LibanCables PDF
LibanCables PDF
LibanCables PDF
As this catalogue is not intended to cover all of LIBAN CABLES SAL possibilities in
Low Tension cables manufacturing, the hereafter listing of the types of cables is not
restrictive but only indicative of the main and most current types we manufacture.
On the other hand, our specification sheets are inspired mainly from International
Electrotechnical Commision Specification (IEC) only in order to conform with the
sustained trend, noticed both regionally and worlwide, towards these same IEC supposed
to inspire any further standardization approaches.
Whereas, in fact, some Low Tension cables may require special conception, fully within
the capabilities of LIBAN CABLES SAL, ISO 9001 certified, precisely because in
position to conceive / tailor your special needs.
That is why, while consulting this catalogue, it is important to take into account that any
combination or change of the constructional details mentioned in this catalogue remain
feasible, on base of special conception / development, matching any special or different
specifications.
Finally, and within our policy of constant improvement, we reserve the right to alter any
part of the information contained in this publication without incurring any obligation.
In all cases this brochure being only indicative, and unless expressly agreed upon, it
cannot be considered by any mean as contractual document.
INDUSTRIAL and DISTRIBUTION
LOW TENSION CABLES
CONTENTS
Page
NOTICE
1 INTRODUCTION 1
2 QUALITY ASSURANCE 2
4 GENERALITIES : 3
4.1 Conductors 3
4.2 Properties of Insulating Materials 4
4.3 Determination of the cross sectional area 4
4.4 Current carrying capacities 4
4.4.1 Buried cables 4
4.4.2 Cables laid in the air 6
4.5 Voltage Drop 7
4.6 Conductors short circuit current 8
4.7 Minimum bending radius 8
6 TECHNICAL INFORMATION 56
6.1 Formulae 56
6.2 Conversion factors and units 57
1 INTRODUCTION
1
2 QUALITY ASSURANCE
Step by step, from raw material to final product, quality constitutes a major concern to
Liban Cables.
Raw material are continuously and repetitively tested from trial orders till the last batch
received afterwards.
- A built in quality control system carried out by the production itself at any step of
work in process.
- A parallel and contradictory procedure is also carried out on the same stages and
products by independent inspectors reporting to the quality control service.
End users and/or third part inspection authorities are also constantly commissioning the
finished products and assessing the strict conformity to ordered specifications.
N.B.: Liban Cables certification to ISO 9001 is planned for January 1997.
For prompt quotation / supplies please make sure your inquiries and your orders are
securing the following data :
2 - Rated voltage.
6 - Number of conductors.
7 - Other requirements.
8 - Packing.
10 - Required validity.
2
4 GENERALITIES
4.1 CONDUCTORS
The commonly used conductors materials are copper and aluminium meeting the
requirements of IEC 60228.
Copper Aluminium
(mm2) (mm2)
6 10
10 16
16 25
25 35
35 50
50 70
70 95
95 150
120 185
150 240
185 300
3
4.2 PROPERTIES OF INSULATING MATERIALS
4
Where the thermal resistivity is different (not 100˚ C.cm/w) the current rating should
be multiplied by the correction factors shown in the following table.
Where the temperature of the soil is different (not 20˚C) the current rating should be
multiplied by the following correction factors.
Soil
temperature Carrying core temperature (˚C)
(˚C)
65 70 75 80 85 90 95 100 105
0 1.20 1.18 1.17 1.15 1.14 1.13 1.13 1.12 1.11
5 1.15 1.14 1.13 1.12 1.11 1.10 1.10 1.09 1.08
10 1.11 1.10 1.09 1.08 1.07 1.07 1.06 1.06 1.06
15 1.05 1.05 1.04 1.04 1.04 1.04 1.03 1.03 1.03
20 1 1 1 1 1 1 1 1 1
25 0.94 0.95 0.95 0.96 0.96 0.96 0.97 0.97 0.97
30 0.88 0.89 0.90 0.91 0.92 0.93 0.93 0.94 0.94
35 0.82 0.84 0.85 0.87 0.88 0.89 0.89 0.90 0.91
40 0.75 0.77 0.80 0.82 0.83 0.85 0.86 0.87 0.87
45 0.67 0.71 0.74 0.76 0.78 0.80 0.82 0.83 0.84
50 0.58 0.63 0.67 0.71 0.73 0.76 0.77 0.79 0.80
5
When several cables or ducts are laid underground with less than one meter spacing the
current rating values should be multiplied by the following correction factors :
Correction factor of proximity effect for underground cables
Single or multicore cables
Number of Touching One diameter
circuits cables spaced cables a = 0.25m a = 0.5m a = 1.0m
a=D
2 0.76 0.79 0.84 0.88 0.92
3 0.64 0.67 0.74 0.79 0.85
4 0.57 0.61 0.69 0.75 0.82
5 0.52 0.56 0.65 0.71 0.80
6 0.49 0.53 0.60 0.69 0.78
D = overall outer sheath diameter a = Space between cables
6
When several cables are grouped, the current ratings values should be corrected as
follows :
Correction of proximity effect for Cables in air
d a
7
Where
DU = Voltage drop in volt
l = Cable length in km
I = Current rating in Amper
R = Conductor resistance at the maximum operating temperature in Ohm/km
L = Inductance in H/km
W = Pulsation = 2 πF = 314 for F = 50 Hz
cos ϕ = Power factor
8
5 INDUSTRIAL AND DISTRIBUTION 0.6 / 1KV POWER CABLES
1. SCOPE
This specification covers single, two,
three or four core cables, PVC or XLPE
insulated and PVC sheathed, rated at 0.6/1
KV, unarmoured type to International
Electrotechnical Commission Publication
IEC 60502-1 for use in cable ducts and
indoors and for underground burial, where 3 2 1
they are not likely to suffer mechanical
damage.
The cables have excellent thermal
properties, high dielectric strength and
high resistance to ageing, abrasion,
moisture, chemicals, acids and oils.
2. CONSTRUCTION
2.1 Conductor
Plain, annealed electrolytic copper or
aluminium conductors, solid, circular 3 2 1
stranded, or sectoral stranded; conforming
to the applicable requirements of IEC
228.
2.2 Insulation
PVC based thermoplastic or XLPE
thermosetting material, conforming to
the applicable requirements of IEC 60502-1.
2.3 Assembly 3 2 1*
Insulated conductors are laid up, filled
where necessary with non-hygroscopic
material and covered with an additional
layer of extruded thermoplastic
material or non-hygroscopic binding
tape.
