FREEMAN

ENCLOSURE SYSTEMS

4160 HALF ACRE RD.


BATAVIA, OH 45103
513-488-8600

FUEL TANK LEVEL INDICATING SYSTEM


MODEL- 4LAP4-RF

CONTROLLER:
ENCLOSURE: TWO 4X FIBERGLASS
(1) 8x6 LOCAL & (1) 6x6 REMOTE
POWER: 24VDC (GENERATOR STARTING BATTERIES)

LOCAL ENCLOSURE: LOCATED ON THE FUEL TANK


HAS FUEL LEVEL FLOAT & RELAYS.

REMOTE ENCLOSURE: LOCATED AT THE FUEL FILL STATION


HAS PILOT LIGHTS, PUSH TO TEST, ALARM HORN & SILENCE ALARM SWITCH

ALARMS:
4 PILOT LIGHTS AND 4 DPDT RELAYS.
TANK LEAK
33% LOW LEVEL
90% HIGH LEVEL
95% CRITICAL HIGH LEVEL

PILOT LIGHTS HAVE PUSH TO TEST FUNCTION.


RELAYS ARE FORM C WITH 2 DRY ISOLATED OUTPUTS.
FOR GENERATOR CONTROL & CUSTOMER CONNECTION.

ALARM HORN & SILENCE ALARM SWITCH WITH AUTOMATIC RESET.


TERMINALS FOR ALL CONNECTIONS.

DRAWING & REVISION HISTORY THIS DOCUMENT IS CREATED BY AND IS THE Drawing REV Number

DATE INITIALS REV No. DESCRIPTION


PROPERTY OF FREEMAN ENCLOSURE SYSTEMS,
LLC. ITS USE IS AUTHORIZED ONLY FOR
4LAP4-RF Number AE753015 1
Description
RESPONDING TO A REQUEST FOR QUOTATION OR
03/15/18 SK 1 PRODUCT IMPROVMENTS FOR THE PERFORMANCE OF WORK FOR FREEMAN
ENCLOSURE SYSTEMS, LLC. THIS DRAWING IS
COVER SHEET FREEMAN
Equipment Designed by Aprvd By Date Sheet
NOT INTENDED TO BE USED FOR CONSTRUCTION
ENCLOSURE SYSTEMS
04/24/15 SK NA DRAWING CONSTRUCTION SET OR DISTRIBUTION WITHOUT CONSENT. ALARM PANEL 4 LAP4-RF SK JL 04/24/15 1 OF 5
9/14/2018 2:02:26 PM
4LAP4-RF
LOCAL ENCLOSURE

ENGINE STARTER

4LAP4-RF
GEN CONTROLLER WIRING CONNECTED BY OTHERS
REMOTE
ENCLOSURE COMMON FOR ALL ALARMS

CABLE TYPE: BELDEN 18/6


CABLE TAG: FT/LAP

THIS DOCUMENT IS CREATED BY AND IS THE Drawing REV Number


PROPERTY OF FREEMAN ENCLOSURE SYSTEMS,
LLC. ITS USE IS AUTHORIZED ONLY FOR
4LAP4-RF Number AE753015 1
Description
RESPONDING TO A REQUEST FOR QUOTATION OR
FOR THE PERFORMANCE OF WORK FOR FREEMAN
ENCLOSURE SYSTEMS, LLC. THIS DRAWING IS
LOCAL ENC SCHEMATIC FREEMAN
Equipment Designed by Aprvd By Date Sheet
NOT INTENDED TO BE USED FOR CONSTRUCTION
ENCLOSURE SYSTEMS
OR DISTRIBUTION WITHOUT CONSENT. ALARM PANEL 4 LAP4-RF SK JL 04/24/15 2 OF 6
9/14/2018 2:02:28 PM
4LAP4-RF
REMOTE ENCLOSURE

