC models, attach
conduit directly to NPT† opening.
Step 7: Nozzle boot is attached to switch plate via (1) 5/16" bolt torqued to
40 in-lbs. The nozzle boot has two available position placements.
PUMP
SCREEN GASKET
POCKET
SCREEN GASKET
½" NPT
CONDUIT HOLE, EARTH GROUND
INLET TANK (2) T-25 THREADED SYMBOL
FLANGE BUNG SCREWS
JUNCTION BOX CAP
JUNCTION BOX CAP
(CAN BE ROTATED 180°)
Step 7
BOLT POSITION
HOLE POST
5/16" BOLT,
40 IN-LBS
fillrite.com 6
| H-SERIES FUEL TRANSFER PUMPS INSTALLATION AND OPERATION MANUAL
Electrical wiring should be performed ONLY by a licensed electrician in compliance with local, state, and national electrical
codes (NEC/ANSI/NFPA 30, NFPA 30A, and NFPA 70) as appropriate to the intended use of the pump. Threaded rigid
conduit, sealed fittings, and conductor seal should be used where applicable. The pump must be properly grounded.
Improper installation or use of this pump can result in serious personal injury or death.
Do not connect the positive or negative power to the green ground/earth screw or ground/earth wire as this could
cause a fire.
Do not attempt to power the pump from vehicle wiring smaller than 12 AWG such as the cigarette lighter wire because
these thin wires could overheat and cause a fire.
For wiring up to upfitter switches, please contact Fill-Rite Technical Support at 1 (800) 720-5192 (M-F, 8am-5pm ET).
Fill-Rite DC fuel pumps are designed to operate at the rated nameplate voltage. Series FR1200, FR4200, and SD1200
are rated for 12V DC while FR2400 and FR4400 are rated for 24V DC. Regardless of how supply line power is provided
(i.e. via a battery or hard line), Fill-Rite requires the circuit contain a fuse to prevent against electrical shorts. For 12V
DC, a 30 amp fuse is necessary while for the 24V DC circuit, a 20 amp fuse.
Voltage drop in wiring varies depending on the distance from the battery to the pump and the gauge of the wire used.
If the distance is greater than the supplied 18' 12 AWG power cable*, refer to local, state, and national electrical codes
to ensure the wire is of the correct size for this application.
The following chart is to be used as a reference and is not a substitute for electrical codes:
Maximum Linear Distance (FT) of Stranded Copper Wire Length by Gauge
10 8 6 4 2
27' 44' 69' 110' 175'
*12 AWG power cable not supplied with pump only models
Electrical bonding is the process of connecting metallic parts such as a fuel storage tank or transfer pump which may
be exposed to electrical faults to a grounding conductor to ensure a low-resistance path to the ground. Bonding also
provides a path for static electricity and induced voltages to drain out through the grounding path. The most common
way to bond is with a copper wire.
If the intention is to operate either a 12V or 24V DC fuel transfer pump from a power supply other than a vehicle battery
system, please contact Fill-Rite Technical Support at 1 (800) 720-5192 (M-F, 8am-5pm ET).
fillrite.com 7
| H-SERIES FUEL TRANSFER PUMPS INSTALLATION AND OPERATION MANUAL
½" NPT
CONDUIT HOLE, EARTH GROUND
THREADED SYMBOL
DC Wiring Instructions
1. Remove pump’s electrical junction box cover and straighten the red and black wire.
2. Screw the furnished cable connector into 1/2" NPT conduit opening on the junction box.
3. Strip 3" of the outer covering from one end of the furnished electrical supply cable.* Be careful not to damage the black and red wire insulation.
4. Loosen cable connector nut and pass the stripped end of the furnished cable through the cable connector. Tighten the cable connector nut.
5. Strip 1/2" of the insulation from the ends of the red and black cable wires. Using the furnished wire nuts, connect the cable wires to the pump wires
matching the colors.
IMPORTANT: Be sure no bare wire is exposed.
6. Fold wires into junction box and replace, making sure the cover gasket is in place. Make sure all screws are seated so there is no space between the
frame and the junction box (see Step 6 diagram on Page 6).
