Manual de Servicio Aire Acondicionado LG
Manual de Servicio Aire Acondicionado LG
Manual de Servicio Aire Acondicionado LG
com
LG
LG
Room Air Conditioner
SERVICE MANUAL
MODELS: AS-H0766KA2 LS-H0766KA2
AS-H0966KA2 LS-C0966KA2
AS-H126RKA2 LS-H0966KA2
AS-H186TKA2 LS-C126RKA2
LS-H246TKA2 LS-H126RKA2
CAUTION
• BEFORE SERVICING THE UNIT, READ THE SAFETY
PRECAUTIONS IN THIS MANUAL.
• ONLY FOR AUTHORIZED SERVICE PERSONNEL.
TABLE OF CONTENTS
LG Model Name ...............................................................................................................................................3
Safety Precautions..........................................................................................................................................5
Dimensions....................................................................................................................................................10
Symbols Used in this Manual ...................................................................................................................10
Indoor Unit................................................................................................................................................10
Outdoor Unit.............................................................................................................................................11
Product Specifications .................................................................................................................................14
Installation .....................................................................................................................................................16
Selection of the Best Location..................................................................................................................16
Piping Length and Elevation.....................................................................................................................16
How to Fix Installation Plate .....................................................................................................................17
Drill a Hole in the Wall ..............................................................................................................................17
Drain hose junction...................................................................................................................................17
Flaring work and connection of piping .......................................................................................................18
Flaring work..............................................................................................................................................18
Connection of Piping Indoor.....................................................................................................................18
Connection of the Pipes-Outdoor.............................................................................................................22
Connecting the cable between indoor unit and outdoor unit ...................................................................23
Connect the Cable to the Indoor Unit. ......................................................................................................23
Connect the Cable to the Outdoor Unit ....................................................................................................24
Checking the drainage and forming the pipings........................................................................................25
Checking the Drainage.............................................................................................................................25
Form the Piping ........................................................................................................................................25
AIR PURGING ................................................................................................................................................26
Air purging................................................................................................................................................26
Air purging with vacuum pump .................................................................................................................26
Test Running .................................................................................................................................................28
Operation .......................................................................................................................................................29
Function of Controls .................................................................................................................................29
Display Function ......................................................................................................................................33
Self-diagnosis Function............................................................................................................................33
Remote Control Operations......................................................................................................................34
Disassembly ..................................................................................................................................................35
Indoor Unit................................................................................................................................................35
Schematic Diagram.......................................................................................................................................38
Electric Control Device .............................................................................................................................38
Wiring Diagram.........................................................................................................................................39
Components Location ..............................................................................................................................40
Troubleshooting Guide .................................................................................................................................42
Refrigeration Cycle Diagram ....................................................................................................................42
2-way, 3-way Valve .................................................................................................................................43
Cycle Parts...............................................................................................................................................49
Electronic Parts ........................................................................................................................................50
Exploded View...............................................................................................................................................57
Replacement Parts List ................................................................................................................................62
Service Manual 3
Safety Precautions
To prevent injury to the user or other people and property damage, the following instructions must
be followed.
■ Incorrect operation due to ignoring instruction will cause harm or damage. The seriousness is
classified by the following indications.
■ Installation
Do not use damaged power cords, plugs, or a Always use the power plug and socket with the
loose socket. ground terminal.
Install the panel and the cover of control box .Do not modify or extend the power cord.
securely.
• There is risk of fire of electric shock. • No grounding may cause electric shock.
Service Manual 5
For re-installation of the installed product, Do not install, remove, or re-install the unit by
always contact a dealer or an authorized ser- yourself.
vice center.
• There is risk of fire, electric shock, explosion, or • There is risk of fire, electric shock, explosion, or
injury. injury.
Be cautious when unpacking and installing the For installation, always contact the dealer or
product. an Authorized service center
• Sharp edges could cause injury. Be especially care- • There is risk of fire, electric shock, explosion, or injury.
ful of the case edges and the fins on the condenser
and evaporator.
Do not install the product on a defective instal- Be sure the installation area does not
lation stand. deteriorate with age.
• It may cause injury, accident, or damage to the • If the base collapses, the air conditioner could fall
product. with it, causing property damage, product failure,
and personal injury.
■ Operation
Do not turn the air-conditioner ON or OFF by Use a dedicated outlet for this appliance.
plugging or unplugging the power plug.
• There is risk of fire or electrical shock. • There is risk of fire or electrical shock.
Grasp the plug to remove the cord from the Do not place a heater or other appliances near
outlet. Do not touch it with wet hands. the power cable.
• There is risk of fire or electrical shock. • There is risk of fire and electric shock.
Do not allow water to run into electrical parts. Do not store or use flammable gas or com-
bustibles near the air conditioner.
• There is risk of fire, failure of the product, or electric • There is risk of fire or failure of product.
shock.
x
Wa Thinner
Service Manual 7
Unplug the unit if strange sounds, odors, or Be cautious that water could not enter the
smoke comes from it. product.
• There is risk of electric shock or fire. • There is risk of fire, electric shock, or product dam-
age.
■ Installation
Always check for gas (refrigerant) leakage after Install the drain hose to ensure that water is
installation or repair of product. drained away properly.
• Low refrigerant levels may cause failure of product. • A bad connection may cause water leakage.
Keep level even when installing the product. Use two or more people to lift and transport
the air conditioner.