Stranded circular copper or
2.4 Sheath
aluminium conductor
PVC based thermoplastic material, 1
conforming to the applicable *stranded sectoral copper or
requirements of IEC 60502-1. aluminium conductor
10
UNARMOURED, PVC INSULATED, PVC SHEATHED
0.6 / 1 KV POWER CABLES
Conforming to IEC 60502-1
DIMENSIONAL CHARACTERISTICS
SINGLE CORE
1 x 1.5 0.8 1.4 1.38 2.98 5.9 13 49 ... ... 1000
1 x 2.5 0.8 1.4 1.78 3.38 6.3 22 62 ... ... 1000
1x4 1.0 1.4 2.25 4.25 7.2 35 86 ... ... 1000
1x6 1.0 1.4 2.95 4.95 7.9 53 113 ... ... 1000
1 x 10 1.0 1.4 3.82 5.82 8.7 89 160 28 99 1000
1 x 16 1.0 1.4 4.83 6.83 9.8 141 225 43 127 1000
1 x 25 1.2 1.4 6.02 8.42 12 223 332 68 177 500
1 x 35 1.2 1.4 7.15 9.55 13 309 434 95 220 500
1 x 50 1.4 1.4 8.30 11.10 14 418 565 128 275 500
1 x 70 1.4 1.4 10.00 12.80 16 604 775 185 356 500
1 x 95 1.6 1.5 11.80 15.00 19 838 1060 256 478 500
1 x 120 1.6 1.5 13.30 16.50 20 1059 1300 324 565 500
1 x 150 1.8 1.6 14.80 18.40 22 1299 1590 398 690 500
1 x 185 2.0 1.7 16.55 20.55 25 1630 1990 499 860 500
1 x 240 2.2 1.8 19.40 23.80 28 2143 2590 655 1100 500
1 x 300 2.4 1.9 21.30 26.10 31 2688 3210 822 1340 500
1 x 400 2.6 2.0 24.10 29.30 34 3439 4070 1051 1680 500
1 x 500 2.8 2.1 27.3 32.90 38 4335 5100 1325 2090 500
1 x 630 2.8 2.2 31.0 36.60 42 5597 6450 1710 2560 500
1 x 800 2.8 2.3 37.1 42.70 48 7203 8250 2188 3240 250
TWO CORE
2 x 1.5 0.8 1.8 1.38 2.98 11 27 131 ... ... 1000
2 x 2.5 0.8 1.8 1.78 3.38 11 44 164 ... ... 1000
2x4 1.0 1.8 2.25 4.25 13 70 233 ... ... 1000
2x6 1.0 1.8 2.95 4.95 15 107 306 ... ... 1000
2 x 10 1.0 1.8 3.82 5.82 16 179 425 55 301 1000
2 x 16 1.0 1.8 4.83 6.83 19 284 590 87 393 1000
2 x 25 1.2 1.8 6.02 8.42 22 450 870 138 560 500
2 x 35 1.2 1.8 7.15 9.55 24 624 1130 191 695 500
11
UNARMOURED, PVC INSULATED, PVC SHEATHED
0.6 / 1 KV POWER CABLES
Conforming to IEC 60502-1
DIMENSIONAL CHARACTERISTICS
THREE CORE
3 x 1.5 0.8 1.8 1.38 2.98 11 40 152 ... ... 1000
3 x 2.5 0.8 1.8 1.78 3.38 12 66 194 ... ... 1000
3x4 1.0 1.8 2.25 4.25 14 105 279 ... ... 1000
3x6 1.0 1.8 2.95 4.95 15 160 373 ... ... 1000
3 x 10 1.0 1.8 3.82 5.82 17 269 530 82 343 1000
3 x 16 1.0 1.8 4.83 6.83 20 426 750 130 454 1000
3 x 25 1.2 1.8 6.02 8.42 23 675 1120 206 650 500
3 x 35 1.2 1.8 shaped shaped 24 945 1310 289 655 500
3 x 50 1.4 1.8 shaped shaped 27 1279 1730 391 840 500
3 x 70 1.4 1.9 shaped shaped 30 1848 2390 565 1110 500
3 x 95 1.6 2.1 shaped shaped 35 2562 3280 783 1500 500
3 x 120 1.6 2.2 shaped shaped 38 3242 4060 990 1810 250
3 x 150 1.8 2.3 shaped shaped 44 3978 5000 1216 2240 250
3 x 185 2.0 2.5 shaped shaped 46 4990 6200 1525 2740 250
3 x 240 2.2 2.7 shaped shaped 52 6557 8050 2004 3500 250
3 x 300 2.4 2.9 shaped shaped 59 8226 10050 2514 4340 250
FOUR CORE
4 x 1.5 0.8 1.8 1.38 2.98 12 53 180 ... ... 1000
4 x 2.5 0.8 1.8 1.78 3.38 13 88 232 ... ... 1000
4x4 1.0 1.8 2.25 4.25 15 140 337 ... ... 1000
4x6 1.0 1.8 2.95 4.95 17 213 456 ... ... 1000
4 x 10 1.0 1.8 3.82 5.82 19 358 655 110 310 1000
4 x 16 1.0 1.8 4.83 6.83 21 568 940 174 545 1000
4 x 25 1.2 1.8 6.02 8.42 25 900 1410 275 785 500
4 x 35 1.2 1.8 shaped shaped 27 1259 1730 385 855 500
4 x 50 1.4 1.9 shaped shaped 30 1705 2320 521 1140 500
4 x 70 1.4 2.1 shaped shaped 34 2464 3220 754 1510 500
4 x 95 1.6 2.2 shaped shaped 39 3417 4400 1044 2030 500
4 x 120 1.6 2.3 shaped shaped 43 4323 5450 1320 2450 250
4 x 150 1.8 2.5 shaped shaped 47 5305 6650 1621 2970 250
4 x 185 2.0 2.7 shaped shaped 53 6654 8350 2033 3730 250
4 x 240 2.2 2.9 shaped shaped 59 8743 10800 2672 4730 250
4 x 300 2.4 3.2 shaped shaped 66 10969 13500 3352 5900 250
12
UNARMOURED, PVC INSULATED, PVC SHEATHED
0.6 / 1 KV POWER CABLES
Conforming to IEC 60502-1
13
UNARMOURED, PVC INSULATED, PVC SHEATHED
0.6 / 1 KV POWER CABLES
Conforming to IEC 60502-1
ELECTRICAL CHARACTERISTICS
14
UNARMOURED, XLPE INSULATED, PVC SHEATHED
0.6 / 1 KV POWER CABLES
Conforming to IEC 60502-1
DIMENSIONAL CHARACTERISTICS
SINGLE CORE
1 x 1.5 0.7 1.4 1.38 2.78 5.7 13 45 ... ... 1000
1 x 2.5 0.7 1.4 1.78 3.18 6.1 22 57 ... ... 1000
1x4 0.7 1.4 2.25 3.65 6.6 35 74 ... ... 1000
1x6 0.7 1.4 2.95 4.35 7.3 53 99 ... ... 1000
1 x 10 0.7 1.4 3.82 5.22 8.1 89 144 28 83 1000
1 x 16 0.7 1.4 4.83 6.23 9.2 141 206 43 108 1000
1 x 25 0.9 1.4 6.02 7.82 11 223 307 68 152 500
1 x 35 0.9 1.4 7.15 8.95 12 309 406 95 192 500
1 x 50 1.0 1.4 8.30 10.3 14 418 525 128 235 500
1 x 70 1.1 1.4 10.00 12.20 16 604 735 185 316 500
1 x 95 1.1 1.5 11.80 14.00 18 838 1000 256 418 500
1 x 120 1.2 1.5 13.30 15.70 19 1059 1240 324 505 500
1 x 150 1.4 1.6 14.80 17.60 21 1299 1520 398 620 500
1 x 185 1.6 1.6 16.55 19.75 24 1630 1890 499 760 500
1 x 240 1.7 1.7 19.40 22.80 27 2143 2460 655 970 500
1 x 300 1.8 1.8 21.30 24.90 29 2688 3060 822 1190 500
1 x 400 1.9 1.9 24.10 28.10 33 3439 3890 1051 1500 500
1 x 500 2.2 2.0 27.00 31.70 36 4335 4870 1325 1860 500
