DESIGN REPORT OF
OPEN RCC FOUNDATION FOR
LSO TOWER OF 230 kV LINE
FROM SP KOIL 230 KV SS TO
THE ORAGADAM 230 KV LINE
CONTENTS
1. LOAD CALCULATIONS … P. 1
Page 1
NAME OF WORK : DESIGN OF RCC FOUNDATION FOR LSO 230 KV TOWER
Page 2
NAME OF WORK : DESIGN OF RCC FOUNDATION FOR LSO 230 KV TOWER
Page 3
NAME OF WORK : DESIGN OF RCC FOUNDATION FOR LSO 230 KV TOWER
Sin²W1 = 1.0000
Sin²W2 = 0.2500
Page 4
NAME OF WORK : DESIGN OF RCC FOUNDATION FOR LSO 230 KV TOWER
Sin²W1 = 0.9330
Sin²W2 = 0.0670
Page 5
NAME OF WORK : DESIGN OF RCC FOUNDATION FOR LSO 230 KV TOWER
Sin²W1 = 0.7501
Sin²W2 = 0.7500
Page 6
NAME OF WORK : DESIGN OF RCC FOUNDATION FOR LSO 230 KV TOWER
Page 7
NAME OF WORK : DESIGN OF RCC FOUNDATION FOR LSO 230 KV TOWER
Page 8
NAME OF WORK : DESIGN OF RCC FOUNDATION FOR LSO 230 KV TOWER
Page 9
NAME OF WORK : DESIGN OF RCC FOUNDATION FOR LSO 230 KV TOWER
Page 10
NAME OF WORK : DESIGN OF RCC FOUNDATION FOR LSO 230 KV TOWER
Page 11
NAME OF WORK : DESIGN OF RCC FOUNDATION FOR LSO 230 KV TOWER
TRANSVERSE LOAD
EARTH WIRE
EARTH WIRE
Weight of earth wire point 250 kg
[WEW*WTSNC1 * MSF]
Weight of man with tools & plant 0 kg
Weight of clamp 10 kg
TOTAL = 260 kg
CONDUCTOR
Weight of conductor 744 kg
[WC*WTSNC1 * MSF]
Weight of Insulator 204 kg
TOTAL = 948 kg
LONGITUDINAL LOAD
EARTH WIRE
Wire pull 0
TOTAL = 0 kg
CONDUCTOR
Conductor pull 0
From Insulator 0
TOTAL = 0 kg
Page 12
NAME OF WORK : DESIGN OF RCC FOUNDATION FOR LSO 230 KV TOWER
TRANSVERSE LOAD
EARTH WIRE
TOTAL = 4520 kg
CONDUCTOR
TOTAL = 9647 kg
VERTICAL LOAD
EARTH WIRE
Weight of earth wire point 250 kg
Weight of clamp 10 kg
TOTAL = 260 kg
CONDUCTOR
Weight of conductor 744 kg
TOTAL = 948 kg
LONGITUDINAL LOAD
EARTH WIRE
Wire pull 0
TOTAL = 0 kg
CONDUCTOR
Conductor pull 0
From Insulator [Pd * Ai * Gi * Cdi * SIN q * 2* MSF ] 65
TOTAL = 65 kg
Page 13
NAME OF WORK : DESIGN OF RCC FOUNDATION FOR LSO 230 KV TOWER
TRANSVERSE LOAD
EARTH WIRE
TOTAL = 4470 kg
CONDUCTOR
TOTAL = 9513 kg
VERTICAL LOAD
EARTH WIRE
Weight of earth wire point 250 kg
Weight of clamp 10 kg
TOTAL = 260 kg
CONDUCTOR
Weight of conductor 744 kg
TOTAL = 948 kg
LONGITUDINAL LOAD
EARTH WIRE
Wire pull 0
TOTAL = 0 kg
CONDUCTOR
Conductor pull 0
From Insulator 91
TOTAL = 91 kg
Page 14
NAME OF WORK : DESIGN OF RCC FOUNDATION FOR LSO 230 KV TOWER
TRANSVERSE LOAD
EARTH WIRE
TOTAL = 2755 kg
CONDUCTOR
TOTAL = 5904 kg
VERTICAL LOAD
EARTH WIRE
Weight of earth wire point 250 kg
Weight of clamp 10 kg
TOTAL = 260 kg
CONDUCTOR
Weight of conductor 744 kg
TOTAL = 948 kg
