DAYLIGHT OPTIMIZATION IN

AN OFFICE BUILDING THROUGH


ATRIUM IMPROVEMENTS
Thiago dos Santos Ferreira

Master thesis in Energy-efficient and Environmental Buildings


Faculty of Engineering | Lund University
Lund University
Lund University, with eight faculties and a number of research centres and specialized
institutes, is the largest establishment for research and higher education in Scandinavia. The
main part of the University is situated in the small city of Lund which has about 112 000
inhabitants. A number of departments for research and education are, however, located in
Malmö. Lund University was founded in 1666 and has today a total staff of 6 000 employees
and 47 000 students attending 280 degree programmes and 2 300 subject courses offered by
63 departments.

Master Programme in Energy-efficient and Environmental Building Design

This international programme provides knowledge, skills and competencies within the area
of energy-efficient and environmental building design in cold climates. The goal is to train
highly skilled professionals, who will significantly contribute to and influence the design,
building or renovation of energy-efficient buildings, taking into consideration the architecture
and environment, the inhabitants’ behaviour and needs, their health and comfort as well as
the overall economy.

The degree project is the final part of the master programme leading to a Master of Science
(120 credits) in Energy-efficient and Environmental Buildings.

Examiner: Jouri Kanters (Energy and Building Design)

Supervisor: Marie-Claude Dubois (Energy and Building Design)

Co-supervisor: Iason Bournas (Energy and Building Design)

Keywords: atria, daylight, optimization, office, atrium

Thesis: EEBD - 18/05


Daylight Optimization in an office building through atrium improvements

Abstract
Daylighting has become a fundamental measure not only to decrease the heating energy
demand in buildings, but also to provide good indoor comfort for the occupants. Atria have
been implemented in buildings since old times as a space to foster interaction and provide
indoor comfort through ventilation and daylight. However, the implementation of this feature
can be complex if good natural light levels are to be achieved, especially in tall buildings.
Bearing that in mind, this thesis reviewed the studies that were developed in the field of
daylighting in atria and proposed an investigation about the atrium parameters that affected
the most the daylight conditions in a building project located in Gothenburg. In order to
evaluate the current atrium and propose modifications that fit the architectural design,
simulations were carried out in different programs. This evaluation concentrated in two main
aspects of the building, which were the geometry and the wall reflectance values. Due to the
size of the study case, the evaluation grid is located only along the atrium and the results are
translated in area, so it is possible to draw a comparison between the different modifications
proposed. Results showed that the geometrical volume alterations were the ones to increase
the most the daylight quantity in the rooms along the atrium. Nonetheless, some of the
modifications on the original project were followed by a floor area addition to compensate
the losses brought by the alterations, therefore daylighting and property value were also
analyzed. Lastly, a few options were investigated when it comes to the daylight quantity in
each floor. Overall, the outcomes demonstrated that shifting the atrium characteristic from an
enclosed one to a semi-enclosed can double the daylight quantity in the adjacent rooms.
Daylight Optimization in an office building through atrium improvements

Acknowledgements
The author is extremely grateful for all the support, suggestions and guidance from Marie-
Claude Dubois. He also would like to thank Iason Bournas for the exchange of ideas, advices
and support. In addition, he is thankful for the study case provided by White Arkitekter, as
well as its aid regarding the hardware usage for simulation purposes. This longtime dream of
pursuing a Master Programme in an international renowned university would not be possible
without the support of the Swedish Institute, which provided a full scholarship for the author
studies in Sweden.
Daylight Optimization in an office building through atrium improvements

Table of content
Abstract ................................................................................................................................... 3
Acknowledgements ................................................................................................................. 4
Table of content ....................................................................................................................... 5
Table of figure ......................................................................................................................... 7
List of tables ............................................................................................................................ 8
Terminology ............................................................................................................................ 9
1 Introduction ................................................................................................................... 10
1.1 Background and problem motivation ...................................................................... 10
1.2 Aims and assumptions............................................................................................. 11
1.3 Limitations .............................................................................................................. 11
2 Atria in office buildings ................................................................................................ 12
2.1 Daylight in office buildings .................................................................................... 12
2.2 Daylight distribution in atria ................................................................................... 13
2.2.1 Geometry ......................................................................................................... 13
2.2.2 Atrium facades ................................................................................................. 16
2.2.3 Skylight aperture .............................................................................................. 18
2.3 Energy efficiency in atria ........................................................................................ 20
2.4 Summary ................................................................................................................. 22
3 Daylight criteria............................................................................................................. 23
3.1 Daylight factor ........................................................................................................ 23
3.1.1 Sky component................................................................................................. 24
3.2 Daylight autonomy and useful daylight illuminance .............................................. 25
3.3 Standards ................................................................................................................. 26
3.3.1 Leadership in Energy and Environmental Design (LEED).............................. 26
3.3.2 BREEAM ......................................................................................................... 27
3.3.3 Miljöbyggnad ................................................................................................... 27
3.3.4 Swedish and European regulations and standards ........................................... 27
4 Methodology ................................................................................................................. 29
4.1 Sahlgrenska Life Science Center ............................................................................ 29
4.1.1 Location ........................................................................................................... 29
4.1.2 Geometry ......................................................................................................... 30
4.2 Simulation tools and workflow ............................................................................... 31
4.2.1 Rhinoceros ....................................................................................................... 32
4.2.2 Grasshopper ..................................................................................................... 32
4.2.3 Honeybee and Ladybug ................................................................................... 32
4.2.4 Radiance and DAYSIM ................................................................................... 32
4.3 Daylight model ........................................................................................................ 33
4.3.1 Simulation input and parameters...................................................................... 33
4.3.2 Parametric scheme ........................................................................................... 34
4.3.3 Analysis grid .................................................................................................... 38
5 Results ........................................................................................................................... 39
5.1 Base cases ............................................................................................................... 39
5.1.1 sDA and area of DF above 1%......................................................................... 40
5.1.2 ADF, DF median and dynamic daylight metrics ............................................. 41
5.2 Parametric study ...................................................................................................... 43
5.2.1 Effect of geometry ........................................................................................... 43
Daylight Optimization in an office building through atrium improvements

5.2.1.1 Spatial daylight autonomy (sDA) .............................................................. 43


5.2.1.2 Area of DF above 1% ................................................................................ 49
5.2.1.3 ADF, DF median and dynamic daylight metrics ....................................... 52
5.2.2 Effect of light reflectance................................................................................. 55
5.2.2.1 sDA and area of DF above 1% .................................................................. 55
5.2.2.2 ADF, DF median and dynamic daylight metrics ....................................... 56
6 Discussion ..................................................................................................................... 57
6.1 Base cases ............................................................................................................... 57
6.2 Parametric study ...................................................................................................... 58
6.2.1 Effect of geometry ........................................................................................... 58
6.2.2 Effect of light reflectance................................................................................. 60
7 Conclusions ................................................................................................................... 61
General conclusions .......................................................................................................... 62
Future studies and limitations............................................................................................ 63
Summary................................................................................................................................ 64
References ............................................................................................................................. 65
Appendix A ........................................................................................................................... 69
Daylight Optimization in an office building through atrium improvements

Table of figure
Figure 1: Atrium well index (WI).......................................................................................... 14
Figure 2: Well efficiency relation.......................................................................................... 15
Figure 3: Types of atria. ........................................................................................................ 20
Figure 4: Angle of visible sky in a building section. ............................................................. 24
Figure 5: Location and surrounding context of the study case. ............................................. 30
Figure 6: Schematic plan and section. ................................................................................... 31
Figure 7: Current features of the base case............................................................................ 31
Figure 8: Thesis work flow.................................................................................................... 32
Figure 9: Tower option. ......................................................................................................... 34
Figure 10: Combination of wings option. .............................................................................. 35
Figure 11: Counter and clockwise addition option. ............................................................... 36
Figure 12: Wing splaying option. .......................................................................................... 37
Figure 13: LRV modification option. .................................................................................... 37
Figure 14: Grid combination for each case. .......................................................................... 38
Figure 15: Grid area and area of DF above 1%. .................................................................... 40
Figure 16: ADF, sDA, DF median and UDI autonomous per base case. .............................. 41
Figure 17: sDA for cases a1 to a3, b1 to b3 and c1 to c3. ..................................................... 44
Figure 18: sDA for cases a1+2 to c3+2+1. ............................................................................ 46
Figure 19: sDA for cases a to abc. ......................................................................................... 48
Figure 20: DF area and area losses/gains for the wing suppression arrangements................ 49
Figure 21: DF area and area losses/gains for the wall splaying options. ............................... 51
Figure 22: ADF, sDA, DF median and UDI autonomous for case a1, b1 and c1. ................ 52
Figure 23: ADF, sDA, DF median and UDI autonomous from cases a to abc...................... 54
Figure 24: sDA for LRV cases. ............................................................................................. 55
Figure 25: ADF, sDA, DF median and UDI autonomous for LRV cases. ............................ 56
Figure 26: Geometry and LRV modifications. ...................................................................... 58
Daylight Optimization in an office building through atrium improvements

List of tables
Table 1: Average daylight factor for office buildings. .......................................................... 23
Table 2: Conversion from vertical daylight factor (Dv) to vertical sky component (Dsv).... 25
Table 3: UDI thresholds. ....................................................................................................... 26
Table 4: Lighting requirements for interior areas, tasks and activities.................................. 26
Table 5: Rendering quality adopted for the thesis simulations.............................................. 33
Table 6: LRV and LTV of the materials adopted for the simulations ................................... 33
Daylight Optimization in an office building through atrium improvements

Terminology
AR Adjacent rooms
ADF Average daylight factor
BBR Boverkets byggregler
BREEAM Building Research Establishment Environmental Method
CIE Commision Internationale de l’Eclairage
IES Illuminating Engineering Society of North America
LEED Leadership in Energy and Environmental Design
CBDM Climate-based Daylight Modelling
DA Daylight autonomy
DF Daylight factor
ERC Externally reflected component
IRC Internally reflected component
MRD Maximum room depth
PAR Plan aspect ratio
SAR Section aspect ratio
SC Sky component
VDF Vertical daylight factor
VSC Vertical sky component
LRV Light reflectance value
LTV Light transmittance value
WE Well efficiency
WI Well index
WID Well indexed depth
WWR Window to wall ratio
UDI Useful daylight illuminance
USGBC United States Green Building Council
Daylight Optimization in an office building through atrium improvements

1 Introduction
1.1 Background and problem motivation
The construction sector accounts for 30% to 40% of the primary energy use worldwide, a
factor that states the real estate market potential to foster a sustainable development with low
energy demand (United Nations Environment Programme, 2007). According to Guzenski
(2011), as the society evolves, buildings should improve at the same pace to bear the possible
energy demand increase caused by existing buildings with low quality envelopes. In this
sense, the architectural design has always been the key factor, not only to diminish the energy
demand for cooling and heating, but also to improve the indoor environmental quality by
applying passive design strategies at the early design stages. In cold climates, heating and
electrical lighting have the largest share of the building energy demand, thus increasing the
daylight component, especially in new buildings, is an effective approach to decrease the
energy need and increase the user comfort (Wong, 2017).

The proper design of buildings coupled with innovative technologies to harvest natural light
properly into the working zones might bring the electrical lighting need to considerably lower
levels (Cammarano et al., 2015). Furthermore, daylight can increase the occupant’s
satisfaction and productivity (Lim, et al. 2017). Better color rendering, as well as the proper
regulation of the circadian cycle are also essential benefits of natural light. However, office
buildings located in dense urban zones, such as city centers and economical districts, can be
a liability to daylighting strategies. Due to the proximity of buildings, the sky component can
be only used on upper floors, hence leaving the bottom floors underlit and dependent on
electrical lighting (Capeluto, 2003). In addition to providing side windows to fetch
daylighting into the building, atria have been largely implemented in different parts of the
world as a strategy. They provide not only natural light indoors, but also generate better
comfort conditions, thus turning these places into pleasant environments where interaction
between occupants are fostered (Samant, 2011).

With the increased awareness about sustainable practices in the construction market,
developers have been launching architectural competitions in the recent years to be able to
choose the projects that suit their needs in the best possible way. However, this type of
competition can generate a series of non-feasible projects construction-wise, as well as further
issues regarding legislation requirements (Sørensen et al., 2015). Since many of the
competitions are set to bring ideas to a specific aim rapidly, the proposed projects lack analysis
and therefore many fundamental aspects are left behind, such as the adaptability to the current
microclimate and even the local culture and values. One aspect that is often neglected at the
competition entry level is daylighting, therefore it is not rare that the proposals do not meet
the topic’s standards and regulations afterwards.

This thesis aims to propose possible improvements in an atrium of an office building which
was submitted through a design competition. The project was previously assessed by White

10
Daylight Optimization in an office building through atrium improvements

Arkitekter and showed that the current daylight conditions in the atrium adjacent rooms were
insufficient to meet the Boverket’s Building Regulation (BBR) due to the building’s height
and its deep plans. The case study is located in Gothenburg in a rather dense cluster of
buildings, which leads to a series of challenges when regulations are to be respected. The
investigated building is part of an under-development Life Science Center, which entails in a
diverse range of typologies such as a research center, a hospital and a business center.

1.2 Aims and assumptions


The utilization of atria is a valid and great strategy to increase daylighting in a building,
especially in cases where the city block configuration fosters the creation of deeper plans,
thus compromising the visual quality of the interior spaces. However, a proper atrium design
is dependent on various factors such as geometry, height, surface reflectance, skylight and
window aperture for example. The main objective of this thesis is to investigate how each
parameter can influence the natural light harvesting into the adjacent rooms that face the
atrium. Bearing this in mind, two research questions shape the framework of this thesis:

 Which parameter influences daylight quantity most significantly in the adjacent


rooms?
 What atrium design would best suit the study case, considering the proposed design
and its surroundings?