1 x 630 2.4 2.2 31.00 35.80 41 5597 6250 1710 2370 500
1 x 800 2.6 2.3 37.10 42.30 48 7203 8050 2188 3040 250
TWO CORE
2 x 1.5 0.7 1.8 1.38 2.78 10 27 120 ... ... 1000
2 x 2.5 0.7 1.8 1.78 3.18 11 44 151 ... ... 1000
2x4 0.7 1.8 2.25 3.65 12 70 195 ... ... 1000
2x6 0.7 1.8 2.95 4.35 13 107 262 ... ... 1000
2 x 10 0.7 1.8 3.82 5.22 15 179 375 55 251 1000
2 x 16 0.7 1.8 4.83 6.23 17 284 530 87 333 1000
2 x 25 0.9 1.8 6.02 7.82 21 450 795 138 483 500
2 x 35 0.9 1.8 7.15 8.95 23 624 1040 191 605 500
15
UNARMOURED, XLPE INSULATED, PVC SHEATHED
0.6 / 1 KV POWER CABLES
Conforming to IEC 60502-1
DIMENSIONAL CHARACTERISTICS
THREE CORE
3 x 1.5 0.7 1.8 1.38 2.78 11 40 137 ... ... 1000
3 x 2.5 0.7 1.8 1.78 3.18 12 66 178 ... ... 1000
3x4 0.7 1.8 2.25 3.65 13 105 235 ... ... 1000
3x6 0.7 1.8 2.95 4.35 14 160 320 ... ... 1000
3 x 10 0.7 1.8 3.82 5.22 16 269 470 82 283 1000
3 x 16 0.7 1.8 4.83 6.23 18 426 675 130 379 1000
3 x 25 0.9 1.8 6.02 7.82 22 675 1020 206 550 500
3 x 35 0.9 1.8 shaped shaped 22 945 1220 289 565 500
3 x 50 1.0 1.8 shaped shaped 25 1278 1610 391 725 500
3 x 70 1.1 1.9 shaped shaped 29 1848 2270 565 985 500
3 x 95 1.1 2.0 shaped shaped 32 2562 3060 783 1280 500
3 x 120 1.2 2.1 shaped shaped 36 3242 3840 990 1590 250
3 x 150 1.4 2.3 shaped shaped 42 3978 4760 1216 2000 250
3 x 185 1.6 2.4 shaped shaped 44 4990 5900 1525 2440 250
3 x 240 1.7 2.6 shaped shaped 50 6557 7650 2004 3100 250
3 x 300 1.8 2.8 shaped shaped 54 8325 9550 2514 3740 250
FOUR CORE
4 x 1.5 0.7 1.8 1.38 2.78 11 53 161 ... ... 1000
4 x 2.5 0.7 1.8 1.78 3.18 12 88 212 ... ... 1000
4x4 0.7 1.8 2.25 3.65 14 140 284 ... ... 1000
4x6 0.7 1.8 2.95 4.35 15 213 391 ... ... 1000
4 x 10 0.7 1.8 3.82 5.22 17 358 580 110 332 1000
4 x 16 0.7 1.8 4.83 6.23 20 568 850 174 456 1000
4 x 25 0.9 1.8 6.02 7.82 24 900 1290 275 665 500
4 x 35 0.9 1.8 shaped shaped 25 1259 1620 385 745 500
4 x 50 1.0 1.9 shaped shaped 28 1705 2150 521 965 500
4 x 70 1.1 2.0 shaped shaped 33 2464 3030 754 1320 500
4 x 95 1.1 2.1 shaped shaped 37 3417 4100 1044 1730 500
4 x 120 1.2 2.3 shaped shaped 41 4323 5150 1320 2150 250
4 x 150 1.4 2.4 shaped shaped 45 5305 6350 1621 2670 250
4 x 185 1.6 2.6 shaped shaped 50 6654 7950 2023 3330 250
4 x 240 1.7 2.8 shaped shaped 56 8743 10300 2672 4230 250
4 x 300 1.8 3.0 shaped shaped 62 10969 12850 3352 5250 250
16
UNARMOURED, XLPE INSULATED, PVC SHEATHED
0.6 / 1 KV POWER CABLES
Conforming to IEC 60502-1
17
UNARMOURED, XLPE INSULATED, PVC SHEATHED
0.6 / 1 KV POWER CABLES
Conforming to IEC 60502-1
ELECTRICAL CHARACTERISTICS
18
5.2 ARMOURED, PVC OR XLPE INSULATED AND PVC SHEATHED CABLES
1. SCOPE
This specification covers PVC or XLPE insulated, circular, twin, three or four
conductors armoured cables, rated at 0.6/1 KV to international Electrotechnical
commission Publication IEC 60502-1 for use indoors, outdoors, in cable ducts, in
water and for direct burial underground, where severe mechanical stresses are
present. These cables have high dielectric strength, an excellent resistance to
deformations under high temperature and pressure, and high resistance to ageing,
abrasion, moisture, chemicals, acids and oils.
2. CONSTRUCTION
2.1 Conductor
Plain, annealed electrolytic copper or Aluminium conductors, solid, circular
stranded, or sectoral stranded, conforming to the applicable requirements of IEC
60228.
2.2 Insulation
PVC based thermoplastic or XLPE thermosetting material, conforming to the
applicable requirements of IEC 60502-1.
2.3 Assembly
Insulated conductors are laid up, filled where necessary with non-hygroscopic
material and covered with an extruded thickness of thermoplastic material.
2.4 Armour
Galvanized round wires, or flat strips, completely covering the assembly of cores
and a counter helix of galvanized steel tape on top; or two layers of steel tape,
complying to the applicable requirements of IEC 60502-1.
2.5 Sheath
PVC based thermoplastic material, conforming to the applicable requirements of
IEC 60502-1.
2.6 TESTS
Conforming to the applicable requirements of IEC 60502-1 either on Raw materials
or on finished products.
20
5.2 ARMOURED, PVC OR XLPE INSULATED AND PVC SHEATHED CABLES
5 4 3 2 1 5 4 3 2 1*
5 6 3 2 1 5 6 3 2 1*
5 7 3 2 1 5 7 3 2 1*
21
GALVANIZED STEEL WIRE ARMOURED
PVC INSULATED, PVC SHEATHED
0.6 / 1 KV POWER CABLES
Conforming to IEC 60502-1
DIMENSIONAL CHARACTERISTICS
TWO CORE
2 x 1.5 0.8 1.0 1.8 1.38 2.98 15 27 345 ... ... 1000
2 x 2.5 0.8 1.0 1.8 1.78 3.38 16 44 394 ... ... 1000
2x4 1.0 1.0 1.8 2.25 4.25 17 70 496 ... ... 1000
2x6 1.0 1.0 1.8 2.95 4.95 19 107 605 ... ... 1000
2 x 10 1.0 1.0 1.8 3.82 5.82 21 179 760 55 635 1000
2 x 16 1.0 1.0 1.8 4.83 6.83 24 284 1270 87 1070 1000
2 x 25 1.2 1.0 1.8 6.02 8.42 28 450 1660 138 1350 500
2 x 35 1.2 1.0 1.8 7.15 9.55 30 624 2000 191 1570 500
THREE CORE
3 x 1.5 0.8 1.0 1.8 1.38 2.98 15 40 374 ... ... 1000
