1 D4 Mfy 0.0.0
1 D4 Mfy 0.0.0
1 D4 Mfy 0.0.0
(a) (b)
Fig. 2 Site Location a) with respect to Sabarmati River, b) within Gota, Ahmedabad (Source: Google Maps)
Build-able Area (For FSI=1.8) 16,081 As per General Development Control Regulations
(GDCR), Gujarat
Additional Build-able Area 8,041 Bought by the Project Partner
(Purchased FSI=0.9)
Total Build-able Area 24,121 FSI = 1.8+0.9
Total Built Area 22,197 As per Table 15
Remaining Area 1,925 Additional Area
a Praja Foundation. Housing, FSI, Crowding and Densities - Handbook Vol I (S. B. Patel (ed.); Vol. 1). Praja Foundation.
Parameter Values
a (Mishra et al. (2021) (Under review)) showed that 35% of the households have 1 air conditioner and 72% of them are installed in the
bedroom area hence the project considers one AC per unit leading to a conditioned area of 4294 m2
b To establish consistency in the use of occupancy, lighting, and equipment schedules were developed using the high-resolution
stochastic model for residential buildings called CREST developed by the Loughborough University, UK.
SDI | Final Design Report | 0:0:0 5
5.0 Goals
The team name “0:0:0” is representative of the three major goals for the project; Net-Zero Energy,
Net-Zero Water and Net-Zero Waste.
Net Zero Energy - The amount of energy generated by on-site renewable energy sources will be
equal to (or greater than) the amount of energy used by the building annually.
Net-Zero Water - As per United States Environmental Protection Agency (USEPA), achieving Net Zero
Water means limiting the consumption of water resources and returning it to the same watershed
so as not to deplete the resources of that region in quantity or quality over the course of the year.
Near-Zero Waste - Project aims to reduce, reuse, and recover waste streams by converting them
into valuable resources along with ensuring proper measures for the safe disposal of hazardous/
toxic waste.
Innovative technologies
Architectural Design
Water Conservation
Renewable energy
Passive strategies
and Materials
Resilience
systems
(Stack and Buoyancy)
MIVAN Construction
Façade systems and
Unit level approach
Natural Ventilation
Earthquake safe
Biomass
systems
balcony
Provide open areas @ 1.5 Usable Terrace Area (atleast Provision of open area
sqm/personb 15% of Roof Space) within 30m of every unit
Challenge 2 - Reducing electrical consumption to be able to meet EPI goals without utilizing
the entire terrace
Hours with need for Possibility to reduce heat Wall and window insulation
refrigerant-based gains in summer with tested to perform during
mechanical cooling < 1000 flexibility in effective WWR heatwaves
hours for every apartment (12% to 30%)
b Need for safe, accessible open areas is crucial, now more than ever (Considering the on-going pandemic). (https://www.downtoearth.
org.in/blog/urbanisation/covid-19-and-green-open-spaces-what-is-going-to-be-our-new-normal--71501)
c A recent survey of affordable homes revealed that the energy usage of naturally ventilated affordable homes was much more closely
related to the total wattage of the home appliances owned by a household than the design related factors such as orientation, window etc.
(https://indianexpress.com/article/india/gujarat-study-to-focus-on-thermal-comfort-and-energy-use-in-affordable-houses-6118460/ )
(Singly Loaded
Walls (Median
Tower Width
Radiation on
Orientation
to Doubly
Corridor)
Corridor)
Loaded
Loaded
Number of
to High)
Towers
(2 to 8)
Fig. 7 Parametric study for massing optimization Top) all possible options, Middle) shortlist based on
maximum irradiation on roof, minimum irradiation on walls, widest floor plate and least number of towers,
Bottom) Top 4 massing options shortlisted
Base Case Optimized Shading Wall & Roof Window 5-Star 5-Star CaaS
(Proposed by Massing (Fixed Shade) Insulation (DGU) Lighting Equipment
Project Partner (4 Towers)
Parameter Capacity
Annual Generation 478,235 kWh
EPI attained with Generation 23.1 kWh/m2-yr
EPI of Project 22.1 kWh/m2-yr
Balance (Positive balance attests to Net-Zero status) 1.0 kWh/m2-yr
Water Required for PV Cleaning 3 liters/panel-week
Total Cost of PV Installation (As detailed in Appendix) ₹ 1,22,90,979
State Subsidy in Gujarat3 ₹ 59,48,800
MNRE Subsidy (20%) 4
₹ 24,58,342
Net Cost of PV Installation ₹ 38,83,983
Annual Maintenance Cost of PV (1% of Total Cost) ₹ 1,22,910
Roof Area Covered 2315 m2
2 Blair, Nate, Nicholas DiOrio, Janine Freeman, Paul Gilman, Steven Janzou, Ty Neises, and Michael Wagner. 2018. System Advisor
Model (SAM) General Description (Version 2017.9.5). Golden, CO: National Renewable Energy Laboratory. NREL/ TP-6A20-70414. https://
www.nrel.gov/docs/fy18osti/70414.pdf.