Considering both questions, some hypotheses were inferred based on the literature review,
which pointed out some trends according to various studies. The main hypotheses are stated
below:

 The atrium geometry is the parameter that most significantly affects the daylight
quantity in adjacent spaces.
 The light reflectance values might affect the daylight quantity in the atrium adjacent
spaces, however it has a limited impact on deep atria.

The simulations developed during the thesis project were structured so the above hypotheses
could be investigated.

1.3 Limitations
Although atria have a considerable impact on the energy balance of a given space or building,
this investigation focused only on how they influence daylighting distribution in the adjacent
rooms (AR). Internal partitions as well as possible obstructions are not considered in the
simulations. Moreover, metrics that evaluate the daylight quality are not investigated. The
thesis solely focuses on daylight levels.

11
Daylight Optimization in an office building through atrium improvements

2 Atria in office buildings


2.1 Daylight in office buildings
The use of daylight in office buildings is important to displace electric lighting and enhance
visual functions as well as occupants’ health. It increases the user comfort for general tasks
while reducing the electrical lighting demand and cooling loads during the summer season
(Chen and Wei, 2013). However, it is fundamental to consider balancing both good
daylighting levels and energy demand issues by wisely analyzing the orientation, the window-
to-wall ratio (WWR), the window head height, the material reflectance, the ceiling height and
the maximum room depth (MRD). By orienting the building towards north, for constructions
located at higher latitudes, the rooms are protected from the sunlight. On the other hand,
shading mechanisms to control overheating and possible glare effects become fundamental if
the spaces are orientated to the south direction.

The WWR also plays a fundamental role for the energy demand of buildings, as well as for
the daylight quality in the office spaces. Fully glazed facades are a liability in most cases, as
it is a source of thermal losses in cold climates and a source of heat gains in warm climates.
A sensitivity analysis using Radiance as the simulation tool and the Useful Daylight
Illuminance (UDI) as one of the metrics was conducted by Dubois and Flodberg (2013). They
found that the optimal WWR lied between 30% and 40%, showing that any additional glass
in the facade would create glare problems for the occupants. Moreover, the reflectance of the
surrounding walls was also assessed and according to the simulations, higher reflectance
values created a better level of uniformity.

The maximum room depth is especially important in working spaces, as it influences the user
ability to have an outdoor view, as well as the design of the electrical lighting system. A
method developed by DeKay and Brown (2014), pointed out that if the depth of the space
increases more than three times the ceiling height, the daylight factor (DF) in the deeper parts
of the room might decrease below 1%. Nonetheless, the outdoor view can be considerably
compromised in dense urban environments, where surrounding buildings could be tall and
close to the analyzed room. As a consequence, the maximum room depth (MRD) tends to
decrease on the lower floors, where the sky view angle measured from the working plane is
noticeably lower. As investigated by Reinhart and LoVerso (2010), the MRD is determined
by the no skyline equation, as it follows:

𝑀𝑅𝐷 = (ℎ − ℎ ) × tan(θ) (1)

Where:
𝑀𝑅𝐷 : Limiting depth of the room
θ: Sky angle
h: height

12
Daylight Optimization in an office building through atrium improvements

Although the WWR is an important component of the daylight equation, the surface
reflectance values can also significantly affect light perception in a space. However, the
surrounding environment is equally important, since it can notably limit the sky view angle
from a specific window, which is a crucial element for the atria design.

2.2 Daylight distribution in atria


The atrium is an architectural element that fosters the three aspects of sustainability in
buildings, namely social, environmental and economical. Moreover, it brings daylight into the
spaces that face the atrium, thus positively affecting the occupants’ productivity as well as
introducing a series of other benefits such as visual permeability between inner facades and
inviting environments that are natural lit (Samant, 2011). However, atria have not always been
part of the architectural design considerations. Although it was largely used as a space where
social interaction was encouraged in older civilizations, its implementation was brought back
in the past 30 years mainly to improve the daylight capabilities of the interior building spaces
(Sharples and Lash, 2007).

According to Samant (2011), it is important to observe some critical elements that could
substantially influence daylight quantity and quality of an atrium space, namely sky
conditions, geometry, roof structures and the characteristic of its enclosing surfaces. Sky
conditions play an important role, since it is the source that emits light towards the building,
whether it is direct or diffuse (Erlendsson, 2014). Some features, such as the geometry, usually
follow the shape of the building, therefore most of the times the atrium quality is bound either
to the outer envelope or to the plan layout. Poorly designed and oriented roof structures also
compromise the daylight levels in the adjoining spaces (Sharples and Shea, 1999). Lastly, the
atrium’s surfaces can contribute to light reflection, especially on the lower floors, which are
dominated by the internally reflected component (IRC) (Samant, 2011).

2.2.1 Geometry
The atrium shape is one of the most influential aspects in the daylight quantity and quality in
its adjacent spaces, as it substantially dictates how light will be distributed in its surrounding
spaces. According to Erlendsson (2014), the circular atrium is the one which tends to
distribute daylight in the most equitable way despite its difficulty to be arranged and
constructed. One of the most common ways to evaluate the geometry in atria is by utilizing
the Well Index (WI). It can also be expressed as the Plan Aspect Ratio (PAR), which concerns
the width to length ratio, as well as the Section Aspect Ratio (SAR), which considers the
height to width ratio.

Sharples and Lash (2007) pointed out that by combining the three measurements included in
the PAR and SAR properties through the WI, it is possible to estimate which type of shape a
given atrium has. Deep atria tend to have higher WI values, whereas atria that have lower
SAR values tend to be shallower. The WI also draws an important relation among the atrium
surfaces as it expresses the relation between the light admitting area and the light receiving

13
Daylight Optimization in an office building through atrium improvements

area. According to Baker et al. (1993), the connection between the supply of daylight in the
rooms that surround the courtyard and the shape of the atrium can be expressed in one value,
which is the product of the following equations (Sharples and Lash, 2007):

𝑤
𝑃𝐴𝑅 = (2)
𝑙

𝑆𝐴𝑅 = (3)
𝑤

𝐻𝑒𝑖𝑔ℎ𝑡 (𝑊𝑖𝑑𝑡ℎ + 𝐿𝑒𝑛𝑔𝑡ℎ)


𝑊𝐼 = (4)
2 × 𝑊𝑖𝑑𝑡ℎ × 𝐿𝑒𝑛𝑔𝑡ℎ

1𝐻 𝑊
𝑊𝐼 = 1+ = 0.5 𝑆𝐴𝑅(1 + 𝑃𝐴𝑅) (5)
2𝑊 𝐿
Figure 1: Atrium well index (WI).

Liu et al. (1991) identified that illuminance levels can be fairly increased in atria with a lower
PAR or rectangular, whilst four-sided and round ones tend to distribute the light more evenly.
He pointed out in his investigation that the design of linear atria must be carefully studied as
they have more exposed surfaces prone to receive light. As for the SAR, the shallower the
atria, the higher the daylight amount in its center. Conversely, deeper geometries will produce
a reduction of the natural light levels especially on the lower floors, where other important
considerations have to be considered, namely wall reflectance and window to wall ratio.

Studies, such as the one performed by Liu et al. (1991) show that the proportion of the atrium
can affect the distribution of daylight in AR. While natural light tends to increase in
rectangular atria, the quadrangular ones seem to provide an equal amount of illumination on
their surfaces. These hypotheses were confirmed in a physical model representing a linear
atrium when its length was increased to twice the original measure in a study conducted by
Matusiak et al. (1999). The daylight factor (DF) showed a substantial increase in the lower
floors. In agreement with this statement, equation 4 can be applied to demonstrate that if the
WI is lower, meaning the atrium is short and wide, the daylight quantity at the base of the
space will be higher.

An investigation conducted by Calcagni and Paroncini (2004) claimed that simple but rather
effective ways of simulating different atrium shapes could be used to guide architects at the
early stages of design. Varying the WI in different ways could be beneficial or represent a
liability to the spaces that share the atrium. Increasing the height or the WI of the building
will most certainly generate a reduction on the daylight levels, whereas maintaining the height
constant and increasing the atrium length or decreasing the WI will compensate the DF
downward trend, as it will enlarge the admitting daylight area. By using a scale model under
a heliodon, the results of Calcagni and Paroncini (2004) studies showed that the DF levels
decreased as the atrium height increased, whereas the DF had an increase when the length

14
Daylight Optimization in an office building through atrium improvements

was widened while the height was kept constant, which was expected since the light admitting
area was enlarged.

Some studies, as the one performed by Laouadi (2004) investigated the splay angle of the
atrium facades as a function of the well index and the well efficiency by using the SkyVision
tool developed by the Institute for Research in Construction in Canada. According to the
author, the well efficiency (WE) is “the ratio of the incident light flux on the well top surface
to the exiting flux from the well bottom surface”. As the WI decreased, the WE also
diminished proportionally for a splay angle of 90 degrees. However, the WE decreased in a
slower pace as the splay angle became lower. Results showed the well efficiency to be at least
twice for an angle of 60° for a well index of 1.

𝑙𝑖𝑔ℎ𝑡 𝑓𝑙𝑢𝑥 (𝑎𝑡𝑟𝑖𝑢𝑚 𝑓𝑙𝑜𝑜𝑟)


𝑊𝐸 = (6)
𝑙𝑖𝑔ℎ𝑡 𝑓𝑙𝑢𝑥 (𝑎𝑡𝑟𝑖𝑢𝑚 𝑤𝑒𝑙𝑙)

Figure 2: Well efficiency relation.

Strategies such as stepped sections might positively impact the AR of an atrium. Although
the addition of interior balconies can lead to an enhancement in the atrium architecture quality,
its consequences on the daylight factor were investigated by Alraddadi (2004) in a physical
scale model in Riyadh. The building studied was composed of four floors and a north south
oriented roof. The aperture was located on the north slope and the terraces, which overlapped
four meters over each other, were built on the south wall. When compared to the base case,
where the atrium had a regular shape from top to bottom, the upper two floors had an increase
of 25,4% and 22,3% on the average daylight factor (ADF), whilst the bottom floor had an
ADF decrease of 1%. This can be explained by the fact that lower floors are more dependent
on the IRC and since the atrium floor area was reduced, the amount of surface reflectance also
decreased. On the other hand, the conclusions drew by the author indicated that the balconies
can still act as light shelves, thus improving the general daylight quality of the adjacent spaces.

Other computer simulations with Radiance, such as the one pursued by Yi et al. (2009),
confirmed the conclusions of Liu et al. (1991). The authors analyzed two buildings located in
subtropical climates with different atrium configurations, where one was enclosed, and one
was linear. While the width was kept constant in the first case, a diverse range of volume
heights were tested along with distinct lengths with the aim of increasing the WI constantly
with multiple combinations of PAR and SAR. The authors confirmed that the height is the
feature that affects the daylight conditions most significantly in enclosed atria. The results
indicate that regardless of the length of the atrium, after a certain height, the lower floors will
not be able to have access to the sky component, which is the fundamental element affecting
the DF calculation. The daylight factor values in the atrium space ranged from 38% to 7% for
a WI that scaled from 0,475 to 1,9.

15
Daylight Optimization in an office building through atrium improvements

Du and Sharples (2010) carried out a research where simulations were performed in atria with
different WI and well-index depth (WID), which considers the distance from a specific point
in the atrium wall to its top edge. The WID criterion was more important for this study, since
it can be used to draw a relation from the measurement point to the top of the building, where
the sky is more visible. The research was conducted in physical models, theoretical
calculations and computer simulations in Radiance. The study indicated that the vertical sky
component (VSC) not only diminished as the WID increases, but also decreased next to the
atrium corners, therefore implying that the center is the best-lit spot. In addition, the study
concluded that the SAR is more influential than the PAR of an atrium. Results have shown
that the sky component (SC) value between the square and the longest plan achieved a
maximum difference of 15%, whereas the impact of SC on an atrium which has its height
equal to its width compared to a deeper one can go up to 173%.

Different PAR ratios were also tested in Radiance simulations performed by Du and Sharples
(2011) under a CIE overcast sky. Results showed that the lower the PAR index, the higher the
daylight levels in the AR, meaning that rectangular atria tend to increase the natural light
distribution along its linear borders. Naturally, the DF was decreased as the distance from the
window increased. Moreover, the study demonstrated that the lower the position of the room
in the atrium, the more affected it is by lower PAR values, meaning that linear atria could
increase the ADF at the bottom and middle floor rooms. Finally, as the lower spaces are
dominated by the IRC, the surface reflectance is an important aspect to increase the daylight
falling into these spaces.

2.2.2 Atrium facades


The last section showed that geometries play an important role affecting the daylight
distribution in atria. In addition, the surfaces that cover this atrium can also improve
dramatically its daylight performance. Their reflectivity and other characteristics will not only
influence the atrium, but more importantly, they will drastically affect the quality of light that
reaches the bottom floors. Although the best performing materials in terms of reflection could
be the specular ones, they might introduce liabilities such as glare for the occupants.

Boubekri and Anninos (1996) also recommended auxiliary strategies, such as the gradual
increase of opening sizes on the lower floors and the surface reflectance on the top pavements.
Most importantly, the same authors found that the DF does not increase proportionally to the
wall reflectance. It is also fundamental to notice that there is a close relation between the
geometry and the reflectance of the inner atrium surfaces.

General but rather important considerations were brought up by Littlefair (2002) about
optimization of daylight levels in atria. Although extremely bright surfaces contain higher
reflectance levels, the average reflectance of the atrium can be steeply reduced if the amount
of glazing is increased either on the roof or on the inner walls. He proposed to roughly estimate
the level of illuminance penetrating the atrium’s AR by using the no skyline method. It simply
implies that areas that lie across this limit will look gloomy, in case they are not lit from the

16
Daylight Optimization in an office building through atrium improvements

other side of the atrium. This strategy can be also coupled with the increase on the window
head height on the lower floors, since their sky visibility is compromised as the atrium
becomes deeper.