• To avoid vibration or water leakage. • Avoid personal injury.
90˚
■ Operation
Use a soft cloth to clean. Do not use harsh Do not touch the metal parts of the product
detergents, solvents, etc. when removing the air filter. They are very
sharp!
• There is risk of fire, electric shock, or damage to the • There is risk of personal injury.
plastic parts of the product.
x
Wa
Do not step on or put anyting on the product. Do not insert hands or other objects through
(outdoor units) the air inlet or outlet while the air conditioner
is plugged in.
• There is risk of personal injury and failure of product. • There are sharp and moving parts that could cause
personal injury.
Service Manual 9
Dimensions
Symbols Used in this Manual
This symbol alerts you to the risk of electric shock.
This symbol alerts you to hazards that could cause harm to the
air conditioner.
Indoor Unit
D
W
Installation plate
Model
7K, 9K Btu Series 12K Btu Series 18K Btu Series
Dimension
W mm 756 900 1,090
H mm 260 285 314
Outdoor Unit
W L2
L1
D
L3
H
Gas side
(3-way valve)
L5
Liquid side
L4
(2-way valve)
MODEL
7k, 9k Btu Series 12k Btu Series
DIM unit
W mm 575 717
H mm 525 498
D mm 260 229
L1 mm 301 270
L2 mm 73 56
L3 mm 392 464
L4 mm 35 17
L5 mm 100 130
Service Manual 11
Outdoor Unit
W L2
L1
D
L3
H
L5 Gas side
(3-way valve)
Liquid side
L4
(2-way valve)
MODEL
18K But Series
DIM
W mm 840
H mm 577
D mm 276
L1 mm 337
L2 mm 64
L3 mm 611
L4 mm 16
L5 mm 156
Outdoor Unit
W
L2
L1
D
L3
L4
H
L11 L10
Gas side
Liquid side
L7 L6 L8 L9
L5
MODEL
AS-H246TKA2
DIM
W mm 870
H mm 655
D mm 320
L1 mm 370
L2 mm 340
L3 mm 25
L4 mm 630
L5 mm 25
L6 mm 546
L7 mm 162
L8 mm 162
L9 mm 54
L10 mm 74.5
L11 mm 79
Service Manual 13
Product Specifications
Table-1
Model Name
AS-H0766KA2 AS-H0966KA2 AS-H126RKA2 AS-H186TKA2 AS-H246TKA2
Item Unit
Cooling Capacity 7000 9000 12000 18500 23500
Btu/h
Heating Capacity 7300 9300 12500 19000 23500
Moisture Removal l/h 1 1.2 1.2 2.2 2.9
Power Source Ø, V, Hz 1Ø,220-240V,50Hz 1Ø,220-240V,50Hz 1Ø,220-240V,50Hz 1Ø,220-240V,50Hz 1Ø,220-240V,50Hz
Indoor 5.0/5.7 5.8/6.6 8.8/9.5 13.4 15.1
Air Circulation m3/min
Outdoor 20 20 22 42 42
Indoor 34 37 40 40 47
Noise Level dB (A)±3
Outdoor 49 49 52 54 57
Cooling 730 940 1250 1760 2290
Input W
Heating 730 970 1140 1900 2450
Running Cooling 3.2 4.1 5.6 7.9 10.5
A
Current Heating 3.2 4.2 5.1 8.5 11.0
E.E.R. Cooling 9.59 9.57 9.6 10.51 10.26
Btu/hW
C.O.P Heating 10.0 9.58 10.96 10.0 9.59
Indoor 7 7 9.5 22 22
Motor Output W
Outdoor 18 18 - 72 82.9
Dimensions Indoor 756x260x155 756x260x155 900x285x156 1090x314x172 1090x314x172
mm
(W x H x D) Outdoor 575x525x260 575x525x260 717x498x229 870x577x276 870x577x276
Indoor 7 7 7.2 12 12
Net. Weight kg
Outdoor 25 26 30 50 60
Refrigerant (R410A) g 660g 710g 720g 1270g 1500g
Airflow Direction Control (Up & Down) O O O O O
Airflow Direction Control (Left & Right) - - - - -
Chaos Wind O O O O O
Timer 7Hr OFF 7Hr OFF 7Hr OFF 7Hr OFF 7Hr OFF
Self Diagnosis O O O O O
Remocon Type L.C.D wireless L.C.D wireless L.C.D wireless L.C.D Wireless L.C.D Wireless
Liquid 1/4"(6.35) 1/4"(6.35) 1/4"(6.35) 1/4"(6.35) 3/8”(9.52)
Service Valve inch(mm)
Gas 3/8"(9.52) 3/8"(9.52) 1/2"(12.7) 5/8"(15.88) 5/8”(15.88)
Sleeping Operation - - - - -
Drain Hose O O O O O
Connecting Cable 1.0mm x 3, 0.75mm x 2 1.0mm x 3, 0.75mm x 2 1.0mm x 3, 0.75mm x 2 1.5mm x 3, 0.75mm x 2 12.5mm x 3, 0.75mm2 x 2
2 2 2 2 2 2 2 2 2
Table-2
Model Name
LS-H0766KA2 LS-H0966KA2 LS-H126RKA2 LS-C126RKA2 LS-C0966KA2
Item Unit
Cooling Capacity 7000 9000 12000 12000 9000
Btu/h
Heating Capacity 7300 9000 13000 - -
Moisture Removal l/h 1 1.2 1.2 1.2 1.2
Power Source Ø, V, Hz 1Ø,220-240V,50Hz 1Ø,220-240V,50Hz 1Ø,220-240V,50Hz 1Ø,220-240V,50Hz 1Ø,220-240V,50Hz
Indoor 5.0/5.7 5.8/6.6 8.8/9.5 8.8/9.5 5.8/6.6
Air Circulation m3/min
Outdoor 20 20 22 22 20
Indoor 35 37 40 40 37