3 MNRE. (2017, January 24). National Solar Mission - Grid Connected Solar Rooftop Program in India. Ministry of New and Renewable
Energy-Government of India. https://solarrooftop.gov.in/notification/Notification-24012017.pdf
4 MNRE. (2017, August 27). Guidelines on implementation of Phase-II of Grid Connected Rooftop Solar Programme for achieving 40 GW
capacity from Rooftop Solar by the year 2022. Ministry of New and Renewable Energy, Government of India . https://mnre.gov.in/img/
documents/uploads/7ccd3b4b3bb94a51af516e2ee4fdede3.pdf
LEGEND
2. Opaque sliding
folding shutters
5. Bottom hinged
opaque shutters
Fig. 15 Proposed shading system
7.2.3 Open Areas
The high density of the project has a risk of making spaces feel cramped. To avoid crowding on open
spaces on the ground and terrace, open spaces have been spread throughout the built mass to
encourage interaction. (Fig. 16 right) The placement of these open areas has been done strategically
in places on the facade that are visible to most units in the periphery. This helps by ensuring that
these open spaces are safe and also avoids any units that have no privacy due to proximity to other
units. The identification of these spots (Fig. 16 left) was done through the development of cones of
vision in grasshopper and creating a heat map on the facades with areas of maximum visibility.
7.2.4 Livability
Choosing to live in a net-zero residence does not only mean choosing an energy-efficient space
but also, choosing an energy-efficient lifestyle. When occupants make this choice, it is imperative
that the project offers them flexibility in aspects like furniture layouts and partitioning systems. This
allows them to alter their space as the familial structure changes. It also crucial to simplify occupant-
driven strategies and devise incentives to maintain occupant interest in the net-zero incentive.
Fig. 17 Possible alterations to interior layouts with change in family structure to increase tenure time
Fig. 18 Comfort band expanded based on recommendations from IMAC and LECaVIR
0 6 12
Fig. 21 Points of evaluation for all 4 massing schemes were scored as shown in Fig. 19. A higher score implies a
better quality of view. For comparison between the four schemes, median values for all points were calculated and
considered
Scoring of Views
The cones of vision have been intersected with
the three layers of the environment - Ground,
Landscape and Sky. The distance between 90
90
Quality
80
80
136
and scored as shown in the table in Fig. 19. For 130
example, if the cone of vision hits the landscape 70
70 129 129
forView
(a) (b)
Fig. 23 The effectiveness of the window design has been tested through thermal autonomy simulations with a)
shutters closed and b) shutters open
7.4.4 Water Treatment - Efficiency and Costs Table 9 Capital cost components
BioMicrobics FAST Nitrification and denitrification system Water saving
is proposed for on-site black water treatment. Plant will Components
Measures
have a capacity of 30 m3 with an efficiency of 85%. The
treated Water is expected to have a quality of at least Low flow Single flow aerator,
30 BOD and 30 TSS so that it can be used for irrigation fixtures Health Faucet, Shower
and ground recharge. The system will be integrated into head (01) and a hand-
a standard septic tank, leading to space savings. The held spray
system also offers higher levels of nitrogen removal (NSF/ Water efficient 2/4 L flushing system
ANSI 245) with an intermittent operation of the blower flushing
reducing electricity usage up to 45%. The system has a
life span of 25 years with low maintenance. A grey water Behavioral Water submetering
treatment system having 85% efficiency catering to 68 m3 measures system
of grey water is proposed on site (As per Table 8). Recycled Grey and Septic tank,
water of 10 TSS and 10 BOD quality will be used to cater black water Nitrification and
to demands such as PV panel cleaning, washing clothes treatment denitrification system,
and utensils. Component of capital costs of the proposed carbon filters
strategies have been detailed in Table 9.
