Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

3VM11163ED220AA0 Datasheet en

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

Data sheet 3VM1116-3ED22-0AA0

circuit breaker 3VM1 IEC frame 160 breaking capacity class N Icu=25kA @
415V 2-pole, line protection TM210, FTFM, In=160A overload protection
Ir=160A, not adjustable short-circuit protection Ii=10 x In nut keeper kit

Model
product brand name SENTRON
product designation Molded case circuit breaker
Product version Line protection
design of the overcurrent release TM210
protection function of the overcurrent release LI
number of poles 2
General technical data
rated insulation voltage Ui 500 V
Max. rated operational voltage Ue with AC 50/60Hz 415 V
Max. rated operational voltage Ue with DC 250 V
power loss [W] / maximum 25 W
Active power loss / for rated value of the current / at AC / 12.65 W
in hot operating state / per pole
mechanical service life (switching cycles) / typical 15 000
Electrical endurance (switching cycles) / at AC-1 / at 6 000
380/415 V 50/60 Hz
Neutral conductors / upgradeable/retrofittable No
ground-fault monitoring version Without
product function
● communication function No
● other measurement function No
net weight 0.65 g
Current
operational current
● at 40 °C 160 A
● at 45 °C 160 A
● at 50 °C 160 A
● at 55 °C 158 A
● at 60 °C 155 A
● at 65 °C 153 A
● at 70 °C 150 A
Switching capacity according to IEC 60947
switching capacity class of the circuit breaker N
breaking capacity maximum short-circuit current (Icu)
● at 240 V 36 kA
● at 415 V 25 kA
breaking capacity operating short-circuit current (Ics)

3VM11163ED220AA0 Subject to change without notice


8.12.2021
Page 1/4 © Copyright Siemens
● at 240 V 27 kA
● at 415 V 18 kA
short-circuit current making capacity (Icm)
● at 240 V 76 kA
● at 415 V 53 kA
design of short-circuit protection For switching capacity values in DC power systems, see the 3VA
Molded Case Circuit Breaker Manual; link available under Service &
Support in the last chapter
Adjustable parameters
Adjustable response value current / li max. 1 600 A
Ground fault protection / tripping switchable / I2t=ON/OFF No
Mechanical Design
height [in] 5.1 in
Height 130 mm
width [in] 2 in
Width 50.8 mm
depth [in] 2.8 in
depth 70 mm
Connections
arrangement of electrical connectors / for main current Front connection
circuit
Auxiliary circuit
number of CO contacts / for auxiliary contacts 0
Accessories
product extension / optional / motor drive No
Environmental conditions
protection class IP / on the front IP40
ambient temperature
● during operation / minimum -25 °C
● during operation / maximum 70 °C
● during storage / minimum -40 °C
● during storage / maximum 80 °C
Certificates
reference code / acc. to IEC 81346-2 Q
General Product Approval Declaration of Conformity

Miscellaneous UK Declaration of
Conformity

Test Certificates Marine / Shipping other

Miscellaneous Miscellaneous

Further information
Information- and Downloadcenter (Catalogs, Brochures,…)
http://www.siemens.com/lowvoltage/catalogs
Industry Mall (Online ordering system)
https://mall.industry.siemens.com/mall/en/en/Catalog/product?mlfb=3VM1116-3ED22-0AA0
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
https://support.industry.siemens.com/cs/ww/en/ps/3VM1116-3ED22-0AA0
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, ...)
http://www.automation.siemens.com/bilddb/cax_en.aspx?mlfb=3VM1116-3ED22-0AA0
CAx-Online-Generator

3VM11163ED220AA0 Subject to change without notice


8.12.2021
Page 2/4 © Copyright Siemens
http://www.siemens.com/cax
Tender specifications
http://www.siemens.com/specifications

3VM11163ED220AA0 Subject to change without notice


8.12.2021
Page 3/4 © Copyright Siemens
last modified: 6/3/2021

3VM11163ED220AA0 Subject to change without notice


8.12.2021
Page 4/4 © Copyright Siemens

You might also like