Noise Level dB (A)±3
Outdoor 49 49 52 52 49
Cooling 700 920 1310 1310 950
Input W
Heating 730 850 1250 - -
Running Cooling 3.1 4.1 6.0 6.0 4.2
A
Current Heating 3.2 3.7 5.8 - -
E.E.R. Cooling 10 9.78 9.16 9.16 9.47
Btu/hW
C.O.P Heating 2.93 3.1 3.05 - 3.1
Indoor 7 7 9.5 9.5 7
Motor Output W
Outdoor 18 18 - - 18
Dimensions Indoor 756x260x155 756x260x155 900x285x156 900x285x156 756x260x155
mm
(W x H x D) Outdoor 575x525x260 575x525x260 717x498x229 717x498x229 575x525x260
Indoor 7 7 7.2 7.2 7
Net. Weight kg
Outdoor 25 26 30 30 26
Refrigerant (R410A) g 650g 690g 800g 670g 690g
Airflow Direction Control (Up & Down) O O O O O
Airflow Direction Control (Left & Right) - - - - -
Chaos Wind O O O O O
Timer 7Hr OFF 7Hr OFF 7Hr OFF 7Hr OFF 7Hr OFF
Self Diagnosis O O O O O
Remocon Type L.C.D wireless L.C.D wireless L.C.D wireless L.C.D wireless L.C.D wireless
Liquid 1/4"(6.35) 1/4"(6.35) 1/4"(6.35) 1/4"(6.35) 1/4"(6.35)
Service Valve inch(mm)
Gas 3/8"(9.52) 3/8"(9.52) 1/2"(12.7) 1/2"(12.7) 3/8"(9.52)
Sleeping Operation - - - - -
Drain Hose O O O O O
Connecting Cable 1.0mm x 3, 0.75mm x 2
2 2
1.0mm x 3, 0.75mm x 2
2 2
1.0mm x 3, 0.75mm x 2
2 2
1.0mm x 3, 0.75mm x 2
2 2
1.0mm x 3, 0.75mm2 x 2
2
Service Manual 15
Installation
Selection of the Best Location
Indoor unit Rooftop Installations:
• Do not have any heat or steam near the unit. • If the outdoor unit is installed on a roof structure, be
• Select a place where there are no obstacles in front of the sure to level the unit. Ensure the roof structure and
unit. anchoring method are adequate for the unit location.
• Consult local codes regarding rooftop mounting.
• Make sure that condensation drainage can be conveniently
routed away.
Do not install near a doorway. Piping Length and Elevation
• Ensure that the space around the left and right of the unit is
more than "A". The unit should be installed as high on the Capacit Pipe Size Standard Max. Max. Additional
wall as possible, allowing a minimum of "B" from ceiling. y Length Elevation Length Refrigerant
(Btu/h) GAS LIQUID (m) B (m) A (m) (g/m)
• Use a stud finder to locate studs to prevent unnecessary 3/8"(Ø9.52) 1/4"(Ø6.35) 4 or 7.5 7 15 20
damage to the wall. 5k~14k
1/2"(Ø12.7) 1/4"(Ø6.35) 4 or 7.5 7 15 20
More than "B" More than "A" 1/2"(Ø12.7) 1/4"(Ø6.35) 4 or 7.5 15 30 20
18k~28k 5/8"(Ø15.88) 1/4"(Ø6.35) 4 or 7.5 15 30 20
5/8"(Ø15.88) 3/8"(Ø9.52) 4 or 7.5 15 30 30
5/8"(Ø15.88) 3/8"(Ø9.52) 7.5 15 30 30
30k~38k
3/4"(Ø19.05) 3/8"(Ø9.52) 7.5 15 30 50
More
More than 70cm than 60cm
(3/16"~5/16")
Installation Plate
5-7mm
• Open the Front Grille.
• Pass Telephone Control Cord Wire through the hole
Type "A" screw
which the power cord goes through.
2. Measure the wall and mark the centerline. It is • Connect Telephone Control Cord Wire to the phone jack
also important to use caution concerning the of telephone PCB of Control Box.
location of the installation plate-routing of the • Fix Telephone Control Cord Wire inside Control box so
wiring to power outlets is through the walls typi- as not to disconnect.
cally. Drilling the hole through the wall for pip- • Close the Front Grille.
ing connections must be done safely.
Installation plate
B
D
Adhesive
C E A
Service Manual 17
Copper tube
Tubing holder
Flaring work
• Firmly hold copper pipe in a die in the dimension shown in
the table above.
Handle When install, make sure that the
"A"
For right rear piping Connecting the pipings to the indoor unit and
drain hose to drain pipe.
Route the indoor tubing and the drain hose in the direction of
• Align the center of the pipes and sufficiently tighten
rear right.
the flare nut by hand.
Drain hose
Indoor unit tubing Flare nut Pipes
• Tighten the flare nut with a wrench.
Insert the connecting cable into the indoor unit from the out- Open-end wrench (fixed)
door unit through the piping hole.
