Data Sheet 3VA2712-5AB03-0AA0: Model
Data Sheet 3VA2712-5AB03-0AA0: Model
Data Sheet 3VA2712-5AB03-0AA0: Model
Model
product brand name SENTRON
Product designation Molded case circuit breaker
Design of the product MCCB
Design of the operating mechanism toggel handle actuator
Type of the driving mechanism manual operating mechanism
Type of the driving mechanism / motor drive No
Design of the overcurrent release ETU320
Voltage
Insulation voltage / rated value 1 000 V
Operating voltage
● at AC / at 50/60 Hz / rated value 690 V
Protection class IP IP20
protection class IP / on the front IP20
protection function of the overcurrent release LI
Power loss [W] / for rated value of the current / at AC 47 W
/ in hot operating state / per pole
Current
Operating current / at 45 °C / rated value 1 250 A
Continuous current / rated value 1 250 A
adjustable pick-up value current
● of the current-dependent overload release / 1 250 A
Full-scale value
● of instantaneous short-circuit trip unit / initial 1 875 A
value
Main circuit
Operating current
● at 40 °C / rated value 1 250 A
● at 50 °C / rated value 1 250 A
● at 55 °C / rated value 1 240 A
● at 60 °C / rated value 1 182 A
● at 65 °C / rated value 1 122 A
● at 70 °C / rated value 1 057 A
Auxiliary circuit
Number of CO contacts / for auxiliary contacts 4
Suitability
● suitability for use system protection
Adjustable parameters
adjustable pick-up value current / of the current- 500 A
dependent overload release / initial value
Product component
● Trip indicator Yes
● Voltage trigger No
● undervoltage release No
Product extension / optional / motor drive No
Product function
Product function
● Ground fault protection No
Short circuit
Operational short-circuit current breaking capacity
(Ics)
● at 415 V / rated value 55 kA
● at 500 V / rated value 36 kA
● at 690 V / rated value 25 kA
Maximum short-circuit current breaking capacity (Icu)
● at 415 V / rated value 55 kA
● at 440 V / rated value 55 kA
● at 500 V / rated value 36 kA
Connections
Arrangement of electrical connectors / for main Main connection on front side
current circuit
● Type of electrical connection / for main current busbar connection
circuit
Mechanical Design
Height 296 mm
Width 210 mm
Depth 183 mm
Mounting type fixed mounting
net weight 14 kg
Environmental conditions
Ambient temperature / during operation
● minimum -25 °C
● maximum 70 °C
Ambient temperature / during storage
● minimum -40 °C
● maximum 70 °C
Certificates
● reference code / acc. to DIN EN 61346-2 Q
● Reference code / acc. to DIN EN 81346-2 Q
Further information
Industry Mall (Online ordering system)
https://mall.industry.siemens.com/mall/en/en/Catalog/product?mlfb=3VA2712-5AB03-0AA0
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
https://support.industry.siemens.com/cs/ww/en/ps/3VA2712-5AB03-0AA0
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, ...)
http://www.automation.siemens.com/bilddb/cax_en.aspx?mlfb=3VA2712-5AB03-0AA0
CAx-Online-Generator
http://www.siemens.com/cax
Tender specifications
http://www.siemens.com/specifications
184
210 124.5
105 14
11
25 10
15.5
30
26.5
14.5
236
204
237
102
32
30
15.5
14
-Q
X1.92
X1.12
X1.22
X1.32
X1.42
X1.93
X1.13
X1.23
X1.33
X1.43
ETU320
-Q1
I >> I
In = 1250A
Ir = 500A - 1250A
Ii = 1250A - 18750A
IN = 625A / 1250A / 2500 A / OFF
X1.11
X1.21
X1.31
X1.41
X1.GF2
X1.GF1
X1.LN1
X1.LN2
X1.Rc2
X1.Rc1
2
N / L-
RTC (Ready to close / Einschaltbereitschaftsmeldeschalter); F5 (Maglatch for trip unit / Auslösemagnet); S24 (trip signalling switch / Ausgelöstmeldeschalter);
AUX1 - AUX4 (Auxiliary switches / Hilfsschalter);