PS※※-OMS0007-B
PRODUCT NAME
ZSE20(F)
ISE20
Table of Contents
Safety Instructions 2
Model Indication and How to Order 8
Summary of Product parts 10
Definition and terminology 11
Mounting and Installation 14
Installation 14
Piping 16
Wiring 17
Outline of Settings [Measurement mode] 19
Pressure Setting 20
3 Step Setting Mode 21
Simple Setting Mode 23
Function Selection Mode 25
Function selection mode 25
Default setting 25
F 0 Units selection function 27
F 1 Setting of OUT1 28
F 3 Digital filter setting 31
F 4 Auto-preset function 32
F 6 Fine adjustment of display value 34
F10 Sub display setting 35
F11 Display resolution setting 40
F80 Power saving mode 41
F81 Security code 42
F82 Input of line name 44
F90 Setting of all functions 45
F98 Output check 47
F99 Reset to default settings 48
Other Settings 49
Maintenance 53
Forgotten the security code 53
Troubleshooting 54
Specification 61
Specifications 61
Dimensions 63
-1-
No.PS※※-OMS0007-B
Safety Instructions
These safety instructions are intended to prevent hazardous situations and/or equipment damage.
These instructions indicate the level of potential hazard with the labels of "Caution", "Warning" or "Danger".
They are all important notes for safety and must be followed in addition to International Standards
(ISO/IEC)*1), and other safety regulations.
*1) ISO 4414: Pneumatic fluid power -- General rules relating to systems.
ISO 4413: Hydraulic fluid power -- General rules relating to systems.
IEC 60204-1: Safety of machinery -- Electrical equipment of machines .(Part 1: General requirements)
ISO 10218-1992: Manipulating industrial robots -Safety.
etc.
Caution indicates a hazard with a low level of risk which, if not avoided, could
Caution result in minor or moderate injury.
Warning indicates a hazard with a medium level of risk which, if not avoided,
Warning could result in death or serious injury.
Danger indicates a hazard with a high level of risk which, if not avoided, will
Danger result in death or serious injury.
Warning
1. The compatibility of the product is the responsibility of the person who designs the
equipment or decides its specifications.
Since the product specified here is used under various operating conditions, its compatibility with specific
equipment must be decided by the person who designs the equipment or decides its specifications
based on necessary analysis and test results.
The expected performance and safety assurance of the equipment will be the responsibility of the
person who has determined its compatibility with the product.
This person should also continuously review all specifications of the product referring to its latest catalog
information, with a view to giving due consideration to any possibility of equipment failure when
configuring the equipment.
2. Only personnel with appropriate training should operate machinery and equipment.
The product specified here may become unsafe if handled incorrectly.
The assembly, operation and maintenance of machines or equipment including our products must be
performed by an operator who is appropriately trained and experienced.
3. Do not service or attempt to remove product and machinery/equipment until safety is
confirmed.
1. The inspection and maintenance of machinery/equipment should only be performed after measures to
prevent falling or runaway of the driven objects have been confirmed.
2. When the product is to be removed, confirm that the safety measures as mentioned above are
implemented and the power from any appropriate source is cut, and read and understand the specific
product precautions of all relevant products carefully.
3. Before machinery/equipment is restarted, take measures to prevent unexpected operation and malfunction.
4. Contact SMC beforehand and take special consideration of safety measures if the
product is to be used in any of the following conditions.
1. Conditions and environments outside of the given specifications, or use outdoors or in a place
exposed to direct sunlight.
2. Installation on equipment in conjunction with atomic energy, railways, air navigation, space, shipping,
vehicles, military, medical treatment, combustion and recreation, or equipment in contact with food and
beverages, emergency stop circuits, clutch and brake circuits in press applications, safety equipment or
other applications unsuitable for the standard specifications described in the product catalog.
3. An application which could have negative effects on people, property, or animals requiring special
safety analysis.
4. Use in an interlock circuit, which requires the provision of double interlock for possible failure by using
a mechanical protective function, and periodical checks to confirm proper operation.
-2-
No.PS※※-OMS0007-B
Safety Instructions
Caution
1.The product is provided for use in manufacturing industries.
The product herein described is basically provided for peaceful use in manufacturing industries.
If considering using the product in other industries, consult SMC beforehand and exchange
specifications or a contract if necessary.
If anything is unclear, contact your nearest sales branch.
Compliance Requirements
1. The use of SMC products with production equipment for the manufacture of weapons of
mass destruction (WMD) or any other weapon is strictly prohibited.
2. The exports of SMC products or technology from one country to another are govemed by the
relevant security laws and regulation of the countries involved in the transaction. Prior to
the shipment of a SMC product to another country, assure that all local rules goveming that
export are known and followed.
Caution
SMC products are not intended for use as instruments for legal metrology.
Products that SMC manufactures or sells are not measurement instruments that are qualified by pattern
approval tests relating to the measurement laws of each country.
Therefore, SMC products cannot be used for business or certification ordained by the measurement laws of
each country.
-3-
No.PS※※-OMS0007-B
Operator
This operation manual is intended for those who have knowledge of machinery using pneumatic
equipment, and have sufficient knowledge of assembly, operation and maintenance of such
equipment. Only those persons are allowed to perform assembly, operation and maintenance.
Read and understand this operation manual carefully before assembling, operating or providing
maintenance to the product.
■Safety Instructions
Warning
■Do not disassemble, modify (including changing the printed circuit board) or repair.
An injury or failure can result.
■Do not use the product in a place where static electricity is a problem.
Otherwise it can cause failure or malfunction of the system.
-4-
No.PS※※-OMS0007-B
Caution
■Do not touch the terminals and connectors while the power is on.
Otherwise electric shock, malfunction or damage to the product can result.
■After maintenance is complete, perform appropriate functional inspections and leak tests.