*12 AWG cable not supplied with pump only models
fillrite.com 8
| H-SERIES FUEL TRANSFER PUMPS INSTALLATION AND OPERATION MANUAL
While rare, there are instances where a 12V or 24V DC Fill-Rite fuel pump does not operate from a vehicle’s electrical system. In these cases, we recommend
calling Fill-Rite Technical Support at 1 (800) 720-5192 (M-F, 8am-5pm ET) to discuss your specific situation. Most of these applications will require equipment
not supplied by Fill-Rite. In addition, we want to ensure that the circuit will be able to handle the necessary power requirements of the pump.
1. Before electrical installation, place the switch lever into the OFF position to prevent accidental spillage once power is engaged to the motor.
2. Fill-Rite requires installing a fuse holder and fuse (not provided) for the protection of the purchased pump.
3. Attach one end of the fuse holder to the red pump wire, as close to the battery or power source as possible. Make a solid connection to the positive
terminal of the power source with the other end of the fuse holder. Make a solid connection with the black pump wire to the negative terminal of
the power source.
4. Check all connections to make sure they are connected per instructions and all electric codes.
5. Install fuse (30 amp fuse for 12V DC; 20 amp fuse for 24V DC) into the fuse holder.
6. The installation is now complete.
This electrical system is common within most vehicles utilizing a 12V This electrical system is uncommon within most vehicles utilizing a 12V
DC power source. In this instance, the positive battery terminal supplies DC power source. The chassis of the vehicle is connected to the positive
power to all devices such as the ignition system. The negative (-) terminal (+) terminal of the battery.
is connected to the vehicle’s frame. Fuse to be located outside of hazardous area, as close to the power source
Fuse to be located outside of hazardous area, as close to the power source as possible. If the wiring from the power source to the pump is greater
as possible. If the wiring from the power source to the pump is greater than 18', refer to the applicable Electrical Code (national, international, or
than 18', refer to the applicable Electrical Code (national, international, or local) to ensure the wire is of the correct size for the application.
local) to ensure the wire is of the correct size for the application.
COMMON UNCOMMON
FUSE FUSE
30 amp fuse for 12V DC 30 amp fuse for 12V DC
20 amp fuse for 24V DC 20 amp fuse for 24V DC
fillrite.com 9
| H-SERIES FUEL TRANSFER PUMPS INSTALLATION AND OPERATION MANUAL
• Ground wire in supply wiring MUST be connected to the ground screw inside the junction box.
Voltage drop in wiring varies depending on the distance from the electrical source to the pump and the gauge of the wire
used. Fill-Rite recommends referring to national, international, or local electrical codes to ensure the wire is of the correct
size for your application. The following chart is to be used as a reference and is not a substitute to electrical codes.
Maximum Linear Distance (FT) of Solid and Stranded Copper Wire Length by Gauge
AWG 16 14 12 10 8 6 4
Solid 39 62 99 158 250
Wire
Stranded 38 61 96 154 245 389 620
fillrite.com 10
| H-SERIES FUEL TRANSFER PUMPS INSTALLATION AND OPERATION MANUAL
1. Remove the junction box cover and straighten the wires to make sure the stripped wire ends are accessible outside the junction box.
2. Install rigid conduit and appropriate wiring from power source to the junction box to maintain the explosion-proof integrity.
3. Connect the pump wires to the power supply lines according to the wiring diagram. Be certain to properly insulate the connections with the appropriate
wire nuts or other connectors. NOTE: The ground wire MUST be connected. Ground wire connection is inside the junction box (Diagram 6b).
4. Fold the wires back into the junction box and replace the cover, making sure the cover gasket is in place.
Diagram 6a Diagram 6b
Effective March 7, 2022, the fuel transfer pump on/off switch lever will need to be installed in the field. Please see Figure 1 for a visual guide on the
proper installation of this lever.
