4lap4-Rf Ae753015 R1
4lap4-Rf Ae753015 R1
4lap4-Rf Ae753015 R1
ENCLOSURE SYSTEMS
CONTROLLER:
ENCLOSURE: TWO 4X FIBERGLASS
(1) 8x6 LOCAL & (1) 6x6 REMOTE
POWER: 24VDC (GENERATOR STARTING BATTERIES)
ALARMS:
4 PILOT LIGHTS AND 4 DPDT RELAYS.
TANK LEAK
33% LOW LEVEL
90% HIGH LEVEL
95% CRITICAL HIGH LEVEL
DRAWING & REVISION HISTORY THIS DOCUMENT IS CREATED BY AND IS THE Drawing REV Number
ENGINE STARTER
4LAP4-RF
GEN CONTROLLER WIRING CONNECTED BY OTHERS
REMOTE
ENCLOSURE COMMON FOR ALL ALARMS
4LAP4-RF
LOCAL ENCLOSURE
TANK FLOATS
3 TB DC+ + 24 POWER DISTRIBUTION CONTROLLER/FLOAT FEED BLACK
4 TB5 FLT1 LEAK FLOAT INPUT WHITE
BELDEN 18/6 2 4 6 8
5 TB6 FLT2 33% LOW LEVEL FLOAT INPUT GREEN CABLE TAG:
6 TB7 FT/LAP
FLT3 90% HIGH LEVEL FLOAT INPUT BROWN
7 TB8 FLT4 95% CRITICAL HIGH LEVEL FLOAT INPUT RED
TO GEN CONTROLLER 1 3 5 7
8 TB9 ALARM COMMON INPUT TO GEN CONTROL BLACK
9 TB10 LEAK ALARM INPUT TO GEN CONTROL WHITE
BELDEN 18/6
10 TB11 LOW LEVEL ALARM INPUT TO GEN CONTROL GREEN CABLE TAG:
CRA
LAP/GC
11 TB12 CRITICAL HIGH LEVEL ALARM INPUT TO GEN CONTROL BROWN
COM
CR2
CR1
CR3
CR4
COM
DC+
FU2
FU1
DC+
12 TB13 CRITICAL HIGH LEVEL ALARM INPUT TO GEN CONTROL RED
9 10 1112 13 1 2 3 4
CONNECTIONS BETWEEN LOCAL ENCLOSURE & REMOTE ENCLOSURE
13 TB DC+ + 24VDC POWER INPUT TO FU2
1 3 5 7
14 TB COM - 24 POWER TO TB COM
15 TB 1 LEAK ALARM CR1-2 2 4 6 8
16 TB 2 LOW LEVEL ALARM CR2-2
17 TB 3 HIGH LEVEL ALARM CR3-2
18 TB 4 CRITICAL HIGH LEVEL ALARM CR4-2
BLUE_18AWG
RELAY N.O.
REFERENCE LINE
NUMBERS
N.O.
