36.

027

EGT 330...335: Room-temperature sensor


How energy efficiency is improved
Accurate detection of room temperature for energy-efficient control of HVAC systems and monitoring
energy consumption.
Areas of application
Temperature detection for heating and air conditioning systems in dry rooms, for example residential,
office and business premises.
Features
• Passive measured value acquisition
• Temperature detection in dry rooms
• Versions with setpoint adjuster, presence button and status LED
• Parameterise with SAUTER EY3600 or a SAUTER Flexotron controller (EGT 332) T
• Integrated resistor (EGT 333) which, in combination with Equitherm controllers, corrects the
setpoint with or without room temperature influence Y04579

Technical description
• With nickel thin-film sensor as per DIN 43760
• Housing made of pure white, fire-retardant thermoplastic (RAL 9010)
• Cable inlet at rear, screw terminals for wires up to 1,5 mm²
Type Nominal value Adjuster Remarks Measuring Weight
at 0 °C range °C kg
EGT 330 F021 200 Ω – – –20...60 0.1
EGT 330 F051 500 Ω – – –20...60 0.1
EGT 330 F101 1000 Ω – – –20...60 0.1
EGT 332 F101 1000 Ω 2.5 kΩ for Flexotron 2) +DDC –20...60 0.1
EGT 333 F101 1000 Ω 1) ±4K for Equitherm+RDT7 . . –20...60 0.1
With occupancy key, 3 LEDs
EGT 335 F101 1000 Ω 2,5 kΩ for DDC –20...60 0.1

Resistance values as per DIN 43760 Degree of protection IP 30 (EN 60529)


Tolerance at 0 °C ± 0,4 K
Average temp. coefficient 0,00618 K-1 Wiring diagram
Self-heating 0.17 K/mW EGT 330 A01632
EGT 332, 335 A06951
Time behaviour in still air EGT 333 A06952
Dead time 50 s Dimension drawing M07634
Time constant 18 min Fitting instructions MV 505479
EGT 333 MV 505530

Accessories
0303124 000* Recessed junction box
0313347 001* Intermediate cover plate for 76 × 76
0369829 100 Neutral housing, pure white
*) Dimension drawing or wiring diagram are available under the same number

1) 1000 Ω when correction knob is in middle position


2) Not for flexotron 100

Operation
The resistance of the nickel measuring resistor changes in relation to the temperature. The
temperature coefficient is always positive, i.e. the resistance increases as the temperature rises.
Table of values (DIN 43760). The elements are interchangeable within the bounds of the given
tolerances.
EGT 332
In addition to the measuring resistor, a potentiometer of 2.5 kΩ is fitted. In conjunction with DDC or a
Flexotron controller, the setpoint can be universally parameterised.
EGT 333
A potentiometer of 47 Ω for varying the measured value by ± 4 K – is fitted in series to the resistor.
Depending on the connection to an Equitherm controller, the setpoint can be corrected either with or
without influencing the room temperature.
EGT 335
As EGT 332, but with occupancy key and a yellow LED for operation plus two green LEDs for status
for ½ and 1. Bridges BR1 and BR2 should be opened if the sensor's earth should be separated.
Contacts S1 become potential-free if BR3 is opened.

Sauter Components 7136027003 06


36.027 EGT 330...335

Engineering and fitting notes


The temperature sensor should not be exposed directly to sources of heat, the effects of radiation or
draughts. With a temperature difference of 5 K between wall and air at a distance of approx. 1 m,
there is an error of 1 K.
Additional technical data
CE conformity as per
EMC Directive 2004/108/EC EN 61000-6-1/ EN 61000-6-2
EN 61000-6-3/ EN 61000-6-4

Wiring diagram

EGT 330 EGT 332 (EGT 335) EGT 333

1 2
4 3 0 1 2

T
T
Ni1000

0% Xs

A01632

A06952a

Dimension drawing

Sauter Components 7136027003 06


EGT 330...335 36.027

Accessories

303124 313347 60
70,5
5

2
3,
Ø 60
65

60
3,7

85
2
4,
7
53

51
77
9

M00815 M07579

Printed in Switzerland
Right of amendment reserved
N.B.: A comma between cardinal
numbers denotes a decimal point
© Fr. Sauter AG, CH-4016 Basle
Sauter Components 7136027003 06