Ventilation: The Building Regulations 2010
Ventilation: The Building Regulations 2010
Ventilation: The Building Regulations 2010
F
Ventilation
APPROVED DOCUMENT
ONLINE VERSION
ONLINE VERSION
2021 edition
This approved document supports Part F of Schedule 1 to the Building Regulations 2010.
This approved document takes effect on 15 June 2022 for use in England. It does not apply to work
subject to a building notice, full plans application or initial notice submitted before that date,
provided the work for each building is started before 15 June 2023. Full detail of the transitional
arrangements can be found in Circular Letter 01/2021 published on gov.uk.
ONLINE VERSION
ONLINE VERSION
Introduction
Those responsible for building work include agents, designers, builders, installers and the building
owner. For further information, see Chapter 7 in Volume 1 and paragraphs A26, B2 and F2 in Volume 2
of the Manual to the Building Regulations.
The Building Regulations can be contravened by not following the correct procedures or not meeting
the technical performance requirements. If the building owner or those responsible for the works
contravene the Building Regulations, the local authority may prosecute them in the magistrates’ court.
For further information on enforcement and sanctions in the existing system, see Chapter B in Volume
2 of the Manual to the Building Regulations.
If building work consists only of installing certain types of services or fittings (e.g. fuel-burning
appliances or replacement windows) and the building owner employs an installer that is registered
with a relevant competent person scheme designated in the regulations, a building control body does
not need to be notified.
For further information about competent person schemes, see Chapter 5 in Volume 1 and Chapter C
in Volume 2 of the Manual to the Building Regulations.
B2
Requirement B2: Internal fire spread (linings)
This section deals with the following requirement from Part B of Schedule 1 to the Building
Regulations 2010.
Requirement
Requirement Limits on application
Internal fire spread (linings)
B2. (1) To inhibit the spread of fire within the building,
the internal linings shall—
(a) adequately resist the spread of flame over
their surfaces; and ➊
(b) have, if ignited, either a rate of heat release
or a rate of fire growth, which is reasonable in
the circumstances.
(2) In this paragraph “internal linings” means the
materials or products used in lining any partition,
wall, ceiling or other internal structure.
Intention
In the Secretary of State’s view, requirement B2 is met by achieving a restricted spread of flame
over internal linings. The building fabric should make a limited contribution to fire growth,
including a low rate of heat release.
It is particularly important in circulation spaces, where linings may offer the main means by which
fire spreads and where rapid spread is most likely to prevent occupants from escaping.
Requirement B2 does not include guidance on the following.
➋
a. Generation of smoke and fumes.
b. The upper surfaces of floors and stairs.
c. Furniture and fittings.
Key
For further information about the use of technical guidance, see Chapter 7 in Volume 1 and Chapter F
in Volume 2 of the Manual to the Building Regulations.
Contents
Introduction i
What is an approved document? i
How is construction regulated in England? i
How do you comply with the Building Regulations? i
What do the Building Regulations cover? ii
When must a building control body be notified? ii
How to use this approved document iii
Where to get further help iv
Section 0: Introduction 1
Summary 1
Application 1
Selected key interactions with other parts of the Building Regulations 3
Section 0: Introduction
Summary
0.1 This approved document is Approved Document F, Volume 2: Buildings other than dwellings.
It gives guidance on how to comply with Part F of Schedule 1 to the Building Regulations. For
guidance relating to dwellings, use Approved Document F, Volume 1: Dwellings.
0.2 This approved document contains the following sections:
Application
0.3 The guidance in Approved Document F, Volume 2 applies only to buildings other than dwellings.
For blocks of flats with shared communal rooms, this approved document should be consulted for
those rooms.
NOTE: Rooms for residential purposes and buildings that contain only rooms for residential
purposes are not dwellings and are covered by the guidance in this approved document.
Exemptions
0.4 Certain types of building are exempt from the Part F requirements of the Building Regulations.
These are outlined in paragraphs A7 to A13 of the Manual to the Building Regulations.
Emergency repairs
0.9 For emergency repairs, if it is not possible to notify the building control body in advance, the
building control body should be notified as soon as possible. If the installer is registered with a
competent person scheme, see Chapter 5 in Volume 1 and Chapter C in Volume 2 of the Manual to
the Building Regulations.
