Generator Protection
Generator Protection
STATOR ROTOR PRIME MOVER EXCITATION SYSTEM VOLTAGE REGULATOR GOVERNOR COOLING SYSTEM
GENERATOR PROTECTION FAULTS IN GENERATOR EXTERNAL FAULTS INTERNAL FAULTS ROTOR EARTH FAULT FAULTS RELATED TO SUB SYSTEMS
GENERATOR PROTECTION
EXTERNAL FAULTS
GENERATOR PROTECTION
INTERNAL FAULTS
GENERATOR PROTECTION
FAULTS RELATED TO SUB-SYSTEMS
UNDER VOLTAGE OVER VOLTAGE UNDER FREQUENCY OVER FREQUENCY REVERSE POWER LOSS OF EXCITATION LOW-FORWARD POWER
GENERATOR PROTECTION
TYPES OF FAULTS (STATOR SIDE)
GENERATOR PROTECTION
VOLTAGE RESTRAINED OVER CURRENT THERMAL OVER LOAD CURRENT UNBALANCE OVER VOLTAGE UNDER VOLTAGE OVER FREQUENCY UNDER FREQUENCY LOSS OF FIELD REVERSE POWER UNDER POWER OUT OF STEP INADVERTANT ENERGISATION EARTH FAULT (100%) EARTH FAULT (95%) GENERATOR DIFFERENTIAL OVER EXCITATION (V/Hz)
GENERATOR PROTECTION
TYPES OF FAULTS (ROTOR SIDE) ROTOR EARTH FAULT EXCITATION UNDER VOLTAGE EXCITATION UNDER CURRENT DIODE FAILURE
GENERATOR PROTECTION
11 kV 11000/110v SINGLE LINE DIAGRAM GENERATOR PROTECTION
400/5 49
27 51V 46
59 40
81 32 64
37
G
400/5
GENERATOR PROTECTION
PROTECTION PHILOSOPHY TYPE OF GENERATOR GENERATOR SIZE NATURE OF GROUNDING ECONOMY TYPE OF CONNECTION TYPE OF LOADS
GENERATOR PROTECTION
ANOTOMY OF FAULTS
PLAIN OVER CURRENT ( SMALL MACHINES) VOLTAGE DEPENDANT OVER CURRENT (LARGE MACHINES)
FAULT AWAY FROM TERMINALS (PLAIN O/C PROTECTION) FAULT CLOSE TO TERMINALS (VOLTAGE DEPENDENT O/C)
STATOR FAULTS
- WHEN O/C FAULT, TERMINAL VOLTAGE REDUCES. - RELAY MAY NOT TRIP, SINCE FAULT CURRENT THROUGH RELAY MAY BE LESS THAN SET POINT
STATOR FAULTS
VOLTAGE CONTROLLED OVER CURRENT
HAS TWO TRIP CHARACTERISTICS THE TERMINAL VOLTAGE DECIDES WHICH CHARCTERISTIC WILL BE FOLLOWED BY THE RELAY WHEN A FAULT OCCURS
STATOR FAULTS
VOLTAGE CONTROLLED OVER CURRENT Pick up level
I>
kI >
Vs >
Voltage Level
GENERATOR PROTECTION
VOLTAGE RESTRAINED OVER CURRENT
I*/ [I>]
1.0
V/Vs
STATOR FAULTS
EARTH FAULT
GENERATOR PROTECTION
EARTHING OF GENERATORS
GENERATOR PROTECTION
EARTHING OF GENERATORS DIRECT EARTHING
Stator Windings
RELAY
GENERATOR PROTECTION
EARTHING OF GENERATORS IMPEDANCE EARTHING
Stator Windings
TYPES OF IMPEDANCES RESISTOR (CURRENT BASED PROTECTION) B) TRANSFORMER (VOLTAGE BASED PROTECTION) C) TRANSFORMER D) (CURRENT BASED PROTECTION)
GENERATOR PROTECTION
EARTHING OF GENERATORS RESISTANCE EARTHING Stator Windings
CURRENT RELAY
GENERATOR PROTECTION
EARTHING OF GENERATORS TRANSFORMER EARTHING (VOLTAGE BASED) Stator Windings
VOLTAGE RELAY
GENERATOR PROTECTION
EARTHING OF GENERATORS TRANSFORMER EARTHING (CURENT BASED) Stator Windings
CURRENT RELAY
GENERATOR PROTECTION
EARTHING OF GENERATORS TRANSFORMER EARTHING (OPEN DELTA) Stator Windings
STATOR FAULTS
EARTH FAULT
WHEN A FAULT OCCURES CLOSE TO NEUTRAL, WITH IMPEDANCE GROUNDING, THE E/F CURRENT MAY BE LESS THAN THE PICK UP THRESHOLD OF THE NORMAL E/F RELAY OR DIFFERENTIAL RELAY
GENERATOR PROTECTION
NORMAL RELAY
GENERATOR PROTECTION
95 TO 100%
95%
GENERATOR PROTECTION
EARTHING OF GENERATORS (Close to neutral faults) Stator Windings
a
CURRENT RELAY
If
If = aV / R
GENERATOR PROTECTION
Measurement of third harmonic voltage across the earthing impedance Use of low frequency voltage injection between star point & earth
GENERATOR PROTECTION