Flare nut
• Do not connect the cable to the indoor unit.
Wrench Connection pipe
• Make a small loop with the cable for easy connection later.
Indoor unit tubing
Tape
Connecting Drain pipe
pipe
Drain hose
Connecting cable Indoor unit drain hose
NOTE: If the drain hose is routed inside the room, insulate Adhesive
Vinyl tape(narrow)
the hose with an insulation material* so that dripping from Wrap the insulation material around the con-
"sweating"(condensation) will not damage furniture or floors.
necting portion.
*Foamed polyethylene or equivalent is recommended.
•Overlap the connection pipe insulation material and the
Indoor unit installation indoor unit pipe insulation material. Bind them together with
vinyl tape so that there is no gap.
• Hook the indoor unit onto the upper portion of the installa- Plastic bands Insulation material
tion plate.(Engage the two hooks of the rear top of the
indoor unit with the upper edge of the installation plate.)
Ensure that the hooks are properly seated on the installa-
tion plate by moving it left and right.
• Wrap the area which accommodates the rear piping hous-
Connecting ing section with vinyl tape.
cable
Connection Indoor
pipe unit pipe
Drain hose Vinyl tape Wrap with vinyl tape
(wide)
Press the lower left and right sides of the unit against the Connecting cable
installation plate until the hooks engage into their slots(click-
ing sound). Pipe
Vinyl tape(narrow)
Service Manual 19
Vinyl tape(wide)
Drain hose Indoor unit tubing Flare nut Pipes
For left rear piping • Tighten the flare nut with a wrench.
Route the indoor tubing and the drain hose to
the required piping hole position. Open-end wrench (fixed)
Flare nut
Indoor unit
Spacer
Installation plate
8cm
• Wrap the area which accommodates the rear piping hous- Indoor unit installation
ing section with vinyl tape.
• Remove the spacer.
Connection Indoor
pipe unit piping • Ensure that the hooks are properly seated on the installa-
Vinyl tape
tion plate by moving it left and right.
Wrap with vinyl tape
(wide)
Pipe
Connecting
Vinyl tape(narrow) cable
Connecting cable
Drain hose
Press the lower left and right sides of the unit against the
installation plate until the hooks engage into their
• Bundle the piping and drain hose together by wrapping slots(clicking sound).
them with cloth tape over the range within which they fit
into the rear piping housing section.
Pipe
Drain hose
Vinyl tape(narrow) Installation Information (For left piping)
• Good case
For left piping. Follow the instruction below.
Wrap with • Press on the upper side of clamp. ( )
vinyl tape(wide)
Piping for
passage through
piping hole
Tubing holder
Service Manual 21
Outdoor unit
Gas side piping
(Bigger diameter)
Liquid side
piping
(Smaller
diameter)
Torque wrench
• If a power plug is not to be used, provide a circuit The power connecting cable connected to
breaker between power source and the unit as the indoor and outdoor unit should be
shown below. complied with the following specifications
(Type "B" approved by HAR or SAA).
NORMAL
CROSS-SECTIONAL
Air Circuit Breaker (mm2) AREA 0.75mm2
Conditioner Use a circuit
NORMAL Grade
breaker or time
CROSS
delay fuse. 5k~12k 14k~18k 24k~28k
-SECTIONAL
AREA 1.0 1.5 2.5
Cable Type(B) H07RN-F H07RN-F H07RN-F
(mm2)
Grade
NORMAL CROSS
30k, 32k 36k, 38k
-SECTIONAL AREA
0.75 0.75
Cable Type(B) H07RN-F H07RN-F
Service Manual 23
Cover control
Refix the control cover to the original position
with the screw.
After the confirmation of the above conditions, prepare the wiring as follows:
1) Never fail to have an individual power circuit specifically for the air conditioner. As for the method of wiring,
be guided by the circuit diagram posted on the inside of control cover.
2) The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from vibrations
to which the unit is subjected during the course of transportation. Check them and make sure that they are
all tightly fastened. (If they are loose, it could cause burn-out of the wires.)
3) Specification of power source.
4) Confirm that electrical capacity is sufficient.
5) See to that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the
name plate.
6) Confirm that the cable thickness is as specified in the power source specification.
(Particularly note the relation between cable length and thickness. (Refer to page 22))
7) Always install an earth leakage circuit breaker in a wet or moist area.
8) The following would be caused by voltage drop.
• Vibration of a magnetic switch, which will damage the contact point, fuse breaking, disturbance of the normal func-
tion of the overload.
9) The means for disconnection from a power supply shall be incorporated in the fixed wiring and have an air
gap contact separation of at least 3mm in each active(phase) conductors.
Pipings
Connecting
cable
Service Manual 25
AIR PURGING
Air purging • Do a leak test of all joints of the tubing(both indoor and out-
door) and both gas and liquid side service valves.
Air and moisture remaining in the refrigerant system have Bubbles indicate a leak. Be sure to wipe off the soap with a
undesirable effects as indicated below. clean cloth.
• Pressure in the system rises. • After the system is found to be free of leaks, relieve the
• Operating current rises. nitrogen pressure by loosening the charge hose connector
at the nitrogen cylinder. When the system pressure is
• Cooling(or heating) efficiency drops.
reduced to normal, disconnect the hose from the cylinder.
• Moisture in the refrigerant circuit may freeze and block cap-
illary tubing.