Minor works
0.10 Minor works must comply with the relevant requirements of the Building Regulations, but the
building control body does not need to be notified.
For mechanical ventilation and air-conditioning systems, minor works include any of the following.
a. Replacing parts.
b. Adding an output or control device if testing and adjusting the system would not affect its
energy efficiency or would not be possible.
c. Providing a self-contained mechanical ventilation or air-conditioning appliance when all the
following apply.
i. Any electrical work is exempt from a requirement to give advance notice to a building
control body.
ii. Testing and adjusting the system would not affect its energy efficiency or would not be possible.
iii. The appliance is not installed in a room that contains an open-flued combustion appliance.
Live/work units
0.11 A unit that contains both living accommodation and space for commercial purposes (e.g. for a
workshop or office) should be treated as a dwelling if the commercial part can be reverted to
domestic use.
0.12 The commercial part of the building can be reverted to domestic use if all of the following apply.
a. There is direct access between the commercial space and the living accommodation.
b. The commercial space and living accommodation are within the same thermal envelope.
c. The living accommodation comprises a substantial proportion of the total area of the unit. What
constitutes a ‘substantial proportion’ should be assessed on a case-by-case basis by the building
control body.
NOTE: A large non-domestic building that contains a small flat for a manager is not treated as
a dwelling. A dwelling that contains a room used as an office or utility space is still treated as a
dwelling.
Mixed-use developments
0.13 When constructing a dwelling as part of a larger building that contains other types of
accommodation, sometimes called a mixed-use development, refer to the two volumes of
Approved Document F as follows.
a. For guidance on each individual dwelling, use Approved Document F, Volume 1: Dwellings.
b. For guidance on the non-dwelling parts of the building, such as shared communal rooms and
commercial or retail space, use this approved document: Approved Document F, Volume 2:
Buildings other than dwellings.
This section deals with the requirements of Part F1(1) of Schedule 1 to the Building Regulations 2010.
Requirement
Requirement Limits on application
Means of ventilation Requirement F1 does not apply to a building or
space within a building:
F1. (1) There shall be adequate means of ventilation
provided for people in the building. a. into which people do not normally go;
b. which is used solely for storage; or
c. which is a garage used solely in connection with
a single dwelling.
Intention
In the Secretary of State’s view, requirement F1(1) is met in a new building other than a dwelling if it
has a means of ventilation that achieves all of the following.
a. Extracts water vapour and indoor air pollutants from areas where they are produced in
significant quantities before they spread through the building, following the guidance on extract
ventilation in Section 1 for the relevant building type.
b. Supplies a minimum level of outdoor air for occupants’ health, following the guidance for whole
building ventilation in Section 1 for the relevant building type.
c. Rapidly dilutes indoor air pollutants and disperses water vapour when necessary in occupiable
rooms and sanitary accommodation, following the guidance for purge ventilation in Section 1 for
the relevant building type.
d. Monitors air quality in specific types of occupiable rooms, following the guidance in paragraphs
1.21 to 1.23.
e. Minimises the entry of external pollutants, following the guidance in Section 2.
f. Achieves all of the following, as far as is reasonably practicable.
i. Produces low levels of noise, following the guidance in paragraphs 1.5 and 1.6.
ii. Offers easy access for maintenance, following the guidance in paragraph 1.7.
iii. Provides protection from rain.
iv. Provides protection from cold draughts.
v. Does not significantly risk occupants’ health.
In the Secretary of State’s view, requirement F1(1) is met for work on an existing building other than a
dwelling by following the guidance in Section 3.
General
1.1 The aim of requirement F1(1) is to protect the health of occupants of the building by providing
adequate ventilation. Without adequate ventilation, mould and internal air pollution may become
hazardous to health and the risk of transmission of airborne infection is increased.
NOTE: The guidance in this approved document is not designed to deal with the products of
tobacco smoking or vaping.
1.2 This approved document sets out guidance for ventilation provision in the following types and uses
of buildings and occupiable rooms.
a. Specific types of occupiable rooms – follow paragraphs 1.21 to 1.23.
b. Offices – follow paragraphs 1.24 to 1.37.
c. Car parks – follow paragraphs 1.38 to 1.40.
d. Building types other than offices or car parks – follow paragraph 1.41.