LONGITUDINAL LOAD
EARTH WIRE
Wire pull 0
TOTAL = 0 kg
CONDUCTOR
Conductor pull 0
TOTAL = 0 kg
Page 15
NAME OF WORK : DESIGN OF RCC FOUNDATION FOR LSO 230 KV TOWER
TRANSVERSE LOAD
EARTH WIRE
TOTAL = 2823 kg
CONDUCTOR
TOTAL = 6049 kg
VERTICAL LOAD
EARTH WIRE
Weight of earth wire point 250 kg
Weight of clamp 10 kg
TOTAL = 260 kg
CONDUCTOR
Weight of conductor 744 kg
TOTAL = 948 kg
LONGITUDINAL LOAD
EARTH WIRE
Wire pull 0
TOTAL = 0 kg
CONDUCTOR
Conductor pull 0
From Insulator 23
TOTAL = 23 kg
Page 16
NAME OF WORK : DESIGN OF RCC FOUNDATION FOR LSO 230 KV TOWER
TRANSVERSE LOAD
EARTH WIRE
TOTAL = 2805 kg
CONDUCTOR
TOTAL = 6001 kg
VERTICAL LOAD
EARTH WIRE
Weight of clamp 10 kg
TOTAL = 260 kg
CONDUCTOR
Weight of conductor 744 kg
TOTAL = 948 kg
LONGITUDINAL LOAD
EARTH WIRE
Wire pull 0
TOTAL = 0 kg
CONDUCTOR
Conductor pull 0
From Insulator 33
TOTAL = 33 kg
Page 17
NAME OF WORK : DESIGN OF RCC FOUNDATION FOR LSO 230 KV TOWER
7. Security condition - 75% Wind & Wind direction theta - 0 deg INTACT WIRE
TRANSVERSE LOAD
EARTH WIRE
TOTAL = 3622 kg
CONDUCTOR
TOTAL = 7632 kg
VERTICAL LOAD
EARTH WIRE
Weight of clamp 10 kg
TOTAL = 260 kg
CONDUCTOR
Weight of conductor 744 kg
TOTAL = 948 kg
LONGITUDINAL LOAD
EARTH WIRE
Wire pull 0
TOTAL = 0 kg
CONDUCTOR
Conductor pull 0
TOTAL = 0 kg
Page 18
NAME OF WORK : DESIGN OF RCC FOUNDATION FOR LSO 230 KV TOWER
8. Security condition - 75% Wind & Wind direction theta - 0 deg BROKEN WIRE
TRANSVERSE LOAD
EARTH WIRE
WIND LOAD ON EARTHWIRE [ Fwew ] 255 kg
TOTAL = 1854 kg
CONDUCTOR
WIND LOAD ON CONDUCTOR [ Fwc ] 569 kg
TOTAL = 3970 kg
VERTICAL LOAD
EARTH WIRE
Weight of clamp 10 kg
TOTAL = 160 kg
CONDUCTOR
Weight of conductor 446 kg
TOTAL = 650 kg
LONGITUDINAL LOAD
EARTH WIRE
CONDUCTOR
Page 19
NAME OF WORK : DESIGN OF RCC FOUNDATION FOR LSO 230 KV TOWER
9. Security condition - 36% Wind & Wind direction theta - 0 deg INTACT WIRE
TRANSVERSE LOAD
EARTH WIRE
TOTAL = 2755 kg
CONDUCTOR
TOTAL = 5904 kg
VERTICAL LOAD
EARTH WIRE
Weight of clamp 10 kg
TOTAL = 260 kg
CONDUCTOR
Weight of conductor 744 kg
TOTAL = 948 kg
LONGITUDINAL LOAD
EARTH WIRE
Wire pull 0
TOTAL = 0 kg
CONDUCTOR
Conductor pull 0
TOTAL = 0 kg
Page 20
NAME OF WORK : DESIGN OF RCC FOUNDATION FOR LSO 230 KV TOWER
10. Security condition - 36% Wind & Wind direction theta - 0 deg BROKEN WIRE
TRANSVERSE LOAD
EARTH WIRE
TOTAL = 1398 kg
CONDUCTOR
TOTAL = 3021 kg
VERTICAL LOAD
EARTH WIRE
Weight of clamp 10 kg
TOTAL = 160 kg
CONDUCTOR
Weight of conductor 446 kg
TOTAL = 650 kg
LONGITUDINAL LOAD
EARTH WIRE