• Water may lead to corrosion of parts in the refrigeration
system. Indoor unit
Therefore, the indoor unit and tubing between the indoor and
outdoor unit must be leak tested and evacuated to remove
any noncondensables and moisture from the system.
If tubing length is less than 10m (33 ft) if tubing length is longer than 10m (33 ft)
Service Manual 27
TEST RUNNING
1. Check that all tubing and wiring have been properly con- NOTE: If the actual pressure is higher than shown, the system is
nected. most likely over-charged, and charge should be removed.
2. Check that the gas and liquid side service valves are fully If the actual pressure are lower than shown, the system is
open. most likely undercharged, and charge should be added.
The air conditioner is now ready for use.
Settlement of outdoor unit
PUMP DOWN
• Anchor the outdoor unit with a bolt and nut(ø10mm) tightly
This is performed when the unit is to be relocated or
and horizontally on a concrete or rigid mount. the refrigerant circuit is serviced.
• When installing on the wall, roof or rooftop, anchor the Pump Down means collecting all refrigerant in the outdoor
unit without loss in refrigerant gas.
mounting base securely with a nail or wire assuming the
influence of wind and earthquake. CAUTION:
• In the case when the vibration of the unit is conveyed to the Be sure to perform Pump Down procedure with the unit
hose, secure the unit with an anti-vibration bushing. cooling mode.
Bolt
Pump Down Procedure
1. Connect a low-pressure gauge manifold hose to the
charge port on the gas side service valve.
2. Open the gas side service valve halfway and purge the air
from the manifold hose using the refrigerant gas.
3. Close the liquid side service valve(all the way in).
4. Turn on the unit's operating switch and start the cooling
Tubing connection operation.
Evaluation of the performance 5. When the low-pressure gauge reading becomes 1 to
Operate unit for 15~20 minutes, then check the system 0.5kg/cm2 G(14.2 to 7.1 P.S.I.G.), fully close the gas side
refrigerant charge: valve stem and then quickly turn off the unit. At that time,
1. Measure the pressure of the gas side service valve. Pump Down has been completed and all refrigerant gas
will have been collected in the outdoor unit.
2. Measure the temperature of the intake and discharge of air.
Power-Failure Compensation Function User Selection ON/OFF
3. Ensure the difference between the intake temperature and
the discharge is more than 8°C(46°F) (Cooling) or 1) Operation Sequence
(Heating). Press the forced switch until BUZZER sounds 2 times
(beep~beep~).
Intake temperature
Release the forced switch if BUZZER sounds.
Discharge air
Check the function selection ON/OFF with the operation LED.
Operation
Function of Controls
• DISPLAY
1) C/O Model
Operation Indicator
• ON while in appliance operation, OFF while in appliance pause.
• Flashing while in disconnection or short in Thermistor. (3 sec off / 0.5 sec on)
2) H/P Model
Operation Indicator
• ON while in appliance operation, OFF while in appliance pause.
• Flashing while in disconnection or short in Thermistor. (3 sec off / 0.5 sec on)
Defrost Indicator
• OFF except when hot start during heating mode operation or while in defrost control.
Service Manual 29
• While in compressor off, the indoor fan repeats low airflow speed and pause.
• While the intake air temp is between compressor on temp. and compressor off temp., 10-min dehumidification
operation and 4-min compressor off repeat.
Compressor ON Temp. ➲ Setting Temp+0.5°C
Compressor OFF Temp. ➲ Setting Temp-0.5°C
• In 10-min dehumidification operation, the indoor fan operates with the low airflow speed.
■ Defrost Control
• While in heating mode operation in order to protect the evaporator pipe of the outdoor unit from freezing,
reversed to cooling cycle to defrost the evaporator pipe of the outdoor unit.
• After 40 min heating mode operation, at 4 min interval, whether to carry out defrost control or not and the time
of defrost control are determined according to the following conditions.
1) While in heating mode operation, the maximum of the indoor pipe temperature is measured and it is com-
pared with the present indoor pipe temperature to get the difference of the indoor pipe temperatures (=the
maximum temperature of indoor pipe ? the present temperature of indoor pipe), according to which, whether
to carry out defrost control or not is determined.
2) According to the need of defrost control shown above and the elapsed time of heating mode operation at that
moment, the defrost control time is determined.
3) When the determined time of defrost control is below 7 min, heating mode operation continues without carry-
ing out defrost control. According to the procedure stated above, the determination is made again. When the
defrost control time is 7 min or longer, defrost control is then carried out.
• While in defrost control, the minimum temp of the indoor pipe is measured and it is compared with the present
temp of the indoor pipe to get the difference of the indoor pipe temperatures (=the present temperature of the
indoor pipe ? the minimum temperature of the indoor pipe). When the difference is 5°C or higher, defrost con-
trol is completed and heating mode operation is carried out.
• While in defrost control, if the defrost time determined before the start of defrost control is completed, defrost
control stops and heating mode operation is carried out regardless of the above condition.
• When the indoor pipe temp is 42°C or above, defrost control is not carried out even if the condition is one of
the defrost conditions above.
• While in defrost control, the compressor is on and the indoor fan, the outdoor fan, and the 4 way valve are off.
■ Forced Operation
• Operation procedures when the remote control can't be used.
• The operation will be started if the power button is pressed.
• If you want to stop operation, re-press the button.