3 x 2.5 0.8 1.0 1.8 1.78 3.38 16 66 434 ... ... 1000
3x4 1.0 1.0 1.8 2.25 4.25 18 105 560 ... ... 1000
3x6 1.0 1.0 1.8 2.95 4.95 20 160 685 ... ... 1000
3 x 10 1.0 1.0 1.8 3.82 5.82 23 269 1170 82 985 1000
3 x 16 1.0 1.0 1.8 4.83 6.83 25 426 1470 130 1170 1000
3 x 25 1.2 1.0 1.8 6.02 8.42 29 675 1960 206 1490 500
3 x 35 1.2 1.0 1.9 shaped shaped 29 945 2140 289 1480 500
3 x 50 1.4 1.0 2.1 shaped shaped 34 1279 2920 391 2030 500
3 x 70 1.4 1.2 2.2 shaped shaped 37 1848 3750 565 2470 500
3 x 95 1.6 1.2 2.3 shaped shaped 42 2562 4800 783 3020 500
3 x 120 1.6 1.2 2.5 shaped shaped 46 3242 6100 990 3850 250
3 x 150 1.8 1.4 2.6 shaped shaped 52 3978 7350 1216 4590 250
3 x 185 2.0 1.4 2.8 shaped shaped 55 4990 8700 1525 5200 250
3 x 240 2.2 1.4 3.0 shaped shaped 61 6557 10800 2004 6250 250
3 x 300 2.4 1.6 3.2 shaped shaped 66 8226 13100 2514 7400 250
22
GALVANIZED STEEL WIRE ARMOURED
PVC INSULATED, PVC SHEATHED
0.6 / 1 KV POWER CABLES
Conforming to IEC 60502-1
FOUR CORE
4 x 1.5 0.8 1.0 1.8 1.38 2.98 16 53 417 ... ... 1000
4 x 2.5 0.8 1.0 1.8 1.78 3.38 17 88 490 ... ... 1000
4x4 1.0 1.0 1.8 2.25 4.25 19 140 640 ... ... 1000
4x6 1.0 1.0 1.8 2.95 4.95 21 213 795 ... ... 1000
4 x 10 1.0 1.0 1.8 3.82 5.82 25 358 1350 110 1100 1000
4 x 16 1.0 1.0 1.8 4.83 6.83 27 568 1720 174 1330 1000
4 x 25 1.2 1.0 1.9 6.02 8.42 31 900 2350 275 1730 500
4 x 35 1.2 1.0 2.0 shaped shaped 32 1259 2640 385 1770 500
4 x 50 1.4 1.2 2.2 shaped shaped 37 1705 3650 521 2470 500
4 x 70 1.4 1.2 2.3 shaped shaped 41 2464 4670 754 2960 500
4 x 95 1.6 1.2 2.5 shaped shaped 47 3417 6450 1044 4080 500
4 x 120 1.6 1.4 2.6 shaped shaped 51 4323 7700 1320 4700 250
4 x 150 1.8 1.4 2.8 shaped shaped 56 5305 9100 1621 5400 250
4 x 185 2.0 1.6 3.0 shaped shaped 61 6654 11100 2023 6500 250
4 x 240 2.2 1.6 3.2 shaped shaped 68 8743 13850 2672 7800 250
4 x 300 2.4 1.6 3.4 shaped shaped 75 10969 17600 3352 10000 250
23
GALVANIZED STEEL WIRE ARMOURED
PVC INSULATED, PVC SHEATHED
0.6 / 1 KV POWER CABLES
Conforming to IEC 60502-1
ELECTRICAL CHARACTERISTICS
24
GALVANIZED STEEL WIRE ARMOURED
XLPE INSULATED, PVC SHEATHED
0.6 / 1 KV POWER CABLES
Conforming to IEC 60502-1
DIMENSIONAL CHARACTERISTICS
TWO CORE
2 x 1.5 0.7 1.0 1.8 1.38 2.78 14 27 327 ... ... 1000
2 x 2.5 0.7 1.0 1.8 1.78 3.18 15 44 372 ... ... 1000
2x4 0.7 1.0 1.8 2.25 3.65 16 70 434 ... ... 1000
2x6 0.7 1.0 1.8 2.95 4.35 18 107 535 ... ... 1000
2 x 10 0.7 1.0 1.8 3.82 5.22 19 179 685 55 560 1000
2 x 16 0.7 1.0 1.8 4.83 6.23 21 284 880 87 685 1000
2 x 25 0.9 1.0 1.8 6.02 7.82 26 450 1550 138 1240 500
2 x 35 0.9 1.0 1.8 7.15 8.95 29 624 1880 191 1450 500
THREE CORE
3 x 1.5 0.7 1.0 1.8 1.38 2.78 15 40 354 ... ... 1000
3 x 2.5 0.7 1.0 1.8 1.78 3.18 16 66 419 ... ... 1000
3x4 0.7 1.0 1.8 2.25 3.65 17 105 490 ... ... 1000
3x6 0.7 1.0 1.8 2.95 4.35 18 160 610 ... ... 1000
3 x 10 0.7 1.0 1.8 3.82 5.22 20 269 795 82 610 1000
3 x 16 0.7 1.0 1.8 4.83 6.23 24 426 1350 130 1050 1000
3 x 25 0.9 1.0 1.8 6.02 7.82 28 675 1820 206 1350 500
3 x 35 0.9 1.0 1.8 shaped shaped 28 945 1990 289 1330 500
3 x 50 1.0 1.0 2.0 shaped shaped 31 1279 2490 391 1600 500
3 x 70 1.1 1.0 2.1 shaped shaped 35 1848 3500 565 2220 500
3 x 95 1.1 1.2 2.2 shaped shaped 39 2562 4480 783 2700 500
3 x 120 1.2 1.2 2.4 shaped shaped 43 3242 5400 990 3150 250
3 x 150 1.4 1.4 2.6 shaped shaped 50 3978 7150 1216 4390 250
3 x 185 1.6 1.4 2.7 shaped shaped 53 4990 8300 1525 4840 250
3 x 240 1.7 1.6 2.9 shaped shaped 58 6557 10350 2004 5800 250
3 x 300 1.8 1.6 3.1 shaped shaped 63 8226 12450 2514 6650 250
25
GALVANIZED STEEL WIRE ARMOURED
XLPE INSULATED, PVC SHEATHED
0.6 / 1 KV POWER CABLES
Conforming to IEC 60502-1
FOUR CORE
4 x 1.5 0.7 1.0 1.8 1.38 2.78 15 53 388 ... ... 1000
4 x 2.5 0.7 1.0 1.8 1.78 3.18 16 88 459 ... ... 1000
4x4 0.7 1.0 1.8 2.25 3.65 18 140 560 ... ... 1000
4x6 0.7 1.0 1.8 2.95 4.35 19 213 705 ... ... 1000
4 x 10 0.7 1.0 1.8 3.82 5.22 22 358 935 110 685 1000
4 x 16 0.7 1.0 1.8 4.83 6.23 25 568 1570 174 1180 1000
4 x 25 0.9 1.0 1.8 6.02 7.82 30 900 2160 275 1540 500
4 x 35 0.9 1.0 1.9 shaped shaped 31 1259 2470 385 1600 500
4 x 50 1.0 1.0 2.1 shaped shaped 35 1705 3340 521 2160 500
4 x 70 1.1 1.2 2.2 shaped shaped 40 2464 4430 754 2720 500
4 x 95 1.1 1.2 2.4 shaped shaped 44 3417 5650 1044 3280 500
4 x 120 1.2 1.2 2.5 shaped shaped 49 4323 7250 1320 4250 250
4 x 150 1.4 1.4 2.7 shaped shaped 53 5305 8700 1621 5000 250
4 x 185 1.6 1.4 2.9 shaped shaped 59 6654 10500 2023 5900 250
4 x 240 1.7 1.6 3.1 shaped shaped 65 8743 13200 2672 7150 250
4 x 300 1.8 1.6 3.3 shaped shaped 71 10969 15950 3352 8350 250
26
GALVANIZED STEEL WIRE ARMOURED
XLPE INSULATED, PVC SHEATHED
0.6 / 1 KV POWER CABLES
Conforming to IEC 60502-1
ELECTRICAL CHARACTERISTICS
27
GALVANIZED STEEL STRIP ARMOURED
PVC INSULATED, PVC SHEATHED
0.6 / 1 KV POWER CABLES
Conforming to IEC 60502-1
DIMENSIONAL CHARACTERISTICS
TWO CORE