Wire pull 2209
TOTAL = 2209 kg
CONDUCTOR
Page 21
NAME OF WORK : DESIGN OF RCC FOUNDATION FOR LSO 230 KV TOWER
TRANSVERSE LOAD
EARTH WIRE
TOTAL = 1594 kg
CONDUCTOR
TOTAL = 3389 kg
VERTICAL LOAD
EARTH WIRE
Weight of earth wire point 250 kg
Weight of clamp 10 kg
TOTAL = 410 kg
CONDUCTOR
Weight of conductor 744 kg
TOTAL = 1098 kg
LONGITUDINAL LOAD
EARTH WIRE
Page 22
NAME OF WORK : DESIGN OF RCC FOUNDATION FOR LSO 230 KV TOWER
TRANSVERSE LOAD
EARTH WIRE
TOTAL = 1695 kg
VERTICAL LOAD
EARTH WIRE
Weight of clamp 10 kg
TOTAL = 310 kg
CONDUCTOR
Weight of conductor 446 kg
TOTAL = 800 kg
LONGITUDINAL LOAD
EARTH WIRE
Wire pull 1594
[ 2*0.5*EWT * MSF] TOTAL = 1594 kg
FOR INTACT WIRES = [ 1.5*1563*MSF] 2391
CONDUCTOR
Page 23
NAME OF WORK : DESIGN OF RCC FOUNDATION FOR LSO 230 KV TOWER
TRANSVERSE LOAD
EARTH WIRE
TOTAL = 1967 kg
CONDUCTOR
TOTAL = 4250 kg
VERTICAL LOAD
EARTH WIRE
Weight of clamp 10 kg
TOTAL = 260 kg
CONDUCTOR
Weight of conductor 744 kg
TOTAL = 948 kg
LONGITUDINAL LOAD
EARTH WIRE
Wire pull [1*1563*COS(0) * MSF ] 1594
TOTAL = 1594 kg
CONDUCTOR
Page 24
NAME OF WORK : DESIGN OF RCC FOUNDATION FOR LSO 230 KV TOWER
EFF. AREA FULL AREA SOLIDITY Cdt Gt WIND LOAD C.G FROM GL
Aet RATIO in kg
IN SQ.M IN SQ.M TRANS LONGI IN METRE
Pd in kg/sq.m = 94.35
q - Angle of incidence of wind direction ^ to Longitdnl face of Tower = 0
Sin q 0
Cos q 1
Aet - Effective area of tower See Table
Cdt - Drag coefficient See Table
Gt - Gust response factor See Table
Page 25
NAME OF WORK : DESIGN OF RCC FOUNDATION FOR LSO 230 KV TOWER
EFF. AREA FULL AREA SOLIDITY Cdt Gt WIND LOAD C.G FROM GL
RATIO in kg
IN SQ.M IN SQ.M TRANS LONGI IN METRE
X-ARM BODY 5.150 22.710 0.227 1.78 2.05 1766 1019 25.35
LOWER BODY 11.360 63.020 0.180 1.80 1.95 3747 2163 12.83
Pd in kg/sq.m = 94.35
q - Angle of incidence of wind direction ^ to Longitdnl face of Tower = 30
Sin q 0.499987
Cos q 0.866033
Aet - Effective area of tower See Table
Cdt - Drag coefficient See Table
Gt - Gust response factor See Table
Page 26
NAME OF WORK : DESIGN OF RCC FOUNDATION FOR LSO 230 KV TOWER
EFF. AREA FULL AREA SOLIDITY Cdt Gt WIND LOAD C.G FROM GL
RATIO in kg
IN SQ.M IN SQ.M TRANS LONGI IN METRE
X-ARM BODY 5.150 22.710 0.227 1.78 2.05 1505 1504 25.35
LOWER BODY 11.360 63.020 0.180 1.80 1.95 3192 3192 12.83
Pd in kg/sq.m = 94.35
q - Angle of incidence of wind direction ^ to Longitdnl face of Tower = 45
Sin q 0.70709
Cos q 0.707123
Aet - Effective area of tower See Table
Cdt - Drag coefficient See Table
Gt - Gust response factor See Table