An investigation by Calcagni and Paroncini (2004), where simulations were performed with
Radiance under a CIE overcast sky, showed that the DF increased 4,8% in average in the AR
when the wall reflectance changed from 30% to 70%. According to the author this low value
is a consequence of the relative high WWR as most of the atrium facade was composed by
large openings, therefore diminishing the reflectance potential to boost the DF in the lower
floors. On the other hand, the DF values for the bottom of the atrium can increase drastically
if the atrium walls are composed mainly by opaque surfaces with high reflectance and a lower
WI.

Another investigation conducted by Samant and Yang (2007) assessed the wall reflectance
potential for increasing the ADF in an atrium. The simulations were performed in Radiance
under CIE overcast sky conditions, while utilizing a grid 85cm above the atrium floor. A
physical scale model was also built. It is important to mention that a comparison between the
measurements taken from the physical experiment and the results from Radiance presented a
difference on the DF that ranged from 5-10%, which according to the author represents a good
agreement. The investigation looked at the thicknesses and different colors of horizontal
bands that were distributed from the top of the atrium towards its base. In addition, the authors
also evaluated how these different arrangements influenced the ADF at the bottom of the
atrium when the WI changed from 0.5 to 2. As expected, the reflectance has a limited
influence on the lower parts of the atrium as its height increases. Nevertheless, a sensitivity
analysis pointed out that the DF increased for a taller atrium if the band at the top of the
geometry was white and large, meaning that more light from the sky could be reflected
downwards.

A more recent study conducted by Du and Sharples (2010) investigated how different inner
wall patterns (different reflectance) and depth affected the vertical daylight factor (VDF) and
the IRC in a square atrium. The authors performed simulations under a CIE standard overcast
sky using both Radiance and measurement data in a scale model under an artificial sky. They
varied not only the WI ratios, but also the assortment of patterns along the atrium surfaces.
Results indicated that the shallower the atrium, the lesser the impact of the reflectance
distributions, as the VDF in this case is strongly responsive to the sky component. On the
other hand, it was concluded that whenever the depth increases (WI>1), the surface
reflectance starts to significantly affect the daylight reflected downwards towards the base of
the atrium. To verify this effect, vertical and horizontal bands were tested on the vertical
surfaces, by varying not only their amount, but also their thicknesses. Results were sorted
according to horizontal band models and vertical band models and measurement points were
placed in three different vertical positions. The outcome identified that the VDF is
considerably affected by the color of the band which is placed at the top of the atrium.
Conversely, an agreement was found between the models with a higher number of stripes and

17
Daylight Optimization in an office building through atrium improvements

the base case model, indicating that the VDF is not so dependent on the increase of the
reflectance distribution. As for the vertical bands, since the same band goes from the top to
the bottom floor, the reflectance tends to be more constant along the height of the atrium.

According to (Samant, 2011), the atrium daylight performance is dependent on predominant


sky conditions, roof configuration, geometry, enclosing surfaces and the properties of the
adjacent spaces. However, in his investigation, he focused in finding the optimal glazing
apertures on each floor of a five-story building. Despite the general claim that openings should
progressively increase from top to bottom, ideal levels can be investigated to maximize the
daylight potential and avoid overheating problems in the atrium’s AR. The author carried out
simulations using the Radiance program where geometry, wall reflectance and other criteria
were constant while the wall openings were varying in length. In addition, the DF was
measured at five different points that ranged from the middle of the atrium up to 5,8 meters
from the window into the room. His findings suggest that rooms in the lower floors are slightly
influenced at the furthest distance from the atrium wall. Moreover, smaller fenestrations on
the higher floors improved the DF on the lower floor, as these spaces are highly dominated
by the IRC. On the other hand, the DF variations after 3,2 meters inside the adjacent spaces
are negligibly influenced by the window aperture. Although the results pointed out that an
optimal internal facade option is composed of openings that range from 60% to 100% top
down.

2.2.3 Skylight aperture


Since the roman ages, atria were an important feature of residential architecture, not only due
to the fact that they could foster synergy between people, but also because they could provide
daylight and ventilation (Murgul, 2015). However, its purpose has been slightly adapted to
other functions and climates, which most of the times leads to a roof construction at the top,
especially in cold regions. Therefore, working on an adequate roof design and aperture size
may improve the sky visibility from the bottom and adjacent atria rooms, hence providing
these spaces with the possibility to fetch daylight as much as possible (Littlefair, 2002).

An investigation carried out by Boubekri and Anninos (1996) pointed out the flat roof as the
best performing option, while the sawtooth configuration tended to direct light only towards
the walls opposing the apertures. According to this author, roofs should be designed in line
with the specific locations. To maximize the illuminance in atria, Matusiak et al. (1999)
investigated not only different inclinations for the glass cover, but also studied the
contribution of nine different reflectors in an atrium that was 6m high and 8m wide. Results
from measurements on a scale model under both artificial overcast sky and clear sky showed
that the performance of the reflector is closely related to the sky type and mainly to the
availability of the direct sun. They found that an inclined reflector placed at the top of the
atrium, that was leaning outwards, performed the best, even though it could potentially block
the lower sun path during the winter. By inserting a double-pitched glass cover in angles

18
Daylight Optimization in an office building through atrium improvements

between 18° and 30°, the VDF on the facades decreased by 50% if compared to the flat roof
of the base case.

Sharples and Shea (1999) carried out an analysis in an atrium where the WI was constant (2.0)
and roof obstructions were modified under the glass pane that was covering the skylight. The
authors built a 1:25 scale model, which represented a five-story building with internal walls
painted with a special paint with an absorptance of approximately 0.98. Instead of using the
typical DF, the researchers calculated the performance of each roof type by measuring the
sunlight hours as a function of the internal illuminance values on the atrium floor. Moreover,
the authors designed the structures of each roof type, namely flat, mono and double pitched,
in order to make sure that regardless of their differences, their daylight blockage coefficient
would be nearly 15%. Although the flat roof generally presented a higher performance for
overcast skies, this research indicated that in the presence of sunlight, the double pitched roof
was the type to provide higher illuminance values, as well as a smoother decrease on the
sunlight hours along the day. This phenomenon can be explained by the fact that a roof with
these features can increase the harvesting potential of sunlight as it provides two surfaces
which are better oriented towards different sun altitudes and positions if compared to a flat
and mono pitched surface.

Later, an investigation conducted by Laouadi and Atif (2001) focused on finding how
different roof shapes would perform under different sky conditions for a latitude of 45°. The
authors tested domes with different configurations as well as pitched, pyramidal and flat
geometries. Although domes performed better in the winter due to the fact that the sun altitude
was lower, this roof configuration might be a liability in the summer, as the optic
characteristics of the glazing reflects more the direct sunlight than the flat skylight. The
author’s results indicated that domes could transmit 78% and absorb nearly 150% more light
than flat roofs at an incidence angle of 70 degrees.

An investigation conducted by Calcagni and Paroncini (2004), showed a comparative


simulation of an atrium with and without roof. The structure has decreased the opening area
by 11% and results have confirmed that the DF was reduced by 45% in the spaces facing the
atrium.

By modifying the width and the clerestory height of a four-story atrium, where its adjoining
rooms were facing south, the ADF of the different variations could be assessed in an
investigation carried out by Ghasemi et al. (2015). Simulations were carried out by using IES
Radiance and compared to results obtained from a physical model which simulated a 48m
long/wide and 16m height building. The ADF divergences between the measured and
simulated models ranged from 14% on the ground floor to 16% on the top floor. This
discrepancy could be caused partly by the low amount of ambient bounces set for the
simulation, since the results might underestimate the reflectance between the surfaces in the
AR. As expected, the lowest clerestory height, measuring 1/8 of the total building height,
presented the worst daylight performance in the atrium AR. Consequently, higher clerestory

19
Daylight Optimization in an office building through atrium improvements

heights had a greater sky view angle, which boosted the difference between the ADF on the
lower and top floors. In order to attenuate the large discrepancy between the results,
techniques such as the reflectors could be considered.

Mohsenin and Hu (2015) worked with DIVA for Rhino to study daylighting in the inner
building envelope comparing different roof apertures. The variations consisted in modifying
the glazing monitor height according to a fraction of the atrium width, ranging from w/2 to
w/10. In addition, different WIs and atrium types were also assessed in line with the previous
criterion. Results showed that regardless of the atrium shape and type, the spatial daylight
autonomy (sDA) and annual solar exposure (ASE) will have a tendency to also increase for
larger monitor heights. In addition, as the WI increased, the difference on the amount of
daylight falling into the AR according to each monitor type becomes higher in atria that are
enclosed. On the other hand, the monitor roof heights do not substantially influence the natural
light harvested in attached atriums, as it is possible to harvest daylight through its exposed
lateral walls.

2.3 Energy efficiency in atria


In addition to its daylight aptitude, atria also have a potential to work as buffer zones
depending on their placement and configuration. On the other hand, they might drastically
increase the building’s energy demand if conditioned and treated as regular indoor spaces that
are regularly occupied. According to Hung and Chow (2001), atria can be classified in four
different types, as shown in Figure 3.

Figure 3: Types of atria.

He points out that centralized ones have a higher likelihood to keep the temperatures closer
to its adjacent zones, as they are enclosed and share the boundaries with potentially heated or
cooled spaces. On the contrary, atria such as the attached and linear ones are more prone to
have higher heat losses to the surroundings. Most of the times, semi-enclosed and linear atria
are wrapped in glazed panes, which can be beneficial depending on the climate. Atria with
glazed facades can turn into not only buffer zones, which feature as transitional spaces
between outdoors and indoors, but also into green houses that are naturally heated by sunlight,
thus serving as pleasant gathering spaces during the winter. On the contrary, glazed facade
atria can represent a liability in regions with warm climates, as the sun will bring additional

20
Daylight Optimization in an office building through atrium improvements

radiation to theses spaces, thus transforming them into uncomfortable areas if not ventilated
properly.

Wang et al. (2017) thoroughly studied the correlation between the SAR of atria and its energy
performance, by utilizing field measurements and thermal simulations in Design Builder, in
two existing enclosed atria in the city of Tianjin, located in a cold climate region in China.
The two spaces were considered to be fully conditioned with setpoints adjusted to 20° and
26° for winter and summer, respectively. The shallow case showed to have more contribution
of solar heat gain, especially at the bottom floor. The temperatures along the atrium height
were more evenly distributed in the winter and in the summer, however more cooling capacity
is needed during the warm season, as most of the atrium area is heated up by the sun. Although
the deep atrium hardly had overheating problems, since its bottom is shaded most of the time
during the year, the temperature gradient between its bottom and its top reached a higher
difference. In terms of energy performance, the deep atrium reduces only the cooling need in
the summer, while the shallow atrium reduces the heating demand, as a big portion of its area
is heated up by the sun.

Another investigation conducted by Aldawoud (2013) focused in finding the relation between
different atrium volumes and their thermal performance by using computer energy
simulations in DOE 2.1E. The atria were assumed to be in thermal equilibrium at a
temperature of 24° and had their only light admitting area through the skylight at their top.
The atria shapes were tested only regarding their PAR, which varied from 0,15 to 1, whereas
their height was kept constant. Among all the four geometries studied, the author found that
the elongated shape had the worst energy performance, both in warm and cold climate regions.
The energy demand of the adjacent spaces in a cold climate location increased up to almost
25% when compared to an atrium that had a square shape (PAR 1), due to its larger light
admittance at the top. The investigation also pointed out that deeper atria tend to perform
better in warm climates, as the middle and bottom floors are protected against direct solar
radiation.

Moosavi et al. (2014) brought up several benefits of atria in buildings, one of them being their
capacity to maintain acceptable comfort conditions inside its space and the adjacent rooms
without necessarily using mechanical systems. Natural ventilation, temperature differences,
solar radiation, wind properties of the region as well as internal loads have to be taken into
account to design a space that adds value to the building. The temperature stratification along
the atrium plays an important role and can drastically change according to the atrium WI and
its openings for example.

Lastly, Laouadi et al. (2002) carried out computer simulations in ESP-r to verify the effect of
different geometries on the energy performance of the adjacent atrium rooms in a building
located in Ottawa, Canada. The energy demand studies were conducted in three different types
of atria 1) enclosed 2) three-sided 3) linear. When compared to the base case, where there
were no openings to the adjacent spaces, the cooling peak loads were significantly reduced to

21
Daylight Optimization in an office building through atrium improvements

41% 18% and 7% for the enclosed, three-sided and linear atria, respectively. The adjacent
rooms were conditioned to a temperature of 21°, therefore contributing to a cool airflow from
these rooms towards the atrium. Nonetheless, there was a substantial increase on the heating
energy demand due to the heat losses and infiltration from the atrium towards the AR.

2.4 Summary
The previous sections were dedicated to the atria features that affect the daylight quantity and
quality in the adjacent rooms and the space itself. As it was previously discussed, the geometry
has been proved to play the largest role when it comes to daylight penetration and distribution
in atria. As described by Baker et al. (1993), there is a strong relation between the well area
at the atrium top, which can be described as the light admitting area, and the surfaces that
receive the incoming light or the light receiving areas. This connection is described by the
well index (WI) which is an equation that facilitates the comparison between different types
of atria. Lower WI values mean that the atrium is shallow and more likely to fetch more
daylight in their bottom and adjacent rooms. On the other hand, higher WI values indicate
that an atrium is deep and probably gloomier at the lower levels. In addition, the SAR and
PAR values are also good indicators of an atrium shape. Atria with lower PAR tend to be
rectangular and have more surfaces exposed to daylight, thus having better chances of
improving the daylight conditions in the AR, whereas aria with higher SAR are classified as
deep, which leads to a consequent decrease on the natural light conditions in the AR.

