INSTALLATION AND MAINTENANCE INSTRUCTIONS

I56-3438-001
12 Clintonville Road, Northford, CT 06472
203.484.7161; Fax: 203.484.7118
SK-Relay www.silentknight.com

Specifications
Normal Operating Voltage: 15 to 32 VDC
Maximum Current Draw: 6.5 mA (LED on)
Average Operating Current: 230μA direct poll; 255μA group poll
EOL Resistance: Not used
Temperature Range: 32˚F to 120˚F (0˚C to 49˚C)
Humidity: 10% to 93% Non-condensing
Dimensions: 41/2˝ H × 4˝ W × 11/4˝ D (Mounts to a 4˝ square by 21/8˝ deep box.)
Accessories: SMB500 Electrical Box
Before Installing Mounting
This information is included as a quick reference installation guide. Refer to The SK-Relay mounts directly to 4-inch square electrical boxes (see Figure
the appropriate Silent Knight control panel installation manual for detailed 2A). The box must have a minimum depth of 21/8 inches. Surface mounted
system information. If the modules will be installed in an existing operational electrical boxes (SMB500) are available from Silent Knight.
system, inform the operator and local authority that the system will be tem- Figure 2A. Module mounting Figure 2B:
porarily out of service. Disconnect power to the control panel before installing with barrier:
the modules.
NOTICE: This manual should be left with the owner/user of this equipment.
General Description
The SK-Relay is intended for use in intelligent, two-wire systems where the in-
dividual address of each module is selected using the built-in rotary switches.
It allows a compatible control panel to switch discrete contacts by code com-
mand. The relay contains two isolated sets of Form-C contacts, which operate
as a DPDT switch and are rated in accordance with the table in the manual.
Circuit connections to the relay contacts are not supervised by the module.
The module also has a panel controlled LED indicator.
Compatibility Requirements
To ensure proper operation, this module shall be connected to a compatible
Silent Knight system control panel (list available from Silent Knight).
Figure 1. Controls and indicators:

C1070-00
Wiring
NOTE: All wiring must conform to applicable local codes, ordinances, and reg-
ulations. When using control modules in nonpower limited applications, the
CB500 Module Barrier must be used to meet UL requirements for the separa-
tion of power-limited and nonpower-limited terminals and wiring. The barrier
must be inserted into a 4˝ × 4˝ × 21/8˝ junction box, and the control module
must be placed into the barrier and attached to the junction box (Figure 2A).
The power-limited wiring must be placed into the isolated quadrant of the
module barrier (Figure 2B).
1. Install module wiring in accordance with the job drawings and appropri-
ate wiring diagrams.
2. Set the address on the module per job drawings.
3. Secure module to electrical box (supplied by installer), as shown in
C1071-00 Figure 2A.
SK-470-001 1 I56-3438-001
Relay Contact Ratings:
CURRENT RATING MAXIMUM VOLTAGE LOAD DESCRIPTION APPLICATION
3A 30 VDC Resistive Non-coded
2A 30 VDC Resistive Coded
.9 A 110 VDC Resistive Non-coded
.9 A 125 VDC Resistive Non-coded
.5 A 30 VDC Inductive (L/R=5ms) Coded
1A 30 VDC Inductive (L/R=2ms) Coded
.3 A 125 VAC Inductive (PF=.35) Non-coded
1.5 A 25 VAC Inductive (PF = .35) Non-coded
.7 A 70.7 VAC Inductive (PF=.35) Non-coded
2A 25 VAC Inductive (PF=.35) Non-coded

WARNING
All relay switch contacts are shipped in the standby state (open) state, but may have transferred to the activated (closed) state during shipping. To ensure that
the switch contacts are in their correct state, modules must be made to communicate with the panel before connecting circuits controlled by the module.

Figure 3. Relay module wiring diagram:


CONNECT MODULES TO LISTED COMPATIBLE
CONTROL PANELS ONLY
)–( )–(
TO NEXT FROM PANEL OR
)+( )+( PREVIOUS DEVICE
DEVICE

CONTROL SIGNAL LINE CIRCUIT (SLC)


MODULE 32 VDC MAX.
TWISTED PAIR
IS RECOMMENDED

)–(
RELAY COMMON 2
)+( IF ANY WIRING TO TERMINALS 4 – 10 IS NONPOWER
NORMALLY CLOSED 2
LIMITED, THE CB500 BARRIER IS REQUIRED. THE CB500
NORMALLY OPEN 2 INCLUDES A NONPOWER LIMITED LABEL, WHICH MUST
RELAY COMMON 1 UNUSED BE PLACED OVER THE POWER LIMITED TERMINAL
NORMALLY CLOSED 1 NORMALLY OPEN 1 INFORMATION ON THE NAMEPLATE LABEL.

MODULE DOES NOT SUPERVISE CONTROLLED CIRCUITS

*NOTE: ANY FAULT IN THE POWER SUPPLY IS LIMITED TO THAT ZONE AND DOES NOT RESULT IN A FAULT IN A SEPARATE ZONE.

C0946-00

SK-470-001 2 I56-3438-001
©2009 Honeywell International Inc.