A6V10248293 Fire Control Panel en
A6V10248293 Fire Control Panel en
A6V10248293 Fire Control Panel en
The diagrams have been simplified and do not include additional network hardware or
security components. Permissible applications are described in the A6V101039439
Network Security Guidelines document. Contact your Siemens IT security expert for more
information.
System overview
2
Smart Infrastructure A6V10207176_m_en_--
2023-07-06
1 Remote access with Cerberus-Remote
2 'Cloud for Buildings'
3 Customer network
4 Management platform
5 Remote access to management platform
6 Remote access with Cerberus Mobile
7 Router + firewall + virtual private network
8 Fire damper with actuator
Transmission of a fault signal
You will find a detailed labeled version of the diagram above along with further information in
the A6V10332842 planning guide, see chapter 'Product documentation'.
3
Smart Infrastructure A6V10207176_m_en_--
2023-07-06
Networking of fire control panels
The diagrams have been simplified and do not include additional network hardware or
security components. Permissible applications are described in the A6V101039439
Network Security Guidelines document. Contact your Siemens IT security expert for more
information.
Up to 32 control panels and terminals can be linked to form one C-WEB network. If the C-
WEB network is connected to a danger management system via BACnet, up to 16 control
panels and terminals can be networked.
Fig. 2: Sub-net
1 Management platform
2 Remote access to management platform
Transmission of a fault signal
4
Smart Infrastructure A6V10207176_m_en_--
2023-07-06
Fig. 3: Backbone
You will find a detailed labeled version of the diagram above along with further information in
the A6V10332842 planning guide, see chapter 'Product documentation'.
5
Smart Infrastructure A6V10207176_m_en_--
2023-07-06
Control panels
From IP8, the fire control panels can be ordered with a periphery board with a 0.5 A or
1.5 A output current per C-NET line.
To convert existing fire control panels, the periphery board with 1.5 A per C-NET line can
be ordered separately.
You will find information on the integrated extinguishing system and the individual
extinguishing components that are available in a separate data sheet with the document ID
'A6V11480005'.
6
Smart Infrastructure A6V10207176_m_en_--
2023-07-06
FC724-ZAG Housing (Comfort)
Detector line (C-NET)
● 504 addresses
● 4 loops/8 stubs
Properties
● Operating unit
● Operating add-on (empty)
● 150 W power supply
● Connect X200 Gateway
● Max. battery capacity 25 Ah
● 1 flooding zone (optional)
Options of the operating unit
● Event printer FTO2001-A1
● Key switch (Kaba) FTO2005-C1
● Key switch (nordic) FTO2006-B1
● Operating add-on (2xLED indicator) FCM7213-Y3
● Operating add-on (4xLED indicator) FCM7214-Y3
● Exting. terminal (1 sector) XCM2002-A2
Extensions
You will find information on the integrated extinguishing system and the individual
extinguishing components that are available in a separate data sheet with the document ID
'A6V11480005'.
7
Smart Infrastructure A6V10207176_m_en_--
2023-07-06
FCM7214-Y3 Operating add-on (4xLED indicator)
● Optional operating add-ons with 96 indicator groups and two LEDs each:
1x red/green LED and 1x yellow LED
8
Smart Infrastructure A6V10207176_m_en_--
2023-07-06
Use
For medium-sized applications, e.g., for industrial plants, regional banks, or office
complexes.
Also suitable for more comprehensive systems thanks to flexible networking options.
Design
Function elements
Operating unit
The following elements are available on the operating unit:
● CPU module and electronics
● Ethernet connection
● Slots for RS232 and RS485 modules and network modules (SAFEDLINK)
● Space for 'Kaba' or 'nordic' key switch
● Space for event printer (depending on version)
● Peripheral data bus connection for optional LED modules
Periphery board
From IP8, the fire control panels can be ordered with a periphery board with a 0.5 A or
1.5 A output current per C-NET line.
To convert existing fire control panels, the periphery board with 1.5 A per C-NET line can
be ordered separately.
Housing
An FHA2007-A1 pivoting mounting plate can be fitted for the following elements above the
periphery board on the rear housing panel:
● 1x fire brigade periphery module (for Germany)
● 2x sounder modules (as an alternative to mounting on U-rail TS35)
● 1x Connect X200 Gateway
Configuration
The following software allows the system to be customized:
● Cerberus-Engineering-Tool
Operation
Each control unit has an integrated operating unit. The control panel can also be operated
via a separate fire terminal FT724.
You will find details and more information in product data sheet A6V10207898.