1.3 Other ventilation solutions may be used, if it can be shown to the building control body that they
satisfy requirement F1(1).
1.4 The guidance set out in this approved document has been designed to meet the indoor pollutant
levels in Appendix B where the outside air is of reasonable quality. In areas where the outside
air is not of reasonable quality, Section 2 provides guidance on limiting the entry of external air
pollutants.
Noise
1.5 Mechanical ventilation systems, including both continuous and intermittent mechanical ventilation,
should be designed and installed to minimise noise. This includes doing all of the following.
a. Correctly sizing and joining ducts.
b. Ensuring that equipment is appropriately and securely fixed, such as using resilient mountings
where noise carried by the structure of the building could be a problem.
c. Selecting appropriate equipment, including following paragraph 1.6.
1.6 For mechanical ventilation systems, fan units should be appropriately sized so that fans operating
in normal background ventilation mode are not overly noisy, taking into consideration the use and
likely background level of noise from other sources. This might require fans to be sized so that they
do not operate near maximum capacity when in normal background ventilation mode.
Performance-based guidance
1.12 Performance criteria for acceptable levels of moisture and pollutants are given in Appendix B.
Ventilation rates designed to meet the performance criteria are given in this guidance or in the
documents referred to.
1.13 Some ventilation system designs can, in certain circumstances, result in lower ventilation rates
than those stated in this guidance or in the documents referred to (e.g. systems with automatic
controls). Where lower ventilation rates are proposed, expert advice should be obtained to
demonstrate that the solution meets the performance standards in Appendix B.
1.28 Food and drink preparation areas should have an intermittent air extract rate of either of the
following.
a. If the area is only for using a microwave and preparing drinks: 15 litres per second.
b. If the area is for using a domestic-type hob or cooker, either of the following.
i. If the extract ventilator is adjacent to the hob/cooker: 30 litres per second.
ii. If the extract ventilator is remote from the hob/cooker: 60 litres per second.
NOTE: This guidance does not apply to commercial kitchens, which should follow the specific
guidance in Table 1.1.
1.29 Specialist buildings and spaces should follow the guidance in Table 1.1.
1.30 For naturally ventilated offices that do not use mechanical supply and extract ventilation, both of
the following should apply.
a. The locations of extract ventilators should be both of the following.
i. As high as practicable.
ii. A maximum of 400mm below the ceiling.
b. Where used, passive stack ventilation terminals should be located in the ceiling.
1.31 For a room with no openable window, the extract ventilation should operate both:
a. while the room is occupied
b. for a minimum of 15 minutes after occupants have left the room.
1.39 As an alternative to paragraph 1.38, either of the following may be considered to provide adequate
ventilation.
a. If the car park has natural ventilation, openings at each car parking level should comply with
both of the following.
i. Have a minimum aggregate equivalent area of 1/20 of the floor area at that level.
ii. Have a minimum of 25% of the aggregate equivalent area on each of two opposing walls.
b. If the car park has mechanical ventilation, either of the following should apply.
i. All of the following.
• Permanent natural ventilation openings with a minimum equivalent area of 1/40 of the
floor area.
• A mechanical ventilation system capable of at least three air changes per hour.
• For exits and ramps, where cars queue inside the building, provision to ensure a local
ventilation rate of at least ten air changes per hour.
ii. Both of the following.
• For a car park in a basement, the provision of a mechanical ventilation system capable of at
least six air changes per hour.
• For exits and ramps, where cars queue inside the building, provision to ensure a local
ventilation rate of at least ten air changes per hour.
1.40 Further guidance can be found in the following documents.
a. The Association of Petroleum and Explosives Administrations’ Code of Practice for Ground Floor,
Multi Storey and Underground Car Parks.
b. CIBSE’s Guide B2 Ventilation and Ductwork.
c. The Health and Safety Executive’s publication EH40/2005 Workplace Exposure Limits.
d. ASHRAE’s ASHRAE Handbook – HVAC Applications, chapter 16 ‘Enclosed Vehicular Facilities’.
Prison cells PSI 17/2012 Certified Prisoner Accommodation (Ministry of Justice, 2012)
Sanitary Same as for offices in paragraph 1.26: sanitary accommodation should have an intermittent air
accommodation extract rate of both of the following.
a. 15 litres per second per shower or bath.
b. 6 litres per second per WC pan or urinal.