2 x 16 1.0 1.0 1.8 4.83 6.83 23 284 1080 87 885 1000
2 x 25 1.2 1.0 1.8 6.02 8.42 26 450 1440 138 1130 500
2 x 35 1.2 1.0 1.8 7.15 9.55 28 624 1760 191 1330 500
THREE CORE
3 x 16 1.0 1.0 1.8 4.83 6.83 24 426 1260 130 965 1000
3 x 25 1.2 1.0 1.8 6.02 8.42 27 675 1730 206 1260 500
3 x 35 1.2 1.0 1.8 shaped shaped 28 945 1890 289 1230 500
3 x 50 1.4 1.0 2.0 shaped shaped 31 1279 2420 391 1530 500
3 x 70 1.4 1.2 2.1 shaped shaped 35 1848 3190 565 1910 500
3 x 95 1.6 1.2 2.2 shaped shaped 39 2562 4160 783 2380 500
3 x 120 1.6 1.2 2.3 shaped shaped 42 3242 5000 990 2750 250
3 x 150 1.8 1.4 2.5 shaped shaped 49 3978 6150 1216 3390 250
3 x 185 2.0 1.4 2.6 shaped shaped 51 4990 7350 1525 3890 250
3 x 240 2.2 1.4 2.8 shaped shaped 57 6557 9300 2004 4750 250
3 x 300 2.4 1.6 3.0 shaped shaped 63 8226 11600 2514 5900 250
FOUR CORE
4 x 16 1.0 1.0 1.8 4.83 6.83 26 568 1500 174 1100 1000
4 x 25 1.2 1.0 1.8 6.02 8.42 30 900 2080 275 1460 500
4 x 35 1.2 1.0 1.9 shaped shaped 31 1259 2370 385 1500 500
4 x 50 1.4 1.2 2.1 shaped shaped 35 1705 3080 521 1900 500
4 x 70 1.4 1.2 2.2 shaped shaped 39 2464 4040 754 2330 500
4 x 95 1.6 1.2 2.4 shaped shaped 44 3417 5350 1044 2980 500
4 x 120 1.6 1.4 2.5 shaped shaped 48 4323 6500 1320 3500 250
4 x 150 1.8 1.4 2.7 shaped shaped 52 5305 7800 1621 4120 250
4 x 185 2.0 1.6 2.8 shaped shaped 58 6654 9700 2023 5100 250
4 x 240 2.2 1.6 3.1 shaped shaped 65 8743 12300 2672 6250 250
4 x 300 2.4 1.6 3.3 shaped shaped 71 10969 15100 3352 7500 250
28
GALVANIZED STEEL STRIP ARMOURED
PVC INSULATED, PVC SHEATHED
0.6 / 1 KV POWER CABLES
Conforming to IEC 60502-1
29
GALVANIZED STEEL STRIP ARMOURED
PVC INSULATED, PVC SHEATHED
0.6 / 1 KV POWER CABLES
Conforming to IEC 60502-1
ELECTRICAL CHARACTERISTICS
30
GALVANIZED STEEL STRIP ARMOURED
XLPE INSULATED, PVC SHEATHED
0.6 / 1 KV POWER CABLES
Conforming to IEC 60502-1
DIMENSIONAL CHARACTERISTICS
TWO CORE
2 x 16 0.7 1.0 1.8 4.83 6.23 22 284 985 87 790 1000
2 x 25 0.9 1.0 1.8 6.02 7.82 25 450 1340 138 1030 500
2 x 35 0.9 1.0 1.8 7.15 8.95 27 624 1650 191 1220 500
THREE CORE
3 x 16 0.7 1.0 1.8 4.83 6.23 23 426 1160 130 865 1000
3 x 25 0.9 1.0 1.8 6.02 7.82 26 675 1600 206 1130 500
3 x 35 0.9 1.0 1.8 shaped shaped 26 945 1770 289 1150 500
3 x 50 1.0 1.0 1.9 shaped shaped 29 1278 2230 391 1340 500
3 x 70 1.1 1.0 2.0 shaped shaped 33 1848 2970 565 1690 500
3 x 95 1.1 1.2 2.2 shaped shaped 37 2562 3900 783 2120 500
3 x 120 1.2 1.2 2.3 shaped shaped 40 3242 4760 990 2510 250
3 x 150 1.4 1.4 2.4 shaped shaped 47 3978 5850 1216 3090 250
3 x 185 1.6 1.4 2.6 shaped shaped 49 4990 7050 1525 3590 250
3 x 240 1.7 1.6 2.8 shaped shaped 55 6557 8950 2004 4400 250
3 x 300 1.8 1.6 2.9 shaped shaped 59 8325 11000 2514 5200 250
FOUR CORE
4 x 16 0.7 1.0 1.8 4.83 6.23 24 568 1380 174 985 1000
4 x 25 0.9 1.0 1.8 6.02 7.82 28 900 1930 275 1310 500
4 x 35 0.9 1.0 1.9 shaped shaped 29 1259 2220 385 1350 500
4 x 50 1.0 1.0 2.0 shaped shaped 32 1705 2820 521 1640 500
4 x 70 1.1 1.2 2.1 shaped shaped 37 2464 3830 754 2120 500
4 x 95 1.1 1.2 2.3 shaped shaped 41 3417 5000 1044 2630 500
4 x 120 1.2 1.2 2.4 shaped shaped 45 4323 6100 1320 3100 250
4 x 150 1.4 1.4 2.6 shaped shaped 50 5305 7400 1621 3720 250
4 x 185 1.6 1.4 2.8 shaped shaped 55 6654 9150 2033 4530 250
4 x 240 1.7 1.6 3.0 shaped shaped 62 8743 11800 2672 5750 250
4 x 300 1.8 1.6 3.2 shaped shaped 68 10969 14400 3352 6800 250
31
GALVANIZED STEEL STRIP ARMOURED
XLPE INSULATED, PVC SHEATHED
0.6 / 1 KV POWER CABLES
Conforming to IEC 60502-1
32
GALVANIZED STEEL STRIP ARMOURED
XLPE INSULATED, PVC SHEATHED
0.6 / 1 KV POWER CABLES
Conforming to IEC 60502-1
ELECTRICAL CHARACTERISTICS
33
DOUBLE STEEL TAPE ARMOURED
PVC INSULATED, PVC SHEATHED
0.6 / 1 KV POWER CABLES
Conforming to IEC 60502-1
DIMENSIONAL CHARACTERISTICS
TWO CORE
2 x 1.5 0.8 1.0 1.8 1.38 2.98 14 27 259 ... ... 1000
2 x 2.5 0.8 1.0 1.8 1.78 3.38 15 44 302 ... ... 1000
2x4 1.0 1.0 1.8 2.25 4.25 16 70 390 ... ... 1000
2x6 1.0 1.0 1.8 2.95 4.95 18 107 485 ... ... 1000
2 x 10 1.0 1.0 1.8 3.82 5.82 20 179 625 55 500 1000
2 x 16 1.0 1.0 1.8 4.83 6.83 22 284 805 87 610 1000
2 x 25 1.2 1.0 1.8 6.02 8.42 25 450 1120 138 810 500
2 x 35 1.2 1.0 1.8 7.15 9.55 27 624 1410 191 975 500
THREE CORE
3 x 1.5 0.8 1.0 1.8 1.38 2.98 14 40 285 ... ... 1000
3 x 2.5 0.8 1.0 1.8 1.78 3.38 15 66 338 ... ... 1000
3x4 1.0 1.0 1.8 2.25 4.25 17 105 448 ... ... 1000
3x6 1.0 1.0 1.8 2.95 4.95 19 160 560 ... ... 1000
3 x 10 1.0 1.0 1.8 3.82 5.82 21 269 730 82 545 1000
3 x 16 1.0 1.0 1.8 4.83 6.83 23 426 975 130 680 1000
3 x 25 1.2 1.0 1.8 6.02 8.42 26 675 1390 206 920 500
3 x 35 1.2 1.0 1.8 shaped shaped 26 945 1530 289 875 500
3 x 50 1.4 1.0 1.9 shaped shaped 30 1279 1990 391 1100 500
3 x 70 1.4 1.2 2.1 shaped shaped 33 1848 2720 565 1440 500
3 x 95 1.6 1.2 2.3 shaped shaped 39 2562 3990 783 2210 500
3 x 120 1.6 1.2 2.4 shaped shaped 42 3242 4800 990 2550 250