Fig. 34 Proposed mechanism for on-site waste segregation, handling and disposal
10 Moora, H. and Barde, H. (2018) ‘Environmental impacts of informal plastic waste management’ , in Emmons, K. (ed.) ‘Closing the Loop:
Innovative partnerships with informal workers to recover plastic waste, in an inclusive circular economy approach – Pune, India case
study’, pp 18-19.
Annual
Capital Monthly Water
Cooling EPI Discomfort
Proposal Costs Cost Losses
(kWh/m2-yr) Hours (hrs)
(INR/Appt) (INR/Appt) (LPD) (All
Appts)
Base Case (Savvy's 15.4 285 25,000 296 0
Proposal with Split DX
Systems)
Proposed Case with Desert 2.5 1003 9,400 48 9000
Cooler
Proposed Case with Desert 3.1 452 34,400 60 9000
Cooler and Split DX System
Proposed Case with CaaS 3.6 234 60,000 69 0
(Shared VRF)
7.6.3 Problem 3 - Financing of Shared HVAC Table 12 Annual cash flows for RESCO
Systems
Cost of investment -1,61,71,983
The proposed CaaS model consists of two participants
that is RESCO, the service provider and Residents. Year 1 Cashflow 23,12,217
RESCO will be responsible for capital expenditure
Year 2 Cashflow 22,82,567
as well as annual operational and maintenance
expenditure. This means RESCO will install as well as Year 3 Cashflow 22,53,213
maintain solar PV array and cooling equipment.
Year 4 Cashflow 22,24,152
To avail this service, the residents will have to pay
Year 5 Cashflow 21,95,382
₹6.2 (prevailing market rate) per unit consumed
that is supplied by RESCO. The parity in the per unit Year 6 Cashflow 21,66,900
electricity rates that consumers will pay to electricity
supplied by RESCO and to electricity supplied by GRID Year 7 Cashflow 21,38,702
will make the proposed CaaS model attractive to the Year 8 Cashflow 21,10,787
residents. Based on the forecasts of annual cash flows
detailed in Table 12, the RESCO will achieve an ROI of Year 9 Cashflow 20,83,151
10.3%. Year 10 Cashflow 20,55,791
In base case, residents pay for purchase and Year 11 Cashflow 20,28,705
maintenance of equipment and electricity which
accounts for ₹16,680 annually. Whereas in the Year 12 Cashflow 20,01,889
proposed CaaS model, RESCO pays for purchase and Year 13 Cashflow 19,75,342
maintenance of equipment and residents pay for
electricity which accounts for ₹5,540. The difference Year 14 Cashflow 19,49,060
between the amounts that the residents pay under Year 15 Cashflow 19,23,041
two scenarios is 66%. The high ROI for RESCO along
with substantial savings for residents makes the Return on Investment 10.3%
business model compelling.
Fig. 37 Survey responses that show people's willingness to adopt the Cooling as a Service (CaaS) model
7.6.5 Summary
A preliminary business plan has been developed for a RESCO to invest in cooling as a service for the
affordable housing market. The highest potential for implementation potential is in new projects. A
more detailed market analysis can reveal the population group that would be the best fit for such a
system to speed-up and ensure uptake.
Waste-based Generator
Net-Zero Water Measures
Waste-based Generator Waste-based Generator
CaaS
Net-Zero Water Measures Net-Zero Water Measures
CaaS
PV CaaS
External
PV Development PV
External Development Lift
External Development
Lift Fire fighting Lift
Fire fightingFabrication work Fire fighting
Fabrication work Electric work Fabrication work
Electric work Electric work
Plumbing
Plumbing Plumbing
Flooring
Flooring Flooring
Finishing Finishing Finishing
Masonary work Masonary work Masonary work
RCC RCC RCC
0 200 400
0 600
200 8000
400 1000
200
600 1200
400800 6001000 800 12001000 1200
Costs (Rs/sqft) Costs (Rs/sqft) Costs (Rs/sqft)
Table 15 Technical feasibility of prefab panels evaluated through verification of length (max = 12m), height
(max = 4m) and weight (max = 8 Tons). Financial feasibility verified if panel is manufactured at least 100 times.
Fig. 44 Different delivery models proposed to encourage buyer participation and increase marketability;
Option 2 selected for detailed development based on discussion with the Project Partner
Table 17 Distribution of different types of units in the project based on results of post-design survey
Table 18 Prospective buyers surveyed showed a willingness to pay extra for the balcony
Table 19 Project costs split between Savvy and a RESCO (third-party investor)