Additionally, studies have showed that the wall reflectance properties of the inner atrium
facades have the potential to increase the daylight quantity at the bottom floors, as well as
expand their uniformity. However, the reflectance property starts to have limited impact as
the atrium becomes deeper. The window to wall ratio is also an important feature of the atrium
surfaces. Investigations, such as the one performed by Samant (2011), demonstrated that a
proper combination of smaller windows at the top floors and larger ones at the bottom floors
can improve the daylight scenario at the lower levels. Lastly, the roof type and aperture proved
to considerably influence the daylight situation in the atrium. Flat skylights are more efficient
under overcast skies, whilst pitched roofs offer the possibility to fetch more properly the
sunlight, depending on their orientation and location.

Atria and their relationship with energy efficiency was also shortly addressed, since this topic
is not included in the thesis project. The energy performance of an atrium is closely related to
its shape. Enclosed ones tend to keep their surrounding temperature more stable, while linear
types are more affected by the outdoor conditions. Shallower atria perform better in terms of
daylight, nonetheless they are more susceptible to overheating problems and heat losses. A
successful atrium case can be found in the Commerzbank project located in Frankfurt, where
an atrium with side openings was implemented to facilitate penetration of daylight into the
building core.

22
Daylight Optimization in an office building through atrium improvements

3 Daylight criteria
3.1 Daylight factor
The Daylight Factor is defined by the International Commission on Illumination or CIE
(International Commission on Illumination, 2018) as “the ratio of the illuminance at a point
on a given plane due to the light received directly and indirectly from a sky of assumed or
known luminance distribution, to the illuminance on a horizontal plane due to an unobstructed
hemisphere of this sky, where the contribution of direct sunlight to both illuminances is
excluded.” The daylight factor is one of the most common criterion to verify the quantity of
daylight in a given space and has been widely used not only by professionals, but also by a
variety of standards to evaluate lighting conditions of projects and existing buildings. It is
expressed as a percentage, which is a product of the following equation:

𝐸 𝑖𝑛𝑡𝑒𝑟𝑖𝑜𝑟
𝐷𝐹 = × 100 [%] (7)
𝐸 𝑒𝑥𝑡𝑒𝑟𝑖𝑜𝑟

Where:
DF: Daylight factor of a given point (%)
E interior: Interior illuminance (lux) of a given point or plane (Normally horizontal at 0,7-
0,85m from the floor with the light sensor pointed upwards)
E exterior: Exterior illuminance (lux) measured under a CIE Standard Overcast Sky

Although the daylight factor was established as the main criterion to investigate whether a
building complies with some of the certification systems, one of its main drawbacks is the
fact that no sunlight is taken into account in the calculations (Bian and Ma, 2017).
Furthermore, this method cannot account for changes in orientation and location, thus
disregarding two important considerations during the initial stages of the design. On the other
hand, this method can be used both as a good indicator for the early design stages, and as an
indicator for the daylight performance of a room or space (Tregenza and Wilson, 2013). The
authors suggested that the minimum ADF suggested in office buildings is 2%. The following
table connects ADF values to the appearance of spaces in office buildings.

Table 1: Average daylight factor for office buildings. Source: Tregenza and Wilson (2013).

Average daylight factor


Rooms without electric lighting
from side windows
1% Gloomy appearance, harsh contrast with view out

2% Areas distant from window may seem underlit


The room looks brightly daylit. Visual and thermal
5%
discomfort may occur with large window areas
Visual and thermal conditions may be unsuitable for
10%
office-type tasks

23
Daylight Optimization in an office building through atrium improvements

As pointed out by Acosta et al. (2018), the daylight factor is influenced directly by the sky
component (SC), the externally reflected component (ERC) and the internally reflected
component (IRC). The DF can be calculated in different ways, through standard equations or
computer simulations, where a grid can be used to determine the position of the sensors that
will measure the availability of daylight.

It is also possible to verify the DF at specific points, which is the case for one of the Swedish
building regulations, the BBR. The code requires that a DF point of 1% is achieved and
measured halfway towards the room depth and one meter from the darkest wall. However, the
point location might be subjective, since some rooms have a particular shape that could bring
difficulties in finding which walls could be used as a reference.

Additionally, the DF conditions in a room can be shown through the average daylight factor
and the median daylight factor. Tregenza and Wilson (2013) highlighted that the ADF is a
strong criterion to be used in the early phases of the design process, however this metric does
not represent the uniformity conditions in the space, since higher values next to the window
could sky rocket the average value. Conversely, the DF median seems to assess in a more
reliable way the daylighting in a space, as the number can tell the amount of points that are
above and below the arithmetical median (Mardaljevic and Christoffersen, 2017).

3.1.1 Sky component


The sky component is the element that has the greatest influence on the daylight conditions
in the space. The DF level is substantially influenced by the portion of sky that is visible from
the window or skylight and by any obstacles that might be placed in front of this fenestration,
such as buildings, overhangs and balconies.

It is possible to have an idea if the space is well lit by estimating the visible portion of the sky
from the window (equation 8).

𝜃
𝐷 = [%] (8)
2

Figure 4: Angle of visible sky in a building section. Source: Tregenza and Wilson (2013).

Where:
𝐷 : Vertical daylight factor
θ: Angle in degrees

24
Daylight Optimization in an office building through atrium improvements

Table 2: Conversion from vertical daylight factor (Dv) to vertical sky component (Dsv). Source:
Tregenza and Wilson (2013).

Dv 5 10 15 20 25 30 35 40 43.5
Dsv/Dv 0.77 0.79 0.81 0.82 0.84 0.86 0.88 0.89 0.91

To understand how the calculations are performed in simulation programs, such as Radiance
and DAYSIM, it is important to understand each type of sky that can be utilized in each
analysis. The CIE has developed a series of sky models for different applications, but the
standard overcast sky is the one used for the DF simulations (Mardaljevic, 2000). Despite its
luminance variation according to the latitude, the overcast sky is always three times brighter
at the zenith as devised by the Moon and Spencer equation, which was standardized by the
CIE:

1 + 2𝑠𝑖𝑛𝜃
𝐿 =𝐿 (9)
3

Where:
𝐿 : Luminance of the sky at the elevation θ
𝐿 : Zenithal luminance

This sky has a more uniform light distribution compared to the clear sky and provides a
smoother light along the building surfaces and streets. On the other hand, calculations handled
by DAYSIM, make use of the Perez All Weather Sky model in order to generate metrics that
take into account the weather conditions from a specific location to calculate the luminance
distribution of the sky (AGi32, 2018). This sky model was created from a series of field
irradiance measurements and can represent a large range of sky patterns through their different
luminance distributions (Nabil and Mardaljevic, 2005).

3.2 Daylight autonomy and useful daylight illuminance


Reinhart and Walkenhorst (2001) defined the daylight autonomy as “the percentage of the
occupied hours of the year when the minimum illuminance requirement at the sensor is met
by daylight alone”. Unlike the daylight factor, the DA method is climate dependent,
consequently being more likely to give a better daylight evaluation of the studied space.
According to Dubois and Flodberg (2013), the consideration of parameters such as sunlight,
user behavior and different types of skies make this approach more reliable. Moreover, the
results obtained from the DA simulations might be used as an alternative metric to obtain
credits and points in different certification systems, namely LEED and BREEAM.

This criterion fostered the development of new metrics based also on dynamic daylight
simulations, such as the useful daylight illuminance (UDI) and the spatial daylight autonomy
(sDA). Based on the user capability, the UDI establishes a range, so it is possible to evaluate
whether the illuminance falling on the analysis plane is advantageous, so the occupant’s tasks

25
Daylight Optimization in an office building through atrium improvements

can be performed with a proper level of daylight. While creating the UDI, Nabil and
Mardaljevic (2005) established a range that goes from 100 lux to 2000 lux, meaning that a
value that lies below that boundary implies a dark environment, whereas the ones that lie
beyond the limit indicate that the space is probably overlit, thus indicating possible glare
issues.

Table 3: UDI thresholds. Source: Nabil and Mardaljevic (2005).

Threshold Description
< 100 lux UDI fell-short (insufficient daylight)
100 – 2000 lux UDI autonomous (total daylight autonomy; no need for electric lighting)
> 2000 lux UDI exceeded (oversupply)

On the other hand, the sDA shows the percentage of the analyzed area that meets the DA
previously established threshold for the occupied hours of the year. According to the
Illuminating Engineering Society (IES), there are two levels for this metric: “Preferred
daylight sufficiency” for an area that achieves a value of 75% and “nominally accepted
daylight sufficiency” for an area that reaches a threshold of 55%. Table 4 shows the
illuminance requirements according to each type of room.

Table 4: Lighting requirements for interior areas, tasks and activities. Source: EN 12464-1 (2011).

Type of room Illuminance (lux) Uniformity


Classrooms, tutorial rooms 300 0,6
Auditorium, lecture halls 500 0,6
Entrance halls 200 0,4
Circulation areas, corridors 100 0,4

3.3 Standards
3.3.1 Leadership in Energy and Environmental Design (LEED)
LEED is the most internationally well-known rating system for environmental-friendly
buildings. The standard was designed by the U.S. Green Building Council (USGBC) and has
certified nearly 100.000 projects around the globe, due to its flexibility as it comprises a wide
range of categories that have different weights (USGBC, 2018). The certification levels are
‘Certified, Silver, Gold and Platinum’. Even the entry category has obligatory credits that
shall be completed if the developer wants the building to be eligible for the certification
scheme.

As for the daylight section, the computer simulations should demonstrate that an sDA with a
threshold of 300 lux for at least 50% of the hours of the year can be achieved in 55% of the
regularly occupied office areas. The accomplishment leads to two points on the overall
certification. However, it is possible to score up to three points if an area of 75% is proven to
meet the DA requirement. Moreover, not more than 10% of the floor area should display an

26
Daylight Optimization in an office building through atrium improvements

annual solar exposure (ASE) of 1000 lux for more than 250 hours. Compliance can
alternatively be demonstrated through illuminance calculations or measurements (USGBC,
2018).

3.3.2 BREEAM
The Building Research Establishment’s Environmental Assessment Method or BREEAM,
was developed by the BRE Group that consists of a private institution focused in the research,
generation and dissemination of knowledge about the built environment. The certification
system was conceived in 1999 and since then it has been adopted by developers in the whole
world (BREEAM, 2018).

The standard is divided into ten categories, ranging from management to innovation. The
daylight category belongs to the section Health and Well-being and it contains three different
criteria to evaluate not only daylight quantitatively, but also qualitatively. In this certification
system, the building complies with the first and mandatory credit by reaching an ADF of 2,1%
in 80% of the net lettable area or an average illuminance of 200 lux for 2600 hours along the
year for latitudes between 55° and 60°. However, an exemplary credit might be achieved if
an ADF of 4,2% in single story buildings or a 3,15% ADF for multiple stories are measured
on the grid corresponding to the evaluated area.

Regularly occupied areas also need to be 7m distant at most from a window that should have
a size of at least 20% of the total inside wall area. Lastly, a shading system should be installed
so possible glare problems can be prevented, thus providing the users with more control over
their visual environment (BREEAM-SE, 2013).

3.3.3 Miljöbyggnad
Miljöbyggnad is the main Swedish environmental certification system used in the Swedish
market since 2011.The idea to develop a rating system for environmentally friendly buildings
was initiated in 2003 by the Swedish Green Building Council (Sweden Green Building
Council, 2018). The certification is provided based on three aspects, which comprise 1)
energy, 2) indoor comfort and 3) materials. The achievement of a certain level of points can
lead also to three ratings, namely gold, silver and bronze. Among the different methods for
assessing daylight, the DF is the most adopted. The minimum thresholds to attain each rating
category vary from 1% to 1,5% and since the calculations are performed utilizing computer
simulations nowadays, it is acceptable by the standard that the simulated DF differs up to
0,2% from the requirement. The system accepts both a point DF (DFp) and a DF median in
the version 3.0 (Miljöbyggnad 3.0, 2015).

3.3.4 Swedish and European regulations and standards


The rules of Boverket’s Building Regulation (BBR) must also be respected when a new
building or a renovation takes place in Sweden. Apart from the mandatory provisions, the
regulation also provides several recommendations that can be followed in order to pursue

27
Daylight Optimization in an office building through atrium improvements

ideal or minimal daylighting conditions in indoor spaces (Boverket, 2015). Section 6.322 on
daylight, which is part of the health aspect, recommends that rooms which are occupied more
than occasionally should be designed to allow exposure to direct sunlight. In addition, it states
that at least one of the rooms shall have a view to the outdoors, thus ensuring that the
occupants can follow daylight shifts along the day. In addition, the EN 12464-1 provides a
further description and guidance concerning daylight quality in working environments.
Aspects such as recommended illuminances, glare issues, color appearance and other
properties of electrical lighting are also proposed.

28
Daylight Optimization in an office building through atrium improvements

4 Methodology
This chapter provides a description of the studied building and its current constraints
according to its location, design and proposed functionality. Apart from providing good
indoor visual comfort by maximizing the daylight conditions in the AR and the ground floor
of the building, the additional aim is to seek compliance with the Swedish building regulations
(BBR, 2015) and verify whether the current and new conditions are able to meet the
requirements of environmental certifications, such as LEED, BREEAM and Miljöbyggnad.
As a result, the current proposal was investigated and simulated to establish a base case
scenario, followed by a series of parametric studies with the intention to verify how different
geometrical transformations and surface reflectance values affect daylight levels in the AR.