Heat pump Model
Cooling Model
Room Temp. ≥ 24°C 21°C ≤ Room Temp. < 24°C Room Temp. < 21°C
Operating mode Cooling Cooling Healthy Dehumidification Heating
Indoor FAN Speed High High High High
Setting Temperature 22°C 22°C 23°C 24°C
• While in forced operation, the key input by the remote control has no effect and the buzzer sounds 10 times to
indicate the forced operation.
Service Manual 31
■ Test operation
• During the TEST OPERATION, the unit operates in cooling mode at high speed fan, regardless of room tem-
perature and resets in 18±1 minutes.
• During test operation, if remote controller signal is received, the unit operates as remote controller sets.
If you want to use this operation, open the front panel upward and Press the power button let it be pressed for
about 3 seconds.
• If you want to stop the operation, re-press the button.
■ Auto restart
• In case the power comes on again after a power failure, Auto Restarting Operation is the function to operate
procedures automatically to the previous operating conditions.
Display Function
1. Heating Model 2. Cooling Model
• Hot-start, Deice
Self-diagnosis Function
Error Error Display LED
Error contents SVC check point
Code (Indoor body operation LED)
• Indoor room temperature
(once) thermistor open/short • Indoor Thermistor
1
• Indoor pipe temperature assembly check
3sec 3sec 3sec thermistor open/short.
Service Manual 33
Disassembly
Indoor Unit
Earth
Conductor
Service Manual 35
Motor cover
Service Manual 37
104 6 6 6 6 103
R1
SMAW-200
12V L(AC)
R2 Q03G
3
5 5 5 5 5 5
LED2
4
OUTDOOR COMP LOAD
Q02G
4 4 4 4 COMP
R02G 4 4
LED1 4WAY
4WAY
OPERATION 220,1/4W FORCE C03T
3 3 3 3 Q01G 5V 10K,1/6W FAN FAN
• Heat Pump Model(LED TYPE)
R01G GND 3 3
220,1/4W
C14L
5V
R14L R15L
2 2 2 2 5V Q01G~04G 103 1K 20K
C12L (SRC1201S) R02E
20
5V 2 2
220/10V R1,R2=4.7K
1 1 1 1 FORCE R01E BZ01E
1K PKM13EPY-4002 12V 1 1
SW(FORCE)
Electric Control Device
INDOOR
R04L
5V CN-MOTOR FAN MOTOR
C01L 12K
AC PART 103 Q01L
R05L
INT 3 3
KTC3198-Y
2SC5343 56K R01F R02F 2 2
560,1/4W 680,1/2W SH-CAPACITOR
1
12V 5 1 1
2
3
4 R04F
T2
120,1/2W
50/60HZ
Schematic Diagram
Wiring Diagram
Indoor Unit
Models: AS-H0766KA2, AS-H0966KA2, Models: LS-C126RKA2
AS-H126RKA2, LS-H0766KA2, LS-C0966KA2
LS-H0966KA2, LS-H126RKA2
AS-H186TKA2, AS-H246TKA2
Outdoor Unit
Models: LS-H0766KA2, Models: LS-C126RKA2 Models: AS-H246TKA2
LS-H0966KA2, LS-C0966KA2
AS-H126RKA2,
LS-H0766KA2,
LS-H0966KA2,
LS-H126RKA2
AS-H186TKA2
Service Manual 39
Components Location
MAIN P.W.B ASSEMBLY
• TOP VIEW
2004/06/19 DIP
250V/T2A CN-DISP1
CN-U/D
FUSE
J8
RY-COMP CN-TH1
D01M
C02H
CN-OPTION
4 C12L
3 CN-4WAY J2
CN-N1
C01H
CN-N2
CN-CENT
J4
C01P
NF01J
J5
J01
J15
C09D J10
CN-MOTOR
J6
R03D
J9
C01J
R04F ZNR01J C07D
C02J
J7
C01F
RY-4WAY RY-FAN R11L
IC01L C11L
ZNR01F
R01L
OSC01B
D02J
R03L
C08D
D01J
C01A
D03J
R02J D01L
C03T
R01A
C01D
D04J
R02F
C14L C01L
R03F
TR01F IC01A
D05J
L01D
J11
NTC
J12
4 1
R04L
C04D
C05J
J14
C02A R14L
IC01J
R01J
Q01L
IC01F
J13
D01D
R01F
5 8 C02D IC01D
C05D
C03D
R02D C06D
C04J SMPS
C03J
PWB: 6870A90239A PWB ASM: 6871A20573
• BOTTOM VIEW
CN-TH1
CN-DISP1 CN-U/D FUSE
J8
R02H
R04H
R01H
C12L
OR6H R03H R05H
R12L
RY-COMP
R15L
CN-OPTION
D01M
OR5H
OR1H
OR4H
OR2H
OR3H
R21H
J26
C02H
J2 CN-4WAY
CN-N1
C01H
R02P
R01P
Q01M
CN-N2
CN-CENT
J4
C01P
R26H
R23H
R22H
R24H
R25H
NF01J
J5
J01 EEPROM
J15 IC01M
J16 C09D
CN-MOTOR
J6
J21 J20
Q01G
1 R03D
MICOM
J9
J22 C01J
ZNR01J R04F
Q02G 43 C07D C02J
J7
C01F
R11L RY-FAN RY-4WAY
C11L IC01L
Q03G 21 ZNR01F
R05L
R01L
OSC01B
J23 J24
D02J
R01B
R01E
R02E
R03L
32
D01J
C08D
C01A
D03J
D01L R02J
R02A
BZ01E J25
J17 R03A
C03T
R01A
D04J
C14L
R02F
C01D
C06J
D06J
R02L
J19 J18 Q04G
R01D
R03F
D05J
IC01A TR01F
L01D
C01L J16
J11
NTC
J12
R04L
C04D
C05J
J14
R14L C02A
IC01J
IC01F
R01J
Q01L
J13
D01D
R01F
IC01D C02D
L02D
C05D
C03D
C06D R02D
SMPS C04J C03J
2004/06/19 DIP
250V/T2A CN-DISP1
CN-U/D
FUSE
J8
RY-COMP
DISPLAY ASSEMBLY
CN-TH1
C02H
D01M