Page 27
NAME OF WORK : DESIGN OF RCC FOUNDATION FOR LSO 230 KV TOWER
EFF. AREA FULL AREA SOLIDITY Cdt Gt WIND LOAD C.G FROM PL
RATIO in kg
IN SQ.M IN SQ.M TRANS LONGI IN METRE
Pd in kg/sq.m = 33.966
q - Angle of incidence of wind direction ^ to Longitdnl face of Tower = 0
Sin q 0
Cos q 1
Aet - Effective area of tower See Table
Cdt - Drag coefficient See Table
Gt - Gust response factor See Table
Page 28
NAME OF WORK : DESIGN OF RCC FOUNDATION FOR LSO 230 KV TOWER
EFF. AREA FULL AREA SOLIDITY Cdt Gt WIND LOAD C.G FROM PL
RATIO in kg
IN SQ.M IN SQ.M TRANS LONGI IN METRE
X-ARM BODY 5.150 22.710 0.227 1.78 2.05 636 367 25.35
LOWER BODY 11.360 63.020 0.180 1.80 1.95 1349 779 12.83
Pd in kg/sq.m = 33.966
q - Angle of incidence of wind direction ^ to Longitdnl face of Tower = 30
Sin q 0.499987
Cos q 0.866033
Aet - Effective area of tower See Table
Cdt - Drag coefficient See Table
Gt - Gust response factor See Table
Page 29
NAME OF WORK : DESIGN OF RCC FOUNDATION FOR LSO 230 KV TOWER
EFF. AREA FULL AREA SOLIDITY Cdt Gt WIND LOAD C.G FROM PL
RATIO in kg
IN SQ.M IN SQ.M TRANS LONGI IN METRE
X-ARM BODY 5.150 22.710 0.227 1.78 2.05 542 542 25.35
LOWER BODY 11.360 63.020 0.180 1.80 1.95 1149 1149 12.83
Pd in kg/sq.m = 33.97
q - Angle of incidence of wind direction ^ to Longitdnl face of Tower = 45
Sin q 0.70709
Cos q 0.707123
Aet - Effective area of tower See Table
Cdt - Drag coefficient See Table
Gt - Gust response factor See Table
Page 30
NAME OF WORK : DESIGN OF RCC FOUNDATION FOR LSO 230 KV TOWER
EFF. AREA FULL AREA SOLIDITY Cdt Gt WIND LOAD C.G FROM PL
RATIO in kg
IN SQ.M IN SQ.M TRANS LONGI IN METRE
Pd in kg/sq.m = 70.763
q - Angle of incidence of wind direction ^ to Longitdnl face of Tower = 0
Sin q 0
Cos q 1
Aet - Effective area of tower See Table
Cdt - Drag coefficient See Table
Gt - Gust response factor See Table
Page 31
NAME OF WORK : DESIGN OF RCC FOUNDATION FOR LSO 230 KV TOWER
V= 260
Tr = 4331
EL + 36.68 V= 948 EW Lg = 0 V= 948
Tr = 9243 Tr = 9243
Lg = 0 Lg = 0
EL + 30.684 C C
V= 948 V= 948
Tr = 9243 Tr = 9243
Lg = 0 Lg = 0
EL + 25.350 C C
V= 948 V= 948
Tr = 9243 Tr = 9243
Lg = 0 Lg = 0
EL + 20.016 C C
LS+0m TOWER
BENDING MOMENT, M AT GROUND LEVEL:
DUE TO CONDUCTOR & EARTH WIRE = 1564659.1 KG.M
LOADS IN KG
V - VERTICAL LOAD; Tr - TRANSVERSE LOAD; Lg - LONGITUDINAL LOAD
Page 32
NAME OF WORK : DESIGN OF RCC FOUNDATION FOR LSO 230 KV TOWER
V= 260
Tr = 4520
EL + 36.68 V= 948 EW Lg = 0 V= 948
Tr = 9647 Tr = 9647
Lg = 65 Lg = 65
EL + 30.684 C C
V= 948 V= 948