As learned from the literature review, the geometry of an atrium is the main aspect
influencing the daylight quantity in a building. As a consequence, this thesis mainly focused
on analyzing the effect of this feature, which comprises not only the building shape, but also
its skylight aperture. In addition, the surface reflectance is studied as it has the potential to
increase daylight quantity and uniformity in a given space. Thus, different reflectance values
are assessed.

Simulations and data analysis were performed using a combination of software: Rhinoceros,
Grasshopper, Honeybee, Ladybug and Excel. The current building design was simplified for
study purposes, as the initial geometry was complex, but without compromising the geometry
and its current features. The dependent metrics used as basis for the evaluation include the
daylight factor (DF), daylight autonomy (DA) and the useful daylight illuminance (UDI).
These are further explained in the following sections.

4.1 Sahlgrenska Life Science Center


The Sahlgrenska Life Science Park is an expansion of the Sahlgrenska University Hospital
located in Gothenburg. The enterprise is currently in the design process, which started in 2016,
and has nearly 90.000 m² of gross floor area, comprising a variety of functions that range from
offices to conference rooms with the main aim of integrating the medical community,
companies of the field and the university hospital (Arkitema Architects, 2018). According to
Moberger (2018), the development also pursues the objective to improve the urban
attractiveness of the region by bringing together major stakeholders of the medical industry,
while providing more job opportunities. Although the complex consists of two main buildings
and a large passage that connects them, this thesis focused on analyzing a single building,
which is described in the following chapters.

4.1.1 Location
The project is located in a cluster of buildings in the outskirts of Gothenburg between Annedal
and Guldheden neighborhoods. The main idea behind the design is to embrace the existing
edifices and create an urban pathway that crosses over Per Dubbsgatan, which is a relatively

29
Daylight Optimization in an office building through atrium improvements

busy road. The connection between the buildings also occur at different levels and places,
hence emphasizing the role of the new proposal as a connector between the functions that are
already in place and the urban configuration, which tends to be slightly reorganized and
improved. Bearing this in mind, the nearest existing buildings were modelled as they may
influence the daylight conditions of the study case.

Figure 5: Location and surrounding context of the study case.

4.1.2 Geometry
Connecting interior and exterior spaces through smooth transitions was one of the goals of
the project (Arkitema Architects, 2018). The shape of the building respects and dialogs with
the existing lines and curves of the urban design and at the same time aims to provide a visual
connection between the floors internally through an atrium, which is the object of this
investigation.

The building consists of eleven floors, where functions as offices, laboratories and classrooms
are distributed. Despite the contrasting nature of the functions which are developed on each
floor, all activities taking place in these spaces are classified as working spaces, hence the
daylight requirements according to standards and regulations apply equally to them as the
spaces are used often. As the analysis (proposed by this thesis) is focused solely on the effect
of atrium geometry and material properties on the daylight quantity in the AR, the area along
the atrium border was the only climate zone considered for this investigation. The premise
behind the analysis grid proposal can be found in the Daylight model chapter.

30
Daylight Optimization in an office building through atrium improvements

Considering the fact that the project is still under development, some functions can still be
changed on the plans, yet the main activity zones are defined according to the schematic plan
in Figure 6.

Figure 6: Schematic plan and section.

To understand the current daylighting situation, the proposed geometry (Figure 7) was
simulated as a base case to allow a comparison with the parametric studies. More information
about the reasons why the shape of the original project was broken down into four sections is
provided in the chapter dedicated to the parametric scheme. The floor area has 4760m² and it
is divided among the three wings as follows: a) 1270m² b) 895m² c) 1650m². Section d was
not studied since it had a restricted facade towards the atrium.

Figure 7: Current features of the base case.

4.2 Simulation tools and workflow


The main objective consists of analyzing the changes on the geometry and on the light
reflectance values (LRV) that substantially affect the daylight levels in the AR. The results
were also evaluated in terms of their potential to achieve the Swedish building regulations
and some of the certification systems.

31
Daylight Optimization in an office building through atrium improvements

The eleven floors were analyzed in the simulations, yet the grid is only placed around the
atrium perimeter, as previously discussed. To achieve the thesis objective, the following
workflow (Figure 8) was established.

Figure 8: Thesis work flow.

4.2.1 Rhinoceros
Rhinoceros (2018) is a modeling software often used by the architecture industry to create
and plan building projects. By integrating the program with Grasshopper (2018), which is a
visual programming tool, it is possible to control shapes and geometry with the goal to analyze
them according to environmental parameters. In this case, Rhino was used as the modeling
tool to create the geometry that will be further investigated.

4.2.2 Grasshopper
Grasshopper (2018) is a tool for visual programming, which allows preparing and editing
algorithms towards an environmental simulation. It is commonly used to perform parametric
experimentations related to geometrical and material variations. It is the environment where
a series of plugins such as Honeybee and Ladybug (Roudsari and Park, 2013) were deployed
for use in this project. Moreover, Grasshopper is directly connected to Rhino, meaning that
every geometry iteration triggered by Grasshopper will immediately affect the 3D model
developed in the previous program’s interface.

4.2.3 Honeybee and Ladybug


Both Honeybee and Ladybug are plug-ins for Grasshopper that allow the user to run a wide
range of environmental analyses, such as energy building performance, daylight availability,
user comfort and shadow range, among others. These tools make use of validated engines for
running the simulations, namely OpenStudio, EnergyPlus, Radiance and DAYSIM (Ladybug
Tools, 2018). The platforms are usually employed to support the early design phases,
nonetheless they can also be used to demonstrate compliance to environmental certification
systems. For this reason, they were the main freeware used in the thesis project.

4.2.4 Radiance and DAYSIM


Currently embedded in many different interfaces, Radiance (Ward and Shakespear, 1998) is
a well-known and validated set of lighting simulation programs based on a hybrid
deterministic-stochastic backward raytracing technique, as it generates results that are

32
Daylight Optimization in an office building through atrium improvements

displayed with a high degree of realism, either as numerical values or as images (Radiance,
2018). DAYSIM (2018) on the other hand is a Climate Based Daylight Modelling (CBDM)
simulation tool that uses the Radiance engine at its core. DAYSIM allows to generate metrics
that evaluate the space on an annual basis by using the daylight coefficient approach combined
with the Perez all weather sky models. Daylight autonomy (DA), useful daylight (UDI),
electrical lighting demand, as well as point-in-time and annual glare analyses are some of the
outputs that the program can generate. For this specific investigation, the tool was used to
calculate the spatial daylight autonomy (sDA) and the UDI.

4.3 Daylight model


4.3.1 Simulation input and parameters
Table 5 shows the Radiance settings used in the simulations. An accurate but rather optimized
set of parameters were chosen due to the large size of the grid and the amount of simulations.
In addition, a relative comparison of design alternatives yields more reliable results than the
reporting of absolute simulation results (Reinhart, 2009). The following values give a solid
rendering performance (Radiance Settings, 2018); however, the ambient bounces were
increased from two to four in order to improve the ambient diffuse calculations.

Table 5: Rendering quality adopted for the thesis simulations.

Ambient Ambient Ambient Ambient Ambient


bounces (ab) division (ad) sampling (as) resolution (ar) accuracy (aa)
4 512 256 128 0,15

Regarding the building configuration, the occupancy schedule for the annual simulations
considered the evaluated areas to be occupied from 9h to 17h with a one-hour break during
week-days. As for the material properties, the light reflectance values were chosen based on
common construction practices, while the current light transmissivity value is for a double-
pane glazing, as the atrium facades are not initially exposed to fully outdoor conditions. The
window to wall ratio for the atrium facades was kept at 40% for all the simulations. Changing
their values would not fit in the time constraints of this investigation.

Table 6: LRV and LTV of the materials adopted for the simulations.

Construction Light reflectance value Light transmissivity value


Glazing, double pane (WWR 40%) - 0,73
External wall 0,40 -
Internal wall 0,70 -
Internal floor 0,40 -
Internal ceiling 0,80 -
Surrounding buildings 0,35 -
Ground 0,25 -

33
Daylight Optimization in an office building through atrium improvements

4.3.2 Parametric scheme


The parametric study was split into two main phases, where the first one assesses the impact
of the changes in the geometry in different ways, while the influence of the surface reflectance
values was explored in the second phase.

Figure 9: Tower option. shows the first set of modifications. In this case, the adjustment was
conducted in each block separately in order to verify the effect of a larger opening in each
orientation. It is important to consider that the geometry modifications triggered an area loss,
which in most real cases compromise the project goals, since it was designed to fit all the
requirements of the developer. To tackle this possible drawback, the adjustments of the
geometry were followed by a volume addition, which varies according to each wing, thus
increasing the height of the building in a specific spot. The towers that are added to the top
contain the same number of floors of the wing that is being pulled down. Each step of the
simulation decreases two floors at a time.

Figure 9: Tower option.

As it can be seen in the previous figure, there are many options to compensate the area losses
and building a tower in one of the wings may represent one among many different ones that
could be chosen for the architects responsible for the project.

34
Daylight Optimization in an office building through atrium improvements

The second series of simulations comprised additions that oppose the first tower options by
creating geometries that rest over two wings and rely on fewer floors to make up for the area
losses. However, for every two floors that are eliminated, only one floor is computed at the
building top, as shown in Figure 10.

The potential of this option lies on increasing the sky view angle from the AR, as fewer floors
will be added to the top. On the other hand, the atrium will be slightly more surrounded by
floor area, which can technically block the sun path in a given direction. Architecturally, this
alternative also pursues a higher degree of integration with its surroundings, keeping therefore
the height of the cluster approximately at the same level.

Figure 10: Combination of wings option.

In addition, these options also seem to be more realistic construction and structural wise. Their
internal organization would also be easily spread over the wings that are not being suppressed,
thus keeping the horizontal and vertical circulations more wisely organized. The combination
of two wings has slightly the same area of the addition of two floors in the tower options,
hence the floor space compensations are relatively similar in these two different ways of
structuring the new volumes.

35
Daylight Optimization in an office building through atrium improvements

The third series of the geometry modifications, that can be seen in Figure 11, proposes a
smoother transition between the heights of the different wings in order to compensate for the
area losses of the volumes that are being pulled down. These solutions tend to be more
architecturally appealing and it is a strategy often applied to fetch daylight into buildings that
are constructed around large urban blocks, not to mention their likelihood to create terraces
to be used as recreational spaces.

Figure 11: Counter and clockwise addition option.

Lastly, the plan aspect ratio or PAR was modified in angles of 5°, thus leading to a stepped
section across the atrium in one specific orientation at a time. The angles range from 5° to
20°. The last angle was determined as it provided a minimum useful floor area on the top
floor. This modification creates a small terrace for each floor and its dimensions varies
according to each angle. The larger the angle, the deeper the terrace. This small balcony
generates an additional outdoor floor area which acts as a reflector, thus increasing the
potential distribution of daylight into the AR.

Differently from the previous options, the low angle inclinations do not extensively decrease
the floor area of the case study, even though the 20° visibly reduces the top floor depth. In
variance with the three precedent alternatives, no area compensation has been added to these
modifications, thus avoiding an architectural disruption in the original volume.

36
Daylight Optimization in an office building through atrium improvements

The final geometry modification resides on the adjustment of all the three wings at the same
time. Due to the combination of wings for this simulation stage, the 20° option could not be
tested, as it does not leave any useful area on the last floor. Moreover, the area loss would be
increased to an amount more than reasonable for any developer in real terms. The alternatives
mentioned above can be seen in Figure 12.

Figure 12: Wing splaying option.

The wall light reflectance values (LRV) were changed from 30% to 70% so the impact of
modifying the material of the inner facade could be assessed. The literature review has
pointed out that the LRV starts to have an important influence when the atrium becomes
deeper. In this specific case, the base cases were chosen for the change of the LRV.

Figure 13: LRV modification option.

The area loss was calculated for each of the alternatives and compared with the gains in
daylighting quality. Recent daylight analyses have shed light on the property value according,
not only to their location, but also their potential to fetch daylight. Saratsis et al. (2017)
analyzed how different block configurations could affect the natural light quantity of the
neighboring buildings in New York. The author studied typologies ranging from perimeter
blocks to double alleys and found that building them with different heights can improve the
percentage of daylit area in a considerable amount on the lower floors. Furthermore, the

37
Daylight Optimization in an office building through atrium improvements

studies showed that buildings that are constructed with different heights instead of one single
block contributed for an increase of the Floor Area Ratio (FAR), meaning that larger floor
area could be built with the same footprint.

This approach also enhances the property value, since more floor area is available for leasing.
Following this methodology, the results are also compared in terms of property value
according to the CBRE report for the last quarter of 2017, which showed that the value for
the prime rents in the city of Gothenburg reached 3000 SEK/m² (Sweden Overall Property
Market View, 2017).

4.3.3 Analysis grid


Since the atrium adjacent spaces consist of landscape offices and its area is the main subject
of this study, the calculated grid depth followed the recommendations for work spaces
proposed by Neufert and Neufert (2012). In order to comfortably accommodate two working
desks next to each other, a room depth of 4,50m was chosen. The hallway was left behind, as
it is not classified as a regularly occupied space.

In relation to the Swedish regulations, the DFp, which is measured half-way through the
room’s depth and one meter from the darkest wall, should not be lower than 1%. Instead of
placing the points in each corner of the grid, the metric utilized for verifying the potential of
each strategy was the area of DF above 1%. As it can be seen in Figure 14, the grid varies
according to each geometry alternative. Nevertheless, the metrics adopted make it possible to
compare the results among the different options. The grid surface is composed of sensors that
are one meter distant from each other.

Figure 14: Grid combination for each case.

The evaluated grids are highlighted in black and are present in each of the eleven floors,
while the wing that is being changed is indicated with the letter.

