USER’S MANUAL

Of

VEGA™ Digital Ammeter


WDS101FCA00
WDS301FCA00

Manufactured by
LARSEN & TOUBRO LIMITED
KIADB INDUSTRIAL AREA,
HEBBAL, HOOTAGALLI,
MYSORE – 570 018
INDIA

Doc. No. 4D060177 Rev. D

1
1.Introduction:
VEGA™ Digital Ammeter measures the current and displays it on
4-digit 7-segment LED display. It is available with auxiliary supply of 90 -
300V AC. The Digital Ammeter is available in both - single-phase and three-
phase configurations and in size of 96 X 96 mm.

1P Ammeter (WDS101FCA00) 3P Ammeter (WDS301FCA00)

2.Operation:
Power-ON the meter by giving auxiliary supply (Check wiring diagram on
meter), meter displays (1)P-On, (2)Display check-all LEDs glow (3)Meter version no.
Connect the measuring input as per wiring diagram.
1-Phase meter displays phase-current continuously.
3-Phase meter displays R, Y, B phase current values with respective R,Y,B LED glowing
on the front panel for phase indication.
Ammeter is provided with ‘k’ LED for indicating the multiplication factor for the unit of
phase current i.e if ‘k’ LED glows, the reading is in kA.

The default display mode is Auto Scroll Mode in which the parameters scroll
automatically. On pressing any key, the meter goes to manual mode.
In manual mode display shall scroll up & down by every UP & DOWN key press
respectively. If key press doesn’t happen for approximately 20 secs, meter returns to
default mode – Auto Scroll mode.

3 Phase Ammeter will show phase current and average current (System
current) as per display sequence table below.
Parameter Indication on display Indication on LED
R Phase Current Current value RLED
Y Phase Current Current value YLED
B Phase Current Current value BLED
Average Current Current value R- Y-B LEDs

2
3.Parameter Programming:
Ammeter is provided with following programming-parameters
Seq.No. Programming Parameters Display

1
CT primary turns

2 CT secondary turns

Meter programming-menu
3
password

Programming procedure:
Seq.No. Action with keys Display

Press UP KEY and DOWN KEY


1 together to enter in the programming
mode. Display will show “PASS”

Then it will display “0000” with left


2
most digit blinking

Enter the password for user


authentication. Default password is
3
“0000”.Password can be changed once
meter displays ‘PPrg’.
Use UP & DOWN key together to
accept the password.
4
Note : Cursor should be at left most
digit. Only then meter will update value

If Password is correct and accepted.


Then meter displays “ACPt” and then
5
shows first programming parameter
“CtPr”

3
If entered password is incorrect. Then
6 displays “PErr” (Password Error) it will
exit programming mode by restart.

Use UP KEY to scroll the main menu Pages scrolling


7
programming pages /sub pages
Parameter default/Previous
Use DOWN KEY to select the page/sub
8 value with left most digit
pages and change the value of it.
blinking
Press UP KEY to increment the value at 0/1/2/3/4/5/6/7/8/9
9
the cursor position
Press DOWNKEY to shift cursor
10
position to right

Press UP & DOWN keys together to


enter in to update-mode. Display will
11 show “UPdt”
Note : Cursor should be at left most
digit. Only then meter will update value

Press UP KEY to accept the entered


value /DOWN key to skip the entered
value.
If UP KEY , then display will show
12
“ACPt” and then it will show updated
value.
If DOWN KEY , then display will
show previous value.
If entered parameter-value is wrong
i.e., if secondary value is more than
13
primary, display will show “derr” (data
error) and displays previous value.

Press UP & DOWN key to exit


programming mode. Meter displays
14
“ESCP” then “rSEt” and exits the
programming mode by restart.

In programming mode, if key press doesn’t happen for approximately 1 minute, the meter
exits the programming mode and restarts.

4
4. Technical Specifications
Auxiliary supply voltage 90 to 300V (P-N)
Measured rated current -/5A
Measured Current Range From 2% to 120% of rated current
Accuracy ±1% from 5% to120% of rated current
Burden:
Auxiliary Supply < 4VA at 240V
Current Input < 0.2VA per Phase
Insulation properties:
Impulse Voltage Test ±4kV as per IEC 62053-21
A.C Voltage Test 4kV double insulation as per IEC 62053-21
Insulation Resistance 500V DC Voltage as per IS 13779
Electrical requirements Test of Power consumption as per IEC 62053-21
Voltage dips and Interrupts as per IEC 61326-1
Short time over current : 20 times of Imax for half a
second as per IEC 62053-21
EMC as per IEC 61326-1
Emission : Class B as per CISPR 22
Electrical fast transient/burst immunity test
(IEC 61000-4-4) : ±4kV
Electrostatic discharge immunity test (IEC 61000-4-2)
: ±8kV air discharge, ±6kV contact
discharge
EMC (Electromagnetic Radiated, radio-frequency, electromagnetic
compatibility) field immunity test (IEC 61000-4-3)
: 10V/m
Immunity to conducted disturbances, induced by radio-
frequency fields (IEC 61000-4-6) : 3V
Surge Immunity Test (IEC 61000-4-5)
: ±4kV
Rated power frequency magnetic field (IEC 61000-4-8)
: 1A/m
Dry Heat Test (70ºC) as per IEC 60068-2-2
Climatic Conditions (with
Cold Test(-20ºC) as per IEC 60068-2-1
panel)
Damp Heat Cyclic Test(55ºC cycle)as per IEC60068-2-30
Operating Temperature 0 ºC to +55 ºC
Storage Temperature -20 ºC to +70 ºC
Humidity 0 to 95% relative humidity non-condensing.
Shock 40g in 3 planes
Vibration 10 to 55Hz, 0.15mm peak amplitude
Casing Plastic mould Protected to IP51 with panel from front side
Weight 290gms (approx.)

5
WARRANTY

Larsen & Toubro Limited warrants that Digital Ammeter is free from defects in
workmanship and material. Larsen & Toubro Limited’s obligation under this warranty
shall be for a period of 18 months from the date of sale subject to the following terms and
conditions provided the notice of defects and satisfactory proof thereof is given to Larsen
& Toubro Limited by its Customer within the warranty period.

1. Larsen & Toubro Limited shall provide only repairs for the sold item.
2. Defective parts shall be serviced or replaced by Larsen & Toubro Limited.

This warranty does not cover any defect in the product caused by accident, misuse,
mishandling (includes improper electrical, mechanical installation), tamper, neglect,
alteration/modification or substitution of any of the components or parts, or any attempt of
internal adjustment by unauthorized service personnel. For applicability of warranty Larsen
& Toubro Limited shall be the sole judge.

Under no circumstance shall Larsen & Toubro Limited be liable for any consequential or
resulting injury or for loss, damage or expense directly or indirectly from the use of this
product.
The foregoing warranty is in lieu of all other warranties, expressed or implied, and is the
sole and exclusive remedy for any claim arising from any defect in the product.

DISCLAIMER
Sufficient care is taken to provide all information regarding the product but Larsen & Toubro
Limited does not claim any responsibility for the damage caused by using the product directly
or indirectly.

6
5.Overall & Panel cut out dimensions:

96mm x 96mm x 45mm (Depth)

7
6.WIRING DIAGRAM
SINGLE PHASE AMMETER

THREE PHASE AMMETER

 2011 Larsen & Toubro Limited