Specifications

three-Phase Voltage control relay


380…480Vac, 2 C/O
RM22TR33

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Range of product Harmony Control Relays

Product or component type 3-phase control relay

Relay type Control relay

Network number of phases 3 phases

Relay name RM22TR

Relay monitored parameters Overvoltage and undervoltage detection


Phase sequence
Phase failure detection

Time delay type Adjustable 0.1...30 s, +/- 10 % of the full scale value on crossing the threshold Tt

Switching capacity in VA 2000 VA

Measurement range 380...480 V voltage AC

Contacts type and composition 2 C/O

Complementary
Reset time 1500 ms at maximum voltage

Maximum switching voltage 250 V AC

Minimum switching current 10 mA at 5 V DC

Maximum switching current 8 A AC

[Us] rated supply voltage 380...480 V AC

Supply voltage limits 304…576 V AC

Operating limits - 20 % + 20 % Un

Power consumption in VA 15 VA at 480 V AC 60 Hz

Voltage detection threshold < 100 V AC

Supply voltage frequency 50...60 Hz +/- 10 %

Output contacts 2 C/O

Nominal output current 8 A

Setting accuracy of the +/- 10 % of the full scale


switching threshold

Switching threshold drift <= 0.05 % per degree centigrade depending permissible ambient air temperature
<= 1 % within the supply voltage range

Setting accuracy of time delay 10 P

Jun 18, 2022 1


Time delay drift <= 0.05 % per degree centigrade depending permissible ambient air temperature
<= 1 % within the supply voltage range

Hysteresis 2 % fixed of selectable

Run-up delay at power-up 650 ms

Maximum measuring cycle 150 ms measurement cycle as true rms value

Threshold adjustment voltage 2...20 % of Un selected

Voltage range 380...480 V phase to phase

Repeat accuracy +/- 0.5 % for input and measurement circuit


+/- 3 % for time delay

Measurement error < 1 % over the whole range with voltage variation
< 0.05 %/°C with temperature variation

Response time <= 300 ms

Overvoltage category III conforming to IEC 60664-1


III conforming to UL 508

Insulation resistance > 100 MOhm at 500 V DC conforming to IEC 60255-27

Mounting position Any position

Connections - terminals Screw terminals, 2 x 0.5...2 x 2.5 mm² (AWG 20...AWG 14) solid without cable end
Screw terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 16) flexible with cable end
Screw terminals, 1 x 0.5...1 x 3.3 mm² (AWG 20...AWG 12) solid without cable end
Screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 24...AWG 14) flexible with cable end

Tightening torque 0.6…1 N.m conforming to IEC 60947-1

Housing material Self-extinguishing plastic

Status LED LED (yellow) relay ON


LED (green) power ON

Mounting support 35 mm DIN rail conforming to EN/IEC 60715

Electrical durability 100000 cycles

Mechanical durability 10000000 cycles

Utilisation category AC-15 conforming to IEC 60947-5-1


DC-13 conforming to IEC 60947-5-1
AC-1 conforming to IEC 60947-4-1
DC-1 conforming to IEC 60947-4-1

Safety reliability data MTTFd = 388.1 years


B10d = 350000

Contacts material Cadmium free

Width 22.5 mm

Net weight 0.09 kg

Environment
Immunity to microbreaks 10 ms

Electromagnetic compatibility Immunity for residential, commercial and light-industrial environments conforming to EN/IEC 61000-6-1
Immunity for industrial environments conforming to EN/IEC 61000-6-2
Emission standard for residential, commercial and light-industrial environments conforming to EN/IEC
61000-6-3
Emission standard for industrial environments conforming to EN/IEC 61000-6-4
Electrostatic discharge - test level: 6 kV level 3 (contact discharge) conforming to IEC 61000-4-2
Electrostatic discharge - test level: 8 kV level 3 (air discharge) conforming to IEC 61000-4-2
Radiated radio-frequency electromagnetic field immunity test - test level: 10 V/m level 3 conforming to
IEC 61000-4-3
Electrical fast transient/burst immunity test - test level: 4 kV level 4 (direct) conforming to IEC
61000-4-4
Electrical fast transient/burst immunity test - test level: 2 kV level 4 (capacitive coupling) conforming to
IEC 61000-4-4
Surge immunity test - test level: 4 kV level 4 (common mode) conforming to IEC 61000-4-5
Surge immunity test - test level: 2 kV level 4 (differential mode) conforming to IEC 61000-4-5
Conducted and radiated emissions class B group 1 conforming to CISPR 11
Conducted and radiated emissions class B conforming to CISPR 22

