Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

FN 4127 Nic - 06 2010

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

FN-4127-NIC NETWORK INTERFACE CARD

SPECIFICATIONS
Supply Voltage 24 VDC Nominal
Quiescent Current Consumption 20mA
Cable Length 4,000ft Max.
Cable Type Belden 9271, Belden 9860
Protocol RS-485
Address Setting Dipswitch
Operating Temperature 32F~120F
Operating Humidity 90%RH

STANDARD FEATURES DESCRIPTION


• Allows for the expansion of up to 64 panels on a
FireNET system The FN-4127-NIC Network Interface Card allows for
the expansion of up to 64 nodes (combination of
• Enables information to be transmitted between
FACP’s or annuciators) on a single FireNET network
control panels
wide system. Using the Loop Explorer configuration
• Network protocol designed for tolerance to
software up to 64 nodes can be programmed to
interference and data corruption
respond to in a variety ways-independently or system
• Each card configured to a unique address
wide. The flexibility extends the comprehensive
through use of a dipswitch
cause and effect programming capability to the entire
• Transmission distance of up to 4,000 ft.
network allowing actions to be started from any point.
• Uses standard type Belden cable suitable for
The network communication protocol has been
RS-485 applications
designed to be extremely tolerant to interference and
• Simple 2-wire loop connection
data corruption. The simple 2 wire loop connection
• Flexible configuration options
makes for ease during installation.
• Network wide Cause & Effect logic
• Fully secure against short or open conditions
ENGINEERING SPECIFICATIONS

The FN-4127-NIC Network interface card shall be


PRODUCT LISTINGS compatible for use with a FireNET 4127 analog
addressable control panel. The NIC shall be
UL 864 Category mounted on the inside of the FACP and is
UOJZ CNN: California
Signal System Control State Fire connected used a standard RS-485 type 2 wire
Unit Sub-Assembly Marshal connection. Up to a maximum of 64 network cards
S8255 NFPA72 compliant can be installed per one complete networked
7170-0410:170
system. The network card shall be addressed by
use of a dipswitch.

Specifications subject to change without notice.

Hochiki America Corporation Find latest revision at www.hochiki.com


7051 Village Drive, Suite 100 Buena Park, CA 90621-2268
Phone: 714/522-2246 Fax: 714/522-2268
Technical Support: 800/845-6692 or technicalsupport@hochiki.com F0063 06/2010