Stop operation if the equipment does not function properly or there is a leakage of fluid.
When leakage occurs from parts other than the piping, the product might be faulty.
Disconnect the power supply and stop the fluid supply.
Do not apply fluid under leaking conditions.
Safety cannot be assured in the case of unexpected malfunction.
■NOTE
○Follow the instructions given below when designing, selecting and handling the product.
●The instructions on design and selection (installation, wiring, environment, adjustment, operation,
maintenance, etc.) described below must also be followed.
Product specifications
Use the specified voltage.
Otherwise failure or malfunction can result.
Do not exceed the specified maximum allowable load.
Otherwise it can cause damage or shorten the lifetime of the Pressure switch.
Design the product to prevent reverse current when the circuit is opened or the product is forced to operate for
operational check.
Reverse current can cause malfunction or damage to the product.
Input data to the Pressure switch is not deleted, even if the power supply is cut off.
(Writing time: 10,000 times, Data duration: 20 years after power off)
Use the clean air.
This can cause operating failure.
If compressed air containing condensate is used, install an air dryer or drain catch before the filter and perform
drainage regularly.
If drainage is not performed regularly and condensate enters the secondary side, it can cause operating failure of
pneumatic equipment.
If regular drainage is difficult, the use of a filter with an auto drain is recommended.
Applicable fluid is air, inert gases and incombustible gases.
Do not use a fluid containing chemicals, synthetic oils including organic solvent, salt and corrosive gases.
Otherwise, damage to the product and malfunction can result.
Check the details of the specifications before using.
Use the specified measurement flow rate and operating pressure.
Otherwise it can cause damage to the pressure switch or inability to measure correctly.
Reserve a space for maintenance.
Allow sufficient space for maintenance when designing the system.
-5-
No.PS※※-OMS0007-B
●Product handling
Installation
Tighten to the specified tightening torque.
If the tightening torque is exceeded the mounting screws and brackets may be broken.
If the tightening torque is insufficient, the product can be displaced and loosen the mounting screws.
Do not apply excessive stress to the product when it is mounted with a panel mount.
Otherwise damage to the product and disconnection from the panel mount can result.
Be sure to ground terminal FG when using a commercially available switch-mode power supply.
Do not drop, hit or apply shock to the Pressure switch.
Otherwise damage to the internal parts can result, causing malfunction.
Do not pull the lead wire forcefully, not lift the product by pulling the lead wire. (Tensile force 35 N or less)
Hold the body when handling to avoid the damage of the Pressure switch which lead to cause the failure and malfunction.
For piping of the Pressure switch, hold the piping with a spanner on the metal part of the piping (Piping
attachment).
Holding other part with spanner leads to damage the Pressure switch.
Eliminate any dust left in the piping by air blow before connecting the piping to the product.
Otherwise it can cause damage or malfunction.
Do not insert metal wires or other foreign matter into the pressure measurement port.
It can damage the pressure sensor causing failure or malfunction.
Never mount a Pressure switch in a location that will be used as a foothold.
The product may be damaged if excessive force is applied by stepping or climbing onto it.
If the entering of foreign material to the fluid is possible, install and pipe the filter or the mist separator to
the inlet to avoid failure and malfunction.
Wiring
Do not pull the lead wires.
In particular, never lift a Pressure switch equipped with fitting and piping by holding the lead wires.
Otherwise damage to the internal parts can result, causing malfunction or to be off the connector.
Avoid repeatedly bending or stretching the lead wire, or placing heavy load on them.
Repetitive bending stress or tensile stress can cause the sheath of the wire to peel off, or breakage of the wire.
If the lead wire can move, fix it near the body of the product.
The recommended bend radius of the lead wire is 6 times the outside diameter of the sheath, or 33 times the
outside diameter of the insulation material, whichever is larger.
Replace the damaged lead wire with a new one.
Wire correctly.
Incorrect wiring can break the Pressure switch.
Do not perform wiring while the power is on.
Otherwise damage to the internal parts can result, causing malfunction.
Do not route wires and cables together with power or high voltage cables.
Otherwise the product can malfunction due to interference of noise and surge voltage from power and high voltage
cables to the signal line. Route the wires (piping) of the product separately from power or high voltage cables.
Confirm proper insulation of wiring.
Poor insulation (interference from another circuit, poor insulation between terminals, etc.) can lead to excess
voltage or current being applied to the product, causing damage.
Design the system to prevent reverse current when the product is forced to operate for operational check.
Depending on the circuit used, insulation may not be maintained when operation is forced, allowing reverse current
to flow, which can cause malfunction and damage the product.
Keep wiring as short as possible to prevent interference from electromagnetic noise and surge voltage.
Do not use a cable longer than 10 m.
Wire the DC(-) line(blue) as close as possible to the power supply.
Environment
Do not use the product in area that is exposed to corrosive gases, chemicals, sea water, water or steam.
Otherwise failure or malfunction can result.
-6-
No.PS※※-OMS0007-B
Do not use in a place where the product could be splashed by oil or chemicals.
If the product is to be used in an environment containing oils or chemicals such as coolant or cleaning solvent,
even for a short time, it may be adversely affected (damage, malfunction, or hardening of the lead wires).
Do not use in an area where surges are generated.
If there is equipment which generates a large amount of surge (solenoid type lifter, high frequency induction
furnace, motor, etc.) close to the Pressure switch, this may cause deterioration or breakage of the internal circuit of
the Pressure switch. Avoid sources of surge generation and crossed lines.
Do not use a load which generates surge voltage.
When a surge-generating load such as a relay or solenoid is driven directly, use a Pressure switch with a built-in
surge absorbing element.
The product is CE marked, but not immune to lightning strikes. Take measures against lightning strikes
in the system.
Mount the product in a place that is not exposed to vibration or impact.
