HV HRC (high-voltage high rupturing capacity) fuses are used for short circuit protection in high-voltage switchgear for the 50 to 60 Hz frequency range Distribution transformers up to 2000 kVA High-voltage motors up to 3 MW Capacitors up to1200 kvar MV voltage transformers Cable feeders
HV HRC Fuse
HV HRC Fuse
Technical characteristics
HV HRC Fuses 3GD are specially suitable for the short circuit protection of supply system units. Properties: Short circuit currents do not rise to their peak levels By virtue of the very short pre-arcing times ts< 5 ms, even short circuit currents of more than 20 to 25 times the rated current of the fuse are cut off The current limiting effect of HV HRC fuses enables the dimensioning of apparatus with lower short circuit rating (e.g. switching devices, instrument transformers, cabel)
HV HRC Fuse
Rated voltage (kV) Rated current (A) 3.6 / 7.2 12 24 36 up to 250 up to 160 up to 100 up to 40
HV HRC Fuse
HV HRC Fuse
Benefits
No ageing Tightness
Silver melting conductors Magneform process - the most reliable closing technique to seal the housing - double sealing of the striker pin system - special plastic foil - also suitable for outdoor applications Thermal overload protection of the switch-fuse combination Due to optimized melting conductor construction
High reliability
HV HRC Fuse
3 4 6 5 7 8 9 1 10 11
1 2 3 4
5 6 7 8
HV HRC Fuse
Fault current i flows Melting conductor heats up Melting conductor evaporates Arc ignites ZB Arc-voltage increases with the number of partial arcs until the arc voltage becomes higher than the source voltage UG Internal arc in the fuse extinguishes
ULB i
G
UG ULB = Arc voltage UG = Source voltage
HV HRC Fuse
Operation
Short circuit current begins to flow
Melting of all main melting conductors Melting of the secondary fusible element Release of the striker pin
iD
tL tS
HV HRC Fuse
Force
Release of the striker pin of the 3GD fuse link prevents a thermal destruction of the fuse when using a switch-fuse combination, in the event of fault currents >In and <Imin
HV HRC Fuse
reforming forces
With a magnetic pressing process we guarantee resistance to ageing and complete sealing against penetration of humidity for the whole lifetime
HV HRC Fuse
Overvoltages
10 ms
2. 2. 20.8 kV
Up = 20.8 kV
Up : Test voltage u = 45 kV ts = 3.8 ms tL = 6.5 ms Ip = 1.32 kA u : Switching overvoltage Ip : Test current (RMS-value) iD : Cut-off current ts : Pre-arcing time tL : Arc extinction time iD = 1.45 kA
HV HRC Fuse