Castell Key
Castell Key
Castell Key
Switchgear
Applications Guide
www.castell.com
London
Cologne
Chicago
Shanghai
Castell Offices
Castell Installations
Contents
Why Choose Castell 4
Interlocking Switchgear 5
How to Design an Interlock System 6
Incomer Interlocking 7
Incomer and Busbar Interlocking 9
Incomer, Generator and Busbar Interlocking 10
Transformer Interlocking 10
Power Factor Correction Equipment/Capacitor Bank Interlocking 11
Wind Farm 12
UPS (Uninterruptable Power Supply) 12
Electrostatic Precipitators (ESP) 13
OEM Equipment 14
Switchgear Symbols 17
Products Overview 18
While every effort has been made to ensure the accuracy of the information provided, no liability can be taken for any errors or omission.
Castell Safety International Limited reserves the right to alter specifications and introduce improvements without prior notice.
www.castell.com
Why Choose Castell?
Founder:
James Harry Castell
1880 - 1953
The ability to work across HV, MV and LV means that a Castell system can be used as a single solution
to provide personnel safety and ensure equipment is used in the correct mode.
Working closely with key switchgear manufacturers has enabled Castell to produce interlocks
designed specifically for use on the leading manufacturers own breakers, isolators, disconnectors
and earth mechanisms.
That makes Castell trapped key interlocks be the perfect choice for protecting personnel in the
switchgear environment.
Castell Offers:
• Expertise in providing the best possible trapped key solution whatever the industry
• 90 years of experience protecting people and assets in industry
• High quality innovative products
• ISO 9001: 2008 accreditation
• Global team dedicated to providing technical support and assistance in selecting the correct solution
• The widest range of rugged and reliable trapped key interlock products globally
• The ability to produce customised solutions to meet the demands of your specific application
• Safety solutions that last for decades
-4- www.castell.com
Interlocking Switchgear
Interlocking Switchgear
Interlocking switchgear ensures that personnel remain safe and equipment is operated to the correct
procedures. Using a well-designed interlocking scheme will ensure that personnel cannot access
potentially dangerous areas without the switchgear system being put in a safe state. A good interlocking
scheme will also ensure that the system operates correctly and there is no chance of, for example,
switching two incoming feeds on to a common bus bar. This ensures that the equipment is not damaged
and the risk of fire and arc flash are greatly reduced.
• Personnel access
• Earthing systems
• High, medium and low voltage hazards
• Switching incomers on to common supply busbars
• Switching UPS systems and generators on to common supply busbars
• Controlling the supply from multiple incomers
The schemes in this application guide are for reference only and the overall system should be designed
and reviewed by a competent electrical engineer.
ABB I Alstom I Terasaki I Schneider Electric I Siemens I Hawker Siddeley I George Ellison I Merlin Gerin
-5-
Trapped Key Interlocking
Coding a System
Please refer to our Interlock and padlock integrity policy.
-6-
Switchgear Interlocking
Operation
Operation
-7-
Switchgear Interlocking
Operation
Operation
-8-
Switchgear Interlocking
Operation
AA AB AB
The system ensures that only two
incomers are supplying at any time.
-9-
Switchgear Interlocking
Operation
Operation
A
Whilst the disconnector is on the A
key cannot be removed. Switching the
disconnector to the off position will allow
the A key to be removed from the K Lock.
- 10 -
Switchgear Interlocking
Operation HV
HV LV
LV
both breakers.
Off
Off On
Off
* All locks can be individually fitted to suit the switchgear
Transformer Door
HV HV
LV
LV
AI Door Interlocks
- 11 -
Switchgear Interlocking
Wind Farm
Operation
HV Circuit Breaker
When the wind turbine is running and
generating electricity the keys are A A C
trapped in the HV and wind turbine circuit
breaker and access can not be gained to
the transformer housing.
B
Operation
Supply
While the UPS is running, the key is
trapped in the KSUPS Interlock. The key
can only be turned and released when
the UPS is put into Bypass. This will
energise the solenoid via a remote signal
from the UPS system.
Turning the key changes the condition of UPS UPS
the switch and released the key, which Bypass
can now be transferred to the AIE access
interlock. This allows access to the UPS
for maintenance.
AIE Access Interlock
The UPS will remain in a safe state until the
key is returned from the AIE and inserted Load A A
back into the KSUPS and trapped. This
allows the UPS to be returned to service. B
* All locks can be individually fitted to suit the switchgear
A
KSUPS Solenoid
Controlled Switch
- 12 -
Switchgear Interlocking
Electrostatic Precipitators
Operation
- 13 -
OEM Equipment
PDS01388(S)
E Max
ABB
OESA/OETL K-FSB-6.4-3
FS1B-CW-65
FS1S-CW-65
OMA Breaker
K-FSB-0-1
Sovereign Range SMM300
Magnum
PDS02499
C-H-OMA
FS1B-CW-65-9.5-22
(post 1996)
- 14 -
OEM Equipment
K-FSB-6.4-4
Glasgow
ACB FS1B-CW-65-9.5-22
FS2B-CW-90-9.5-22
RA8240
K-FSB-13.5-3
Terasaki
XFHA34-RO-3D5
AT6-AT40
FS2B-CW-65-STD
- 15 -
OEM Equipment
K-FSB-6.4-3
Fuser Monobloc
Socomec
S3 K-FSB-6.4-4
FS1B-CW-65-9.5-22 +
Mono Bloc 800 Type 3620-3121 Locking lever STD-LEV
K-FSB-6.4-4
FS2B-ACW-65-9.5-22
3WT (Braised Body)
Siemens
3WL FS2B-ACW-65-9.5-8
(Braised body)
CL1062
CL1019
Masterpact CL1019
Schneider
CL1019
- 16 -
Switchgear Interlocking
Contacts Contacts
G closed open
A
A
- 17 -
Products
Products Overview
Overview
Mechanical Isolation
FS / Q K
- 18 -
Notes
- 19 -
CSI-CAB/SWG-2020-EN Issue 2
Castell Safety International Castell Safety International Kirk Key Interlock SPS China
The Castell Building Tower 185 9048 Meridian Circle NW 2F, Building 63,
217 Kingsbury Road 60185 Frankfurt am Main North Canton, OH 47720 No 421 Hongcao Road, Xuhui District
London, NW9 9PQ Germany USA Shanghai PRC, 200233
UK China
t: +44 (0)20 8200 1200 t: +49 (0)69 50 50 47 310 t: +1 800 438 2442 t: +86 (0)21 6151 9028
f: +44 (0)20 8205 0055 f: +49 (0)69 50 50 47 450 f: +1 330 497 4400 f: +86 (0)21 6151 9030
ISO 9001
Q 10297
While every effort has been made to ensure the accuracy of the information provided, no liability can be taken for any errors or omission.
Castell Safety International Limited reserves the right to alter specifications and introduce improvements without prior notice.