Otherwise failure or malfunction can result.
Prevent foreign matter such as remnant of wires from entering the Pressure switch.
Take proper measures for the remnant not to enter the Pressure switch in order to prevent failure or malfunction.
Do not use the product in an environment that is exposed to temperature cycle.
Heat cycles other than ordinary changes in temperature can adversely affect the inside of the product.
Do not expose the product to direct sunlight.
If using in a location directly exposed to sunlight, shade the product from the sunlight.
Otherwise failure or malfunction can result.
Keep within the specified fluid and ambient temperatures range.
The fluid and ambient temperatures should be -5 to 50 °C. Operation under low temperature (5 °C or less) leads to
cause damage or operation failure due to frozen moist in the fluid or air.
Protection against freezing is necessary. Air dryer is recommended for elimination of drain and water.
Avoid sudden temperature change even within specified temperature.
Do not operate close to a heat source, or in a location exposed to radiant heat.
Otherwise malfunction can result.
Maintenance
Turn off the power supply, stop the supplied air, exhaust the residual pressure and verify the release of
air before performing maintenance.
There is a risk of unexpected malfunction.
Perform regular maintenance and inspections.
There is a risk of unexpected malfunction.
Perform drainage regularly.
If condensate enters the secondary side, it can cause operating failure of pneumatic equipment.
Do not use solvents such as benzene, thinner etc. to clean the Pressure switch.
They could damage the surface of the body and erase the markings on the body.
Use a soft cloth to remove stains. For heavy stains, use a cloth soaked with diluted neutral detergent and fully
squeezed, then wipe up the stains again with a dry cloth.
-7-
No.PS※※-OMS0007-B
Model Indication and How to Order
-8-
No.PS※※-OMS0007-B
○Accessories/Part numbers
If an option is required independently, order with the following part numbers.
Items Part No. Remarks
Bracket A ZS-46-A1 Self tapping screws: Nominal size 3 x 8L (2 pcs)
Bracket B ZS-46-A2 Self tapping screws: Nominal size 3 x 8L (2 pcs)
Panel mount adapter ZS-46-B -
Panel mount adapter + Front protective
ZS-46-D -
cover
Lead wire with connector ZS-46-3L 3 cores, 2 m
Front protective cover ZS-27-01 -
R1/8 piping adapter ZS-46-N1 -
NPT1/8 piping adapter ZS-46-N2 -
-9-
No.PS※※-OMS0007-B
Summary of Product parts
○Names of individual parts
-10-
No.PS※※-OMS0007-B
■Definition and terminology
Term Definition
A Performs pressure setting automatically by detecting the increase and
decrease in pressure. For example, if this function is used for a suction test,
Auto-preset
the pressure setting will be completed by performing suction and release of
the workpiece.
B Shows the minimum pressure from when the power was supplied to the
Bottom value display (mode)
current time.
C The problem of the switch output turning ON and OFF repeatedly around the
Chattering
set value at high frequency due to the effect of pulsation.
A function to delay the response time of switch output in order to prevent
Chattering prevention function
chattering.
D The setting time from when the pressure applied to the pressure switch
reaches the set value, to when the ON-OFF output actually begins working.
Delay time Delay time setting can prevent the output from chattering.
The response time indicates when the set value is 90% in relation to the step
input.
Shows how precisely the pressure can be displayed or set by the digital
digit (Min. setting unit) pressure switch. When 1 digit = 1 kPa, the pressure is displayed in increments
of 1 kPa, e.g., 1, 2, 3, …, 99, 100.
Function to add digital filtering to the fluctuation of pressure value. Smooth the
fluctuation of displayed value for sharp start up or fall of the pressure.
When the function is valid, digital filtering is reflected to the ON/OFF of the
Digital filter
switch output.
Output chattering or flicker in the measurement mode display can be reduced
by setting the digital filter.
Shows The maximum deviation between the displayed pressure value and
Display accuracy
the true pressure.
Indicates the colour of the number of digital display. Always green, always
Display colour red, green (switch OFF) red (switch ON), red (switch OFF) green (switch
ON) are available.
Indicate in how many the rated pressure range can be divided to display.
Display resolving power (Example: When the value can be displayed down to 0.001 MPa for the
product for 0 to 1 Mpa, the resolution is 1/1000)
Displayed pressure value can be adjusted within the range of 5%R.D. (5%
Display value fine adjustment of displayed value). It is used if the true pressure value is known, or to
(function) eliminate differences between the displayed values of different instruments
that are measuring the same pressure.
-11-
No.PS※※-OMS0007-B
Term Definition
F Abbreviation of full span and full scale; difference between the minimum and
maximum rated pressure values. means the maximum fluctuation range of
F.S. the pressure switch rated value.
(full span/full scale) For example, when the rated pressure range is -0.100 to 1.000 [MPa]:
F.S. = 1.000 - (-0.100) = 1.100 [MPa]
(Reference: 1%F.S. = 1.100 x 0.01 = 0.011 [MPa])
Fine adjustment mode Refer to "Display value fine adjustment (function)".
Fluid contact part (or wetted Part of the pressure switch which contacts detected fluid. Pressure sensor,
part) seal and fitting are included.
-12-
No.PS※※-OMS0007-B
Term Definition
P Shows the maximum pressure from when the power was supplied to the
Peak value display (mode)
current time.
The diameter of the connecting part of the switch for connecting with the
Port size
object to be measured.
Operating mode in which the digital display turns off and power consumption
Power saving mode
is reduced.
The set pressure value that determines the point at which the pressure switch
Pressure setting
turns ON and OFF.
Pressure limit that if exceeded will result in mechanical and/or electrical
Proof pressure
damage to the product.
R Current read value
For example, when the display value is 1.000[MPa], 5%R.D. is 5% of
R.D.