C12L
CN-N1
CN-OPTION
C01H
CN-N2
J4
NF01J
C01P
J5
CN-CENT
J01
J15
C09D J10
J6
R03D
CN-MOTOR
J9
C01J
R04F ZNR01J C07D
C02J
C01F J7
RY-4WAY RY-FAN R11L
IC01L C11L
ZNR01F
R01L
D02J
R03L
OSC01B
C08D
C01A
D01J
R02J D01L
D03J
C03T
C01D
R01A
D04J
C14L
R02F
C01L
D06J
TR01F IC01A
D05J
R03F
L01D
NTC
J11
4 1
J12
C04D
R04L
C02A R14L
J14
C05J
IC01J
Q01L
R01J
J13
IC01F
IC01D
D01D
5 8 C02D
R01F
C03D
C05D
R02D C06D
C04J SMPS
C03J
PWB: 6870A90239A PWB ASM: 6871A20573
Service Manual 41
Schematic Diagram
Troubleshooting Guide
Troubleshooting Guide
Refrigeration Cycle Diagram
(1) Cooling Only Models
INDOOR UNIT OUTDOOR UNIT
LIQUID SIDE
CAPILLARY TUBE
HEAT HEAT
EXCHANGE EXCHANGE
(EVAPORATOR) (CONDENSER)
GAS SIDE
COMPRESSOR
CHECK VALVE
LIQUID SIDE (Heating Model only)
3-WAY VALVE
CAPILLARY TUBE
HEAT HEAT
EXCHANGE EXCHANGE
(EVAPORATOR) (CONDENSER)
GAS SIDE
REVERSING
3-WAY VALVE
ACCUMU VALVE
LATOR (Heating Model Only)
COMPRESSOR COOLING
HEATING
Valve cap
Hexagonal wrench (4mm) Open position
Flare nut Flare nut Closed position
Open position
Closed position Pin
To To
piping piping Service Service
connection connection port cap port
To outdoor unit To outdoor unit
Service Manual 43
Pumping Down
Gas side
Closed
3-Way
valve
Lo
CLOSE CLOSE
• Procedure
(1) Confirm that both the 2-way and 3-way valves (6) Operate the air conditioner at the cooling
are set to the open position. cycle and stop it when the gauge indicates
– Remove the valve stem caps and confirm that 1kg/cm2g.
the valve stems are in the raised position.
– Be sure to use a hexagonal wrench to operate (7) Immediately set the 3-way valve to the closed
the valve stems. position.
– Do this quickly so that the gauge ends up indi-
(2) Operate the unit for 10 to 15 minutes. cating 3 to 5kg/cm2g.
(3) Stop operation and wait for 3 minutes, then (8) Disconnect the charge set, and mount the 2-
connect the charge set to the service port of way and 3-way valve’s stem nuts and the ser-
the 3-way valve. vice port nut.
– Connect the charge hose with the push pin to – Use torque wrench to tighten the service port
the service port. nut to a torque of 1.8 kg.m.
– Be sure to check for gas leakage.
(4) Air purging of the charge hose.
– Open the low-pressure valve on the charge set
slightly to air purge from the charge hose. Do not use the existing charge set for R-22.
It is necessary to use new charge set for R-410A.
(5) Set the 2-way valve to the closed position. The pressure of R-410A is 1.6 times higher than
that of R-22. Thus, the high pressure side gauge of
charge set should be used higher pressure gauge
of 50kg/cm2 range.
Gas side
3-Way
valve Open
Lo
OPEN CLOSE
• Procedure
(1) Confirm that both the 2-way and 3-way valves (3) Open the valve (Lo side) on the charge set and
are set to the back seat. discharge the refrigerant until the gauge indi-
cates 0 kg/cm2G.
(2) Connect the charge set to the 3-way valve’s – If there is no air in the refrigerant cycle (the
port. pressure when the air conditioner is not running
– Leave the valve on the charge set closed. is higher than 1 kg/cm2G), discharge the refrig-
– Connect the charge hose to the service port. erant until the gauge indicates 0.5 to 1
kg/cm2G. if this is the case, it will not be neces-
sary to apply a evacuatin.
– Discharge the refrigerant gradually; if it is dis-
charged too suddenly, the refrigeration oil will
also be discharged.
Service Manual 45
Evacuation
(All amount of refrigerant leaked)
Gas side
3-Way
valve Open
Vacuum pump
Lo
OPEN CLOSE
• Procedure
(1) Connect the vacuum pump to the center hose (3) Close the valve (Lo side) on the charge set,
of charge set center hose turn off the vacuum pump, and confirm that
the gauge needle does not move (approxima-
(2) Evacuation for approximately one hour. tely 5 minutes after turning off the vacuum
– Confirm that the gauge needle has moved pump).
toward -76 cmHg (vacuum of 4 mmHg or less).
