UPS ENERTRONIC I
• Industrial version
• Single-phase and three-phase output
ENERTRONIC I UPS – developed
to meet industrial demands
To maintain crucial tasks and minimise downtime some critical • IGBT power semiconductor in the rectifier and inverter
consumers require power, which is independent of public grid • Input power factor ≥ 0.99
disturbances. Those critical customers are for example: • Input current THD (THDi) < 5%
• Excellent control properties for high voltage stability,
• Petrochemical installations even with large load changes
• Refineries • Electronic switchgear (EUE) and internal service
• Power stations and substations bypass
• Process computers • Extensive reporting and monitoring functions
• Control rooms
• SCADA systems
2
ENERTRONIC I – technical details
for your extra safety
manual bypass
input load EUE output load
bypass- switch switch UPS
input output
3
Web browser: system TCP/IP protocol: complete
values and configuration data are transferred
Figure 4: ENERTRONIC I with standard control unit Figure 5: Extensive reporting and monitoring functions
4
Touch Panel (optional)
• Graphic interface with display of the energy flow and the
system status
• Support for all common standard languages
• Event monitor for the last 1200 events. Complete
documentation of data, time and report in clear text
• Customized configuration possible
• Function setting of the remote control as well as adjustment
of the operating parameters
Technical Data
ENERTRONIC I 3-3 (three-phase input and three-phase output)
Power*1 (cosϕ = 0.8) [kVA] 10 20 30 40 50 60 80 100 120 140 160 200 240
Power*1 (cosϕ = 1.0) [kW] 8 16 24 32 40 48 64 80 96 112 128 160 192
Operating temperature range 0 ... 40 °C (reduction in power beyond this)
Relative air humidity 5 ... 95% (non-condensing)
Volume < 65 dBA (as a function of power)
Protection class IP20 (further classes on request)
Installation height 1000 m (without reduction in power)
Cable entry point below (above on request)
Colour RAL 7035 (other colours on request)
Ventilation redundant forced-air ventilated
Classification VFI-SS-111 (according to IEC / EN 62040-3)
Standards
Safety IEC / EN 62040-1, IEC / EN 60950-1
EMC IEC / EN 62040-2
Power IEC / EN 62040-3
Input
Voltage 3 / N 400 V ± 15% (further voltages on request)
Frequency 50 Hz ± 5% / 60 Hz ± 5%
THDi (100% load) ≤5
Input power factor ≥ 0.99
Transformer Isolation transformer as an option
Output (inverter mode)
Voltage 380 V / 400 V / 415 V (further voltages on request)
Voltage tolerance (static) ± 1%
Frequency tolerance ± 0.1%
Total harmonics distortion THDu Linear Load ≤ 1%
Efficiency up to 94% (as a function of the configuration)
Overload operation - inverter 200% for 3 s, 150% for 60 s, 125% for 10 min
Overload operation - bypass 1000% for 100 ms, 150% for 10 min
Short-circuit behaviour - inverter up to 350% for 3 s (up to 700% as an option)
Short-circuit behaviour - bypass 1000% for 100 ms
Transformer isolation transformer
Battery
Nominal voltage 110 V
220 V
400 V
Battery technologies Lead, nickel cadmium, lithium Ion (optional)
(*1higher power ratings on request) Specifications are subject to change without notice.