1.000[MPa], which becomes 0.05[MPa]. When the display value is
0.800[MPa], 5%R.D. is 5% of 0.800[MPa], which becomes 0.04[MPa].
The pressure range within which the product will meet all published
specifications.
Rated pressure range
Values outside of this range can be set as long as they are within the set
pressure range, but the specifications cannot be guaranteed.
-13-
No.PS※※-OMS0007-B
Mounting and Installation
■Installation
○Mounting with bracket
●Mount the bracket to the body with mounting screws (Self tapping screws: Nominal size 3 x 8L (2 pcs)),
then set the body to the specified position.
: Tighten the bracket mounting screws to a torque of 0.5±0.05 Nm.
Self tapping screws are used, and should not be re-used several times.
-14-
No.PS※※-OMS0007-B
○Mounting with panel mount adapter
●Mount part (a) to the front of the body and fix it. Then insert the body with (a) into the panel until (a)
comes into contact with the panel front surface. Next, mount part (b) to the body from the rear and insert
it until (b) comes into contact with the panel for fixing.
•Panel mount adapter (Part No.: ZS-46-B)
Panel mount adapter + Front protective cover (Part No.: ZS-46-D)
: The panel mount adapter can be rotated through 90 degrees for mounting.
-15-
No.PS※※-OMS0007-B
■Piping
○Tightening the connection thread
●For connecting to the body (piping specification: -M5)
After hand tightening, apply a spanner of the correct size to the spanner flats of the piping body, and
tighten with a 1/6 to 1/4 rotation.
As a reference, the tightening torque is 1 to 1.5 Nm.
(When replacing the piping adapter ZS-46-N, tighten it using the same method.)
-16-
No.PS※※-OMS0007-B
■Wiring
○Wiring connections
●Connections should be made with the power supply turned off.
●Use a separate route for the product wiring and any power or high voltage wiring. Otherwise, malfunction
may result due to noise.
●If a commercially available switching power supply is used, be sure to ground the frame ground (FG)
terminal. If the switching power supply is connected for use, switching noise will be superimposed and it
will not be able to meet the product specifications. In that case, insert a noise filter such as a line noise
filter/ferrite between the switching power supplies or change the switching power supply to the series
power supply.
-17-
No.PS※※-OMS0007-B
○Internal circuit and wiring examples
Z/ISE20(F)-□-□-□-□□□
Output specification
-N
NPN open collector 1 output
Max. 28 V, 80 mA
Residual voltage: 1 V or less
-P
PNP open collector 1 output
Max. 80 mA
Residual voltage: 1 V or less
-18-
No.PS※※-OMS0007-B
Outline of Settings [Measurement mode]
Power is supplied.
The product code is displayed for approximately 3 sec. after supplying power.
: Within approximately 0.2 second after power-on, the switch starts.
[Measurement mode]
Detects the pressure after power is supplied, and indicates the display and switch
operating status. This is the basic mode; other modes should be selected for set-point
changes and other function settings.
Measurement mode screen
Sub display
In measurement mode, the display of the sub display can be temporarily changed by pressing the
or buttons.
: One arbitrary display mode can be added to the sub display by setting the [F10] sub display setting.
If the sub display is switched during the arbitrary display setting, the display will be returned to the arbitrary display 30
seconds later. (The default setting does not include arbitrary display.)
Set either of set Select the set Change the Other Settings
value or value, hysteresis function •Zero-clear
hysteresis. and delay time. settings. function
(3 step setting (Simple setting (Function selection •Key-lock
mode) mode) mode) function
(Refer to page 21.) (Refer to page 23.) (Refer to page 25.) (Refer to page 49.)
-19-
No.PS※※-OMS0007-B
Pressure Setting
Default settings
When the pressure exceeds the set value, the switch will be turned on. When the pressure falls below the set
value by the amount of hysteresis or more, the switch will be turned off. The default setting is to turn on the
pressure switch when the pressure reaches the centre of the atmospheric pressure and upper limit of the
rated pressure range. If this condition, shown to the below, is acceptable, then keep these settings.
●ISE20
Item Default setting
[P_1] Set value of OUT1 0.500 MPa
[H_1] Hysteresis of OUT1 0.050 MPa
●ZSE20
Item Default setting
[P_1] Set value of OUT1 -50.5 kPa
[H_1] Hysteresis of OUT1 5.1 kPa
●ZSE20F
Item Default setting
[P_1] Set value of OUT1 50.0 kPa
[H_1] Hysteresis of OUT1 5.0 kPa
Zero-clear of display
The display is reset to zero when the and buttons are pressed simultaneously for 1 second.
For the first operation, perform a zero-clear without pressure at measurement mode.
-20-
No.PS※※-OMS0007-B
3 Step Setting Mode
3 step setting mode
In this mode, the set values can be input in just 3 steps.
Use this mode if the product is to be used straight away, after changing only the set values.
(The current pressure value is displayed on the main display.)
<Operation>
[3 step setting mode (hysteresis mode)]
In the 3 step setting mode, the set value (P_1 or n_1) and hysteresis (H_1) can be changed. Set the items
on the sub display (set value or hysteresis) with or button. When changing the set value, follow
the operation below. The hysteresis setting can be changed in the same way.
(1) Press the button once when the item to be changed is displayed on the sub display.
The set value on the sub display (right) will start flashing.
●Press the button once to increase the value by one digit, press and hold to continuously
increase.
●Press the button once to reduce the value by one digit, press and hold to continuously reduce.
●When the and buttons are pressed and held simultaneously for 1 second or longer, the
set value is displayed as [- - -], and the set value will be the same as the current pressure value
automatically (snap shot function (Refer to page 49.)). Afterwards, it is possible to adjust the value by
pressing the or button.