Tr = 9647 Tr = 9647
Lg = 65 Lg = 65
EL + 25.35 C C
V= 948 V= 948
Tr = 9647 Tr = 9647
Lg = 65 Lg = 65
EL + 20.016 C C
LS+0m TOWER
1,21,740 KG
LOADS IN KG
V - VERTICAL LOAD; Tr - TRANSVERSE LOAD; Lg - LONGITUDINAL LOAD
Page 33
NAME OF WORK : DESIGN OF RCC FOUNDATION FOR LSO 230 KV TOWER
V= 260
Tr = 4470
EL + 36.7 V= 948 EW Lg = 0 V= 948
Tr = 9513 Tr = 9513
Lg = 91 Lg = 91
EL + 30.684 C C
V= 948 V= 948
Tr = 9513 Tr = 9513
Lg = 91 Lg = 91
EL + 25.35 C C
V= 948 V= 948
Tr = 9513 Tr = 9513
Lg = 91 Lg = 91
EL + 20.016 C C
LS+0m TOWER
1,21,386 KG
LOADS IN KG
V - VERTICAL LOAD; Tr - TRANSVERSE LOAD; Lg - LONGITUDINAL LOAD
Page 34
NAME OF WORK : DESIGN OF RCC FOUNDATION FOR LSO 230 KV TOWER
V= 260
Tr = 2755
EL + 36.68 V= 948 EW Lg = 0 V= 948
Tr = 5904 Tr = 5904
Lg = 0 Lg = 0
EL + 30.684 C C
V= 948 V= 948
Tr = 5904 Tr = 5904
Lg = 0 Lg = 0
EL + 25.35 C C
V= 948 V= 948
Tr = 5904 Tr = 5904
Lg = 0 Lg = 0
EL + 20.016 C C
LS+0m TOWER
LOADS IN KG
V - VERTICAL LOAD; Tr - TRANSVERSE LOAD; Lg - LONGITUDINAL LOAD
Page 35
NAME OF WORK : DESIGN OF RCC FOUNDATION FOR LSO 230 KV TOWER
V= 260
Tr = 2823
EL + 36.68 V= 948 EW Lg = 0 V= 948
Tr = 6049 Tr = 6049
Lg = 23 Lg = 23
EL + 30.684 C C
V= 948 V= 948
Tr = 6049 Tr = 6049
Lg = 23 Lg = 23
EL + 25.35 C C
V= 948 V= 948
Tr = 6049 Tr = 6049
Lg = 23 Lg = 23
EL + 20.016 C C
LS+0m TOWER
72,875 KG
LOADS IN KG
V - VERTICAL LOAD; Tr - TRANSVERSE LOAD; Lg - LONGITUDINAL LOAD
Page 36
NAME OF WORK : DESIGN OF RCC FOUNDATION FOR LSO 230 KV TOWER
V= 260
Tr = 2805
EL + 36.68 V= 948 EW Lg = 0 V= 948
Tr = 6001 Tr = 6001
Lg = 33 Lg = 33
EL + 30.684 C C
V= 948 V= 948
Tr = 6001 Tr = 6001
Lg = 33 Lg = 33
EL + 25.35 C C
V= 948 V= 948
Tr = 6001 Tr = 6001
Lg = 33 Lg = 33
EL + 20.016 C C
LS+0m TOWER
72,794 KG
LOADS IN KG
V - VERTICAL LOAD; Tr - TRANSVERSE LOAD; Lg - LONGITUDINAL LOAD
Page 37
NAME OF WORK : DESIGN OF RCC FOUNDATION FOR LSO 230 KV TOWER
V= 160
Tr = 1854
EL + 36.68 V= 948 EW Lg = 2768 V= 650
Tr = 7632 Tr = 3970
Lg = 0 Lg = 5722
EL + 30.684 C C
V= 948 V= 650
Tr = 7632 Tr = 3970
Lg = 0 Lg = 5722
EL + 25.35 C C
V= 948 V= 948
Tr = 7632 Tr = 7632
Lg = 0 Lg = 0
EL + 20.016 C C
LS+0m TOWER
LOADS IN KG
V - VERTICAL LOAD; Tr - TRANSVERSE LOAD; Lg - LONGITUDINAL LOAD
Page 38
NAME OF WORK : DESIGN OF RCC FOUNDATION FOR LSO 230 KV TOWER
V= 260
Tr = 3622
EL + 36.68 V= 948 EW Lg = 0 V= 650
Tr = 7632 Tr = 3970
Lg = 0 Lg = 5722
EL + 30.684 C C
V= 948 V= 650
Tr = 7632 Tr = 3970
Lg = 0 Lg = 5722
EL + 25.35 C C
V= 948 V= 650
Tr = 7632 Tr = 3970
Lg = 0 Lg = 5722