Extract ventilators in sanitary accommodation should be capable of continuous operation if
required.
Schools and Education (School Premises) Regulations 1999
education Building Bulletin 101 Guidelines on Ventilation, Thermal Comfort and Indoor Air Quality in Schools
(ESFA, 2018)
Building Bulletin 101 can also be used as a guide to the ventilation required in other educational
buildings, such as further education establishments, where the accommodation is similar to that
in schools, e.g. sixth form accommodation. However, the standards may not be appropriate for
particular areas where more hazardous activities take place than are normally found in schools,
e.g. some practical and vocational activities that require containment or fume extraction.
Building Bulletin 101 can also be used for children’s centres and other early years settings, including
day nurseries, playgroups, etc.
Shops and CIBSE Guide B2 Ventilation and Ductwork (2016)
general retail
premises
Sports centres CIBSE Guide B2 Ventilation and Ductwork (2016)
and swimming Sport England Sports Halls Design and Layouts: Updated and Combined Guidance (2012)
pools
Supermarkets CIBSE Guide B2 Ventilation and Ductwork (2016)
and food stores
Transportation CIBSE Guide B2 Ventilation and Ductwork (2016)
buildings and
facilities
NOTE:
1. Common spaces are as defined in Appendix A.
2.1 Ventilation systems should be designed to minimise the intake of external air pollutants following
paragraphs 2.2 to 2.6 if either of the following applies.
a. The pollutant values in the location of the building exceed any of the limits in Table 2.1. This may
have been determined through an air quality assessment. Where modelling or monitoring data is
required, expert advice should be sought.
b. The building is located near to any of the following sources of significant local pollution.
i. Road traffic, including traffic junctions and underground car parks.
ii. Combustion plant (such as heating appliances) running on conventional fuels, most
commonly natural gas.
iii. Other combustion processes (for example, waste incineration, thermal oxidation abatement
systems).
iv. Discharges from industrial processes.
v. Fugitive (i.e. not effectively controlled) discharges from industrial processes and other
sources.
vi. Exhaust discharges from building ventilation systems.
vii. Construction and demolition sites, which are a source of particles and vaporous discharges.
viii. Other significant sources of local air pollution which may be detrimental to health.
Table 2.1 Limit values from Schedule 2 to the Air Quality Standards Regulations 2010
Pollutant Exposure limit Exposure time
Carbon monoxide 10mg/m3 8-hour average
Sulphur dioxide 350μg/m3 1-hour average
125μg/m 3
1-day average
Nitrogen dioxide 200μg/m3 1-hour average
40μg/m 3
1-year average
Benzene 5μg/m3 1-year average
Lead 0.5mg/m 3
1-year average
PM2.5 25μg/m3 1-year average
PM10 50μg/m3 1-day average
40μg/m 3
1-year average
NOTE: This section only gives guidance for typical situations. Expert advice may also be able to
provide additional guidance on the suitability of other technologies to minimise the intake of
external air pollutants, including filtration.
NOTE: The Building Research Establishment’s Ventilation for Healthy Buildings: Reducing the Impact
of Urban Air Pollution provides guidance on minimising the ingress of external pollutants into non-
domestic urban buildings.
General
3.1 When building work in an existing building includes work on ventilation, for example:
a. building an extension
b. adding a wet room
c. replacing part of the ventilation system
the work should meet the relevant standards in this approved document.
3.2 When other building work is carried out that will affect the ventilation of the existing building,
for example:
a. replacing windows or doors
b. doing energy efficiency work
the ventilation of the building should either:
a. meet the standards in the relevant approved document
b. not be less satisfactory than before the work was carried out.
NOTE: Ventilation through infiltration should be considered to be part of the ventilation provision
of a building. Reducing infiltration might reduce the indoor air quality of the building below the
standards given in Appendix B.
3.3 When a building undergoes a material change of use, Part F of Schedule 1 to the Building
Regulations applies to the building or part of the building that has changed use. Guidance in
Section 1 should be followed.
NOTE: Ventilation equipment is considered to be a ‘controlled service or fitting’ and providing or
extending this equipment in or in connection with a building is considered to be building work.