-21-
No.PS※※-OMS0007-B
The Pressure switch turns on within a set pressure range (from P1L to P1H) during window comparator
mode. Set P1L, the lower limit of the switch operation, and P1H, the upper limit of the switch operation and
WH1 (hysteresis) following the instructions given on page 21.
(When reversed output is selected, the sub display (left) shows [n1L] and [n1H].)
Please refer to the "List of output modes" on page 30 for the relationship between the set values and
operation.
: Setting of the normal/reverse output switching and hysteresis/window comparator mode switching are
performed with the function selection mode [F 1] Setting of OUT1.
-22-
No.PS※※-OMS0007-B
Simple Setting Mode
<Operation>
[Simple setting mode (hysteresis mode)
In the simple setting mode, the set value, hysteresis and delay time can be changed while checking the
current pressure value (main display).
(1) Press and hold the button between 1 and 3 seconds in measurement mode. [SEt] is displayed
on the main display. When the button is released while in the [SEt] display, the current pressure value
is displayed on the main display, [P_1] or [n_1] is displayed on the sub display (left), and the set value
is displayed on the sub display (right) (Flashing).
(2) Change the set value with or button, and press the button to set the value. Then, the
setting moves to hysteresis setting. (The snap shot function can be used. (Refer to page 49.))
(3) Change the set value with or button, and press the button to set the value. Then, the
setting moves to the delay time of the switch output.
(The snap shot function can be used. (Refer to page 49.))
(4) Press the or button, the delay time of the switch output can be selected.
Delay time setting can prevent the output from chattering.
(5) Press the button for 2 seconds or longer to complete the OUT1 setting.
If the button is pressed for less than 2 seconds, the setting will be returned to P_1.
1: Selected items (1) to (4) become valid after pressing the button.
2: After enabling the setting by pressing the button, it is possible to return to measurement mode by pressing the
button for 2 seconds or longer.
3: When the output mode (refer to page 28) is set to error output or output OFF, the simple setting mode cannot be used.
(The setting changes to measurement mode by releasing the button when [SEt] is displayed.)
-23-
No.PS※※-OMS0007-B
In the window comparator mode, set P1L, the lower limit of the switch operation, and P1H, the upper limit of
the switch operation, WH1 (hysteresis) and dt1 (delay time) following the instructions given on page 23.
(When reversed output is selected, the sub display (left) shows [n1L] and [n1H].)
Please refer to the "List of output modes" on page 30 for the relationship between the set values and
operation.
-24-
No.PS※※-OMS0007-B
Function Selection Mode
■Function selection mode
In measurement mode, press the button between 3 and 5 seconds, to display [F 0]. Select to display
the function to be changed [F□□]. Press and hold the button for 2 seconds or longer in function
selection mode to return to measurement mode.
: Some products do not have all the functions. If no function is available or selected due to configuration of other functions, [- - -] is
displayed on the sub display (right).
■Default setting
The default setting is as follows.
If no problem is caused by this setting, keep these settings.
To change a setting, enter function selection mode.
-25-
No.PS※※-OMS0007-B
●Other parameter settings
Item Page Default setting
[F 2] - No configurable items
[F 3] Digital filter setting Page 31 0 ms
[F 4] Auto-preset function Page 32 Not used
[F 5] - No configurable items
[F 6] Fine adjustment of display value Page 34 0%
[F10] Sub display setting Page 35 std (Standard)
[F11] Display resolution setting Page 40 1000-split
[F80] Power saving mode Page 41 OFF
[F81] Security code Page 42 OFF
[F82] Input of line name Page 44 AAAA
[F90] Setting of all functions Page 45 OFF
[F96] - No configurable items
[F97] - No configurable items
[F98] Output check Page 47 N/A (normal output)
[F99] Reset to default settings Page 48 OFF
-26-
No.PS※※-OMS0007-B
■[F 0] Units selection function
This setting is only available for models with the units selection function.
The unit that can be displayed is different depending on the pressure range.
(kPa/MPa can still be selected if the product does not have the units selection function.)
<Operation>
Press the or button in function selection mode to display [F 0].
-27-
No.PS※※-OMS0007-B
■[F 1] Setting of OUT1
Set the output mode of OUT1.
Output turns on when the pressure is greater than the set value. The default setting is to turn on the
pressure switch when the pressure reaches the centre of the atmospheric pressure and upper limit of the
rated pressure range.
Output ON lights in green and output OFF lights in red as default setting.
Please refer to the "List of output modes" on page 30 for the relationship between the set items and operation.
<Operation>
Press the or button in function selection mode to display [F 1].
Pressure setting
Set the pressure based on the [Err] Error output is
setting method on page 21. selected
Press the button
Hysteresis mode: [P_1] to move on to display
Window comparator mode: [P1L][P1H] colour setting.
"P" is changed to "n" as [P_1] [n_1] when
reversed output is selected.
The snap shot function can be used.
(Refer to page 49.)
No.PS※※-OMS0007-B
Hysteresis setting
Set the pressure referring to
the setting method on page 21.
-29-
No.PS※※-OMS0007-B
●List of output modes
If the point at which the switch output changes is outside of the set pressure range due to the selection
of normal or reversed output, the hysteresis value is automatically adjusted.
-30-
No.PS※※-OMS0007-B
■[F 3] Digital filter setting
The Digital filter can be selected to filter the pressure measurement.
Output chattering or flicker in the measurement mode display can be reduced by setting the digital filter.
<Operation>
Press the or button in function selection mode to display [F 3].
-31-
No.PS※※-OMS0007-B
■[F 4] Auto-preset function
This function will automatically calculate and set the optimum pressure based on the actual operating
condition, when hysteresis mode has been selected.
<Operation>
Press the or button in function selection mode to display [F 4].
Auto-preset function
Press the or button to select the auto-preset function.
