Victaulic® FireLock™ Series FL-ECLH

Extended Coverage, Quick Response


Pendent and Recessed Pendent Sprinklers K5.6 (8.1),
K8.0 (11.5), K11.2 (16.2), K14.0 (20.2) 42.01

1.0  PRODUCT DESCRIPTION

QUICK RESPONSE EXTENDED COVERAGE PENDENT SPRINKLERS


SIN V5614 V3428 V3412 V3414
ORIENTATION PENDENT PENDENT PENDENT PENDENT
K-FACTOR1 5.6 Imp./8.1 S.I. 8.0 Imp./11.5 S.I. 11.2 Imp. /16.2 S.I. 14.0 Imp./20.2 S.I.
3/4" NPT/ 20mm BSPT/ 3/4" NPT/ 20mm BSPT/ 3/4" NPT/ 20mm BSPT/
CONNECTION 1/2” NPT/15mm BSPT
IGS Grooved IGS Grooved IGS Grooved
MAX. WORKING PRESSURE 175 psi (1200 kPa) 175 psi (1200 kPa) 175 psi (1200 kPa) 175 psi (1200 kPa)
GLOBE RE-DESIGNATION GL5614 – – –
GLOBE EQUIVALENT – GL8109 GL1112 –

QUICK RESPONSE EXTENDED COVERAGE RECESSED PENDENT SPRINKLERS


SIN V5614 V3428 V3412 V3414
ORIENTATION PENDENT PENDENT PENDENT PENDENT
K-FACTOR1 5.6 Imp./8.1 S.I. 8.0 Imp./11.5 S.I. 11.2 Imp. /16.2 S.I. 14.0 Imp./20.2 S.I.
CONNECTION 1/2” NPT/15mm BSPT 3/4" NPT/ 20mm BSPT 3/4" NPT/ 20mm BSPT 3/4" NPT/ 20mm BSPT
MAX. WORKING PRESSURE 175 psi (1200 kPa) 175 psi (1200 kPa) 175 psi (1200 kPa) 175 psi (1200 kPa)
ESCUTCHEON Recessed Recessed Recessed Recessed
GLOBE RE-DESIGNATION GL5614 – – –
GLOBE EQUIVALENT – GL8109 GL1112 –

AVAILABLE WRENCHES
SPRINKLER V56-2 Recessed V56 Open End V34 Recessed V34 Open End
PENDENT ■ ■ ■ ■

Factory Hydrostatic Test: 100% @ 500 psi/3447 kPa/34 bar


Min. Operating Pressure: UL/FM: 7psi/48 kPa/.5 bar
Temperature Rating: See tables in section 2.0
1 For K-Factor when pressure is measured in bar, multiply S.I. units by 10.0.

ALWAYS REFER TO ANY NOTIFICATIONS AT THE END OF THIS DOCUMENT REGARDING PRODUCT INSTALLATION, MAINTENANCE OR SUPPORT.

victaulic.com
42.01 16377 Rev A Updated 02/2021 © 2021 Victaulic Company. All rights reserved.
1
victaulic.com

2.0 CERTIFICATION/LISTINGS

SIN V5614
Nominal K Factor Imperial 5.6
Nominal K Factor S.I.2 8.1
Installation Type Pendent Recessed Pendent
Maximum Approved Approved
Coverage Area Temperature Temperature Minimum
Width x Length Flow Pressure Ratings Adjustment Flow Pressure Ratings Spacing
Ft. x Ft Listing GPM PSI In GPM PSI Ft.
mxm Agency Response L/min kPa F°/C° Response mm L/min kPa F°/C° m
135°F/57°C 135°F/57°C
16 x 16 26 21.5 155°F/68°C 1/2 and 3/4 26 21.5 155°F/68°C
UL QR QR
4.9 x 4.9 98 148 175°F/79°C 15 and 20 98 148 175°F/79°C
200°F/93°C 200°F/93°C
135°F/57°C 135°F/57°C 8.0
18 x 18 33 34.7 155°F/68°C 1/2 and 3/4 33 34.7 155°F/68°C 2.4
UL QR QR
5.5 x 5.5 125 239 175°F/79°C 15 and 20 125 239 175°F/79°C
200°F/93°C 200°F/93°C
20 x 20 40 51 1/2 and 3/4 40 51
UL QR 135°F/57°C QR 135°F/57°C
6.1 x 6.1 151 352 15 and 20 151 352

