Technical description
• With nickel thin-film sensor as per DIN 43760
• Housing made of pure white, fire-retardant thermoplastic (RAL 9010)
• Cable inlet at rear, screw terminals for wires up to 1,5 mm²
Type Nominal value Adjuster Remarks Measuring Weight
at 0 °C range °C kg
EGT 330 F021 200 Ω – – –20...60 0.1
EGT 330 F051 500 Ω – – –20...60 0.1
EGT 330 F101 1000 Ω – – –20...60 0.1
EGT 332 F101 1000 Ω 2.5 kΩ for Flexotron 2) +DDC –20...60 0.1
EGT 333 F101 1000 Ω 1) ±4K for Equitherm+RDT7 . . –20...60 0.1
With occupancy key, 3 LEDs
EGT 335 F101 1000 Ω 2,5 kΩ for DDC –20...60 0.1
Accessories
0303124 000* Recessed junction box
0313347 001* Intermediate cover plate for 76 × 76
0369829 100 Neutral housing, pure white
*) Dimension drawing or wiring diagram are available under the same number
Operation
The resistance of the nickel measuring resistor changes in relation to the temperature. The
temperature coefficient is always positive, i.e. the resistance increases as the temperature rises.
Table of values (DIN 43760). The elements are interchangeable within the bounds of the given
tolerances.
EGT 332
In addition to the measuring resistor, a potentiometer of 2.5 kΩ is fitted. In conjunction with DDC or a
Flexotron controller, the setpoint can be universally parameterised.
EGT 333
A potentiometer of 47 Ω for varying the measured value by ± 4 K – is fitted in series to the resistor.
Depending on the connection to an Equitherm controller, the setpoint can be corrected either with or
without influencing the room temperature.
EGT 335
As EGT 332, but with occupancy key and a yellow LED for operation plus two green LEDs for status
for ½ and 1. Bridges BR1 and BR2 should be opened if the sensor's earth should be separated.
Contacts S1 become potential-free if BR3 is opened.
Wiring diagram
1 2
4 3 0 1 2
T
T
Ni1000
0% Xs
A01632
A06952a
Dimension drawing
Accessories
303124 313347 60
70,5
5
2
3,
Ø 60
65
60
3,7
85
2
4,
7
53
51
77
9
M00815 M07579
Printed in Switzerland
Right of amendment reserved
N.B.: A comma between cardinal
numbers denotes a decimal point
© Fr. Sauter AG, CH-4016 Basle
Sauter Components 7136027003 06