-32-
No.PS※※-OMS0007-B
●Auto-preset
When auto-preset is selected in function selection mode, the set value can be calculated and memorized
from the measured pressure. Repeating the suction and release of the workpiece to be set for several
times will automatically optimize the set value.
If setting is not necessary press the and buttons simultaneously for 1 second or longer.
-33-
No.PS※※-OMS0007-B
■[F 6] Fine adjustment of display value
This function is to manually perform a fine adjustment of the displayed pressure value.
Pressure can be adjusted in the following range of 5%R.D.
<Operation>
Press the or button in function selection mode to display [F 6].
-34-
No.PS※※-OMS0007-B
■[F10] Sub display setting
Change the display style of the sub display.
<Operation>
Press the or button in function selection mode to display [F10].
-35-
No.PS※※-OMS0007-B
<Sub display>
•Standard
The Standard display function displays the items and values on the sub display.
The displayed item varies depending on the setting of the output mode. Select the displayed items by
pressing the or button in measurement mode.
•2 value display
The 2 value display function displays the items listed below on the right and left side of the sub display.
No.PS※※-OMS0007-B
Table showing the rated pressure range when RAnG is selected.
Pressure range Rated pressure Characters displayed on the sub display
Vacuum pressure -101.3 kPa
Compound pressure 100 kPa
Positive pressure 1 MPa
Table showing the output mode and output form of OUT1 when Md1 is selected.
Output mode Output style Display style
Normal output
Hysteresis mode
Reversed output
Normal output
Reversed output
When using the 2 value display function, 3 step setting is not available for the display.
(When setting 3 step, select each set value to be displayed by pressing the or button.)
When output operation mode is changed after selecting the 2 value display, the selected display items will
not be applicable and [- - -] will be displayed. In this case, select items for the 2 value display setting again.
-37-
No.PS※※-OMS0007-B
•Level bar display
The Level bar display is a function used to visualize the pressure and the ON area for the switch output on
the sub display.
The display style varies depending on the setting of the output mode.
(In hysteresis mode or window comparator mode)
The threshold bar displaying the switch output ON area is displayed according to the table below, using the
output mode.
(During error output or when the output is off)
The threshold bar will not be displayed. Only the pressure value meter is displayed.
Output mode Output style Threshold bar display style
Normal output
Hysteresis mode
Reversed output
Normal output
Reversed output
The Level bar display resolution (pressure for one "O") varies depending on the output mode.
-38-
No.PS※※-OMS0007-B
During an error output or when the output setting is off, the pressure value meter at the atmospheric
pressure is displayed according to the table below.
Rated range Display at atmospheric pressure
Vacuum pressure
Compound pressure
Positive pressure
•Display OFF
The Sub display is not displayed.
-39-
No.PS※※-OMS0007-B
■[F11] Display resolution setting
This function is to change the pressure display resolution.
The flicker of the display can be reduced.
<Operation>
Press the or button in function selection mode to display [F11].
: It may not be possible to change the resolution depending on the unit of pressure selected.
The units that allow display resolution to be selected are [MPa], [kPa(ZSE20(F) only)], [kgf/cm 2], [bar],
[psi] and [inHg]
(The units [kgf/cm2], [bar], [psi] and [inHg] can only be set when using a product with units selection
function.)
Page 27 [F 0] Units selection function
-40-
No.PS※※-OMS0007-B
■[F80] Power saving mode
Power saving mode can be selected.
When selected and no buttons are pressed for 30 seconds, the pressure switch will shift to power saving
mode.
<Operation>
Press the or button in function selection mode to display [F80].
In power saving mode, when buttons are pressed the display is normal, but if no buttons are
pressed for 30 seconds, it will revert to power saving mode. (Power saving is only enabled in
measurement mode)
-41-
No.PS※※-OMS0007-B
■[F81] Security code
The security code can be turned on or off and the security code can be changed when unlocked.
<Operation>
Press the or button in function selection mode to display [F81].
Security code
Press the or button to select the setting of security code.
[oFF] (not use) is Press the button to set. Move on to security code checking.
selected
Press the
button to return to Security code checking
function selection
Press the or button to input the
mode.
security code on the sub display (right).
(The default setting is [000].)
For instructions on how to enter the security code, refer to "How to input
and change the security code" on page 52.
If the security code entered is incorrect, [FAL] will be displayed, and the
security code must be entered again.
If the wrong security code is entered 3 times, [nG] is displayed and the
device returns to function selection mode.
-42-
No.PS※※-OMS0007-B
Security code changing
Press the or button to input the changed
security code on the main display.
For instructions on how to enter the security code,
refer to "How to input and change the security code"
on page 52.
If the security code function is enabled, it is will be necessary to input a security code to release the
key-lock.
: If a key is not pressed for 30 seconds while entering the security code, function selection mode will return.
-43-
No.PS※※-OMS0007-B
■[F82] Input of line name
Function to display the specified character string on the sub display.
To display in the measurement mode, select 2 value display [dUAL] or character string display [LinE] using
the setting on [F10] Sub display setting.
<Operation>
Press the or button in function selection mode to display [F82].
-44-
No.PS※※-OMS0007-B
●Special function setting
■[F90] Setting of all functions
All functions can be set in turn.
<Operation>
Press the or button in function selection mode to display [F90].
[on](use) is selected
[oFF] (not use) is
selected Setting of functions
Press the
button to set. Return to [oFF](not used), then
press the button to set. Press the
Return to function button for 2
selection mode. Return to function selection second or longer.
mode.
-45-
No.PS※※-OMS0007-B
●Setting of each function
Order Function
1 Display unit selection
2 Output mode setting of OUT1
3 Reversed output setting of OUT1
4 Pressure setting of OUT1
5 Hysteresis setting of OUT1
6 Delay time setting of OUT1
7 Display colour setting
8 Digital filter setting
9 Auto-preset function
10 Fine adjustment of display value
11 Sub display setting
12 Display resolution setting
13 Power saving mode
14 Security code
15 Input of line name
: Measurement mode can return from any setting item by pressing the button for 2 seconds or longer.