5
ENERTRONIC I UPS – the most important
technical data at a glance
Technical Data
ENERTRONIC I 3-1 (three-phase input and single-phase output)
Power (cosϕ = 0.8) [kVA] 10 20 30 40 50 60 80 100 120 140 160 200
Power (cosϕ = 1.0) [kW] 8 16 24 32 40 48 64 80 96 112 128 160
Operating temperature range 0 ... 40 °C (reduction in power beyond that)
Relative air humidity 5 ... 95% (non-condensing)
Volume < 65 dBA (as a function of power)
Protection class IP20 (further classes on request)
Installation height 1000 m (without reduction in power)
Cable entry point below (above on request)
Colour RAL 7035 (other colours on request)
Ventilation redundant forced-air ventilated
Classification VFI-SS-111 (according to IEC / EN 62040-3)
Standards
Safety IEC / EN 62040-1, IEC / EN 60950-1
EMC IEC / EN 62040-2
Power IEC / EN 62040-3
Input
Voltage 3 / N 400 V ±15% (further voltages on request)
Frequency 50 Hz ± 5% / 60 Hz ± 5%
THDi (100% load) ≤5
Input power factor ≥ 0.99
Transformer Isolation transformer as an option
Output (inverter mode)
Voltage 220 V / 230 V / 240 V (further voltages on request)
Voltage tolerance (static) ± 1%
Frequency tolerance ± 0.1%
Total harmonics distortion THDu Linear load: < 1%
Efficiency up to 91% (as a function of configuration)
Overload operation - inverter 200% for 3 s, 150% for 60 s, 125% for 10 min
Overload operation - bypass 500% for 100 ms, 150% for 10 min
Short-circuit behaviour - inverter 300% for 3 s (up to 400% as an option)
Short-circuit behaviour - bypass 500% for 100 ms
Transformer Isolation transformer
Battery
Nominal voltage 110 V
220 V
Battery technologies Lead, nickel cadmium, lithium ion (optional)
Specifications are subject to change without notice.
6
Modern power electronics
for efficient operation
[%]
140
120
100
80
60
40
20
0
0 0,2 0,4 0,6 0,8 1 0,8 0,6 0,4 0,2 0
inductive powerfactor capacitive
Rectifier Inverter
The rectifier consists of an IGBT semi-conductor rectifier bridge The inverter converts the direct current into single-phase volt-
with power factor correction (power factor = 1), which converts age (ENERTRONIC I 3-1) or three-phase voltage (ENERTRONIC I
the three-phase supply current into a controlled direct current 3-3) by means of sine-optimized pulse-width control in the
in order to feed the inverter. At the same time the connected IGBT semi-conductor and the output isolation transformer. As
battery is charged and/or always kept in its optimum charge a consequence of the high switching frequency relative to the
state by a trickle charging operation. base frequency and optimum control of the pulse width, a very
high level of efficiency is achieved, even with partial loads and
The rectifier is designed to simultaneously supply the fully a very small distortion factor with a non-linear load. Further-
loaded inverter and after a power failure, recharge the dis- more, this promotes an excellent dynamic response with load
charged battery. The rectifier has a start-up delay with soft step changes.
start in order to ramp up the start-up current after a power fail-
ure. In the course of the reconnection of parallel installations, a In the event of voltage dips or black-outs, the battery con-
series switching delay is automatically activated in order to nected to the DC bus bar is used automatically and free-of-in-
limit the in-rush current to that of an individual rectifier. terruption for the delivery of current. The battery discharging
alarm is activated and if the battery reaches its end of dis-
The rectifier has a charge current and voltage limit in accor- charge limit, the inverter switches off automatically and an
dance with the data supplied by the battery supplier. A temper- alarm is activated.
ature-compensated charging characteristic line can also be
integrated if required. Automatic switching of the load to the bypass supply occurs
when the inverter supply can no longer be guaranteed within
the prescribed tolerances.
7
www.benninguk.com • www.benning.us
www.benning.de
y
c
SCCP Natur
CO2
BENNING worldwide 9001 14001 50001 al R
e so
ur
c
es
Austria Greece South East Asia
Benning GmbH Benning Hellas Benning Power Electronics Pte Ltd
Elektrotechnik und Elektronik Chanion 1, Lykovrisi 141 23 85, Defu Lane 10
Eduard-Klinger-Str. 9 ATHENS #05-00
3423 ST. ANDRÄ-WÖRDERN Tel.: +30 (0) 2 10 / 5 74 11 37 SINGAPORE 539218
Tel.: +43 (0) 22 42 / 3 24 16-0 Fax: +30 (0) 2 10 / 5 78 25 54 Tel.: +65 / 68 44 31 33
Fax: +43 (0) 22 42 / 3 24 23 E-mail: info@benning.gr Fax: +65 / 68 44 32 79
E-mail: info@benning.at E-mail: sales@benning.com.sg
784370.14 GB 11/2018 paus Design & Medien, Bocholt Subject to alterations. Printed on chlorine free paper.
E-mail: info@benning.com.tr