NOTE: Some building work does not need to be notified to the local authority. Details of such
work are set out in the Manual to the Building Regulations.
3.4 If work is carried out which increases the energy efficiency of a building, airtightness may be
increased. In these circumstances, any useful ventilation which was lost should be replaced in order
to maintain a healthy indoor environment. When carrying out work which is likely to increase the
airtightness of the building, it should be demonstrated to the building control body that the work
meets the requirements of Part F1(1), where it is an applicable requirement. Refer to paragraphs 3.1
and 3.2 for the relevant standards that should be met. For domestic-type installation of common
energy efficiency measures in existing buildings, Approved Document F, Volume 1: Dwellings
contains guidance on meeting the requirements of Part F of the Building Regulations.
This section deals with the requirements of Part F1(2) of Schedule 1 and regulations 39 and 44 of the
Building Regulations 2010.
Requirement
Requirement Limits on application
F1. (2) Fixed systems for mechanical ventilation and any Requirement F1 does not apply to a building or
associated controls must be commissioned by space within a building:
testing and adjusting as necessary to secure that
a. into which people do not normally go;
the objective referred to in sub-paragraph (1) is
met. b. which is used solely for storage; or
c. which is a garage used solely in connection with
a single dwelling.
Regulations
Information about ventilation
39. (1) This regulation applies where paragraph F1(1) of Schedule 1 imposes a requirement in relation to building
work.
(2) The person carrying out the work shall not later than five days after the work has been completed
give sufficient information to the owner about the building’s ventilation system and its maintenance
requirements so that the ventilation system can be operated in such a manner as to provide adequate
means of ventilation.
Commissioning
44. (1) This regulation applies to building work in relation to which paragraph F1(2) of Schedule 1 imposes
a requirement, but does not apply to the provision or extension of any fixed system for mechanical
ventilation or any associated controls where testing and adjustment is not possible.
(2) This regulation also applies to building work in relation to which paragraph L1(b) of Schedule 1 imposes a
requirement, but does not apply to the provision or extension of any fixed building service where testing
and adjustment is not possible or would not affect the energy efficiency of that fixed building service.
(3) Where this regulation applies the person carrying out the work shall, for the purpose of ensuring
compliance with paragraph F1(2) or L1(b) of Schedule 1, give to the local authority a notice confirming that
the fixed building services have been commissioned in accordance with a procedure approved by the
Secretary of State.
(4) The notice shall be given to the local authority—
(a) not later than the date on which the notice required by regulation 16(4) is required to be given; or
(b) where that regulation does not apply, not more than 30 days after completion of the work.
NOTE: Where the building control body is an approved inspector, see regulation 20 of the Building
(Approved Inspectors etc.) Regulations 2010 (as amended).
Except for the items marked * (which are from the Continuous operation Uninterrupted running of a
Building Regulations 2010), these definitions apply mechanical ventilation device, such as mechanical
only to Approved Document F, Volume 2: Buildings extract ventilation or mechanical supply and
other than dwellings. extract ventilation. The air flow rate provided by
Air permeability The measure of airtightness of mechanical ventilation need not be constant but
the building fabric. It is defined as the air leakage may be varied, under either manual or automatic
rate per hour per m2 of envelope area at the test control, in response to the demand for removal of
reference pressure differential of 50Pa. pollutants or water vapour.
Bathroom A room that contains a bath or Extract ventilation The removal of air directly
shower and which can also include sanitary from an internal space or spaces to the outside.
accommodation. Extract ventilation may be by natural means or
by mechanical means (e.g. by an extract fan or a
Building control body A local authority or an central system).
approved inspector.
Free area The geometric open area of a ventilator.
Common space A space where large numbers of
people are expected to gather (e.g. a shopping mall Habitable room A room used for dwelling
or foyer of a cinema or theatre) or which is used purposes but which is not solely a kitchen, utility
mainly for circulation in buildings which do not room, bathroom, cellar or sanitary accommodation.
contain dwellings (e.g. a corridor or lift lobby in an Infiltration The uncontrolled exchange of air
office building). This does not include areas used between the inside and outside of a building,
solely or principally for circulation in buildings through gaps and cracks.
containing dwellings, including corridors or lift Intermittent operation When a mechanical
lobbies in blocks of flats. ventilator does not run all the time, usually running
only when there is a particular need to remove
pollutants or water vapour (e.g. during cooking
or bathing). Intermittent operation may be under
either manual control or automatic control.