: Function set before returning to the measurement mode is maintained.
-46-
No.PS※※-OMS0007-B
■[F98] Output check
Correct operation of the switch output can be confirmed.
The output can be turned ON/OFF manually.
<Operation>
Press the or button in function selection mode to display [F98].
Output check
Press the or button to select output check.
Return to
function
selection mode.
Press the
button to return to
[n](normal output),
then press the Press the button
button to set. for 2 second or longer.
Return to function
selection mode.
: Measurement mode can return from any setting item by pressing the button for 2 seconds or longer.
-47-
No.PS※※-OMS0007-B
■[F99] Reset to default settings
If the product settings are uncertain, the default values can be restored.
<Operation>
Press the or button in function selection mode to display [F99].
-48-
No.PS※※-OMS0007-B
Other Settings
○Snap shot function
The current pressure value can be stored to the switch output ON/OFF set point.
When the items of sub display (left) below are selected in 3 step setting mode, simple setting mode or
function selection mode ([F 1] Setting of OUT1), by pressing the and buttons simultaneously for
1 second or longer, the value of the sub display (right) shows [- - -], and the values corresponding to the
current pressure values are automatically displayed.
Output mode Configurable items Sub display (left) Snap shot function
OUT1 set value ( ) ○
Hysteresis mode
Hysteresis ○
OUT1 set value ( ), ( ) ○
Window comparator mode
Hysteresis x
•Hysteresis
The hysteresis is calculated from the equation below and set.
Normal output: (OUT1 set value) - ( current pressure value)
Reverse output: (current pressure value) - (OUT1 set value)
If the calculation result becomes 0 or less, [Err] is displayed on the sub display (right) and the set value is
not changed.
○Zero-clear function
The displayed value can be adjusted to zero if the pressure being measured is within 7%F.S (3.5%F.S. for
compound pressure) of the zero point set at the time of default settings.
(The zero clear range varies by ±1%F.S. due to variation between individual products.)
In measurement mode, when the and buttons are pressed for 1 second or longer simultaneously,
the main display shows [- - -], and the reset to zero. The display returns to measurement mode
automatically.
-49-
No.PS※※-OMS0007-B
○Key-lock function
The key-lock function is used to prevent errors occurring due to unintentional changes of the set values. If
the button is pressed while the keys are locked, [LoC] is displayed on the sub display (left) for
approximately 1 second.
(Each setting and peak/bottom values are displayed with and buttons.)
(2) Select the key-locking/un-locking with or button, and press the button to set.
-50-
No.PS※※-OMS0007-B
<Operation – With security code input ->
•Locking
(1) Press the button for 5 seconds or longer in measurement mode. When [oPE] is displayed on the
main display, release the button.
The current setting [LoC] or [UnL] will be displayed on the sub display.
(2) Select the key [LoC] with or button, and press the button to set.
•Unlocking
(1) Press the button for 5 seconds or longer in measurement mode. When [oPE] is displayed on the
main display, release the button.
The current setting [LoC] or [UnL] will be displayed on the sub display.
(2) Select the un-locking [UnL] with or button. Setting is recognized by pressing the
button, then security code is required.
(3) For instructions on how to enter the security code, refer to "How to input and change the security
code" on page 52.
(4) If inputted security code is correct, the indication of the main display changes to [UnL], and pressing
the one of , or button releases key-lock and the measurement mode returns.
If the security code entered is incorrect, [FAL] will be displayed, and the security code must be entered
again. If the wrong security code is entered 3 times, [LoC] is displayed and the device returns to
measurement mode.
-51-
No.PS※※-OMS0007-B
●How to input and change the security code
The left most digit starts flashing.
Press the or button to select a value.
Press the button to make the next digit to the right flash.
(If the button is pressed at the last digit, the first digit will start
flashing.)
-52-
No.PS※※-OMS0007-B
Maintenance
How to reset the product after a power cut or forcible de-energizing
The setting of the product will be retained as it was before a power cut or de-energizing. The output condition
is also basically recovered to that before a power cut or de-energizing, but may change depending on the
operating environment. Therefore, check the safety of the whole installation before operating the product. If
the installation is using accurate control, wait until the product has warmed up (approximately 10 to 15
minutes).
<Operation>
Press the button for 5 seconds or longer in measurement mode. When [oPE] is displayed on the
main display, release the button.
The current setting [LoC] or [UnL] will be displayed on the sub display.
Decide on the security code referring to "How to input and change the security code" on page 52.
-53-
No.PS※※-OMS0007-B
Troubleshooting
○Troubleshooting
Applicable pressure switch: ZSE20(F)/ISE20
When any failure occurs with this product, the following chart can be used to identify the cause of the failure.
If a cause applicable to the troubles cannot be identified and normal operation is recovered by replacement
with a new product, this indicates that the product itself was faulty. Problems with the product may be due to
the operating environment (installation etc). Please consult SMC.
The pressure switch The switch output does Refer to Trouble No.1
The operation light is
does not operate not turn OFF. ON.
normally.
Yes
No Refer to Trouble No.2
-54-
No.PS※※-OMS0007-B
Displayed value is not The display is Refer to Trouble No.7
correct unstable.
The Display
measurement unit Refer to Trouble No.12
cannot be changed.
-55-
No.PS※※-OMS0007-B
○Troubleshooting list
Problem Problem possible
Problem Investigation method Countermeasures
No. causes
•The switch
output does not (1) Check the set pressure value.
turn OFF. (2) Check the settings of the (1) Adjust the set pressure
The operation operation mode, hysteresis and value.
