Skid Instrumentations

Download as docx, pdf, or txt
Download as docx, pdf, or txt
You are on page 1of 3

S.

NO Tag as per Description: Services/installed Installe Remarks/status


P&ID Tag as per Manual d Qty
01 PI-1801 PI-1602, connection On 2” fuel line 01
Bottom/½” NPT-M, 0- 40PSI
02 TI-1601 TI-1601, OP Temp: 185F, Heater 01
Thermo well 500mm/2”
150RF
03 TI-1503 TI-1602, OP Temp: 108F, Gas inlet 14”/600 01
Thermo well 500mm/2” RTJ
150RF
04 TT-1103 TI-1603, OP Temp: 138F, Gas outlet 14”/600 01
Thermo well 500mm/2” RTJ
150RF
05 TI-140A, TI-1604A, OP Temp: 785F, Burner Flue 01
Thermo well 305mm/2”,
150RF
06 Missing TI-1604B, OP Temp: 785F, Burner Flue 01
Thermo well 305mm/2”,
150RF
07 LG-1001 LG-1601 C.D: 14mm, Heater 01
connection: 2”, 150#RF
08 PSLL-1801 PSLL-1601, connection: Burner inlet (on 2”
Bottom/1/2” NPT-F fuel line
Cal: 12PSI, (Pressure: 20/40
oper/Max)
09 PSHH- PSHH-1602, connection: Burner inlet (on 2”
1801 Bottom/1/2” NPT-F fuel line
Cal: 28PSI, (Pressure: 20/40
oper/Max)
10 PSL-1103, PSL-1603A/B, connection: (Air Fan Forced Air) 02
PSL-1111 Bottom/1/2” NPT-F
Cal: 0.5 PSI, (Pressure: Amb:
01/02 oper/Max)
11 TSHH- TSHH-1604. Thermo well: Heater
1601 500mm, 2” 150RF
Connection: fixed Bottom,
Set Point: 150F, Op Temp:
185F
12 TIC-1602 TIC-1602, operating Temp: Heater
185F, Thermo well conn:2”,
O/P: 3 to 15PSI,
150#RF/500mm,
Press: 20Psi
13 TT-1102 TT-1601/A, TT-1603/1A, TT- INLET Gas 04
(3 Qty) 1603/2A, TT-1603/3A. Transmitters
TT-1501 Specs: Pt-100, 4 to 20mA, Op
Temp: 108F, Range: 0-150F,
Mounting: 2” Bracket
14 TT-1102 TT-1601/B, TT-1603/1B,TT- OUTLET Gas 04
(3 Qty) 1603/2B, TT-1603/3B Transmitters
TT-1103 Specs: Pt-100, 4 to 20mA, Op
Temp: 138F, Range: 0-150F
Mounting: 2” Bracket
15 IN LOGIC Differential Temp Controller: 1
TDIC 1601.
Input signal: 2x4-20mA
O/p: 4-20mA,
Switch oper/set: full scale,
Power supply: 24V
Alarm Switch: 2SPDTx 24dc
2A, Mounting: from Panel
16 TDSL- Diff Temp switch: TDSLL- 03
1102 1603.
IN LOGIC Power supply: 24V, input
signal: 4 – 20mA, O/Signal: 2
switches,
Function: Diff Trip
17 TY-1601, I/P Transducer. 01
Power: 24V
I/P signal: 4 – 20mA
O/P signal: 3-15PSI
18 LSLL-1001 Level Switch: LSLL-1601 Heater
Upper Fluid/lower fluid:
Air/water, Center distance:
14”, switch operating Lower,
switch setting: Full scale.
19 TCV-1622 TCV-1602A-B: Temp: 32-86F Burner inlet 02
(Qty:2) Inlet Press: 20PSI,
Supply/input: 20/3-15 psi,
Fail: close, Body Type: Globe
20 TCV-1801 TCV-1601, Body size: 10”, IN/OUT Gas 01
Body Type: Butterfly, Fail
position: Close, (INLET Pr:
833psi Min 950psi max),
(OUTLET Pr: 826psi Min
950psi max) Pneumatic
conn: 1/4”.
21 PCV-1001 PCV-1601, Function: Gas 2” fuel gas 01
reduction, (Inlet pr: 40/60psi
oper/Max) outlet Pr: 20psi,
22 XY-1621, XY-1621-1622, Type: Gas to Burner 02
Qty:2 universal 3 way, Fluid:
instrument Air, Max
pressure: 55-110psi, Body
size: ¼”, Power supply:
110VDC, Action: Universal
23 XX-1823 XV-1623, Type: 2 way valve To Pilot A-B 01
N.C, Fluid: Natural Gas, Max
Pressure: 20psi, Action:
open, Fail position: close
24 XV-1614 XV-1624, Type: 2 way valve To Flare 01
N.O, Fluid: Natural Gas, Max
Pressure: 20psi, Action:
close, Fail position: open
25 XV-1822 Pneumatic shut off valve: XV- 2” fuel gas line
1621, Function: Gas to
Burner, Max Pressure: 20psi,
Body size: 2”, installation: in
line, Action: Direct, Limit
switch: ZSH/ZSL: 1521/1621,
Fail position: close
26 XV-1822 Pneumatic shut off valve: XV- 2” fuel gas line
1622, Function: Gas to
Burner, Max Pressure: 20psi,
Body size: 2”, installation: in
line, Action: Direct, Limit
switch: ZSH/ZSL: 1522/1622,
Fail position: close

Water Bath Heater skid Instrumentations