3 x 150 1.8 1.4 2.5 shaped shaped 48 3978 5900 1216 3140 250
3 x 185 2.0 1.4 2.7 shaped shaped 51 4990 7150 1525 3690 250
3 x 240 2.2 1.4 2.9 shaped shaped 57 6557 9100 2004 4550 250
3 x 300 2.4 1.6 3.1 shaped shaped 63 8226 11200 2514 5500 250
34
DOUBLE STEEL TAPE ARMOURED
PVC INSULATED, PVC SHEATHED
0.6 / 1 KV POWER CABLES
Conforming to IEC 60502-1
DIMENSIONAL CHARACTERISTICS
FOUR CORE
4 x 1.5 0.8 1.0 1.8 1.38 2.98 15 53 322 ... ... 1000
4 x 2.5 0.8 1.0 1.8 1.78 3.38 16 88 388 ... ... 1000
4x4 1.0 1.0 1.8 2.25 4.25 18 140 520 ... ... 1000
4x6 1.0 1.0 1.8 2.95 4.95 20 213 660 ... ... 1000
4 x 10 1.0 1.0 1.8 3.82 5.82 22 358 875 110 625 1000
4 x 16 1.0 1.0 1.8 4.83 6.83 25 568 1180 174 785 1000
4 x 25 1.2 1.0 1.8 6.02 8.42 28 900 1710 275 1090 500
4 x 35 1.2 1.0 1.9 shaped shaped 30 1259 1970 385 1100 500
4 x 50 1.4 1.2 2.1 shaped shaped 34 1705 2620 521 1440 500
4 x 70 1.4 1.2 2.2 shaped shaped 39 2464 3860 754 2150 500
4 x 95 1.6 1.2 2.4 shaped shaped 44 3417 5100 1044 2730 500
4 x 120 1.6 1.4 2.5 shaped shaped 48 4323 6250 1320 3250 250
4 x 150 1.8 1.4 2.7 shaped shaped 52 5305 7550 1621 3870 250
4 x 185 2.0 1.6 2.9 shaped shaped 58 6654 9300 2023 4680 250
4 x 240 2.2 1.6 3.1 shaped shaped 64 8743 11850 2672 5800 250
4 x 300 2.4 1.6 3.3 shaped shaped 70 10969 14600 3352 7000 250
35
DOUBLE STEEL TAPE ARMOURED
PVC INSULATED, PVC SHEATHED
0.6 / 1 KV POWER CABLES
Conforming to IEC 60502-1
ELECTRICAL CHARACTERISTICS
36
DOUBLE STEEL TAPE ARMOURED
XLPE INSULATED, PVC SHEATHED
0.6 / 1 KV POWER CABLES
Conforming to IEC 60502-1
DIMENSIONAL CHARACTERISTICS
TWO CORE
2 x 1.5 0.7 1.0 1.8 1.38 2.78 14 27 251 ... ... 1000
2 x 2.5 0.7 1.0 1.8 1.78 3.18 14 44 293 ... ... 1000
2x4 0.7 1.0 1.8 2.25 3.65 15 70 348 ... ... 1000
2x6 0.7 1.0 1.8 2.95 4.35 17 107 434 ... ... 1000
2 x 10 0.7 1.0 1.8 3.82 5.22 19 179 570 55 446 1000
2 x 16 0.7 1.0 1.8 4.83 6.23 21 284 735 87 540 1000
2 x 25 0.9 1.0 1.8 6.02 7.82 24 450 1040 138 730 500
2 x 35 0.9 1.0 1.8 7.15 8.95 26 624 1340 191 905 500
THREE CORE
3 x 1.5 0.7 1.0 1.8 1.38 2.78 14 40 274 ... ... 1000
3 x 2.5 0.7 1.0 1.8 1.78 3.18 15 66 326 ... ... 1000
3x4 0.7 1.0 1.8 2.25 3.65 16 105 395 ... ... 1000
3x6 0.7 1.0 1.8 2.95 4.35 17 160 500 ... ... 1000
3 x 10 0.7 1.0 1.8 3.82 5.22 19 269 675 82 490 1000
3 x 16 0.7 1.0 1.8 4.83 6.23 22 426 895 130 600 1000
3 x 25 0.9 1.0 1.8 6.02 7.82 25 675 1280 206 810 500
3 x 35 0.9 1.0 1.8 shaped shaped 25 945 1430 289 775 500
3 x 50 1.0 1.0 1.9 shaped shaped 28 1278 1850 391 965 500
3 x 70 1.1 1.0 2.0 shaped shaped 31 1848 2540 565 1260 500
3 x 95 1.1 1.2 2.1 shaped shaped 35 2562 3390 783 1610 500
3 x 120 1.2 1.2 2.3 shaped shaped 40 3242 4560 990 2310 250
3 x 150 1.4 1.4 2.4 shaped shaped 46 3978 5700 1216 2940 250
3 x 185 1.6 1.4 2.6 shaped shaped 49 4990 6800 1525 3340 250
3 x 240 1.7 1.6 2.8 shaped shaped 55 6557 8700 2004 4150 250
3 x 300 1.8 1.6 3.0 shaped shaped 59 8325 10650 2514 4840 250
37
DOUBLE STEEL TAPE ARMOURED
XLPE INSULATED, PVC SHEATHED
0.6 / 1 KV POWER CABLES
Conforming to IEC 60502-1
DIMENSIONAL CHARACTERISTICS
FOUR CORE
4 x 1.5 0.7 1.0 1.8 1.38 2.78 15 53 307 ... ... 1000
4 x 2.5 0.7 1.0 1.8 1.78 3.18 16 88 371 ... ... 1000
4x4 0.7 1.0 1.8 2.25 3.65 17 140 457 ... ... 1000
4x6 0.7 1.0 1.8 2.95 4.35 19 213 585 ... ... 1000
4 x 10 0.7 1.0 1.8 3.82 5.22 21 358 790 110 540 1000
4 x 16 0.7 1.0 1.8 4.83 6.23 23 568 1090 174 695 1000
4 x 25 0.9 1.0 1.8 6.02 7.82 27 900 1580 275 955 500
4 x 35 0.9 1.0 1.8 shaped shaped 27 1259 1830 385 955 500
4 x 50 1.0 1.0 1.9 shaped shaped 31 1705 2380 521 1200 500
4 x 70 1.1 1.2 2.1 shaped shaped 36 2464 3330 754 1620 500
4 x 95 1.1 1.2 2.3 shaped shaped 41 3417 4790 1044 2420 500
4 x 120 1.2 1.2 2.4 shaped shaped 45 4323 5900 1320 2900 250
4 x 150 1.4 1.4 2.6 shaped shaped 50 5305 7150 1621 3470 250
4 x 185 1.6 1.4 2.8 shaped shaped 55 6654 8850 2033 4230 250
4 x 240 1.7 1.6 3.0 shaped shaped 61 8743 11300 2672 5250 250
4 x 300 1.8 1.6 3.2 shaped shaped 67 10969 13900 3352 6300 250
38
DOUBLE STEEL TAPE ARMOURED
XLPE INSULATED, PVC SHEATHED
0.6 / 1 KV POWER CABLES
Conforming to IEC 60502-1
ELECTRICAL CHARACTERISTICS
39
5.3 CONCENTRIC CONDUCTOR, PVC INSULATED AND SHEATHED
0.6 / 1 KV POWER CABLES
1. SCOPE
This specification covers circular, single, twin, three or four PVC insulated
conductors with a concentric conductor over the assembly of cores, rated 0.6/1KV,
type NYCY to VDE 0271; for use in aerial, direct burial, conduit, open tray and
undergroud duct installations, These cables offer high resistance to ageing,
abrasion, moisture, chemicals, oils and acids and afford protection of phase
coductors against external ingress.
2. CONSTRUCTION
2.1 Conductor
Plain, annealed electrolytic copper con-
ductors, solid, circular stranded, or sec-
toral stranded conforming to the ap-
plicable requirements of IEC 60228.