Sanitary accommodation A space containing one Ventilation opening Any means of purpose-
or more flush toilets (WCs) or urinals. Sanitary provided ventilation (whether permanent or
accommodation containing one or more cubicles closable) that opens directly to external air, such
counts as one space if there is free circulation of as the openable parts of a window, a louvre or a
air throughout the space. background ventilator. It also includes any door
Shared communal rooms Rooms in buildings that opens directly to external air.
containing dwellings, which provide facilities Whole building ventilation (general ventilation)
for the residents, for example a laundry room, Nominally continuous ventilation of rooms or
occupied lobby or gym. This does not include spaces at a relatively low rate to dilute and remove
areas used solely or principally for circulation in pollutants and water vapour not removed by
buildings containing dwellings, including corridors extract ventilation, purge ventilation or infiltration,
or lift lobbies. as well as to supply outdoor air into the building.
Surface water activity A measure of the availability
of water to micro-organisms. Surface water
activity is determined from the ratio of the
vapour pressure of the water in the substrate to
the vapour pressure of pure water at the same
temperature and pressure. This ratio, in steady-
state conditions, is numerically equal to the
equilibrium relative humidity of the air, except that
the latter is commonly expressed as a percentage.
Thermal envelope The combination of thermal
elements of a building which enclose a particular
conditioned indoor space or groups of indoor
spaces.
Utility room A room containing a sink or other
feature or equipment that may reasonably be
expected to produce significant quantities of water
vapour.
Ventilation The supply and removal of air (by
natural and/or mechanical means) to and from a
space or spaces in a building. It normally comprises
a combination of purpose-provided ventilation and
infiltration.
Introduction
B1 This appendix sets out the levels of moisture and other pollutants that the provisions in this
approved document are designed to control. The provisions are designed to control all of the
following.
a. Bio-effluents, as described in paragraph B2a.
b. Moisture levels, as described in paragraph B2b.
c. Indoor air pollutants, as described in paragraph B2d.
NOTE: The guidance in this approved document may not be adequate to address pollutants
from flueless combustion space heaters. This approved document does not directly address
contamination from outdoor sources.
NOTE: A strategy for achieving good indoor air quality includes reducing the release of water
vapour and air pollutants. This approved document does not provide guidance on such strategies.
B3 As an alternative to using TVOC, the individual VOCs may be applied where their use is supported
by robust independent evidence. Public Health England’s Indoor Air Quality Guidelines for Selected
Volatile Organic Compounds (VOCs) in the UK should be used. Testing against these metrics is likely
to be more complex than testing against TVOC.
Where the Health and Safety Executive gives guidance for specific situations, that guidance should be
followed in preference to the guidance given here.
Extract ventilation
B5 Office equipment can emit pollutants, including ozone and organic compounds. For example, a
study by Black and Wortham (1999) suggests the following emission rates for laser printers and dry
paper copiers assuming 30 minutes use in an hour.
a. 25mg/h for TVOC.
b. 3mg/h for ozone.
To meet the performance criteria for these pollutants requires an extract rate of 20 litres per second
per machine during use.
B6 For sanitary accommodation, the extract rates used for dwellings have been applied.
B7 For food and beverage preparation areas, the extract rates used for dwellings have been applied.
NOTE: The guidance in this appendix is based on the Scientific Advisory Group for Emergencies
(SAGE) EMG/SPI-B advisory group paper Application of CO2 monitoring as an approach to managing
ventilation to mitigate SARS-CoV-2 transmission.
People exhale carbon dioxide (CO2) when they breathe out. If there is a build-up of CO2 in an area it can
indicate that ventilation needs to be improved.
Checking levels of CO2 using a monitor can help to identify areas that are poorly ventilated.