EL + 20.016 C C
LS+0m TOWER
Page 39
NAME OF WORK : DESIGN OF RCC FOUNDATION FOR LSO 230 KV TOWER
SECURITY CONDITION - 9 36% WIND THETA = 0 DEG
V= 160
Tr = 1398
EL + 36.68 V= 948 EW Lg = 2209 V= 650
Tr = 5904 Tr = 3021
Lg = 0 Lg = 4678
EL + 30.684 C C
V= 948 V= 650
Tr = 5904 Tr = 3021
Lg = 0 Lg = 4678
EL + 25.35 C C
V= 948 V= 948
Tr = 5904 Tr = 5904
Lg = 0 Lg = 0
EL + 20.016 C C
LS+0m TOWER
LOADS IN KG
V - VERTICAL LOAD; Tr - TRANSVERSE LOAD; Lg - LONGITUDINAL LOAD
Page 40
NAME OF WORK : DESIGN OF RCC FOUNDATION FOR LSO 230 KV TOWER
V= 260
Tr = 2755
EL + 36.68 V= 948 EW Lg = 0 V= 650
Tr = 5904 Tr = 3021
Lg = 0 Lg = 4678
EL + 30.684 C C
V= 948 V= 650
Tr = 5904 Tr = 3021
Lg = 0 Lg = 4678
EL + 25.35 C C
V= 948 V= 650
Tr = 5904 Tr = 3021
Lg = 0 Lg = 4678
EL + 20.016 C C
LS+0m TOWER
LOADS IN KG
V - VERTICAL LOAD; Tr - TRANSVERSE LOAD; Lg - LONGITUDINAL LOAD
Page 41
NAME OF WORK : DESIGN OF RCC FOUNDATION FOR LSO 230 KV TOWER
V= 1098 V= 1098
Tr = 3389 Tr = 3389
Lg = 5084.19 Lg = 5084
EL + 23.216 C C
V= 1098 V= 1098
Tr = 3389 Tr = 3389
Lg = 5084.19 Lg = 5084
EL + 20.016 C C
LS+0m TOWER
LOADS IN KG
V - VERTICAL LOAD; Tr - TRANSVERSE LOAD; Lg - LONGITUDINAL LOAD
Page 42
NAME OF WORK : DESIGN OF RCC FOUNDATION FOR LSO 230 KV TOWER
V= 310
Tr = 797
EL + 36.68 V= 1098 EW Lg = 1594 V= 800
Tr = 3389 Tr = 1695
Lg = 5084 Lg = 3389
EL + 30.684 C C
V= 1098 V= 800
Tr = 3389 Tr = 1695
Lg = 5084.19 Lg = 3389
EL + 25.35 C C
V= 1098 V= 1098
Tr = 3389 Tr = 3389
Lg = 5084.19 Lg = 5084
EL + 20.016 C C
LS+0m TOWER
LOADS IN KG
V - VERTICAL LOAD; Tr - TRANSVERSE LOAD; Lg - LONGITUDINAL LOAD
Page 43
NAME OF WORK : DESIGN OF RCC FOUNDATION FOR LSO 230 KV TOWER
V= 410
Tr = 1594
EL + 36.68 V= 1098 EW Lg = 2391 V= 800
Tr = 3389 Tr = 1695
Lg = 5084 Lg = 3389
EL + 30.684 C C
V= 1098 V= 800
Tr = 3389 Tr = 1695
Lg = 5084.19 Lg = 3389
EL + 25.35 C C
V= 1098 V= 800
Tr = 3389 Tr = 1695
Lg = 5084.19 Lg = 3389
EL + 20.016 C C
LS+0m TOWER
LOADS IN KG
V - VERTICAL LOAD; Tr - TRANSVERSE LOAD; Lg - LONGITUDINAL LOAD
Page 44
NAME OF WORK : DESIGN OF RCC FOUNDATION FOR LSO 230 KV TOWER
V= 260
Tr = 1967
EL + 36.68 V= 948 EW Lg = 1594 V= 948
Tr = 4250 Tr = 4250
Lg = 3389 Lg = 3389
EL + 30.684 C C
V= 948 V= 948
Tr = 4250 Tr = 4250
Lg = 3389.46 Lg = 3389
EL + 25.35 C C
V= 948 V= 948
Tr = 4250 Tr = 4250
Lg = 3389.46 Lg = 3389
EL + 20.016 C C
LS+0m TOWER
LOADS IN KG
V - VERTICAL LOAD; Tr - TRANSVERSE LOAD; Lg - LONGITUDINAL LOAD
Page 45
NAME OF WORK : DESIGN OF RCC FOUNDATION FOR LSO 230 KV TOWER
LOCATION NUMBER:
LOC.