SIN V3428
Nominal K Factor Imperial 8.0
Nominal K Factor S.I.2 11.5
Installation Type Pendent Recessed Pendent
Maximum Approved Approved
Coverage Area Temperature Temperature Minimum
Width x Length Flow Pressure Ratings Adjustment Flow Pressure Ratings Spacing
Ft. x Ft Listing GPM PSI In GPM PSI Ft.
mxm Agency Response L/min kPa F°/C° Response mm L/min kPa F°/C° m
135°F/57°C 135°F/57°C
16 x 16 26 10.6 155°F/68°C 1/2 and 3/4 26 10.6 155°F/68°C
UL QR QR
4.9 x 4.9 98 731 175°F/79°C 15 and 20 98 731 175°F/79°C
200°F/93°C 200°F/93°C
135°F/57°C 135°F/57°C
18 x 18 33 17.0 155°F/68°C 1/2 and 3/4 33 17.0 155°F/68°C 8.0
UL QR QR
5.5 x 5.5 125 117 175°F/79°C 15 and 20 125 117 175°F/79°C 2.4
200°F/93°C 200°F/93°C
135°F/57°C 135°F/57°C
20 x 20 40 25.0 155°F/68°C 1/2 and 3/4 40 25.0 155°F/68°C
UL QR QR
6.1 x 6.1 151 172 175°F/79°C 15 and 20 151 172 175°F/79°C
200°F/93°C 200°F/93°C

2 For K-Factor when pressure is measured in bar, multiply S.I. units by 10.0.

NOTES
• Listings and approval as of printing.

42.01 16377 Rev A Updated 02/2021 © 2021 Victaulic Company. All rights reserved.

victaulic.com 2
victaulic.com

2.0  CERTIFICATION/LISTINGS (CONTINUED)


SIN V3412
Nominal K Factor Imperial 11.2
Nominal K Factor S.I.2 16.2
Installation Type Pendent Recessed Pendent
Maximum Approved Approved
Coverage Area Temperature Temperature Minimum
Width x Length Flow Pressure Ratings Adjustment Flow Pressure Ratings Spacing
Ft. x Ft Listing GPM PSI In GPM PSI Ft.
mxm Agency Response L/min kPa F°/C° Response mm L/min kPa F°/C° m
135°F/57°C 135°F/57°C
16 x 16 30 7 155°F/68°C 1/2 30 7 155°F/68°C 8.0
UL QR QR
4.9 x 4.9 115 50 175°F/79°C 15 115 50 175°F/79°C 2.4
200°F/93°C 200°F/93°C
16 x 16 30 7 135°F/57°C 1/2 30 7 10.0
FM QR QR 135°F/57°C
4.9 x 4.9 115 50 155°F/68°C 15 115 50 3.0
135°F/57°C 135°F/57°C
18 x 18 33 9 155°F/68°C 1/2 26 10.6 155°F/68°C 8.0
UL QR QR
5.5 x 5.5 125 60 175°F/79°C 15 98 73 175°F/79°C 2.4
200°F/93°C 200°F/93°C
18 x 18 33 9 135°F/57°C 1/2 33 9 10.0
FM QR QR 135°F/57°C
5.5 x 5.5 125 60 155°F/68°C 15 125 60 3.0
135°F/57°C
20 x 20 40 13 155°F/68°C 1/2 40 13 135°F/57°C 8.0
UL QR QR
6.1 x 6.1 150 90 175°F/79°C 15 150 90 175°F/79°C 2.4
200°F/93°C
20 x 20 40 13 135°F/57°C 1/2 40 13 10.0
FM QR QR 135°F/57°C
6.1 x 6.1 150 90 155°F/68°C 15 150 90 3.0

SIN V3414
Nominal K Factor Imperial 14.0
Nominal K Factor S.I.2 20.2
Installation Type Pendent Recessed Pendent
Maximum Approved Approved
Coverage Area Temperature Temperature Minimum
Width x Length Flow Pressure Ratings Adjustment Flow Pressure Ratings Spacing
Ft. x Ft Listing GPM PSI In GPM PSI Ft.
mxm Agency Response L/min kPa F°/C° Response mm L/min kPa F°/C° m
135°F/57°C 135°F/57°C
18 x 18 37 7 155°F/68°C 1/2 and 3/4 37 7 155°F/68°C
UL QR QR
5.5 x 5.5 140 50 175°F/79°C 15 and 20 140 50 175°F/79°C
200°F/93°C 200°F/93°C 12.0
135°F/57°C 135°F/57°C 3.7
20 x 20 40 8 155°F/68°C 1/2 and 3/4 40 8 155°F/68°C
UL QR QR
6.1 x 6.1 150 60 175°F/79°C 15 and 20 150 60 175°F/79°C
200°F/93°C 200°F/93°C

2 For K-Factor when pressure is measured in bar, multiply S.I. units by 10.0.

NOTES
• Listings and approval as of printing.

42.01 16377 Rev A Updated 02/2021 © 2021 Victaulic Company. All rights reserved.

victaulic.com 3
victaulic.com

3.0  SPECIFICATIONS – MATERIAL


Deflector: Bronze 7⁄16"/11 mm
Bulb Nominal Diameter: 3.0mm Nominal make-in

Load Screw: Bronze Frame


Pip Cap: Bronze Pip cap and
spring seal 2¼"/
Spring Seal Assembly: PTFE coated Beryllium nickel Bulb 59 mm
alloy Load screw
Deflector
Frame: Brass
Lodgement Spring: Stainless steel 1¼"/
31 mm
Installation Wrench: Ductile iron
V5614
Sprinkler Frame Finishes:
• Plain brass ½"/13 mm
Nominal make-in
• Chrome plated
Frame
• White polyester painted3, 4
Lodgement spring
• Flat black polyester painted3, 4 Pip cap and 2½"/
spring seal 63 mm
• Custom polyester painted3, 4 Bulb
Load screw
• VC-2505 Deflector
3 Not available on the Intermediate Level Style Pendent.
4 UL Listed for corrosion resistance. 13⁄8"/
5 UL Listed and FM Approved for corrosion resistance. 36 mm

NOTE V3428, V3412, V3414


• For cabinets and other accessories refer to separate sheet.

