A6V10224199 en
A6V10224199 en
A6V10224199 en
The diagrams have been simplified and do not include additional network hardware or
security components. Permissible applications are described in the A6V101039125
Network Security Guidelines document. Contact your Siemens IT security expert for more
information.
System overview
2
Smart Infrastructure A6V10087532_n_en_--
2021-10-22
1 Remote access with SintesoView/ Sinteso Touch
2 FS cloud applications
3 Customer network
4 Management platform
You will find a detailed labeled version of the diagram above along with further information in
the A6V10906627 planning guide, see chapter 'Product documentation'.
FCL2006-A1 Line card (interactive) 1x loop with max. 128 devices or 1 stub
with 32 devices
FCI2007-A1 I/O card (RT) Outputs for alarm, fault, local alarm
3
Smart Infrastructure A6V10087532_n_en_--
2021-10-22
Networking of fire control panels
The diagrams have been simplified and do not include additional network hardware or
security components. Permissible applications are described in the A6V101039125
Network Security Guidelines document. Contact your Siemens IT security expert for more
information.
Up to 32 control panels and terminals can be linked to form one FCnet network. If the FCnet
network is connected to a danger management system via BACnet, up to 16 control panels
and terminals can be networked.
Fig. 2: Sub-net
1 Management platform
4
Smart Infrastructure A6V10087532_n_en_--
2021-10-22
Fig. 3: Backbone
2 FS cloud applications
3 Customer network
4 Management platform
You will find a detailed labeled version of the diagram above along with further information in
the A6V10906627 planning guide, see chapter 'Product documentation'.
5
Smart Infrastructure A6V10087532_n_en_--
2021-10-22
Control panels
From MP8, the fire control panels can be ordered with a periphery board with a 0.5 A or
1.5 A output current per FDnet line.
To convert existing fire control panels, the periphery board with 1.5 A per FDnet line can be
ordered separately.
6
Smart Infrastructure A6V10087532_n_en_--
2021-10-22
FC2030-AA Housing (Comfort)
7
Smart Infrastructure A6V10087532_n_en_--
2021-10-22
Extensions
● Optional operating add-ons with 96 indicator groups and two LEDs each:
1x red/green LED and 1x yellow LED
● Optional operating add-ons with 48 indicator groups and two LEDs each:
1x red/green LED and 1x yellow LED
8
Smart Infrastructure A6V10087532_n_en_--
2021-10-22
FH2004-A1 Housing (Large Extension)
9
Smart Infrastructure A6V10087532_n_en_--
2021-10-22
DL3750+ Matrix printer (external)
Use
For medium-sized applications, e.g., for industrial plants, regional banks, or office
complexes.
As part of a modernization process, for a gradual and seamless transition from older
systems to Sinteso.
Design
Function elements
Operating unit
The following elements are available on the operating unit:
● CPU module and electronics
● Ethernet connection
● Slots for RS232 and RS485 modules and network modules (SAFEDLINK)
● Space for 'Kaba' or 'nordic' key switch
● Space for event printer (depending on version)
● Peripheral data bus connection for optional LED modules
Periphery board
From MP8, the fire control panels can be ordered with a periphery board with a 0.5 A or
1.5 A output current per FDnet line.
To convert existing fire control panels, the periphery board with 1.5 A per FDnet line can be
ordered separately.
Card cage
There is a card cage mounted on the rear housing panel for inserting a maximum of two
module bus cards.
10
Smart Infrastructure A6V10087532_n_en_--
2021-10-22
Housing
An FHA2007-A1 pivoting mounting plate can be fitted for the following elements above the
periphery board on the rear housing panel:
● 1x fire brigade periphery module (for Germany)
● 1x sounder module (as an alternative to mounting on U-rail TS35)
● 1x Connect X200 Gateway
Configuration
The following software allows the system to be customized:
● SintesoWorks
Operation
Each control unit has an integrated operating unit. The control panel can also be operated
via a separate FT2040 or FT2080 (Touch) fire terminal.
You will find details and more information in the product data sheet 009386 or
A6V10378271.
11
Smart Infrastructure A6V10087532_n_en_--
2021-10-22
Setup
Basic equipment
4 Mains terminals on TS35 DIN rail - Space for socket, relay modules, etc.
Extensions
(3) Power supply kit (150 W, B) FP2005-A1 Additional power supply for retrofitting (no
diagram)
12
Smart Infrastructure A6V10087532_n_en_--
2021-10-22
Position Designation Type Comment
12 Loop extension (FDnet) FCI2003-A1 For loop extension of the periphery board
(2 loops) FCI2002-A1 from two to four
loops, number of addresses remains the
same
Loop extension (FDnet/C-NET, P) FCI2025-A1 For loop extension of the periphery board
(2 loops, P) FCI2023-A1 from two to four
loops, number of addresses remains the
same.
Line card (FDnet/C-NET, P) FCL2008-A1 For four extra FDnet lines of 1.5 A each
Line card (MS9i) FCL2003-A1 For two addressed MS9i detector lines
Line card (interactive Ex) FCL2007-A1 For one addressed interactive Ex line
I/O card (RT) FCI2007-A1 For extra alarm and fault outputs
13
Smart Infrastructure A6V10087532_n_en_--
2021-10-22
Position Designation Type Comment
19 Battery (12 V, 17 Ah, VdS) FHA2025-A1 For the emergency power supply
Battery (12 V, 25 Ah, VdS) BAT12-25 For the emergency power supply
20 Fire brigade periphery module FCI2001-D1 For Germany (FBF, FSD, ÜE, FSE, ÖA,
KL)
14
Smart Infrastructure A6V10087532_n_en_--
2021-10-22
Type Overview
Housing (Comfort)
Type FC2030-AA
15
Smart Infrastructure A6V10087532_n_en_--
2021-10-22
Details for ordering
Control panel
Extensions
16
Smart Infrastructure A6V10087532_n_en_--
2021-10-22
Type Designation Weight Order number
compartment)
Network (backbone)
17
Smart Infrastructure A6V10087532_n_en_--
2021-10-22
Cloud Gateway
Batteries
License keys
External printer
18
Smart Infrastructure A6V10087532_n_en_--
2021-10-22
Product documentation
Title Document ID
System documentation
Planning 008843
Mounting/Installation 008851
Data sheets
Guarantee
The application-specific technical data is guaranteed only in combination with the Siemens
products listed in the 'Device combinations' section. If third-party products are used, any
guarantee provided by Siemens will be invalidated.
19
Smart Infrastructure A6V10087532_n_en_--
2021-10-22
Technical data
● Stubs 4 (8)
Integrated inputs/outputs:
20
Smart Infrastructure A6V10087532_n_en_--
2021-10-22
Fire control panel (modular)/(modular, P) FC2030 in housing (Comfort)
Color:
21
Smart Infrastructure A6V10087532_n_en_--
2021-10-22
Fire control panel (modular)/(modular, P) FC2030 in housing (Comfort)
LPCB 126bn/02
FM 048514
22
Smart Infrastructure A6V10087532_n_en_--
2021-10-22
Issued by
© Siemens Switzerland Ltd, 2007
Siemens Switzerland Ltd
Technical specifications and availability subject to change without notice.
Smart Infrastructure
Global Headquarters
Theilerstrasse 1a
CH-6300 Zug
+41 58 724 2424
www.siemens.com/buildingtechnologies
Document ID A6V10087532_n_en_--
Edition 2021-10-22