Figure 1
fillrite.com 11
| H-SERIES FUEL TRANSFER PUMPS INSTALLATION AND OPERATION MANUAL
Operation Instructions
Always keep the nozzle in contact with the container being filled during the filling process to minimize the possibility of
static electricity build up. A spark around flammable vapors will cause an explosion resulting in death or serious injury.
1. If equipped, reset meter to “0” (do not reset while in use as this
will cause damage to the meter). Diagram 7
2. Remove dispensing nozzle from nozzle boot.
3. Move the switch lever to the “ON” position to power the pump NOZZLE BOOT
(Diagram 7).
4. Insert the dispensing nozzle into the container to be filled.
5. Operate the nozzle to dispense fluid; release nozzle when the
desired amount of fluid has been dispensed.
6. Move switch lever to the “OFF” position (Diagram 8) to turn
off the pump.
"ON" Position
7. Remove the dispensing nozzle from the container being filled and
store it in the nozzle boot. SWITCH LEVER
Security
Diagram 8
Your Fill-Rite fuel transfer pump is
equipped with a locking link located next to Diagram 9
the switch lever for security. With the pump NOZZLE BOOT
turned off and the nozzle in the stored
position, a padlock can be inserted through
the locking link and the nozzle handle.
Fill-Rite recommends a commercial grade
laminated steel padlock with an adjustable
shackle (Diagram 9). "OFF" Position
SWITCH LEVER
Troubleshooting
The following troubleshooting guide is provided to offer basic diagnostic assistance in the event you encounter abnormal service from your Fill-
Rite fuel transfer pump. If you have questions, please feel free to contact Fill-Rite Technical Support at 1 (800) 720-5192 (M-F, 8am-5pm ET) or by
email at FillRiteTech@fillrite.com.
Please disconnect all power supply sources from either your AC or DC pump prior to performing any service or maintenance,
as well as relieve any pressure within either the suction tube or discharge hose. Failure to do so can result in damage to the
equipment and personal injury or death.
fillrite.com 12
| H-SERIES FUEL TRANSFER PUMPS INSTALLATION AND OPERATION MANUAL
Troubleshooting (continued)
Pump hums but will Motor failure Contact Fill-Rite Technical Support at 1 (800) 720-5192 (M-F, 8am-5pm ET)
not operate Broken rotor key Remove all debris and replace key
fillrite.com 13
| H-SERIES FUEL TRANSFER PUMPS INSTALLATION AND OPERATION MANUAL
A series of fuel transfer pumps with UL/cUL, ATEX, IECEx, CE, EAC, and INMETRO certifications that are compatible with gasoline, diesel fuel, blended fuels
such as biodiesel up to 20%, gasoline with up to 15% ethanol, mineral spirits, and kerosene.
fillrite.com 14
| H-SERIES FUEL TRANSFER PUMPS INSTALLATION AND OPERATION MANUAL
FR1200, FR2400, FR4400, FR600, SD1200, and SD600 (Dimensions displayed in inches)
13.0
8.4
2.5
3.4 4.3
11.1
13.7
8.4
2.5
4.2
4.3
11.8
fillrite.com 15
| H-SERIES FUEL TRANSFER PUMPS INSTALLATION AND OPERATION MANUAL
H-Series Model Information: FR1200, FR2400, FR4200, FR4400, FR600, SD1200, SD600
Model Number Nozzle Hose Meter Inlet Tube Power Cord Special Voltage Outlet
FR1204H Pump Only Model
FR1210H Manual 12'
FR1210HA Auto Gasoline 12'
FR1210HA1 Auto Diesel 12'
FR1210HARC Auto Arctic 15' Swivel
FR1210HN
FR1211H Manual 12' 807C 12V DC
Metal Telescoping
12 AWG at 18'
FR1211HL Manual 12' 807CL 20" - 34 ½"
fillrite.com 16
| H-SERIES FUEL TRANSFER PUMPS INSTALLATION AND OPERATION MANUAL
H-Series Model Information: FR1200, FR2400, FR4200, FR4400, FR600, SD1200, SD600 (continued)