42.01 16377 Rev A Updated 02/2021 © 2021 Victaulic Company. All rights reserved.

victaulic.com 4
victaulic.com

4.0 DIMENSIONS
23⁄8"/60 mm
2"/51 mm
Hole in ceiling

Typical ceiling
1⁄8"/3 mm Min.
7⁄8"/22 mm Max.

11⁄8"/29 mm Min.
17⁄8"/48 mm Max. Finished surface

215⁄16"/75 mm

V5614

23⁄8"/60 mm
2"/51 mm
Hole in ceiling

7⁄8"/22 mm Max. (¾" Adj.)


5⁄8"/16 mm Max. (½" Adj.)
1⁄8"/3 mm Min.
Typical ceiling

17⁄8"/47 mm Max. Finished surface


13⁄8"/34 mm Min. (½" Adj.)
11⁄8"/29 mm Min. (¾" Adj.)

215⁄16"/75 mm

V3428, V3412, V3414

5.0 PERFORMANCE
Sprinkler is to be installed and designed as per NFPA, FM Datasheets, or any local standards.

42.01 16377 Rev A Updated 02/2021 © 2021 Victaulic Company. All rights reserved.

victaulic.com 5
victaulic.com

6.0 NOTIFICATIONS

WARNING
• Read and understand all instructions before attempting to install
any Victaulic products.
• Always verify that the piping system has been completely depressur-
ized and drained immediately prior to installation, removal, adjust-
ment, or maintenance of any Victaulic products.
• Wear safety glasses, hardhat, and foot protection.
Failure to follow these instructions could result in death or serious
personal injury and property damage.

• These products shall be used only in fire protection systems that are designed and installed in accordance with
current, applicable National Fire Protection Association (NFPA 13, 13D, 13R, etc.) standards, or equivalent
standards, and in accordance with applicable building and fire codes. These standards and codes contain
important information regarding protection of systems from freezing temperatures, corrosion, mechanical
damage, etc.
• The installer shall understand the use of this product and why it was specified for the particular application.
• The installer shall understand common industry safety standards and potential consequences of improper
product installation.
• It is the system designer's responsibility to verify suitability of materials for use with the intended fluid media
within the piping system and external environment.
• The material specifier shall evaluate the effect of chemical composition, pH level, operating temperature,
chloride level, oxygen level, and flow rate on materials to confirm system life will be acceptable for the intended
service.
Failure to follow installation requirements and local and national codes and standards could compromise system
integrity or cause system failure, resulting in death or serious personal injury and property damage.

7.0  REFERENCE MATERIALS


Ratings: All glass bulbs are rated for temperatures from -67°F/-55°C.
1-40: Victaulic FireLock™ Automatic Sprinklers Installation and Maintenance Instructions
I-V9: Style V9 Victaulic FireLock™ IGS™ Installation-Ready™ Sprinkler Coupling Installation Instructions

User Responsibility for Product Selection and Suitability Note


Each user bears final responsibility for making a determination as to the suitability of This product shall be manufactured by Victaulic or to Victaulic specifications. All products
Victaulic products for a particular end-use application, in accordance with industry to be installed in accordance with current Victaulic installation/assembly instructions.
standards and project specifications, as well as Victaulic performance, maintenance, Victaulic reserves the right to change product specifications, designs and standard
safety, and warning instructions. Nothing in this or any other document, nor any verbal equipment without notice and without incurring obligations.
recommendation, advice, or opinion from any Victaulic employee, shall be deemed to Installation
alter, vary, supersede, or waive any provision of Victaulic Company's standard conditions Reference should always be made to the Victaulic installation handbook or installation
of sale, installation guide, or this disclaimer. instructions of the product you are installing. Handbooks are included with each shipment
Intellectual Property Rights of Victaulic products, providing complete installation and assembly data, and are available
No statement contained herein concerning a possible or suggested use of any material, in PDF format on our website at www.victaulic.com.
product, service, or design is intended, or should be constructed, to grant any license Warranty
under any patent or other intellectual property right of Victaulic or any of its subsidiaries Refer to the Warranty section of the current Price List or contact Victaulic for details.
or affiliates covering such use or design, or as a recommendation for the use of such
material, product, service, or design in the infringement of any patent or other intellectual Trademarks
property right. The terms “Patented” or “Patent Pending” refer to design or utility patents Victaulic and all other Victaulic marks are the trademarks or registered trademarks of
or patent applications for articles and/or methods of use in the United States and/or other Victaulic Company, and/or its affiliated entities, in the U.S. and/or other countries.
countries.

42.01 16377 Rev A Updated 02/2021 © 2021 Victaulic Company. All rights reserved.

victaulic.com 6

You might also like