38
Daylight Optimization in an office building through atrium improvements

5 Results
Under the guidance of the two objective questions, the results of the current daylight situation
in the building, as well as the proposals are presented in the following sections. Firstly, an
investigation was carried out to verify how the AR in the current project were performing in
terms of daylight quantity. Secondly, different qualitative proposals were developed utilizing
parametric schemes, which considered the characteristics of the initial architectural concept.
The scenarios, both current and future, were assessed using different metrics, consisting of
ADF, sDA, DF median, UDI and specially the grid area that had a DF above 1%, which can
be translated into areas that are potentially certifiable for the Swedish regulations and
standards, such as BBR and Miljöbyggnad.

To answer the first research question, the study focused on geometry and wall LRV changes.
According to the literature review, the atrium geometry showed to be the most influential
aspect, hence this thesis project concentrated the investigations mainly on this atrium feature.
Nonetheless, the walls LRV also demonstrated to considerably impact the daylight values
mostly at the bottom floors, especially in atria with high WI. Secondly, an analysis was made
to choose the optimal solution in terms of daylight quantity and less area losses. To wrap the
study up, some options were chosen to be carefully studied in terms of daylight conditions
per floor. The daylight metrics are assessed in absolute values, so comparisons could be drawn
in an a more accessible way. General conclusions are discussed in the last chapter.

5.1 Base cases


The current daylight situation in the AR was assessed to be able to draw a comparison and
most importantly, understand how the modifications affected and improve the building’s
natural light conditions. Due to the building’s complex geometry, simplifications were made,
and the evaluation grid was placed only around the atrium, so the simulation time was
optimized, and the results of the improvements could be properly seen, as the outer facades
could significantly distort the results. As for the present scenario, it is important to understand
that the results from this investigation can be different from previous or future studies that
have been or will be carried out, as the project is still under development and will go probably
through great modifications.

The grid, which had its dimensions explained in the previous chapters, runs along the
perimeter of the atrium and changes according to each type of modification, thus leading to
four different base cases. Due to the high amount of data and the building area, it was
important to show the general impact of each improvement using less data, but rather
condensed in a few values that could be accessible. The metrics commonly used to evaluate
the daylight conditions in adjacent rooms were adopted, however they were quantified in area,
so all the proposals could be compared.

Shortly, the sDA shows the percentage of the area that has a daylight autonomy of 300 lux
for 50% of the time of the year, while the daylight factor was quantified in terms of area that
had a value of 1% or more. Lastly, the behavior of daylight was evaluated in each floor by
using the ADF, the sDA, the DF median and the UDI autonomous. These metrics are utilized
by certification systems, except the UDI, which is calculated as a percentage of the floor area
that is complying with the criteria of the metric for at least 50% of the time along the year.

39
Daylight Optimization in an office building through atrium improvements

5.1.1 sDA and area of DF above 1%


The following graphs show an overview of the current daylight situation on the base cases in
relation to the area of the proposed grid. The area that is seen in the vertical axis of Figure 15
is the sum of the grid along the perimeter of the atrium on eleven floors. Each grid varies
according to the wing that is being studied, meaning that the rooms that are investigated are
always located across and adjacent to the wing that is being modified. The letter indicates the
wing that is being changed. The impact of the modifications in case a will be assessed by the
opposite and adjacent rooms for instance, which are highlighted in black. The abc proposal
does not follow the above-mentioned rule though, since there is no wing being suppressed,
but rather splayed in angles, so all the atrium perimeter is being assessed.

As shown in Figure 15, none of the base cases present an sDA of more than 35%. However,
this value decreases to the 29% on base case abc, which is expected as its grid area is bigger
if compared with base case c. The values are presented in percentages, so comparisons among
the grids could be drawn. It can also be noticed that both the amount of area of DF above 1%
and the sDA decrease similarly as the grids are combined.

Figure 15: Grid area and area of DF above 1%.

As for the sDA metric, it is clear that the rooms that are located on the top floors and on the
opposite side of wing c will have more advantage due to its south orientation. It can also be
noticed that base case b had the lowest values, 33% for sDA and 37% for DF area above 1%
if compared to the same family of modifications. Base case c performed the best, achieving
an sDA value of 34,5%, while having 40% of its area with a DF above 1%. Base case abc
achieved an sDA value of 29,3% and a portion of 34% of its area with a DF above 1%, thus
being featured as the worst-case scenario.

40
Daylight Optimization in an office building through atrium improvements

5.1.2 ADF, DF median and dynamic daylight metrics


Figure 16 shows the daylight performance for the four base cases. The dot near the left lower
edges of the graphs represents the 1st floor, while the one near the upper right bounds
represents the 11th floor. The higher the floor, the higher the ADF, sDA and DF median values.

Figure 16: ADF, sDA, DF median and UDI autonomous per base case.

41
Daylight Optimization in an office building through atrium improvements

As it can be seen, all the cases behave in a similar way, where all the floors but the two upper
ones are located below BREEAM and LEED requirements. Note that the ADF of 2,1% is the
first BREEAM requirement, which precedes the demand of a daylight factor uniformity that
is not analyzed in this thesis.

The upper floors that have their values lying on the right upper side of the graphs are
complying with the certification requirements due to their higher sky view angle. This
scenario is in line with the findings of an investigation conducted by Du and Sharples (2010),
who claimed that the sky component dominates the region of the atrium where the distance
from the top edge towards a point at the bottom equals the atrium width. Therefore, a vertical
point in one of the atrium walls that equals the correspondent wing width represents the
boundary where the SC is more influential. On the other hand, the IRC has more potential to
generate a positive impact on the daylight conditions in the AR from that point downwards.

The ADF difference that ranges from 0,14% to 4,23% between the bottom and the top floors
in base case a illustrates the strong imbalance between stories. To tackle this setback, the
modifications will keep track on how many floors are able to reach the right upper quarter,
meaning that the proposals are able to improve the daylight quantity in each floor and increase
the chances of meeting the standards.

Base case c demonstrates a great potential to become autonomous in terms of daylight, as its
grids have more access to sunlight due to the orientation of the building. The 10th and 11th
floors reached sDA values of 61,4% and 83,2%, which are lower if compared to the same
floors on base case b, 71,2% and 87,8%, respectively. However, most of its floors have higher
values if compared to the floors in base case b. The ADF and sDA seem to be better distributed
among floors in the options that included the grid on wing b. Lastly, case abc decreased
somewhat the values, yet they follow a more uniform increase towards the top floors.

Regarding the DF median and the UDI autonomous, the top floor in all cases increased steeply
if compared to the one underneath. The DF median reached a value of 3,85% on the 11th floor
of case b, while its 10th floor presented a value of 2,18%. Increasing the number of bounces
in the simulations would possibly lower the difference in the values between the floors,
nevertheless this investigation aims to quantify the impact of changes in a broader way and
increasing the quality of the simulations would drastically increase their time.

The DF median is a rather revealing metric and shows that while half of the values in a room
are above a certain number, the other half is below. This metric is acceptable by Miljöbyggnad
and illustrates in a better way the daylight conditions in a room in terms of distribution,
whereas the ADF can be always boosted by the values next to the fenestrations. As it can be
seen, just three of the base cases are able to achieve the certification system on the top three
floors. Base case a presented DF median values for the 9th, 10th and 11th floors of 1,19%,
2,17% and 3,65%, respectively.

The maximum UDI of 60% is reached on the top floor of base case b. Some of the UDI values
on base case c are slightly lower if compared to its alternatives. That can be explained due to
the fact that the grids are facing south and east, therefore the upper floor values tend to fall on
the UDI exceeded range.

42
Daylight Optimization in an office building through atrium improvements

5.2 Parametric study


The results from the parametric studies will be presented in the following chapters. Each
investigation, namely geometry and LRV effects, were separated into their own sections, so
their impact on the building daylight performance could be analyzed separately. The main
idea of this parametric study is to test how different shapes and materials can affect this
specific atrium design, however they also open a precedent for further investigations in atria
that do not have regular shapes, where the interaction between the different components is not
so evident, but rather complex to understand. In addition, the intention of these studies is to
compare options and verify which could combine cost effectiveness with high daylight gains
in the AR.

5.2.1 Effect of geometry


As reviewed in the literature about atria, the geometry is the most important factor when it
comes to daylight quantity in the AR. It defines not only how the space embrace the building
and its occupants, but also how light will be able to penetrate it, since this is one of the most
desired characteristics of atria. Illuminating these areas with light is desirable, yet many atria
also have the intention to illuminate the adjacent rooms. Due to its shape, the studied atrium
has an aesthetical potential to surprise and create an interesting effect indoors. On the other
hand, and as evaluated in the previous chapters, its shape and depth does not allow daylight
to properly permeate the AR.

To tackle this setback, some proposals were created in line with the original project to avoid
massive changes. Since the quantity of daylight in a room is strongly dependent on the portion
of the sky that it sees, the main concept lies on the potential to maximize this view by pulling
down different wings of the edifice and see how the illumination levels change according to
every alteration. Each modification has a cost and therefore the proposals also account for
area losses and additions.

5.2.1.1 Spatial daylight autonomy (sDA)


The first set of studies show how each modification affects the daylight conditions in the
adjacent rooms by utilizing the sDA. This metric was particularly chosen as it considers the
annual climatic variations and the location of the building. The sDA also provides the
possibility to understand with only one number how the natural light situation improves or
declines in the whole case study.

As the daylight quantity in the indoor spaces are mostly dependent on how much they can see
the sky, the main goal was to gradually increase the sky view angle by decreasing the height
of the building in steps of two floors at a time. According to the municipal regulations, it is
possible to build up to 75m height on the site, so the proposals were developed according to
this regulation.

The letter “a” stands for the wing that is being modified and the number next to it stands for
the tower that is being stacked to make up for the area losses. The relation between area losses
and daylight gains is shown in the area of DF above 1% chapter.

43
Daylight Optimization in an office building through atrium improvements

Figure 17 shows the first group of modifications that were proposed.

Figure 17: sDA for cases a1 to a3, b1 to b3 and c1 to c3.

44
Daylight Optimization in an office building through atrium improvements

As it can be seen, regardless of the tower position, the increase on sDA for the all the floors
are substantial. By decreasing two floors on option a1, the sDA increased from 33,5% to 39%.
Case a3 showed to have the best performance in terms of daylight autonomy.

Despite the fact that the grids are oriented towards north, a3 has the tower in a position that
has less surface area blocking the visibility of the sky from the AR. If compared with the base
case, bringing down eight floors increased from 33,5% to 60% the area that is achieving 300
lux for over 50% of the time during the year. LEED requires this area to be at least 55%, so
the only options that have the potential to achieve this condition are the 8 floors step in each
of the a cases.

The second set of investigations comprised modifications on wing b. Since the towers that are
created to compensate the area losses on this wing have a larger floor area, all the options for
this case will have an area surplus, which can be advantageous for the developer if the natural
light conditions increase alongside as well. The first two recommendations increase in about
the same level the daylight performance in the AR.

Cases b1 and b2 behaved similarly. The first one increased the sDA from 32,5% to 58% when
eight floors were pulled down. Conversely, b3 appeared to underperform in relation to the
previous cases, as its last modification presented a value of 50%. This option seems to demand
a strong effort, as the building area is larger than the others and the rooms do not get the same
good daylight conditions as cases b1 and b2. This could be explained by the fact that the tower
which is located in the south side blocks most of the sky view and sun path from the rooms
located in the opposite side of the atrium.

Wing c has the largest amount of floor space when related to the distinct wings and
consequently has the largest potential to increase the natural light situation in the AR.
Conversely, diminishing the number of floors in this wing will substantially decrease the area,
which might represent a drawback for the developer.

The graphs show a dramatic growth of the sDA values regardless where the tower addition is
being placed. Despite the building located in front of wing c, the analyzed areas are still able
to take a great advantage of the east and southeast orientations. By pulling two floors on wing
c towards the ground, the c1 values increased from 34,5% to 45%. The tower that is placed
across wing b blocks most of its sky visibility, nevertheless its height does not represent a
large impact in the universe of such a considerable improvement. Lastly, the suppression of
eight floors has sharply rose the sDA from 34,5% to 77% in case c3. This steep growth can
be explained as the inner atrium facades have mostly become an outdoor envelope, as they
are more exposed towards the surrounding conditions. If compared to the actual scenario, the
last modification has more than doubled the daylit area.

Overall, all the geometry adjustments within the tower alternatives significantly improved the
AR daylight quantity. Although they all similarly contribute to a better well-lit indoor
environment, it is important to consider the placement of the tower not only in terms of
obstacle, but also in terms of aesthetical value. So far, the c family of modifications has
presented the greatest improvements, followed by the cases a1, a2 and a3. In contrast to cases
b1, b2 and b3, the rooms investigated in the previous alternatives are facing the sky directly,
while the spaces in the second set of modifications are lying across each other.

45
Daylight Optimization in an office building through atrium improvements

Figure 18 illustrates the daylight behavior in the AR for the different geometry compositions.

Figure 18: sDA for cases a1+2 to c3+2+1.

The idea of these alternatives was to verify whether these options would be advantageous
over the tower arrangement.

46
Daylight Optimization in an office building through atrium improvements

The options that merged two wings (a1+2 and a2+3) to compensate the area losses are now
increasing one floor at a time, whilst the wing that is being suppressed still decreases two
floors. On the other hand, cases a1+2+3 and a3+2+1 increased in steps, which follow either a
clockwise or counter clockwise direction. Both groups of changes increased the sDA alike,
even though choices a1+2 and a2+3 showed a better performance than a1+2+3 and a3+2+1
when only two floors were deducted from the original volume. The lower values are probably
due to the addition of all the free wings1 one floor up in case1+2+3, which blocks more the
sky view from the AR.

