Aros ST Sentry Multistandard
Aros ST Sentry Multistandard
Aros ST Sentry Multistandard
60
Fig. 1 Block diagram UPS in parallel up to 8 units
61
SENSITIVE SUPPLY COMPATIBLE advanced technology excellent capabilities
For power supply sources that are The active filter reduces harmonic Input distortion: (THDi) 4%
particularly sensitive to harmonics distortion of the phase and neutral Input power factor: >0.99
(generator sets or transformers of low currents. The Digital Signal Processor
power with respect to that of the UPS) it (DSP) and the current mode instantly Sentry Multistandard can also be
is often a good idea to take action to control and monitor the input current to supplied without the Active Filter
limit the harmonics injected back into the maintain a perfect sinewave with less for installations less sensitive to
supply by the UPS. than 4% harmonic distortion current harmonics.
maximum efficiency
SENTRY MULTISTANDARD series is also OTHER CHARACTERISTICS
Thanks to the active filter Sentry
available with built-in active filter using Suitable for powering capacitive loads
Multistandard systems have low input
high frequency Isolated Gate Bipolar such as blade servers, without any
distortion even at low loads and their
(IGBT) Technology with Digital Signal reduction of the active power, from 0.8
overall efficiency is not affected by
Processor (DSP) control. The Active leading to 0.8 lagging
generator frequency variations or line
Filter helps to reduce harmonics High level diagnostics: event log with
impedance
generated by the UPS into the supply 128 messages, states, measurements
which could disrupt the operation of reduction of neutral current and alarms - available from the built-in
downstream generators and The active filter reduces the input LCD in several languages
transformers whose rating is closely neutrals current by up to 3.5 times Reduced noise levels: high frequency
matched to that of UPS. their nominal rating to help avoid inverter bridge
oversizing input protections and Back feed protection standard: to
conductors avoid energy feeding back into the
mains supply (in compliance with CEI
maximum reliability 11-20; DK5600)
Sentry Multistandard systems are Power factor correction (input power
extremely reliable. Overall UPS factor, close to 1)
performance is unaffected should the By pass may be deactivated to allow
harmonic filter fail operation as a frequency converter (at
50 or 60 Hz)
Emergency operation: the UPS can be
set to operate only when the mains
fails (for emergency lighting)
62
Leading Cos (capacitive loads) Multistandard Output Power Lagging Cos (inductive loads)
Operating status, alarms, applied load,
cos 0,8 cos 0,9 100% kW cos 1 cos 0,9 cos 0,8
battery charging.
1,00
Active Power
0,75
100% kVA
0,25
63
Sentry Multistandard Technical data
Three-phase input
Three-phase output
64