LOSS OF FIELD IN GENERATORS GENERATOR WILL OVER SPEED & OPERATE AS AN INDUCTION GENERATOR (OVER SPEEDS OF THE ORDER OF 2 TO 5% ) GENERATOR WILL CONTINUE TO DELIVER POWER WILL DERIVE EXCITATION FROM THE SYSTEM STATOR CURRENT WILL BE 200% THERE WILL BE HEAVY ROTOR CURRENT RESULTS IN OVER HEATING
GENERATOR PROTECTION
LOSS OF FIELD IN GENERATORS PHASE ANGLE N ANGLE BETWEEN VOLTAGE & CURRENT
IMPEDANCE ANGLE E
= 360O - N
GENERATOR PROTECTION
LOSS OF FIELD IN GENERATORS
I E N
GENERATOR PROTECTION
N = 0o (360O) N = +30o N= +60o N= +90o N = +120o N = +150o N = +180o FORWARD RESISTIVE FORWARD RESISTIVE + FORWARD CAPACITIVE FORWARD RESISTIVE + FORWARD CAPACITIVE FORWARD CAPACITIVE (LOSS OF FIELD) REVERSE RESISTIVE + FORWADRD CAPACITIVE REVERSE RESISTIVE + FORWARD CAPACITIVE REVERSE RESISTIVE
N = +210o (-150O) REVERSE RESISTIVE + FORWARD INDUCTIVE N = +240o (-120O) REVERSE RESISTIVE + FORWARD INDUCTIVE N = +270o (-90O) N = +300o (-60O) N = +330o (-30O) FORWARD INDUCTIVE FORWARD INDUCTIVE + FORWARD RESISTIVE FORWARD INDUCTIVE + FORWARD RESISTIVE
GENERATOR PROTECTION
Z
NORMAL
LOSS OF FIELD
GENERATOR PROTECTION
Z
NORMAL
R
K1
LOSS OF FIELD
K2
GENERATOR PROTECTION
REVERSE POWER GENERATORS GENERATOR WILL BECOME MOTOR HARMFUL TO THE PRIME MOVER ( STEAM TURBINE WILL OVER HEAT) (DIESEL ENGINE WILL EXPLODE DUE TO UNBURNT FUEL) (HYDRAULIC TUBINE WILL HAVE CAVITATION)
GENERATOR PROTECTION
INADVERTANT ENERGISATION - APPLICATION OF FULL VOLTAGE AT STANDSTILL COASTING TO STOP BEFORE SYNCHRONISM - PRESENCE OF UNBALANCE VOLTAGE DUE TO FLASH OVER AT IONE OR TWO POLES OF BREAKER
GENERATOR FORCED TO START AS INDUCTION MOTOR RESULTING IN MECHANICAL DAMAGES TO PRIME MOVER AND EXCESSIVE HEATING IN THE ROTOR
GENERATOR PROTECTION
V/Hz PROTECTION - INCORRECT VOLTAGE REGULATOR ACTION - LOAD THROW - OFF - SUDDEN OVER VOLTAGE / OVER FREQUENCY
GENERATOR PROTECTION PACKAGES VOLTAGE MV11 MND11 MVP-01 DIFFERENTIAL MD32-G SC14S ROTOR UBO/CR LOAD SHARING RRS
SYNCHRONISING SCM21 / SPM21 ISLANDING UFD34 UM30 MW33 LOAD SHEDDING UFD34 MW33 MX7/5 REX-8
BUS-1
BC1
PT1
L S R L S R
BUS-2
BC2
BUS-3
B1
-
B2 PT2
L L S S R R
B3
PT3
L S R L S R
CT1
CT2
CT3
G1
G2
G3
GRID INCOMER TRANSFORMER REVERSE POWER RELAY LOW FORWARD POWER RELAY UNDER VOLTAGE RELAY DIRECTIONAL O/C + E/F RELAY
dF/dT RELAY UNDER FREQ. RELAY OVER FREQ. RELAY VECTOR SURGE RELAY
DG
PLANT LOADS
Fig. -2
SYNCHRONISATION OF GENERATORS
SYNCHRONISING IS THE PROCESS OF ELECTRICALLY CONNECTING TWO AC POWER SOURCES WITH ROTATING MACHINES WITHOUT ANY DISTURBANCE TO EXISTING SYSTEM AND WITHOUT ANY DAMAGE TO THE EXISTING SYSTEM
SYNCHRONISATION
SINGLE GENERATOR TO A BUS (DEAD BUS / LIVE BUS SYNCH.) MULTIPLE GENERATORS TO A BUS (SIZE, VINTAGE, RESPONSE TIMES) AUTO CHANGEOVER IN BUS CONNECTIONS MANUAL & AUTO SYNCHRONISATION REVERSE SYNCHRONISATION
SYNCHRONISING OF GENERATORS
COMMON BUS
B1
PT1 SCM 21
PT2
B2
G1
G2
PHASE ANGLE
VOLTAGE
ADJUSTABLE SETTINGS FOR (F, (V, (E MINIMUM V,F FOR CB CLOSURE DEAD BUS / DEAD LINE SELECTION CB CLOSURE ONLY IF E IS DECREASING BREAKER OPERATING TIME MINIMUM RECLOSING TIME 2LINE + 1 BUS CONFIGURATION U/V + O/V PROTECTION SYNCHRONISING TROLLEY
IN ADDITION TO SCM21 FEATURES: INC / DEC PULSES FOR GOVERNOR INC / DEC PULSES FOR AVR ADJUSTABLE PULSE WIDTH PULSES PROPORTIONAL TO (F, (V KICKER PULSE CONTROL ANTI MOTORING CONTROL
REVERSE SYNCHRONISATION
DG PLANT LOADS
PROTn. RELAY
DIFF. RELAY
SYNCH. RELAY
SCHEME FOR : AUTO START, SYNCH.& LOAD SHARING GRID ISLANDING & LOAD SHEDDING PC SYSTEM WITH SOFTWARE COMMUNICATION SOFTWARE FOR CENTRALISED DAS AND CONTROL
Fig.-3