The arrangement a2+3 presented blandly higher values, which are in line with the lack of
obstructions in front of the studied rooms. The same case also had a considerably growth that
ranged from 33,5% to 57%, being slightly similar to case a2. It is noticeable though, that the
volumes presented in this group of adjustments demonstrated to be less effective than the
tower group a1, a2 and a3. When comparing a1+2+3 to a3+2+1, the first has overperformed
the last in the eight floors change. By looking at the models, it is clear that the sky view angle
is modestly wider from the AR in a1+2+3.

Option b1+2 showed the most excellent performance between the four new shapes by
demonstrating an sDA that increased from 32,5% to 57% if compared to b1+2+3 that showed
an increase that ranged from 32,5% to 50%. A closer look into the performance of the left
grids for case b1+2 might reveal higher values regardless of the changes in the atrium shape,
since they are oriented towards southwest. Cases in the b family are more sensitive to
additions and subtractions in the original volume, even though in some cases, distinct
configurations can present nearly the same results. This situation is illustrated by cases b1+3
and b1+2+3, where the values have a steady growth and both cases reached their peak with
an sDA of 52% and 50%, respectively. Both cases also share the same obstacle creation in
front to the sun path. It is also worth comparing these four cases with the tower options and
as it can be seen, case b3 achieved similar results to b1+2+3. The difference between these
two options is rather low.

Decreasing the number of floors on wing c revealed to be the most powerful strategy for the
sDA metric, as it exposed a good portion on the atrium facade towards the surrounding and
consequently towards daylight and sunlight from the south. These cases are specially
interesting as they directly show that the building configuration on the free wings have little
if no influence at all on the sDA. Concerning the suppression of eight floors, the four cases
presented an increase from 34,5% to 76%, which is more than double. Since LEED requires
a 75% sDA for achieving three points, all the options within this configuration are able to
fulfill the demand.

By looking at the four different cases, option c1+2 showed the greatest improvement. The
combination of the wings offered no obstruction and the starting sDA values in the first
change substantially increased from 34,5% to 46%. The last two cases on the bar charts
presented almost equal results, except for the first modification in case c1+2+3, where the
sDA increased from 34,5% to 44%.

The four last geometry improvements came in the shape of a stepped section. They were
designed to be splayed in angles of 5° to 20° in each of the wings that were studied before.

1
Free wings: Wings that are not being suppressed.

47
Daylight Optimization in an office building through atrium improvements

For the four following shapes, all the previous grids and adjacent rooms were investigated
together, as there are no wings being diminished this time.

It is clear in Figure 19 that splaying the walls of the atrium brought an interesting increase of
the sDA in the AR. In case a, the sDA ranged from 35% for an angle of 5° to 44% for an angle
of 20°. Case b presented relatively lower values with an sDA of 33%, 35%, 39% and 41% for
each angle. Case c reached a maximum sDA of 41% and apparently is the wing that takes
more space of the building in order to be splayed. If all the wings are combined, the daylight
scenario proved to advance sharply in relation to the changes in one wing only, even though
it is important to consider that this option takes a higher effort to be implemented. A 20° angle
was not feasible on the abc option, because it would not leave any available space on floors
10th and 11th.

Figure 19: sDA for cases a to abc.

The first splay in case abc reached the same sDA value as the 20° splay in modifications b
and c. Finally, the 15° splay accomplished a steep degree of natural light, with an sDA of
53%. Changes b and c correlate, as they show rather similar results. By splaying wing c
though, the geometric features of the atrium change drastically and give a preferred and
exceptional sense of higher quality for the occupants who sit in the AR. Option a demonstrated
to be the best wing performer by fulfilling an sDA of 44% against the initial 29,5%.

The advantage of these new geometries is the establishment of an alluring atrium outline from
the inside. Furthermore, the wall area along the atrium also increase, which consequently
provides more spaces with a view to the outside, and most importantly with daylight. Bearing
that in mind, the sunlight harvesting is a unique advantage of wing a. By decreasing the PAR
in each floor, the light admitting area will increase, leading therefore to a drop on the WI.

48
Daylight Optimization in an office building through atrium improvements

5.2.1.2 Area of DF above 1%


Figure 20 displays the grid area with a DF above 1% as a function of the area losses. Each
point on the graph corresponds to one modification step, that vary from the suppression of
two to eight floors. The grid area is the sum of the values in the eleven floors. The area losses
and gains are presented in relative values in relation to the original total floor area.

Figure 20: DF area and area losses/gains for the wing suppression arrangements.

49
Daylight Optimization in an office building through atrium improvements

The daylight factor is a well stablished metric and provides a good idea whether a given space
has a potential to fetch daylight under overcast sky conditions. Although it does not take into
account local climate factors, it is widely used by certification systems, such as Miljöbyggnad
and BREEAM, as well as by some regulations, especially the BBR. As a consequence, this
investigation has chosen to demonstrate the percentage of grid area that is achieving a DF
above 1% due to the size of the study, which is considering a large amount of area, and due
to the fact that this data is more comprehensive for this scale, as the whole building is being
analyzed. Besides, the main goal is to compare the difference between the shapes and evaluate
which could be more cost effective and improve the daylight conditions in the AR at the same
time.

It is interesting to observe that group a is split into three different directions concerning area
losses and additions. In terms of cost effectiveness, a3 lost approximately 5% of the project
floor area to achieve the same DF results as case a2, which on the contrary, had an area gain
of 5%. Considering the CBRE report for the last quarter of 2017, this addition could represent
a potential leasing value of nearly 8,3 million SEK per year. Case a1 had the worst
performance among the three, however the area losses were not so significant. It achieved a
peak of 67% of DF area above 1% and a total area subtraction of 1%.

The area of DF above 1% in option b1 went up from 37% to 64% and had its area increased
to 5% in relation to the base case. On the other hand, b3 demonstrated an enormous increase
of 11% in the potential leasing area but did not perform as good as b1 in area of DF above
1%. The wing that is being added on this case is the largest, however it blocks most of the sky
view from the opposite AR. The AR in group c were the ones that were affected the most,
thus having the highest area of DF above 1%. The three cases within this family displayed
nearly the same increase on DF values if compared to the base case, that ranged from 50% to
79%. Conversely, the area losses were large, particularly in option c3, where the area deficit
reached 11% of the original floor area. This situation could represent a profit loss of
approximately 18,3 million SEK per year.

The area of DF above 1% in cases a1+2 and a2+3 increased steadily, despite its similarities.
The second one though, has neither lost, nor gained area. As a consequence of wing b having
the smallest floor area, there is usually a leasing space surplus regardless of the volume
arrangement to compensate its suppression. Yet, the escalation on the DF area above 1% is
not as satisfying as in group a, for instance. Alternative b1+2 started with an area of DF above
1% of 40% and ended up at 61%. According to the chart, group c brought a great improvement
in DF area in spite of its considerable floor space losses. Option c2+3 drastically increased
the area of DF above 1% from 40% to 79%, almost doubling the base case value.

There is a downward trend for the counter and clockwise additions. As the area of DF above
1% increases, the area losses also increase, as in type c3+2+1, which reached an area loss of
12,5% of the original floor space. This percentage might represent a loss of nearly 19,9 million
SEK per year. Concerning the area of DF above 1%, the last modification reached a value of
79%. Option b1+2+3 and b3+2+1 continued to have a rentable area surplus, but in these
specific cases the volume diminishes whereas the DF area increases. On the last modification
of type b1+2+3, the space loss tends to find an equilibrium with the original case by having
an extra area of only 3%, yet it improved the area of DF above 1% from 37% to 58%.

50
Daylight Optimization in an office building through atrium improvements

Whilst presenting area losses of up to 5% in relation to the base case, the area of DF above
1% went up from 39% to 66% and 65% in types a1+2+3 and a3+2+1, respectively.

As for the volume alterations that concern the wing splaying, Figure 21 embraces the last
stage of geometry modifications.

Figure 21: DF area and area losses/gains for the wall splaying options.

Although they do not offer any increase on the floor area, the idea was to test the potential of
the stepped section and in what level they could boost the area of DF above 1% while splaying
the walls in certain angles. Most importantly, a relation can be drawn between the families
that work with wing suppression and the group that rely on the wall splay, showing their
strengths and weaknesses. Whereas the grid remains constant in the past modifications, the
angled volumetric alterations widely open the office area towards the atrium. Types a, b and
c coincide to some extent in area losses. Case a presented an area of DF above 1% that
increased from 38% to 45%, while losing a floor space that encompassed a range from 1% to
6% in relation to the base case.

Wing b demonstrated a great performance and peaked to an area of DF above 1% of 49%,


whilst presenting a deficit floor space of 7% for an angle of 20°. In this specific scenario, the
AR were elongated towards southwest, hence decreasing the PAR step by step on each floor.
This occurrence is in line with the studies conducted by Liu et al. (1991), where his findings
showed lower PAR values improved the DF conditions in the AR. Nevertheless, this type of
shape could unevenly distribute the illuminance across the space. Alteration c has the largest
facing wall towards the atrium and can consequently take a great advantage of the
homogenous illuminance from the north orientation without any need of shading devices. It
also demonstrated to be the most efficient option in area of DF above 1%, as it presented a
value of 49% value, but with an area loss of 7% if compared to the original shape.

The cases that combined all the wings in the effort to fetch daylight as much as possible
achieved an area of DF above 1% of 46% by inclining the walls 5°. Unfortunately, the last
splay of 15° sharply expanded the area losses to 24% of the base case floor area.

51
Daylight Optimization in an office building through atrium improvements

5.2.1.3 ADF, DF median and dynamic daylight metrics


Due to the large amount of data and the limitation of time, four cases were selected to be
investigated in relation to how the improvements affected each floor. It was also interesting
to examine the same impacts on the wall splaying options. By looking at Figure 22, it is
possible to compare the results of each increasing step. The code “2f”, for instance, represents
the number of floors that are being suppressed.

Figure 22: ADF, sDA, DF median and UDI autonomous for case a1, b1 and c1.

52
Daylight Optimization in an office building through atrium improvements

The points that lie on the upper right quarter on the graphs on the left are the floors that are
complying with both BREEAM and LEED requirements. For the figures on the right, the
threshold line for the DF median was placed at the 1% value, which is the minimum required
for achieving Miljöbyggnad. As the floors on wing a are pulled down, the sDA and ADF
started to increase at a steady rate. The highest numbers on the top floor for both metrics are
reached when only two floors are suppressed.

As the number of floors decreased in case a, the tower increased in height, meaning that the
sky view from the grid is being blocked. The ADF on the top floor decreased from 4,95% in
modification a1-2f to 4,1% in modification a1-8f. On the other hand, most of the values for
both metrics increased on the lower pavements as more floors on wing a were suppressed.
This phenomenon can be noticed by a difference in the ADF between the sixth floor of a1-2f
and the sixth floor of a1-8f that shifted from 0,75% to 2,2%, respectively. The a1-8f alteration
brought six floors towards the first LEED requirement, whilst the base case had only two
floors in compliance with the standard. Regarding the DF median and UDI autonomous
evaluation, the base case had eight floors below the Miljöbyggnad threshold of 1%.

As the modifications took place, the number of floors with a higher DF median started to
increase and reached a maximum value for the a1-8f alteration of 0,67%, 2,28% and 3,85%
for the 2nd, 6th and 11th floors. Comparing to the base case values for the same floors,
suppressing eight floors considerably increased the DF median in the lower and middle floors.
As seen, the UDI for the base case follows a continuous upward trend until it peaks to
approximately 59%. On the contrary, the a1-8f alternative shows a downward fashion towards
the upper floors, a behavior that is aligned with the fact that the tower is serving as an obstacle,
yet it does not compromise the UDI on the bottom floors.

In case b1, the situation differs from the preceding case in the sense that the modifications did
not seem to affect drastically the daylight in the AR of the lower floors. A particular feature
of alternative b1 is that the steep difference between some floors in relation to the ADF
remains, such as the one between the 6th and 11th floors in modification b1-4f, with values of
0,88% and 4,82%, respectively. Nevertheless, as the floors on wing b were being removed,
the middle floors on b1-8f responded with an increase on the daylight quantity and showed
sDA values that ranged from 60% to 87% from the 6th floor up. In relation to the UDI metric,
the maximum values were achieved in modification b1-8f, especially in the floors below the
top ones. It can be speculated that some of the illuminance values could be falling on the UDI
exceeded range. Regardless of the option, the UDI follows the same trend and decreases in a
small scale before it reaches the upper most floor. This can be confirmed by the similar values
between b1-2f, b1-4f, b1-6f and b1-8f on the 9th floor which are 59,3%, 58,4%, 58,8% and
58,8%. The base case had only three floors complying with a DF median of 1%, while b1-8f
increased the number to eight.

Case c1 outperformed the anterior choices visibly, not only in ADF terms, but also in sDA
and UDI. As the modifications were taking place, the values increased steeply, which can be
illustrated by the bottom floor sDA of case c1-2f, that showed a value of 8,8%, against the
bottom floor of case c1-8f that displayed an sDA of 39,6%. The ADF also increased
significantly between the two alterations, from 0,18% to 0,86%. The trend of having lower
ADF values on the upper stories as the tower is erected remains and it demonstrates that the
volume that is being built to compensate the area losses does impact the daylight performance
to some extent.

53
Daylight Optimization in an office building through atrium improvements

Step c1-6f, scored eight floors over the Miljöbyggnad requirement, while c1-8f scored almost
the totality, leaving just one floor behind. The UDI autonomous peaked at 54,7% for most of
the steps, which is relatively lower if compared to a1. Lastly, the UDI shows a uniformity
among the majority of the upper floors for the last step (c1-8f), meaning that most of the times
during the year, the illumination levels fall between 100 and 2000 lux and indicate that no
electrical lighting is needed during the occupied hours.

