Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Knox 50KW

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

ASW50K-LT

> Three-Phase String Inverter 50kW

Smart string monitoring High yield


Integrated DC and AC surge protection Derating only starts above 45℃
Excellent power density
ASW50K-LT

Technical data ASW50K - LT

Input (DC)
Max PV array power 62500 Wp STC
Max input voltage 1000 V
MPP voltage range / rated input voltage 200 - 950 V / 625 V
Min input voltage 200 V
Initial feed-in voltage 300 V
Max operating input current per MPPT input A / input B 30 A / 30 A / 40 A
Max input current per string input A / input B 12 A
Number of independent MPP inputs / strings per MPP input 3 / A: 3; B: 3;C:4
Output (AC)
Rated power 50000 W
Max apparent AC power 55000 VA

220 V / 380 V
AC nominal voltage 230 V / 400 V

AC voltage range 160 - 300 V

50 Hz / 45 Hz to 55 Hz
AC grid frequency / range
60 Hz / 55 Hz to 65 Hz
Rated grid frequency / rated grid voltage 50 Hz / 230 V
Max output current / Rated output current 80 A / 75.8 A
Power factor at rated power /adjustable displacement power factor 1 / 0.8 overexcited to 0.8 underexcited
Feed-in phases / AC connection 3 / 3-N-PE
Harmonic distortion (THD) at rated output <=3%
Efficiency
Max efficiency / European efficiency
Safety Protection
> 98.6 % / > 98 %
Input-side disconnection device ●

Ground fault monitoring / grid monitoring ● / ●

DC reverse polarity protection


● /●
/ AC short circuit current capability

All-pole-sensitive residual-current monitoring unit ●

Smart string monitoring ●

DC surge arrester (Type II ) ●

AC surge protection ●

Protection class (according to IEC 62109-1) / overvoltage


I / AC : III ; DC : II
category (according to IEC 62109-1)

Dimensions (W / H / D) 510 / 790 / 265 mm


Weight 63 kg
Operating temperature range -25 ℃ ... +60 ℃
General data
Noise emission (typical) < 60 dB(A)
Self-consumption (at night) <1W
Topology Transformerless
Cooling concept Forced convection
Degree of protection (according to IEC 60529) IP65
Climatic category (according to IEC 60721-3-4) 4K4H
Max permissible value for relative humidity (non-condensing) 100 %
Max operating altitude 4000 m

Features
DC connection H4
AC connection Terminal block
Mounting type Wall-mounting bracket
Display Graphic
LED Indicators (Status / Fault / Communication) ●

Interface: 2 x RS485 ●

Modbus data protocol ●

Anti-PID ○

Certificates and approvals (more available upon request) IEC 62109-1/2, IEC 60068, IEC 61683, IEC 61727, IEC 62116, NB/T32004-2013
Type designation ASW50K-LT
● standard features ○ optional features - not available Data at nominal conditions. All information is subject to change. Version: August 2019

You might also like