Standards EN/IEC 60255-1

Product certifications GL
CSA
RCM

2
Jun 18, 2022
CE
EAC
CCC
UL

Ambient air temperature for -40…70 °C


storage

Ambient air temperature for -20…50 °C at 60 Hz


operation -20…60 °C at 50 Hz AC/DC

Relative humidity 93…97 % at 25…55 °C conforming to IEC 60068-2-30

Vibration resistance 0.075 mm (f= 10…58.1 Hz) not in operation conforming to IEC 60068-2-6
1 gn (f= 10…58.1 Hz) not in operation conforming to IEC 60068-2-6
0.035 mm (f= 58.1…150 Hz) in operation conforming to IEC 60068-2-6
0.5 gn (f= 58.1…150 Hz) in operation conforming to IEC 60068-2-6

Shock resistance 15 gn (duration = 11 ms) for not in operation conforming to IEC 60068-2-27
5 gn (duration = 11 ms) for in operation conforming to IEC 60068-2-27

IP degree of protection IP20 (terminals) conforming to IEC 60529


IP40 (housing) conforming to IEC 60529
IP50 (front panel) conforming to IEC 60529

Pollution degree 3 conforming to IEC 60664-1


3 conforming to UL 508

Dielectric test voltage 2.5 kV, 1 min AC 50 Hz conforming to IEC 60255-27

Packing Units
Unit Type of Package 1 PCE

Number of Units in Package 1 1

Package 1 Weight 104.0 g

Package 1 Height 2.6 cm

Package 1 width 8.2 cm

Package 1 Length 9.5 cm

Unit Type of Package 2 S02

Number of Units in Package 2 40

Package 2 Weight 4.535 kg

Package 2 Height 15 cm

Package 2 width 30 cm

Package 2 Length 40 cm

Unit Type of Package 3 P06

Number of Units in Package 3 640

Package 3 Weight 81.06 kg

Package 3 Height 75 cm

Package 3 width 60 cm

Package 3 Length 80 cm

Offer Sustainability
Sustainable offer status Green Premium product

REACh Regulation REACh Declaration

EU RoHS Directive Pro-active compliance (Product out of EU RoHS legal scope)


EU RoHS Declaration

Mercury free Yes

RoHS exemption information Yes

China RoHS Regulation China RoHS declaration

Jun 18, 2022 3


Environmental Disclosure Product Environmental Profile

Circularity Profile End of Life Information

4
Jun 18, 2022
Product datasheet RM22TR33
Dimensions Drawings

Dimensions

Jun 18, 2022 5


Product datasheet RM22TR33
Mounting and Clearance

Mounting and Clearance

Rail Mounting

6
Jun 18, 2022
Product datasheet RM22TR33
Connections and Schema

3-Phase Voltage Control Relay

Wiring Diagram

L1,L2,L3 : Supply to be monitored


11-14,12 : 1st C/O contact of output relay
21-24,22 : 2nd C/O contact of output relay

Jun 18, 2022 7


Product datasheet RM22TR33
Technical Description

Function Diagrams

Phase Failure Detection (U measured < 0.7 x nominal supply voltage)

Control of Overvoltage and Undervoltage

Legend
Un Nominal supply voltage
R Output relay
Tt Overvoltage and undervoltage threshold delay (adjustable on front panel from 0.3 to 30 s)
H Hysteresis
U> Overvoltage threshold
U< Undervoltage threshold
L1, L2, L3 Phases of the supply voltage monitored
11-12, 11-14 R1 output relay connections
Relay status: black color = energized.