(4) Disconnect the charge hose from the vacuum
pump.
– Vacuum pump oil.
If the vacuum pump oil becomes dirty or
depleted, replenish as needed.
Gas Charging
(After Evacuation)
Gas side
Open
3-Way
Check valve valve
Charging
cylinder
Lo
(1) OPEN CLOSE
• Procedure
\
(3) Open the valve (Lo side on the charge set and (5) Mount the valve stem nuts and the service
charge the system with liquid refrigerant. port nut.
– If the system can not be charged with the spec- – Use torque wrench to tighten the service port
ified amount of refrigerant, it can be charged nut to a torque of 1.8 kg.m.
with a little at a time (approximately 150g each – Be sure to check for gas leakage.
time) while operating the air conditioner in the
cooling cycle; however, one time is not suffi-
cient, wait approximately 1 minute and then
This unit is charged with R-410A.
repeat the procedure (pumping down-pin).
Pay attention not to charge R-22.
Service Manual 47
11 40˚C
Suction Pressure
Outdoor Temp.
(Kg/cm2.g)
10 30˚C
(˚C)
9 20˚C
10˚C
8
0˚C
7
5
5 10 15 20 25 30 35 40
Indoor Temp. (˚C)
Cycle Parts
Trouble analysis
1. Check temperature difference between intake and discharge air and operating current.
NOTICE
Temperature difference between intake and discharge air depends on room air humidity. When the room air
humidity is relativery higher, temperature difference is smaller. When the room air humidity is relatively lower
temperature difference is larger.
2. Check temperature and pressure of refrigeration cycle.
NOTICE
1. The suction pressure is usually 8.5~9.5 kg/cm2G(Cooling) at normal condition.
2. The temperature can be measured by attaching the thermometer to the low pressure tubing and wrap it with
putty.
Service Manual 49
Electronic Parts
Product does not operate at all.
(* Refer to Electronic Control Device drawing and Schematic diagram.)
Turn off Main Power
(After 10 seconds)
NO YES
Check the voltage of power(About AC 220V, 60Hz) Primarily, the operating condition of Micom is OK.
(About AC 220/240V, 50Hz)
While the compressor has been stopped, the compressor does not
operate owing to the delaying function for 3 minutes after stopped.
Cause by the remote control Caused by other parts except the remote control
Check point
Service Manual 51
When the sensor circuit for indoor temperature and connector are in bad
connection or are not engaged, Compressor/Outdoor Fan is stopped.
• The pin NO 63 of Micom, and the part for driving TRIAC(the input and
output signal of IC01M, PIN NO 7, 10)
• Check the pattern
• Check the TRIAC
- TRIAC Open: Indoor Fan Motor never operate
- TRIAC short: Indoor Fan Motor always operates in case of ON or OFF.
Service Manual 53
• Confirm that the Vertical Louver is normally geared with the shaft of
Stepping Motor.
• If the regular torque is detected when rotating the Vertical Louver with
hands Normal
• Confirm the assembly conditions that are catching and interfering parts
in the rotation radial of the Vertical Louver
In heating Mode, the indoor fan operates in case the pipe temperature
is higher than 28°C.
Check point Comp ON Comp OFF Check point Fan ON Fan OFF
• 4 way Relay
Between Micom
DC 5V DC 0V
(NO.51) and GND
Between IC02M
Below DC 1V About DC 12V
(NO.11) and GND
Service Manual 55
Exploded View
Indoor Unit
135316
135313
152302
131410 733010
359011
342800
354210
147581
268711 268712
35211B 346810
W0CZZ 135516
135311 352150
146811
267110
249951
Service Manual 57
135316
Option Parts
152313
135314
152302
131410 733010
359011
267110
342800
159901-1
159901-2 35211B
Part for 145201
Plasma Models
268712 249951
266090 346810
135516
268714-1 268714-2
352150
668713
145200 146811
264110
264110 266090
Part for Plasma
268714 Models
263230 263230
W6640 W0CZZ-1
437211
349480
437212
554031
435301
435511
546810
559010
649950
552111
552116
552202
Part for
H/P Models
567502
Part for
External Models 561410
554160
447900
550140 552203-1
430411
552203-2
Service Manual 59
437211
435301
237204-2
435300
237204-1
435511
554031
546810
552111
559010
552202 649950
550140 552203-1
561410
552116
Outdoor Unit
554032
437212
435512
552111
649950
W0CZZ-1
435511
559010
W0CZZ-2
668713
546810
552202 552116
Part for
H/P Models
553000
567502
435301 447910 Part for
External Models
554160
552203-2
550140
430410
437210 552203-1
Service Manual 61
NOTE) *Please ensure GCSC since these parts may be changed depending upon the buyer's request.
(GCSC WEBSITE http://biz.LGservice.com)
NOTE) *Please ensure GCSC since these parts may be changed depending upon the buyer's request.
(GCSC WEBSITE http://biz.LGservice.com)
Service Manual 63
NOTE) *Please ensure GCSC since these parts may be changed depending upon the buyer's request.
(GCSC WEBSITE http://biz.LGservice.com)
NOTE) *Please ensure GCSC since these parts may be changed depending upon the buyer's request.
(GCSC WEBSITE http://biz.LGservice.com)
Service Manual 65