TPH King 60 - 120KVA PDF

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

CATALOGO PRODODOTTI

THREE PHASE UPS 60 : 120kVA Rev. 4 TPH KING Series

Monitoring and control data are shown on an


easy to understand front panel display
featuring pushbutton controls, LCD read out
for event logs and diagnostics and a mimic
diagram for system status. The power
protection system can be remotely monitored
via RS232, dry contact or SNMP interface.

PRINCIPLES OF WORKING

The backup series is composed by: Rectifier,


Inverter, Static Switch, manual by-pass and
Battery.
The Rectifier-Inverter line normally feeds the
users, and the Battery is kept charged by the
Rectifier.
If a black out occurs, the Battery supplies
power energy to users always through the
Inverter. When the blackout is over, the
Rectifier provides for Battery charge.
If a short circuit or an overload occurs to the
users, the Static By-pass switches the load
over the emergency line. When the fault is
over, the Inverter feeds users.

FEATURES

 High efficiency up to 96.5%


 Filtered, stabilized and regulated sine wave
supply
 Unity input power factor for energy saving
and low reflected harmonic pollution to the
utility
 Wide input voltage window and input
 frequency window, the battery usage is
TPHKING series represents the last  minimized
Transformer-less double conversion (VFI)  Zero transfer time
Power protection technology designed to  Superior overload capability
Protect a wide area of critical applications  Battery monitoring and temperature
Including server rooms, networks,  dependent charging function
Telecommunication system, industrial LCD display for measurements, alarms and
Processes and medical equipment. Unmatched power history
Reliability, excellent electrical performance,  Device to avoid a complete battery
exceptionally compact size and outstanding discharge
cost-efficiency housed in an attractive
 ON LINE – OFF LINE working settable
enclosure are only some features of this new  Insulation transformer (option)
UPS solution.  Low audible noise, variable load-dependent
TPH KING series is available in a variety of  DC fan speed
models from 60kVA to 120KVA. The TPH KING  Customer slot, RS 232 and dry contact
series is provided in three cabinet size in order  interface as standard, USB, RS485 and
to allow longer battery backup times therefore  SNPM as option
avoid the use of additional battery cabinets.  Made In Italy
CATALOGO PRODODOTTI

THREE PHASE UPS 60 : 120kVA Rev. 4 TPH KING Series

 Dual input feed as option INTERFACES


 Personalizing 60Hz output converter
 Emergency Power Off. The TPH KING is provided with three standard
interfaces:
- Serial RS232
- USB port
- Emergency Power OFF (EPO)
CONTROL PANEL

The user friendly control panel si composed by


three parts:
- Power Management LCD Display (PMD);
- LED indicators;
- Keys.

Serial RS 232
The smart port is an intelligent RS232 serial
port that allows the UPS to a computer. The
connector is a standard D-Type, 9 pin, female.
Power Management Display (PMD) The software optionally allows the computer to
The 2x20 character LCD simplifies the monitor the mains voltage and the UPS status
communication with the UPS and provides the continuously.
necessary monitoring information about the
UPS.
The menu driven LCD enables the access to
the:
- Event register;
- Monitor the input and output U, I, f, P
- Battery runtime;
- Start up and shutdown of UPS;
- ON LINE – OFF LINE modality settable USB port
- Diagnosis (Service Mode); USB port for remote signaling and automatic
- Adjustments and testing. computer shutdown
LED indicators
The mimic diagram serves to indicate the
general status of the UPS. The LED indicators 4 3

show the power flow status and in the event of


mains failure or load transfer from inverter to
by-pass and vice-versa. The corresponding 1 2