PROPERTY OF FREEMAN ENCLOSURE SYSTEMS,
LLC. ITS USE IS AUTHORIZED ONLY FOR
4LAP4-RF Number AE753015 1
Description
RESPONDING TO A REQUEST FOR QUOTATION OR
TANK FLOATS/CONNECTIONS/LEGEND
FOR THE PERFORMANCE OF WORK FOR FREEMAN
ENCLOSURE SYSTEMS, LLC. THIS DRAWING IS
NOT INTENDED TO BE USED FOR CONSTRUCTION
Equipment Designed by Aprvd By Date Sheet
FREEMAN
ENCLOSURE SYSTEMS
OR DISTRIBUTION WITHOUT CONSENT. ALARM PANEL 4 LAP4-RF SK JL 04/24/15 4 OF 5
9/14/2018 2:02:31 PM
4LAP4-RF LOCAL ENCLOSURE 4LAP4-RF REMOTE ENCLOSURE
DOOR LAYOUT BACK PLATE LAYOUT DOOR LAYOUT BACK PLATE LAYOUT
3
1
15 16 17
15 16 17
2
18 19 4
95% CRITICAL
ALARM SILENCE TANK LEAK HIGH LEVEL
5 6 7 R R 14
2 4 6 8
CRA
COM
FU1
DC+
ENCLOSURE 11 12 G 1 2 3 4
CR1
CR2
CR3
CR4
COM
FU1
DC+
9 10 1112 13
10
1 3 5 7
2 4 6 8 33% LOW
5 6 7 LEVEL
FREEMAN A
ENCLOSURE SYSTEMS
FREEMAN 9
ENCLOSURE SYSTEMS
19 2 TERMINAL END PLATE 2 POLE 22-12 AWG EL-LAB-WAGO 2002-1292 WAGO BECKER
4LAP4-R REMOTE ENCLOSURE
20 4 TERMINAL 2 POLE DBL STK 22-12 AWG EL-LAB-WAGO 2002-2201 WAGO BECKER
21 1 TERMINAL DBL STK END PLATE 22-12 AWG EL-LAB-WAGO 2002-2292 WAGO BECKER
22 4 TERMINAL 4 POLE 22-12 AWG EL-LAB-WAGO 2002-1401 WAGO BECKER
23 4 TERMINAL END PLATE 4POLE 22-12 AWG EL-LAB-WAGO 2002-1492 WAGO BECKER
24 4 DIN RAIL CLAMPS EL-LAB-WAGO 249-116 WAGO BECKER
THIS DOCUMENT IS CREATED BY AND IS THE Drawing REV Number
25 10" DIN RAIL EL-LAB-WAGO 210-112 WAGO BECKER
PROPERTY OF FREEMAN ENCLOSURE SYSTEMS,
LLC. ITS USE IS AUTHORIZED ONLY FOR
4LAP4-RF Number AE753015 1
Description
RESPONDING TO A REQUEST FOR QUOTATION OR
FOR THE PERFORMANCE OF WORK FOR FREEMAN
ENCLOSURE SYSTEMS, LLC. THIS DRAWING IS
ENCLOSURE LAYOUT/BOM FREEMAN
Equipment Designed by Checked by Date Sheet
NOT INTENDED TO BE USED FOR CONSTRUCTION
ENCLOSURE SYSTEMS
OR DISTRIBUTION WITHOUT CONSENT. ALARM PANEL 4 LAP4-RF SK JL 04/24/15 5 OF 5
9/14/2018 2:02:34 PM
5 5
95% CRITICAL
ALARM SILENCE TANK LEAK HIGH LEVEL
4LAP4-RF
LOCAL PUSH TO TEST
90% HIGH
LEVEL
ENCLOSURE
5 5
33% LOW
LEVEL
FREEMAN FREEMAN
ENCLOSURE SYSTEMS ENCLOSURE SYSTEMS
STANDARD MAX
JOB NAME/# MATERIAL QUANTITY ENCLOSURE
DIMENTIONS DIMENTIONS
4LAP4-RF LOCAL BLACK/WHITE 1 8x6 5X5 5-1/8x 5-1/8
Drawing REV Number
4LAP4-RF REMOTE BLACK/WHITE 1 6x6 5X5 5-1/8x 5-1/8 THIS DOCUMENT IS CREATED BY AND IS THE
PROPERTY OF FREEMAN ENCLOSURE SYSTEMS, ENGRAVING FACE PLATE Number
0
LLC. ITS USE IS AUTHORIZED ONLY FOR
RESPONDING TO A REQUEST FOR QUOTATION OR Description
FOR THE PERFORMANCE OF WORK FOR FREEMAN
ENCLOSURE SYSTEMS, LLC. THIS DRAWING IS
NOT INTENDED TO BE USED FOR CONSTRUCTION Project Name Designed by Checked by Date Sheet #
FREEMAN
ENCLOSURE SYSTEMS
OR DISTRIBUTION WITHOUT CONSENT. SDK JL
9/14/2018 2:02:36 PM