9
Smart Infrastructure A6V10207176_m_en_--
2023-07-06
Setup
10
Smart Infrastructure A6V10207176_m_en_--
2023-07-06
Position Designation Type Comment
10 Mounting plate FHA2007-A1 e.g., for fire brigade periphery module
or Connect X200 Gateway
11 Loop extension (C-NET) FCI2003-A1 For loop extension of the periphery board
(4 loops) FCI2004-A1 from two to four loops,
number of addresses remains the same
Loop extension (FDnet/C-NET, P) FCI2025-A1 For loop extension of the periphery board
(4 loops, P) FCI2024-A1 from two to four
loops, number of addresses remains the same
12 RS485 module (isolated) FCA2002-A1 For peripheral devices with RS485 interface
13 RS232 module (isolated) FCA2001-A1 For devices with an RS232 interface
14 Network module (SAFEDLINK) FN2001-A1 For networking several stations
15 Connect X200 Gateway and CXG3.X200 For connecting an FS720 station to Cloud for
mounting plate (X200) Buildings
FHA2063‑A1 The mounting plate FHA2007‑A1 and the
accessory set + ACDC (X200) FCA2056‑A1 or
the mounting plate (X200) FHA2063‑A1 and
the accessory set + ACDC (X200)
FCA2056‑A1 must be ordered separately.
16 Sounder module FCA2005-A1 For splitting one conventional sounder into
four
17 Battery (12 V, 17 Ah, VdS) FA2005-A1 For the emergency power supply
Battery (12 V, 25 Ah, VdS) BAT12-25
18 Fire brigade periphery module FCI2001-D1 For Germany (FBF, FSD, ÜE, FSE, ÖA, KL)
19 19" mounting kit FHA2016-A1 For installation in 19" third-party housing
20 License key Sx FCA20xx For special functions
21 Cable kit (communication) FCA2014-A1 For flexible connections running to the
modules on the operating unit
22 Power supply kit (150 W, B) FP2005-A1 For extra power supply
Repeater (SAFEDLINK) FN2002-A1 Not in overview, as not an installation part.
For extending the system bus C-WEB from
1000 m to 2000 m between two stations. Max.
1x repeater (SAFEDLINK) between two
stations
11
Smart Infrastructure A6V10207176_m_en_--
2023-07-06
Type Overview
Housing (Comfort)
12
Smart Infrastructure A6V10207176_m_en_--
2023-07-06
Details for ordering
Control panels
Extensions
You will find information on the integrated extinguishing system and the individual
extinguishing components that are available in a separate data sheet with the document ID
'A6V11480005'.
13
Smart Infrastructure A6V10207176_m_en_--
2023-07-06
Type Designation Weight Order number
FP2004-A1 Power supply kit (150 W, A) for 1.286 kg A5Q00020825
EN-compliant installation in empty
housing
FP2005-A1 Power supply kit (150 W, B) for 1.181 kg A5Q00018779
extension
Network (backbone)
Cloud Gateway
Batteries
License keys
External printer
14
Smart Infrastructure A6V10207176_m_en_--
2023-07-06
Product documentation
Title Document ID
System documentation
System description A6V10210355
Product data A6V10210368
Planning A6V10210362
Mounting/Installation A6V10210390
System data sheet
FS720 – Fire detection system A6V10227649
Data sheets
FC721 - fire control panel A6V10203220
FC722 - fire control panel A6V10206525
FC723 - fire control panel for modernization A6V10379246
FC724 - fire control panel A6V10207176
FC726 - fire control panel (modular) A6V10263277
FT724 - fire terminal A6V10207898
Fire detection system with integrated A6V11480005
single‑sector extinguishing
Network Security Guidelines A6V101039439
Planning overview A6V10332842
Guarantee
The application-specific technical data is guaranteed only in combination with the Siemens
products listed in the 'Device combinations' section. If third-party products are used, any
guarantee provided by Siemens will be invalidated.
15
Smart Infrastructure A6V10207176_m_en_--
2023-07-06
Technical data
16
Smart Infrastructure A6V10207176_m_en_--
2023-07-06
Fire control panel (4 loops)/(4 loops, P) FC724 in housing (Comfort)
Approvals VdS G209077
LPCB 126bn/07
FM 3051081
DNV GL (marine) MEDB00003US,
see document A6V10339425
17
Smart Infrastructure A6V10207176_m_en_--
2023-07-06
Issued by © Siemens 2007
Siemens Switzerland Ltd Technical specifications and availability subject to change without notice.
Smart Infrastructure
Global Headquarters
Theilerstrasse 1a
CH-6300 Zug
+41 58 724 2424
www.siemens.com/buildingtechnologies
Document ID A6V10207176_m_en_--