LOC.
CRITICAL LOAD CASE --> 2 8
LOADS in kg
VERTICAL FORCE, THRUST @ GL 151362 1,23,325
p.46
Page 46
FOUNDATION DESIGN FOR LSO 230 KV TRANSMISSION TOWER
Tower slope :
Tan Q = 0.1584
True length factor 1.0125
Dimensions of foundations
Volume of concrete :
The formula for calculating the volume of conical pyramid frustum of soil
A1 = B^2+4*B*HL*TAN(alpha)+PIE*HL^2*(TAN(alpha))^2
A2 = B^2+4*B*(HL*TAN(alpha)+Hu*TAN(beta))+PIE*(HL*(TAN(alpha)+Hu*TAN(beta))^2
Vu = Hu/3 * {A1+A2+(A1*A2)^0.5}
VL = B^2*HL+2*B*Hl^2*TAN(alpha)+1/3*PIE*HL^3*(TAN(alpha))^2
Where
B = Width of soil frustum 5.000
HL = Height of wet soil 4.100
TAN(alpha) 0.268
TAN(beta) 0.577
Hu = Height of dry soil 0.000
A1 = 50.762
A2 = 50.762
Vu = 0.000 cum
VL = 152.721 cum
Wte = 950
F= 18720
Wc = 0.900
sinQ = 0.259
h= 5.078 m or
2.900 m
Moment due side thrust at the base of the footing 62143 kgm
Wte = 950
F= 470
Wc = 0.900
sinQ = 0.259
h= 0.805 m
2.900 m
Moment due side thrust at the base of the footing 4433 kgm
P. 50
FOUNDATION DESIGN FOR LSO 230 KV TRANSMISSION TOWER
Compression reinforcement :
From table 2 of SP 16
pt = 0.4
Hence Ast = 5258 sqmm
Ast provided
Dia of bar = 16 mm
Unit wt of bar = 1.6 kg/m
No of bar = 28
Ast = 5607 sqmm > 5258
From table 2 of SP 16
pt = 0.300
Hence Ast = 4108 sqmm
Ast provided
Dia of bar 16 mm
Unit wt of bar 1.6 kg/m
No of bar 28
Ast = 5607 sqmm
P. 51
FOUNDATION DESIGN FOR LSO 230 KV TRANSMISSION TOWER
Uplift reinforcement :
MUX2 = 0.87*415*Ast*d1*(1-Ast*(415/1000*d2*15))
Nmm/m
119998330.9
Ast* 226017
1-Ast* 6.36503E-05
a= 6.36503E-05
b= -1
c= 530.9254244
Hence Ast = 550
MUY2 60034858.01
MUY2 = 0.87*415*Ast*d1*(1-Ast*(415/1000*d2*20))
Nmm/m
60034858.01
Ast* 117702
1-Ast* 6.36503E-05
a= 6.36503E-05
b= -1
c= 510.0567959
Hence Ast = 528
At section X-X
N/sqmm
At section Y-Y
Wte = Wt * {(1+sinQ)/(1-sinQ)}
3.400
F1 = 8393 5486 kgm
0.400
F2 = 4879 6131 kgm
0.300
F3 = 8030 6615 kgm
0.100
F4 = 3348 6777 kgm
Total = 24651
Total overturning moment due to uplift & side thrust 282021 kgm
Total resisting moment 362714 kgm
P. 54