4LAP4-RF
LOCAL ENCLOSURE

THIS DOCUMENT IS CREATED BY AND IS THE Drawing REV Number


PROPERTY OF FREEMAN ENCLOSURE SYSTEMS,
LLC. ITS USE IS AUTHORIZED ONLY FOR
4LAP4-RF Number
AE753015 1
Description
RESPONDING TO A REQUEST FOR QUOTATION OR
FOR THE PERFORMANCE OF WORK FOR FREEMAN
ENCLOSURE SYSTEMS, LLC. THIS DRAWING IS
REMOTE ENC SCHEMATIC FREEMAN
Equipment Designed by Aprvd By Date Sheet
NOT INTENDED TO BE USED FOR CONSTRUCTION
ENCLOSURE SYSTEMS
OR DISTRIBUTION WITHOUT CONSENT. ALARM PANEL 4 LAP4-RF SK JL 04/24/15 3 OF 5
9/14/2018 2:02:29 PM
FUEL TANK FLOATS TO 4LAP4-RF CONNECTIONS LOCAL/REMOTE ENCLOSURES
TERMINAL STRIP TB, RELAYS CR 1-4 & CRA,
FUSE / WIRE
ITEM # DESCRIPTION CABLE TYPE
TERMINAL # COLOR
4LAP4-RF LOCAL ENCLOSURE 4LAP4-RF REMOTE ENCLOSURE
1 FU1 POWER INPUT +24VDC BLUE
#12 BLU AWG
2 TB COM - 24VDC POWER INPUT & CONTROLLER FEED BLUE

TANK FLOATS
3 TB DC+ + 24 POWER DISTRIBUTION CONTROLLER/FLOAT FEED BLACK
4 TB5 FLT1 LEAK FLOAT INPUT WHITE
BELDEN 18/6 2 4 6 8
5 TB6 FLT2 33% LOW LEVEL FLOAT INPUT GREEN CABLE TAG:
6 TB7 FT/LAP
FLT3 90% HIGH LEVEL FLOAT INPUT BROWN
7 TB8 FLT4 95% CRITICAL HIGH LEVEL FLOAT INPUT RED
TO GEN CONTROLLER 1 3 5 7
8 TB9 ALARM COMMON INPUT TO GEN CONTROL BLACK
9 TB10 LEAK ALARM INPUT TO GEN CONTROL WHITE
BELDEN 18/6
10 TB11 LOW LEVEL ALARM INPUT TO GEN CONTROL GREEN CABLE TAG:

CRA
LAP/GC
11 TB12 CRITICAL HIGH LEVEL ALARM INPUT TO GEN CONTROL BROWN

COM
CR2
CR1

CR3

CR4
COM

DC+
FU2
FU1
DC+
12 TB13 CRITICAL HIGH LEVEL ALARM INPUT TO GEN CONTROL RED
9 10 1112 13 1 2 3 4
CONNECTIONS BETWEEN LOCAL ENCLOSURE & REMOTE ENCLOSURE
13 TB DC+ + 24VDC POWER INPUT TO FU2
1 3 5 7
14 TB COM - 24 POWER TO TB COM
15 TB 1 LEAK ALARM CR1-2 2 4 6 8
16 TB 2 LOW LEVEL ALARM CR2-2
17 TB 3 HIGH LEVEL ALARM CR3-2
18 TB 4 CRITICAL HIGH LEVEL ALARM CR4-2

FUEL TANK FLOATS


FLT-2 (N.C.) FLT-3 (N.O.)
LOW 3 7
90% HIGH LEVEL FLOAT
LEVEL FLOAT SET @ 90%
SET @ 33%
FLT-4 (N.O.)
3 6 95 % CRITICAL HIGH
LEVEL FLOAT
3 8
SET @ 95% SCHEMATIC LEGEND
FLT-1 (N.O.) CONTACT BLOCK
LEAK FLOAT TERMINAL NUMBERS MOMENTARY PUSH BUTTON SYMBOL
N.O. PUSH TO CLOSE WIRE NUMBERS
3 5 PILOT LIGHT DESCRIPTION TEXT
RELAY & CONTACT NUMBER CR1-1 PILOT LIGHT SYMBOL "RED LENS"
RELAY 1 CONTACT 1(N.C.)
PILOT LIGHT TERMINAL NUMBERS

RELAY COIL (CR)

BLUE_18AWG
RELAY N.O.
REFERENCE LINE
NUMBERS

FIELD WIRING EXTERNAL


LINE RELAY N.C.
OF THE ENCLOSURE RELAY COIL
REFERENCE REFERENCE LINE NUMBERS
TERMINAL
N.O. NUNBERS NUMBERS
NOTE N.C. REFERENCE
TERMINALS & TERMINAL NUMBER LINE NUMBERS IS UNDERLINED
N.O.
RELAY CONTACT TERMINAL NUMBERS
N.C.

