Cable Size

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

CABLE 

SELECTION CHART
 Circuit  Recommended  CT's 
Recommended  CIRCUIT 
Breaker  Cable Cross  STANDARD 
Earth Cable  BREAKER SIZE
Rating  Section Area  SIZE
(mm²)
(amps) (mm²)
6A / 10A 1.5 mm² 1.5 mm² 6A 800A 200 / 5
16A 2.5 mm² 1.5 mm² / 2.5 mm² 10A 1000A 300 / 5
20A 4 mm² 2.5 mm² / 4 mm² 16A 1200A 400 / 5
32A 2X4mm² / 6 mm² 2X4mm²/ 6 mm² 20A 1600A 600 / 5
40A 10 mm² 10 mm² 32A 2000A 800 / 5
40A / 63A 16 mm² 16 mm² 40A 2500A 1200 / 5
63A / 80A 25 mm² 16 mm² 63A 1600 / 5
100A  35 mm² 16 mm² / 25 mm² 80A 2400 / 5
125A 35mm² / 50 mm² 16 mm² / 25 mm² 100A BUS BAR SIZE
200A , 
160A 70 mm² 35 mm² 125A : 20mm X 10mm
300A
180A 95 mm² 50 mm² 160A 400A : 30mm X 10mm
200A 120 mm² 70 mm² 180A 600A : 50mm X 10mm 
(or) 2 X 30mm X 
250A 150 mm² 95 mm² 200A 800A :
10mm
300A 185 mm² 95 mm² 220A 1200A : 2 X 60mm X 
350A 240 mm² 120 mm² 250A 1600A : 10mm

2 x 80mm X 
400A 300 mm² 150 mm² 300A 2400A : 10mm (or) 2 x 
100mm X 10mm

2 X 1C X 120 mm² / 
630A 2 X 4C X 240 mm² 350A
1 X 1C X 240mm²

2 X 1C X 150 mm² / 
800A 2 X 4C X 300 mm² 400A
1 X 1C X 300mm²
1000A 3 X 4C X 240 mm² 3 X 1C X 120 mm²  630A

TRANS FORMER CABLE SIZE
CABLE SIZE IN 
TR SIZE BREAKER IN LVP EARTH CABLE SIZE IN mm²
mm²
1000 KVA 1600A 7 X 1C X 630 mm² 2 X 1C X 150 mm² 
1500 KVA 2500A 11 X 1C X 630 mm² 2 X 1C X 150 mm² 