Dangerous Substances and Explosive Atmospheres Code of Practice for Ground Floor, Multi Storey and
Regulations 2002, SI 2002/2776 Underground Car Parks. Second Edition [1995]
Education (School Premises) Regulations 1999, Building and Engineering Services Association
SI 1999/2 (BESA)
Factories Act 1961, c. 34 (thebesa.com)
Health and Safety at Work etc. Act 1974, c. 37 BESA DW 143 Guide to Good Practice – Ductwork
Air Leakage Testing [2013]
Planning (Listed Buildings and Conservation Areas)
Act 1990, c. 9 BESA DW 144 Specification for Sheet Metal
Ductwork [2016]
Welfare of Farmed Animals (England) Regulations
2007, SI 2007/2078 BESA DW 154 Specification of Plastics Ductwork
[2000]
Other documents BESA DW 172 Specification for Kitchen Ventilation
Systems [2018]
American Conference of Government Industrial
Hygienists (ACGIH) BESA TR 40 Guide to Good Practice for Local
Exhaust Ventilation [2020]
(acgih.org)
Building Research Establishment (BRE)
Industrial Ventilation: A Manual of Recommended
Practice for Design. Thirtieth Edition [2019] (www.bre.co.uk)
Industrial Ventilation: A Manual of Recommended Ventilation for Healthy Buildings: Reducing the
Practice for Operation and Maintenance. Second Impact of Urban Air Pollution [2011]
Edition [2020]
Building Services Research and Information
Association (BSRIA)
(www.bsria.com)
BG 43 Flexible Ductwork: A Guide to Specification,
Procurement, Installation and Maintenance [2013]
Chartered Institution of Building Services European Concerted Action (ECA) on Indoor Air
Engineers (CIBSE) and its Impact on Man
(www.cibse.org) Guidelines for Ventilation Requirements in Buildings.
AM10 Natural Ventilation in Non-domestic Buildings Working Group Report No. 11. EUR 14449 EN [1992]
[2005] Health and Safety Executive (HSE)
AM13 Mixed Mode Ventilation [2000] (hse.gov.uk)
Commissioning Code M Commissioning HSE Catering Information Sheet No. 10, Ventilation
Management [2003] in catering kitchens [2017]
Guide A Environmental Design [2015] EH40/2005 Workplace Exposure Limits. Containing
Guide B2 Ventilation and Ductwork [2016] the list of workplace exposure limits for use with
the Control of Substances Hazardous to Health
TM31 Building Log Book Toolkit [2006]
Regulations 2002 (as amended). Fourth Edition
TM40 Health and Wellbeing in Building Services [2020]
[2020]
HSG 258 Controlling Airborne Contaminants at
TM64 Operational Performance: Indoor Air Quality Work. A Guide to Local Exhaust Ventilation (LEV).
– Emissions Sources and Mitigation Measures [2020] Third Edition [2017]
Department for Environment, Transport and the HSG 202 General Ventilation in the Workplace –
Regions (DETR) Guidance for Employers [2000]
Expert Panel on Air Quality Standards: Ozone [1994] Home Office
Department of Health Estates and Facilities Code of Practice for the Housing and Care of
Division (part of NHS Digital) Animals Bred, Supplied or Used for Scientific
Purposes [2014]. Available at: https://www.gov.uk/
HTM 03-01 Specialised Ventilation for Healthcare government/publications/code-of-practice-for-
Premises: Part A – Design and validation [2021] the-housing-and-care-of-animals-bred-supplied-or-
HTM 03-01 Specialised Ventilation for Healthcare used-for-scientific-purposes
Premises: Part B – Operational Management and
Performance Verification [2007] McGraw-Hill Education
Building Bulletin 101: Guidelines on Ventilation, Manual to the Building Regulations: A Code of
Thermal Comfort and Indoor Air Quality in Practice for Use in England [2020]
Schools [2018]. Available at: https://www.gov.uk/ Ministry of Justice
government/publications/building-bulletin-101-
ventilation-for-school-buildings (www.gov.uk/moj)
PSI 17/2012 Certified Prisoner Accommodation [2012]
ONLINE VERSION
ONLINE VERSION
ONLINE VERSION
ONLINE VERSION
ONLINE VERSION
ONLINE VERSION
ONLINE VERSION
ONLINE VERSION
The Building Regulations 2010, Approved Documents are available from:
RIBA Books
Online: www.architecture.com/ribabooks
Telephone: +44 (0)20 7496 8383
Email: sales@ribabookshops.com
9 781914 124778
ONLINE VERSION