2.2 Insulation 4 3 2 1
40
CONCENTRIC CONDUCTOR PVC INSULATED, PVC SHEATHED
0.6 / 1 KV POWER CABLES
Conforming to VDE 271 / 3.69
TYPE : NYCY
DIMENSIONAL CHARACTERISTICS
TWO CORE
1x 2.5 +2.5 0.9 1.8 1.78 3.58 9.3 43 112 1000
1x4+4 1.0 1.8 2.25 4.25 9.0 69 147 1000
1x6+6 1.0 1.8 2.95 4.95 9.9 101 197 1000
1 x 10 +10 1.0 1.8 3.82 5.82 12 175 287 1000
1 x 16 + 16 1.0 1.8 4.83 6.83 13 283 413 1000
1 x 25 + 25 1.2 1.8 6.02 8.42 15 443 580 1000
FOUR CORE
3x 2.5 + 2.5 0.9 0.8 1.8 1.78 3.58 15 87 315 1000
3x4+4 1.0 0.8 1.8 2.25 4.25 17 130 380 1000
3x6+6 1.0 0.8 1.8 2.95 4.95 18 207 505 1000
3 x 10 + 10 1.0 0.8 1.8 3.82 5.82 21 353 710 1000
3 x 16 + 16 1.0 1.2 1.8 4.83 6.83 24 567 1030 1000
3 x 25 + 25 1.2 2.2 2.0 6.02 8.42 29 902 1530 500
* - Solid conductor for sizes up to and including 4 mm2.
- Stranded circular conductor for sizes of 6 mm2 and above.
- Greater sections also available
ELECTRICAL CHARACTERISTICS
Nominal Voltage Drop Current carrying capacity**
cross DC Resistance at 20˚C* Cos ϕ = 0.8 Underground Cable Cables in air
section
Two Core Three core Two Core Three core Two Core Three core
41
5.4 SELF SUPPORTED, AERIAL, PVC OR XLPE INSULATED,
0.6 / 1 KV POWER CABLES
1. SCOPE
This specification covers PVC or XLPE
insulated, multicore, self supporting
cables rated 0.6/1KV; for use outdoors
in overhead and surface mounting 1
applications on walls, in street lighting
and other overhead electrical
applications. These cables have high
2 5
dielectric strength, excellent aging,
thermal, chemical and mechanical
properties which make them highly
resistant to the most strenuous weather 3
conditions.
2. CONSTRUCTION
2.1 Conductor
4
Plain, annealed electrolytic copper or al-
uminium conductors, solid, circular
stranded conforming to the applicable re-
quirements of IEC 60228.
2.2 Insulation
PVC based thermoplastic or XLPE ther-
mosetting material conforming to the ap-
plicable requirements of VDE 0209.
2.3 Assembly
Insulated conductors are laid up, filled
with non-hygroscopic material and cov-
ered with an extruded thermoplastic ma-
terial or a PVC binding tape.
2.4 Suspension strand
Torsion free strand of galvanized steel
wires, laid up together parallel to the as-
sembly of cores under a common PVC Stranded circular copper
sheath. 1 or aluinium conductor
2.5 Sheath 2 PVC or XLPE insulation
PVC based thermoplastic material si-
multaneously covering steel supporter and 3 Bedding
assembly of cores and conforming to the
applicable requirements of VDE 0209.
4 PVC sheath
2.6 TESTS
Conforming to the applicable re- 5 Stranded galvanized steel wires
quirements of relative specifications.
42
SELF SUPPORTED AERIAL
PVC INSULATED, PVC SHEATHED
0.6 / 1 KV POWER CABLES
Conforming to VDE 0271 / 3.69
DIMENSIONAL CHARACTERISTICS
TWO CORE
2 x 1.5 0.8 7/1.2 1.8 1.38 2.98 7.2 11 21 27 252 ... ... 1000
2 x 2.5 0.8 7/1.2 1.8 1.78 3.38 7.2 12 22 44 285 ... ... 1000
2x4 1.0 7/1.2 1.8 2.25 4.25 7.2 14 24 70 352 ... ... 1000
2x6 1.0 7/1.2 1.8 2.95 4.95 7.2 15 25 107 427 ... ... 1000
2 x 10 1.0 7/1.2 1.8 3.82 5.82 7.2 17 27 179 545 55 421 1000
2 x 16 1.0 7/1.2 1.8 4.83 6.83 7.2 19 29 284 710 87 515 1000
2 x 25 1.2 7/1.2 1.8 6.02 8.42 7.2 22 32 450 990 138 680 500
THREE CORE
3 x 1.5 0.8 7/1.2 1.8 1.38 2.98 7.2 12 22 40 273 ... ... 1000
3 x 2.5 0.8 7/1.2 1.8 1.78 3.38 7.2 13 23 66 315 ... ... 1000
3x4 1.0 7/1.2 1.8 2.25 4.25 7.2 14 24 105 400 ... ... 1000
3x6 1.0 7/1.2 1.8 2.95 4.95 7.2 16 26 160 494 ... ... 1000
3 x 10 1.0 7/1.2 1.8 3.82 5.82 7.2 18 28 269 650 82 463 1000
3 x 16 1.0 7/1.2 1.8 4.83 6.83 7.2 20 30 426 870 130 575 1000
3 x 25 1.2 7/1.2 1.8 6.02 8.42 7.2 23 33 675 1240 206 770 500
FOUR CORE
4 x 1.5 0.8 7/1.2 1.8 1.38 2.98 7.2 12 22 53 301 ... ... 1000
4 x 2.5 0.8 7/1.2 1.8 1.78 3.38 7.2 14 24 88 353 ... ... 1000
4x4 1.0 7/1.2 1.8 2.25 4.25 7.2 15 25 140 458 ... ... 1000
4x6 1.0 7/1.2 1.8 2.95 4.95 7.2 17 27 213 575 ... ... 1000
4 x 10 1.0 7/1.2 1.8 3.82 5.82 7.2 19 29 358 775 110 525 1000
4 x 16 1.0 7/1.2 1.8 4.83 6.83 7.2 22 32 568 1060 174 665 1000
4 x 25 1.2 7/1.2 1.8 6.02 8.42 7.2 26 36 900 1530 275 905 500
43
SELF SUPPORTED AERIAL
PVC INSULATED, PVC SHEATHED
0.6 / 1 KV POWER CABLES
Conforming to VDE 0271 / 3.69
ELECTRICAL CHARACTERISTICS
Nominal DC Resistance at 20˚C (1) Voltage Drop (2)
Current carrying capacity (3)
cross Cos ϕ = 0.8
section Copper Alu
Copper Alu Copper Alu
44
SELF SUPPORTED AERIAL
XLPE INSULATED, PVC SHEATHED
0.6 / 1 KV POWER CABLES
Conforming to VDE 0271 / 3.69
DIMENSIONAL CHARACTERISTICS
TWO CORE
2 x 1.5 0.7 7/1.2 1.8 1.38 2.78 7.2 10 20 27 241 ... ... 1000
2 x 2.5 0.7 7/1.2 1.8 1.78 3.18 7.2 11 21 44 272 ... ... 1000
2x4 0.7 7/1.2 1.8 2.25 3.65 7.2 12 22 70 316 ... ... 1000
2x6 0.7 7/1.2 1.8 2.95 4.35 7.2 13 23 107 383 ... ... 1000
2 x 10 0.7 7/1.2 1.8 3.82 5.22 7.2 15 25 179 496 55 372 1000
2 x 16 0.7 7/1.2 1.8 4.83 6.23 7.2 17 27 284 650 87 1456 1000
2 x 25 0.9 7/1.2 1.8 6.02 7.82 7.2 21 31 450 915 138 1605 500
THREE CORE
3 x 1.5 0.7 7/1.2 1.8 1.38 2.78 7.2 11 21 40 258 ... ... 1000
3 x 2.5 0.7 7/1.2 1.8 1.78 3.18 7.2 12 22 66 299 ... ... 1000
3x4 0.7 7/1.2 1.8 2.25 3.65 7.2 13 23 105 356 ... ... 1000
3x6 0.7 7/1.2 1.8 2.95 4.35 7.2 14 24 160 441 ... ... 1000
3 x 10 0.7 7/1.2 1.8 3.82 5.22 7.2 16 26 269 590 82 403 1000
3 x 16 0.7 7/1.2 1.8 4.83 6.23 7.2 18 28 426 795 130 500 1000
3 x 25 0.9 7/1.2 1.8 6.02 7.82 7.2 22 32 675 1140 206 670 500
FOUR CORE
4 x 1.5 0.7 7/1.2 1.8 1.38 2.78 7.2 11 21 53 282 ... ... 1000
4 x 2.5 0.7 7/1.2 1.8 1.78 3.18 7.2 12 22 88 333 ... ... 1000
4x4 0.7 7/1.2 1.8 2.25 3.65 7.2 14 24 140 405 ... ... 1000
4x6 0.7 7/1.2 1.8 2.95 4.35 7.2 15 25 213 510 ... ... 1000
4 x 10 0.7 7/1.2 1.8 3.82 5.22 7.2 17 27 358 700 110 452 1000
4 x 16 0.7 7/1.2 1.8 4.83 6.23 7.2 20 30 568 970 174 575 1000
4 x 25 0.9 7/1.2 1.8 6.02 7.82 7.2 24 34 900 1410 275 785 500
45
SELF SUPPORTED AERIAL
XLPE INSULATED, PVC SHEATHED
0.6 / 1 KV POWER CABLES
Conforming to VDE 0271 / 3.69
ELECTRICAL CHARACTERISTICS
46
5.5 CONTROL, PVC OR XLPE INSULATED AND PVC SHEATHED
MULTICORE CABLES.