LED indicators will change colors from green


(normal) to red (warning).
Keys EMERGENCY POWER OFF
The keys allow the user to operate the UPS to The Emergency Power Off facility must use a
perform settings and adjustments, to start up normally closed contact, which opens to
and shut down the UPS, to monitor on the LCD operate the emergency stop sequence.
display the voltages, currents, frequencies and The emergency stop port is located at the front
other values. of the UPS TPH KING module. In order to allow
removal, maintenance or testing of any remote
emergency stop facility without disturbing the
normal operation of the UPS, itis
CATALOGO PRODODOTTI

THREE PHASE UPS 150 : 800kVA Rev. 4 TPH KING Series

recommended that a terminal block, with N+XPOWER SCALABLE PARALLEL


linking facilities, be installed between the UPS REDUNDANCY
and the stop button.
The TPH KING UPS may be paralleled for
power capacity or for redundancy up to 20
1. Use a screened cable with 1 pair (section units to increase the power capacity or
of wire 0.6mm2) and maximum length of configuring a parallel redundant UPS system.
100m. The standard version is not provided with this
2. Connect the cable as shown in figure. feature which is optional and field upgradable.
EMERGENCY STOP SWICHT

(N.C. = Normally Closed)

The UPS TPH KING is provided with the


following accessories:

SNMP card for monitoring and integration in


network management. The Simple Network
Management Protocol (SNMP) is a worldwide-
standardized communication-protocol. It is INPUT AND OUTPUT
used to monitor any device in the network via
simple control language.

Dry contact interface

Optional relay card to monitor the main status


of the UPS.

Block diagram

Input Inverter
contactor contactor
CATALOGO PRODOTTI

THREE PHASE UPS 60 : 120KVA Rev. 4 TPH KING Series

TPH King TPH King TPH King TPH King


Model
60 80 100 120
Rated power
VA/KW 60/54 80/72 100/90 120/108

INPUT
Nominal voltage 3x380/220V+N, 3x400V/230V+N, 3x415/240V+N
Voltage tolerance Load <100% (-23% +20%), <80% (-30% +20%), <60% (-40% +20%)
Power factor 0.99 at full load
frequency 35 ÷70Hz 40 ÷ 72Hz
Current distortion THiD ≤ 3% at full load
Inrush current Absent
OUTPUT
Voltage 380/400/415V 3F+N
Voltage stability <±1% static, <±4% dynamic (step load 0-100% or 100-0%)
Voltage distortion <2% with linear load, <4% with non-linear load (EN62040-3)
Frequency 50Hz or 60Hz
F. tolerance ±0.1% free running, ±2% or ±4% with mains, adjustable
Waveform Sinusoidal
Transfer time 0 ms.
Crest factor 3:1
Overload 125% for 10 minutes, 150% for 1 minute at pf 0.8
Power Factor 0.9
Unbalanced load 100% all 3 phases regulated independently
Short capability Inverter 3 In for 40 msec – Bypass 10 In for 10msec
BATTERY
Type Maintenance free VRLA, sealed lead acid
Recharge time 5h at 90%
Batteries Voltage 240VDC
Battery Test Automatic and periodically (adjustable)
EFFICIENCY
ON LINE mode 95.5% at 100% load, 95% at 50% load
OFF LINE mode 98%
MISCELLANEOUS
Battery storage Max 6 months at ambient temperature
Operating Temp. from 0°C to + 40°C
Noise 100-50% 55/49dBA
Humidity (non condensing) 0-95%
Interfaces RS232 and EPO standard, dry contacts, SNMP, RS485 & USB optional
Positioning Min. 20cm rear space for fan ventilation
Dimensions (mm) 345x710x720 345x710x1045 440x910x1420 500x850x1600
Weight w/o batt. 60 65 95 100 160 165 170 180 200
Protection degree IP20
Colour Grey RAL 7024
Immunity class C3
STANDARDS
Safety IEC/EN 62040-1-1, IEC/EN 60950-1
EMC IEC/EN 62040-2, IEC/EN61000-3-2, IEC/EN61000-6-2,
Performance EN 62040-3
ELIT Srl reserves his right to do modifications to his products without notice.