Model Number Nozzle Hose Meter Inlet Tube Power Cord Special Voltage Outlet
Model Number Nozzle Hose Meter Inlet Tube Power Cord Voltage Outlet
FR1205HE Pump Only Model
fillrite.com 17
| H-SERIES FUEL TRANSFER PUMPS INSTALLATION AND OPERATION MANUAL
fillrite.com 18
| H-SERIES FUEL TRANSFER PUMPS INSTALLATION AND OPERATION MANUAL
fillrite.com 19
| H-SERIES FUEL TRANSFER PUMPS INSTALLATION AND OPERATION MANUAL
Accessories
METER
STRAIGHT PIPE FILTER HEAD
STREET ELBOW
STRAIGHT PIPE
SWIVEL
NOZZLE
FILTER
HOSE
fillrite.com 20
| H-SERIES FUEL TRANSFER PUMPS INSTALLATION AND OPERATION MANUAL
Accessories (continued)
Outlet Size
Accessory Series Notes
3/4" 1"
807CMK Gallons
800
807CLMK Liters
Mechanical
901CMK4200 Gallons
900
901CLMK4200 Liters
900CD Programmable
Meter 900 Programmable with
900CDP
Integral Pulsar
fillrite.com 21
| H-SERIES FUEL TRANSFER PUMPS INSTALLATION AND OPERATION MANUAL
fillrite.com 22
Safety Testing Approvals Installation
Pump must be installed in compliance with EN 60079-14 or IEC 60079-14, as
applicable.
The Fill-Rite line of pumps have been safety tested for regulatory compliance. This
product family is approved by UL/cUL. For the “E” series products they are approved to Material of Construction
ATEX, IECEx, INMETRO, EAC, and CE.
Materials of construction of the external surface of the unit: painted steel, painted cast
iron, painted aluminum, zinc plated steel.
Materials of construction of the wetted parts: cast iron, zinc plated steel, 300 series
stainless steel, bronze, carbon, ceramic, polyester, fiber, fluorocarbon, buna.
2809
Repair and Maintenance
Contact the place of purchase for warranty repair and maintenance.
The following standards were used to show compliance in the European Union:
EN IEC 60079-0:2018, Ed 7 “Explosive atmospheres – Part 0: Equipment – Specific Conditions of Use
General requirements” 1. Consult the manufacturer if dimensional information on the flameproof joints is
necessary.
EN 60079-1:2014, Ed 7 “Explosive atmospheres – Part 1: Equipment protection
by flameproof enclosures “d”” 2. ISO Class 4.6, M5 hex-head screws (Yield Stress 240 MPa) shall be used to replace
the DC Motor terminal cover fasteners.
EN ISO 80079-36:2016, Ed 1 “Explosive atmospheres – Part 36: Non-electrical
equipment for explosive atmospheres – Basic method and requirements”
3. ISO Class 8.8, M6 hex-head screws (Yield Stress 640 MPa) shall be used to replace
the DC Motor motor tie-rod fasteners.
EN ISO 80079-37:2016, Ed 1 “Explosive atmospheres – Part 37: Non-electrical 4. An electrically conductive hose and nozzle must be used with flammable liquids.
equipment for explosive atmospheres – Non electrical type of protection To minimize static electricity buildup, always keep the nozzle in contact with the
constructional safety “c”, control of ignition source “b”, liquid immersion “k”” container being filled during the fueling process.
Directive 2014/34/EU – Equipment and protective systems intended for use in
potentially explosive atmospheres. Motor Tag Information
Directive 2011/65/EU – Restrictions of the use of certain hazardous substances in
electrical and electronic equipment. The motor tag on your Fill-Rite pump contains important technical and
performance information. Be certain this label remains affixed to the
The following standards were used to show compliance for IECEx certification:
pump at all times.
IEC 60079-0:2017, Ed 7
IEC 60079-1:2014, Ed 7
Fill-Rite Company
8825 Aviation Drive
Fort Wayne, Indiana 46809 USA
T 1 (800) 720-5192
1 (260) 747-7524
F 1 (800) 866-4681
FIL-MN-712v.3