1
1. SCOPE
This specification covers multicore
cables for signalisation and control pur-
poses, PVC insulated and sheathed rat-
ed 0.6 / 1 KV; to International Electro-
2
technical Commission IEC 60502-1,
for use in cable ducts and indoors and
for underground burial. High re-
sistance to deformations under high
temperature and pressure, and high re-
sistance to ageing, abrasion, moisture, 3
chemicals, acids and oils.
2. CONSTRUCTION
2.1 Conductor
Plain, annealed electrolytic copper con-
ductors, solid or circular stranded con-
forming to the applicable requirements
of IEC 60228. 1
2.2 Insulation
PVC based thermoplastic or XLPE
thermosetting material conforming to
the applicable requirements of IEC 60502-1.
2
2.3 Assembly
Insulated conductors are laid up, filled
where necessary with non-hygroscopic
material or covered with a layer of non-
hygroscopic tape. 4
The assembly is covered with an extruded 5
layer of PVC in armoured cables.
2.4 Armour ( in armoured cables ) 3
Galvanized steel wires or double steel
tapes, covering the assembly of cores,
complying to the applicable re-
quirements of IEC 60502-1. Solid circular copper
1 conductor
2.5 Sheath
PVC based thermoplastic material con- 2 PVC or XLPE insulation
forming to the applicable requirements
of IEC 60502-1. 3 PVC sheath
2.6 TESTS 4 Bedding
Conforming to the applicable re-
quirements of IEC 60502-1 either on Round galvanized steel
5
raw materials or on finished products. wire armour
47
UNARMOURED, PVC INSULATED, PVC SHEATHED
0.6 / 1 KV CONTROLE CABLES
Conforming to IEC 60502-1
DIMENSIONAL CHARACTERISTICS
mm mm mm mm mm Kg/Km Kg/Km m
48
ARMOURED, PVC INSULATED, PVC SHEATHED
0.6 / 1 KV CONTROLE CABLES
Conforming to IEC 60502-1
DIMENSIONAL CHARACTERISTICS
mm mm mm mm mm mm Kg/Km Kg/Km m
49
UNARMOURED, XLPE INSULATED, PVC SHEATHED
0.6 / 1 KV CONTROLE CABLES
Conforming to IEC 60502-1
DIMENSIONAL CHARACTERISTICS
mm mm mm mm mm Kg/Km Kg/Km m
50
ARMOURED, XLPE INSULATED, PVC SHEATHED
0.6 / 1 KV CONTROLE CABLES
Conforming to IEC 60502-1
DIMENSIONAL CHARACTERISTICS
mm mm mm mm mm mm Kg/Km Kg/Km m
51
5.6 AERIAL BUNDLED CONDUCTORS (TORSADES)
3
Round stranded and compacted
2
aluminium conforming to the applicable 4 2
requirements of IEC 60228. 1 3
MAR
Extruded black XLPE.
KIN
G
Design :
The cable consist of three phase
conductors and one or two optional
street lighting conductors stranded
arround the messenger. Stranded Aluminium alloy
1 conductor (Neutral / Messenger)
Core identification : 2 XLPE Insulation
Either by longitunal ridges or by Stranded Aluminium conductor
3
numbering. (Phase or street lighting conductor)
4 XLPE Insulation
Marking :
5 Marking
Embossed on the phase insulation.
52
AERIAL BUNDLED CONDUCTORS (TORSADES0
3 PHASES + NEUTRAL / MESSENGER + STREET LIGHTING CONDUCTOR
Conforming to NFC 33 - 209
TECHNICAL CHARACTERISTICS
Nominal Diameters DC Resistance at Current carrying
Nominal
Conductors Insulation 20˚C capacity
cross
section street street Overall weight street street
phase lighting phase lighting phase lighting phase lighting
53
5.6.2 - 2 and 4 ALUMINIUM CONDUCTORS + PILOT COPPER CONDUCTOR
CONFORMING TO NFC 33 - 209
1 2 3 4
Phase Conductor 1
MARKING
3 Marking
Pilot Conductor
5 XLPE Insulation
TECHNICAL CHARACTERISTICS
mm2
mm mm mm mm Kg/Km Ω/Km Amp V/A Km daN daN
2x16 4.7 7.0 7.9 14.8 140 1.91 83 3.98 190 290
2x25 6.0 8.7 9.6 18.2 213 1.20 108 2.54 300 450
4x16 4.7 7.0 7.9 17.8 280 1.91 74 3.28 190 290
4x25 6.0 8.7 9.6 21.8 426 1.20 97 2.18 300 450
2x16+2x1.5 4.6 7.0 7.8 16.0 191 1.91 83 3.98 190 290
4x16+2x1.5 4.5 7.0 7.8 17.4 328 1.91 74 3.28 190 290
2x25+2x1.5 5.8 8.6 9.4 19.5 270 1.20 108 3.54 300 450
4x25+2x1.5 5.8 8.6 9.4 21.6 486 1.20 97 2.18 300 450
54
6 TECHNICAL INFORMATION
6.1 Formulae
Ohms law U = RI
U = Rated Voltage in V
Joules law W = RI2 t 1 (volts)
Resistance of a line 1 (between phase in three
R = 2L phase system).
(feed and return) xS
I = Current in A (Amperes).
DC Power P(w) = U I R = Resistance in (ohms).
W = Energy in Ws (Watt
Single phase Power P(w) = U I cos ϕ 1 second).
t = Time in s (second)
Three phase Power P(w) = √3 U I cos ϕ
L = Length of cable in m
DC Current P (w) 1 1 (meter).
I=
U x = Conductivity (56 for
1 1 copper and 34 for
AC Single core current P(VA) P (W)
I= = 1 1 Aluminium).
U U cos ϕ Cross sectional area in
S =
1 1 mm2.
AC Three phase current
I = P(VA) = P (W)
P = Power in W (Watt) or
1 1 VA (Volt Ampere).
U 3 U 3 cos ϕ
Cosϕ = Power factor.
Efficiency P output e = Efficiency.
e= ∆u = Voltage drop sending to
P input receiving end of line in
V(Volts).
Voltage drop
If current known
2LI
∆u = S=2LI
Single phase xS x ∆u
AC/DC systems
If power known
2 L P(w) 2L P(w)
∆u = S=
xSU x ∆u U
If current known
1.73 L I cos ϕ 1.73 L I cos ϕ
∆u = S=
Three phase xS x ∆u
system
If power known
L P(w) L P(w)
∆u = S=
xSU x ∆u U
56
6.2 Conversion factors and units
57
Pressure : The SI unit for pressure is the Pa = 1 N/m2
1 N /m2 = 10-5 Kgf / cm2 = 10-5 bar
1Kgf / cm2 = 105 N / m2 = 1 bar
Pa = Pascal, N/m2 = Newton per square meter
Kgf / cm2 = Kilogramme force per square centimeter
58