Incorrect
light stays ON. output type. (2) Set the operation mode,
pressure setting
1 (In hysteresis mode or window hysteresis and output
•The switch comparator mode, and normal type again.
output does not output/ reversed output)
turn ON.
The operation
light stays OFF. Product failure Replace the product.
-56-
No.PS※※-OMS0007-B
Problem Problem possible
Problem Investigation method Countermeasures
No. causes
(1) Check if the output current is 80
(1)(2) Connect the
mA or more.
appropriate load.
(2) Check if the connected load
(3) Use a relay with a surge
complies with the specification.
Excess current voltage suppressor or
Check if the load is short circuited.
was applied to take measures to prevent
(3) Check if the relay without surge
the output (Er1) surge.
protection is connected.
(4) Separate the wiring from
(4) Check if the wiring is in the same
the high-voltage and/or
route as (or bundled together
power line.
with) a high-voltage or power line.
No.PS※※-OMS0007-B
Problem Problem possible
Problem Investigation method Countermeasures
No. causes
Incorrect power Check if the power supply voltage is Supply power in the range
supply in the range 12 to 24 VDC ±10%. 12 to 24 VDC ±10%.
(1) Check the power supply wiring. (1) Check and correct the
(2) Check if there is bending stress wiring.
9 Display flashes. Incorrect wiring
applied to any part of the lead (2) Correct the wiring (bend
wire. radius and stress).
-58-
No.PS※※-OMS0007-B
Problem Problem possible
Problem Investigation method Countermeasures
No. causes
Key-lock mode is Check if the key-lock function is
Buttons do not Check the key-lock function.
13 activated turned on.
work.
Product failure Replace the product.
The body of the Imperfect Confirm that the product is properly in Mount the body on the panel
pressure switch installation panel mount adapter claws. mount.
14
has become
loose. Product failure Replace the product.
Effect of line
pressure
fluctuation (1) Adjust the set pressure
(1) Check the set pressure values
because value.
(hysteresis)
hysteresis is too (2) Change the response
(2) Check the delay time.
narrow or delay time setting.
time of the switch
The operation is
is too short
16 unstable.
(chattering) (1) Check the power supply wiring. (1) Check and correct the
(2) Check if there is bending stress wiring.
Incorrect
applied to any part of the lead (2) Correct the wiring.
wiring/broken
wire. (Reduce the tensile force
lead wire
(bending radius, tensile force to or increase the bending
the lead wire) radius.)
Product failure Replace the product.
-59-
No.PS※※-OMS0007-B
○Error indication function
This function is to display error location and content when a problem or error has occurred.
Error Error displayed Description Measures
If the error cannot be reset after the above measures are taken, or errors other than above are displayed,
please contact SMC.
-60-
No.PS※※-OMS0007-B
Specification
■Specifications
ZSE20 ZSE20F ISE20
Product No.
(Vacuum pressure) (Compound pressure) (Positive pressure)
Applicable fluid Air, non-corrosive gas and non-flammable gas
Rated pressure range 0.0 to -101.0 kPa -100.0 to 100.0 kPa -0.100 to 1.000 MPa
Pressure
spec.
Set pressure range 10.0 to -105.0 kPa -105.0 to 105.0 kPa -0.105 to 1.050 MPa
Min. setting unit 0.1 kPa 0.001 MPa
Proof pressure 500 kPa 1.5 MPa
Power supply voltage 12 to 24 VDC10%, ripple max. 10% (p-p)
Electric
spec.
(NPN output)
Internal voltage drop
1 V or less (Load current 80 mA)
(Residual voltage)
1.5 ms or less (delay time available for anti-chattering function:
Delay time 1
20,100,500,1000,2000 or 5000 ms)
Hysteresis
Hysteresis mode
Variable from 0 2
Window comparator mode
-61-
No.PS※※-OMS0007-B
ZSE20 ZSE20F ISE20
Product No.
(Vacuum pressure) (Compound pressure) (Positive pressure)
Enclosure IP40
Environment
Withstand voltage 1000 VAC for 1 minute between terminals and housing
Insulation resistance 50 MΩ or more between terminals and housing (with 500 VDC megger)
Operation: -5 to 50 oC, Storage: -10 to 60 oC
Ambient temperature range
(No condensation or freezing)
Operating humidity range Operation, Storage: 35 to 85%RH (No condensation)
Standard CE, RoHS
Length of lead wire with connector 2m
1: Value without digital filter (at 0 ms).
2: If the applied pressure fluctuates around the set value, the hysteresis must be set to a value more than the amount of fluctuation or
chattering will occur.
3: This setting is only available for models with the units selection function. Only MPa or kPa is available for models without this function.
4: The response time indicates when the set value is 90% in relation to the step input.
○Cable specifications
Conductor area 0.15 mm2 (AWG26)
Insulator
○Piping/weight specifications
Product No. M5 01 N01
Port size M5 x 0.8 R1/8 NPT1/8
Pressure-sensing part Silicon
fluid contact
Materials in
Piping port (Common) PBT, CB156, heat resistant PPS, O-ring: HNBR
part
Body 22 g 32 g 34 g
-62-
No.PS※※-OMS0007-B
■Dimensions
M5 type
01/N01 type
-63-
No.PS※※-OMS0007-B
○Bracket mounting dimensions
●Bracket A
●Bracket B
-64-
No.PS※※-OMS0007-B
○Mounting dimensions of panel mount adapter
-65-
No.PS※※-OMS0007-B
○Panel cutout dimensions
Mount individually
<Horizontal> <Vertical>
-66-
No.PS※※-OMS0007-B
Revision history
A: Contents revised in several places.
B: Contents revised in several places.
[September 2016]
Note: Specifications are subject to change without prior notice and any obligation on the part of the manufacturer.
© 2015-2016 SMC Corporation All Rights Reserved
No.PS※※-OMS0007-B