THIS DOCUMENT IS CREATED BY AND IS THE Drawing REV Number

N.O.
PROPERTY OF FREEMAN ENCLOSURE SYSTEMS,
LLC. ITS USE IS AUTHORIZED ONLY FOR
4LAP4-RF Number AE753015 1
Description
RESPONDING TO A REQUEST FOR QUOTATION OR
TANK FLOATS/CONNECTIONS/LEGEND
FOR THE PERFORMANCE OF WORK FOR FREEMAN
ENCLOSURE SYSTEMS, LLC. THIS DRAWING IS
NOT INTENDED TO BE USED FOR CONSTRUCTION
Equipment Designed by Aprvd By Date Sheet
FREEMAN
ENCLOSURE SYSTEMS
OR DISTRIBUTION WITHOUT CONSENT. ALARM PANEL 4 LAP4-RF SK JL 04/24/15 4 OF 5
9/14/2018 2:02:31 PM
4LAP4-RF LOCAL ENCLOSURE 4LAP4-RF REMOTE ENCLOSURE

DOOR LAYOUT BACK PLATE LAYOUT DOOR LAYOUT BACK PLATE LAYOUT
3
1

15 16 17
15 16 17
2
18 19 4
95% CRITICAL
ALARM SILENCE TANK LEAK HIGH LEVEL

5 6 7 R R 14

2 4 6 8

4LAP4-RF PUSH TO TEST


90% HIGH
LEVEL 8
1 3 5 7
LOCAL

CRA
COM
FU1
DC+
ENCLOSURE 11 12 G 1 2 3 4

CR1

CR2

CR3

CR4
COM
FU1
DC+
9 10 1112 13
10
1 3 5 7
2 4 6 8 33% LOW
5 6 7 LEVEL

FREEMAN A
ENCLOSURE SYSTEMS
FREEMAN 9
ENCLOSURE SYSTEMS

4LAP4-R REMOTE ENCLOSURE 22 18


22 13
23 19
23 20
21

FUEL TANK LEVEL ALARM 4LAP4-RF BOM


ITEM # QTY DESCRIPTION PART # MFG SUPPLIER
1 1 ENCLOSURE 6x6 EL-LAB-HOFF-6X6X4 FG SCRCVR 4R HOFFMANN BECKER
2 1 ENCLOSURE BACK PLATE EL-LAB-HOFFMAN 6X6 PANEL HOFFMANN BECKER
3 1 ENCLOSURE 8x6 EL-LAB-HOFFMAN 8X6X4 BOX HOFFMANN BECKER
4 1 ENCLOSURE BACK PLATE EL-LAB-HOFFMAN 8X6 PANEL HOFFMANN BECKER
5 2 PUSH BUTTON MOMENTARY RED EL-LAB-SQD ZB5AA4 SCHNEIDER BECKER 5 5
6 2 MOUNTING COLLAR EL-LAB-SQD ZB5AZ009 SCHNEIDER BECKER
7 5 CONTACT BLOCK NO EL-LAB-SQD ZBE101 SCHNEIDER BECKER
8 2 PILOT LIGHT RED EL-LAB-IDEC HW1P-2FQD-R-24V IDEC BECKER 95% CRITICAL
ALARM SILENCE TANK LEAK HIGH LEVEL
9 1 PILOT LIGHT AMBER EL-LAB-IDEC HW1P-2FQD-A-24V IDEC BECKER
10 1 PILOT LIGHT GREEN EL-LAB-IDEC HW1P-2FQD-G-24V IDEC BECKER
11 1 HORN EL-LAB-MALLORY SC628NR SONALERT BECKER 4LAP4-RF
12 1 HORN GASKET EL-LAB-MALLORY ACC03 SONALERT BECKER LOCAL PUSH TO TEST
90% HIGH
LEVEL
13 4 RELAY & BASE DPDT 24VDC EL-LAB-WAGO 788-312 WAGO BECKER
ENCLOSURE
14 1 RELAY & BASE SPST 24VDC EL-LAB-WAGO 875-304 WAGO BECKER 5 5
15 2 FUSE 3A EL-LAB-WAGO 51220027 WAGO BECKER
33% LOW
16 2 FUSE TERMINAL BLOCK EL-LAB-WAGO 2002-1681 WAGO BECKER LEVEL

