Insulators:
For LV/MV Overhead Line: Pin/Shackle Insulator and For 11KV Line Pin/Disc Insulator
For Pin Insulator for LV/MV line: Stalk Length 135mm Shank Length 125 mm, min Load 2KN.
For Pin Insulator for 11KV line: Stalk Length 165mm Shank Length 150 mm, min Load 2KN.
D Clamp
D clamp shall be made of MS Flat size of 50mmX6mm,height of 75mm Galvanized and only used for vertical configuration for
LV/MV Line only.
Pole Top Clamp
Pole Top clamp made from Flat iron 50mmX8mm.
Stay wire Rod
Stay wire Rod shall not be less than 1.8 m Long and 19mm Dia. Anchor Plate shall not be less than 45mmX45mmX7.5mm.
Overhead Conductor (min)
For LV/MV Line: AAC(All Alu. Conductor) 7/1/2.21mm, ACSR 6/1/1/2.11mm, AAAC (All Alu. Alloy Conductor)
7/2.09mm(20Sqmm)
For 11KV/33KV Line : AAC(All Alu. Conductor) N/A, ACSR 6/1/1/2.11mm, AAAC (All Alu. Alloy Conductor)
7/2.56mm(30Sqmm)
Binding Wire
Binding Wire with insulator shall be done with 2.6mm(12SWG) soft aluminum wire.
Earthing in Overhead Line
Earthing wire shall not be less than 4mm(8SWG) and min 3 earthling Pit per KM shall be required.
If there is no Continuous wire for earthling in overhead line than each pole should be earthed.
Same Support
For LV/MV Line on Same Support Vertical distance: Between Phase to Earth shall be min 30cm and Between Phase to Phase
min 20cm
For LV/MV Line on Same Support Horizontal distance: Between Live wire on either side of support shall be 45cm.
For LV/MV Line on Same Support Horizontal distance: Between Live wire on same side of support shall be 30cm.
For LV/MV Line on Same Support Horizontal distance: Between central of pin insulator to end of cross Arm shall be 05cm.
For HV Line in Triangular Configuration for 11KV/33KV Line shall be min 1.5meter.
Overhead Line Struts
The Pit for Struts shall be located not less than 1.8meter from pole side. The depth of Pit shall be at least 1.2meter
Danger board
All Support carrying HV Line shall be fitted with Danger Board( IS:2551-1982) at height of 3meter.
Anti Climbing Device
For HV Line (IS:278-1978) having 4Point Barbs 75mm+12mm apart weight 128/125 gm/meter shall be wrapped helically with
pitch of 75mm around Limb of Pole height of 3.5meter to 5 to 6 meter.
Looping Box
Looping Bus shall be fabricated from MS Sheet of 1.6mm(16SWG) thickness, Min Size 250mmX200mmX100mm for single
cable entry and for 250mmX300mmX100mm for more than two cable entry
Feeder Pillar
Feeder Pillar shall be fabricated min 2mm thick MS sheet and hinged type double door at front side. If width of Pillar shall be
less than 60cm than single hinged type door shall be permitted.
Min height of Pedestal of Feeder Pillar shall be not less than 45cm and 1 to 2 meter height from Road Level.
Each Feeder Pillar shall be earthed with 2 no of Earthing electrode
Substation
Clear Height of S/S Building shall be min 3.6meter.
Area of Sub station
Sub Station Total Transformer Room Area Total S/S Area (Transformer, HT/LT
Panel without D.G)