17 2 FUSE BLOCK END PLATE EL-LAB-WAGO 2002-1692 WAGO BECKER


FREEMAN FREEMAN
18 9 TERMINAL 2 POLE 22-12 AWG EL-LAB-WAGO 2002-1201 WAGO BECKER ENCLOSURE SYSTEMS ENCLOSURE SYSTEMS

19 2 TERMINAL END PLATE 2 POLE 22-12 AWG EL-LAB-WAGO 2002-1292 WAGO BECKER
4LAP4-R REMOTE ENCLOSURE
20 4 TERMINAL 2 POLE DBL STK 22-12 AWG EL-LAB-WAGO 2002-2201 WAGO BECKER
21 1 TERMINAL DBL STK END PLATE 22-12 AWG EL-LAB-WAGO 2002-2292 WAGO BECKER
22 4 TERMINAL 4 POLE 22-12 AWG EL-LAB-WAGO 2002-1401 WAGO BECKER
23 4 TERMINAL END PLATE 4POLE 22-12 AWG EL-LAB-WAGO 2002-1492 WAGO BECKER
24 4 DIN RAIL CLAMPS EL-LAB-WAGO 249-116 WAGO BECKER
THIS DOCUMENT IS CREATED BY AND IS THE Drawing REV Number
25 10" DIN RAIL EL-LAB-WAGO 210-112 WAGO BECKER
PROPERTY OF FREEMAN ENCLOSURE SYSTEMS,
LLC. ITS USE IS AUTHORIZED ONLY FOR
4LAP4-RF Number AE753015 1
Description
RESPONDING TO A REQUEST FOR QUOTATION OR
FOR THE PERFORMANCE OF WORK FOR FREEMAN
ENCLOSURE SYSTEMS, LLC. THIS DRAWING IS
ENCLOSURE LAYOUT/BOM FREEMAN
Equipment Designed by Checked by Date Sheet
NOT INTENDED TO BE USED FOR CONSTRUCTION
ENCLOSURE SYSTEMS
OR DISTRIBUTION WITHOUT CONSENT. ALARM PANEL 4 LAP4-RF SK JL 04/24/15 5 OF 5
9/14/2018 2:02:34 PM
5 5

95% CRITICAL
ALARM SILENCE TANK LEAK HIGH LEVEL

4LAP4-RF
LOCAL PUSH TO TEST
90% HIGH
LEVEL

ENCLOSURE
5 5
33% LOW
LEVEL

FREEMAN FREEMAN
ENCLOSURE SYSTEMS ENCLOSURE SYSTEMS

4LAP4-R REMOTE ENCLOSURE

STANDARD MAX
JOB NAME/# MATERIAL QUANTITY ENCLOSURE
DIMENTIONS DIMENTIONS
4LAP4-RF LOCAL BLACK/WHITE 1 8x6 5X5 5-1/8x 5-1/8
Drawing REV Number
4LAP4-RF REMOTE BLACK/WHITE 1 6x6 5X5 5-1/8x 5-1/8 THIS DOCUMENT IS CREATED BY AND IS THE
PROPERTY OF FREEMAN ENCLOSURE SYSTEMS, ENGRAVING FACE PLATE Number
0
LLC. ITS USE IS AUTHORIZED ONLY FOR
RESPONDING TO A REQUEST FOR QUOTATION OR Description
FOR THE PERFORMANCE OF WORK FOR FREEMAN
ENCLOSURE SYSTEMS, LLC. THIS DRAWING IS
NOT INTENDED TO BE USED FOR CONSTRUCTION Project Name Designed by Checked by Date Sheet #
FREEMAN
ENCLOSURE SYSTEMS
OR DISTRIBUTION WITHOUT CONSENT. SDK JL
9/14/2018 2:02:36 PM

You might also like