As for the angle modifications, the results from each wing for the 15° splay and their
combinations were merged into Figure 23.

Figure 23: ADF, sDA, DF median and UDI autonomous from cases a to abc.

According to the sDA and DF area analyses, the combination and inclination of the walls
along the atrium perimeter presented a great result, nonetheless the floor area losses were also
significant. According to the chart that plotted the eleven floor values, the performance of
case abc15° outworked the one wing splays by placing four stories on the upper right quarter
on the left chart. The ADF in the 7th floor sky rocketed to 2% against 0,51% from the base
case. The major contrast between the one wing splay options and the abc cases is that the
bottom floors are also benefited if the whole perimeter is inclined. This phenomenon can be
clearly observed in the chart, if one considers the higher ADF and sDA values of the lower
floors of case abc15°. Almost half of the floors on abc15° had complying DF median values.

Option c15° leads the growth trend in sDA, except on the top floor. It is clear that by inclining
wing c, the sky view is opening towards the southeast orientation, thus benefiting directly the
rooms across and adjacent to that inner facade because of the sunlight access. The ADF is
also greater in most of the cases. Looking at the UDI autonomous, the options presented a
similar behavior for most of the floors and if compared to the base case, the numbers on the
first floors increased dramatically.

54
Daylight Optimization in an office building through atrium improvements

5.2.2 Effect of light reflectance


For this specific thesis project, the aim was to study the potential of the reflectance values
keeping the same WWR of 40% along the whole inner facade and compare these plans with
the changes made on the geometry. For the present case, five diverse LRV were tested 1) 30%
2) 40% 3) 50% 4) 60% and 5) 70%. The second option is already adopted by the base case.

5.2.2.1 sDA and area of DF above 1%


The wall reflectance values were analyzed in the four base cases, so they could be compared
with the geometry modification approach. The results shown in Figure 24 reveal a gradual but
effective impact of higher LRV.

Figure 24: sDA for LRV cases.

By increasing the surface reflectance from 30% to 70%, an overall sDA increase from 33%
to 42% could be reached in case c. The results among the four base cases vary without no
notable divergences and follow the same upward trend. Base case c presented a slightly higher
number. This combination of grids seems to be the most beneficial between the four, as both
have a preferred cardinal orientation. However, case abc is the realistic approach, since the
whole perimeter will be affected by the LRV, as the building structure remains originally the
same. Looking closer into case abc, the sDA increased in a slow pace if compared with the
massive effects caused by the volumetric changes. A material that could potentially contribute
with a LRV of 70%, would increase the spatial daylight autonomy from 30% to 37%.

55
Daylight Optimization in an office building through atrium improvements

The area of DF above 1% was also analyzed for the LRV modifications, but since there was
no area losses or gains, the main objective was to assess this strategy under a uniform overcast
sky. The behavior of the enhancements coincides with the sDA evaluation and show the same
upward trend among the different base cases. Type c is the one which shows the maximum
area of DF above 1%, with 46%, whereas the combination of rooms abc underperformed by
reaching its highest improvement with a value of 41%. According to the chart, it is apparently
beneficial to locate office rooms along the perimeter suggested by type c, as it presented an
area of DF above 1% that was higher than type abc. Option b, where the rooms analyzed are
situated across each other, displayed the second lowest performance.

5.2.2.2 ADF, DF median and dynamic daylight metrics


Lastly, case abc was chosen to be further investigated when it comes to the daylight metrics
in each floor, as it is composed of a group of grids that correspond to office rooms along the
atrium perimeter. Figure 25 presents the evaluation of each floor and how the average daylight
factor, sDA and DF median increase according to the enhancement on the wall LRV.

Figure 25: ADF, sDA, DF median and UDI autonomous for LRV cases.

Looking at the ADF at the bottom floor, the value stepped from 0,09% to 0,19%, but it took
a LRV 40% higher to be able to raise it to that level. Despite the higher sky component
influence on the top floors, these floors showed to be also sensible to LRV changes. The ADF
on the upper rooms jumped from 3,71% with a LRV of 30% to 4,12% with a LRV of 70%. It
can be also noticed that the reflectance values are most influential on the bottom floors, since
these changes doubled the ADF on the AR.

The DF median shows the same fashion, where the highest floor has considerably higher
values in relation to the 10th floor. Only the 60% and 70% LRV are able to push three floors
towards the Miljöbyggnad achievement. As for the UDI autonomous, the digits tend to
increase homogenously. The 11th floor showed a low difference in the UDI metric for different
LRV, while the uppermost divergence was felt on the second floor, which the LRV of 30%
reached an UDI of 15% and the LRV of 70% reached an UDI of 26%.

56
Daylight Optimization in an office building through atrium improvements

6 Discussion
This thesis aimed to evaluate the current daylight conditions of the building, as well as to
propose changes to improve the natural light scenario in the AR. The discussion chapter was
divided according to the results sections to facilitate their comprehension. As discussed
before, the metrics chosen for this investigation are in line with the Swedish regulations and
some of the most widely adopted certification systems in the construction sector. In order to
answer to the two questions that guided this investigation, the parametric studies were
concentrated in the geometry and LRV effects. As mentioned in the literature review, these
were the most influential parameters affecting the atria studied. Most importantly, the split of
the building into different wings was a product of the current design, so the proposals could
offer a variety of forms to still keep the architectural dialogue with the surroundings, while
improving the daylighting conditions of the building.

6.1 Base cases


The daylight assessment of the base cases consisted of adopting a perimeter grid along the
atrium in four different ways according to each base case. Since the main objective was to
study the influence of the building geometry on the daylighting in the perimeter offices, the
original windows located on the outer building envelope were not considered. On the other
hand, the original side fenestrations could be inserted for future studies to verify how the side
lighting conditions could further improve the daylight conditions. Some of the LRV may also
differ from the original project. However, the base cases analyses lay the ground for the
parametric studies, so the results can be comparable. Consequently, this investigation lies on
the relation of a specific atrium assessment and its urban context. This is useful for taking
early decisions and guide the project process at the beginning of the design stage.

Results for sDA showed that none of the base cases complied with the LEED certification
system, as all the values were below 55% for the grids analyzed. Moreover, the base cases
presented different values for both sDA and area of DF above 1%. These variations could not
only be due to different grid combinations, but also to the internal configuration of the
building, which is relatively complex. Base case b, that combined the largest grids, was the
second worst performer. Base case c featured as the best performer. The average values were
negatively affected on base case b, as the AR have a lower sky view angle on the lower floors,
especially when the evaluation points reach the narrowest side of the atrium. This
phenomenon was previously discussed in the literature view, where it was pointed out that
the DF values in the corner of rectangular atria are usually lower. The combination of the
three grids for base case abc, which is the scenario that probably resembles reality, since most
of the office rooms are potentially located along the atrium perimeter, presented the worst
results. The proportional daylit area is lower than the other base cases, which could be due to
the number of corners presented in this particular grid combination.

The evaluation of each floor showed that only the two top floors were complying with the
regulations and certification systems. Their ADF, DF median, sDA and UDI were steeply
increasing towards the top floors due to an open sky view angle. The analyses of the base
cases also show that the current atrium configuration provides a great lack of daylight
uniformity among the floors.

57
Daylight Optimization in an office building through atrium improvements

6.2 Parametric study


The parametric studies were divided into changes on the geometry and the LRV of the inner
atrium facades. The following chapters discuss the main outcomes of the investigation. Figure
26 shows all the parameters investigated and their respective AR grids.

Figure 26: Geometry and LRV modifications.

6.2.1 Effect of geometry


According to the simulations carried out in this thesis, the geometry proved to significantly
influence the daylight conditions in the AR. It can be generally observed that the sDA values
dramatically increased as the number of floors were displaced in each wing (different
geometries resulted in different outcomes). Option a2 performed worse than a1 while
suppressing two floors, for instance. That reaction can be fairly understood since there is more
mass surrounding the atrium than in the other cases and the tower that is being erected blocks
the sunlight path on the south orientation. Option b3 faced the same problem, however this
family of modifications presented lower results if compared to cases a and c. Most
importantly, options b1 and b2 show that it is possible to increase the daylight penetration in
different ways, as long as the atrium configuration shifts from an enclosed shape to a semi-
enclosed one.

Surprisingly, the stepped height solution underperformed in relation to the tower cases. One
could suggest that a higher tower resting over one wing could block a considerable portion of
the sky, thus diminishing the potential of the grid to fetch daylight. On the contrary, the
investigations demonstrated that distributing the volumes over the opposite and adjacent
wings at the same time might represent a liability. If the tower is added in certain spots, it can
probably help the light to penetrate on the rooms by contributing with its reflection. However,
this would have to be further investigated in a more detailed study. It is confirmed that having
only one higher volume resting over one wing is more beneficial than having more volumes
added to the top of the free wings, even if they are shorter.

58
Daylight Optimization in an office building through atrium improvements

By drawing a relation between the tower cases and the other volume additions, one can see
that the difference is small, yet the tower alternatives produced higher results. As mentioned
before, surrounding the atrium again with a mass will produce the same effect of reducing the
sky view angle, even though the height of the floors is distributed along the free wings. On
the other hand, it is crucial that the tower is positioned in the right place, otherwise it might
block the sky view and compromise the daylight performance in the AR. Looking at the big
picture, regardless of the shape chosen, the increase on the natural light quantity is significant,
especially on cases c, where the sDA increased from 34,5% to 76%.

Regarding the wall splaying options, there is no area compensation on these cases, as any
addition on the top would most likely compromise the aesthetics of the initial proposal and
create a conflict with the inclined walls. One of the advantages of the stepped section is the
automatic creation of terraces in front of every wing that is being pushed inwards. The terraces
can not only produce interesting places for social interaction, but also provide a reflective
horizontal surface next to the office window.

To facilitate the comparison and understanding of how much area loss or gain each volumetric
change is producing, the space changes were calculated as percentages in relation to the
original building shape, so it was possible to draw an instant relation between area of DF
above 1% and leasable area alterations. It is crucial to understand that the area of DF above
1% concerns only the perimeter of the atrium that is being analyzed, however the alterations
to improve the daylight situation on the edifice take place in the whole volume.

Despite the substantial increase in area of DF above 1% in all c cases, they presented great
area losses, since wing c has the largest floor space. Option a2+3 is an attractive choice, since
the leasing area did not change. As previously mentioned, volume a2+3 offers no obstruction
to the AR in the atrium, so it enhances their view to the sky, hence leading to a higher DF.
Cases b1, b2 and b3 have all succeeded not only in elevating the DF area, but also in increasing
the leasing area. In short, the b cases offered more advantage in terms of leasing space but
lacked in terms of daylight quantity in comparison to the other alternatives.

Each floor was also evaluated for a1, b1, c1 and the wall splaying cases. It is clear that the
daylight penetration does not reach a sufficient depth in the rooms in the b cases, as the wing
that is being suppressed is located in their adjacencies and not across them. Consequently, the
top floors remain with high levels of daylight and the lower ones show a slight increase as
wing b is pulled down. On the other hand, the bottom floors evaluated in case c presented
higher increase on their values. Although the LEED threshold of 75% is not drawn in the
chart, it is possible to see that a great portion of the c1-8f points lie on the right side of it,
meaning that most of them can even achieve three points in the certification. Conversely, the
DF median values are high enough on the top floors to be considered satisfactory.

The simulations indicated that this option had higher values for the UDI exceeded metric, thus
demonstrating that a shading system in this case would be valuable to avoid overheating, as
the facades are fully exposed to the south and southeast directions. Lastly, splaying all the
inner atrium walls together amplified the sky view from the AR, which can be confirmed
since most of the floors on option abc15° indicated a growing uniformity between their DF
median.

59
Daylight Optimization in an office building through atrium improvements

Overall, the original volume is rather complex, but it offers a number of possible combinations
that can be interesting in terms of architectural design, as well as in terms of daylight for the
occupied spaces along the atrium perimeter. The WI cannot be fully related to the
modifications, as it considers atria that have regular shapes such as rectangular and square
geometries. Even so, the results prove that it is possible to combine different heights and
achieve exceptional outcomes in terms of daylight quantity.

6.2.2 Effect of light reflectance


Different LRV were also evaluated in the simulations. The light reflectance value is especially
important in enclosed atria as it can improve uniformity in the AR and elevate the daylight
levels at the bottom floors and ground. However, its effect can be rather limited as it was
proven the DF levels are extremely influenced by the sky component.

The LRV qualifies as an important strategy if there is no space for major changes in the design,
but it strongly depends on the properties of the materials and on the WWR. As previously
examined, the larger the WWR, the lesser the influence of the wall reflectance. This balance
is slightly complicated, as bigger windows will open the sky view, but at the same time
decrease the number of reflective surfaces towards the atrium. Some strategies have already
been discussed in the literature review and suggested that the openings on the top floors could
be smaller to avoid glare problems, while they could be larger on the bottom rooms. This
approach would be able to direct more reflected light towards the bottom, where the big
openings would be ready to collect more daylight effectively.

By just changing the LRV of the inner walls from 30% to 70%, the sDA increased from 33%
to 41% in case abc. Although it is discernible that the values considerably increased, it is
evident that this strategy used alone is not sufficient to raise the numbers towards a full
compliance with standards and regulations. Moreover, the results showed a daylight
imbalance between the floors, as the difference in the ADF at the bottom floor and the top
floor is steep, for example.

There is also a potential strategy that lies on the combination of both high LRV and one of
the geometry modifications. However, a more dedicated approach has to be carried out in
order to find which volume alterations could enhance this compendium. For this investigation,
the internal walls and floors were set with a LRV of 70% and 40%, respectively, representing
most of the materials available in the market and widely applied in office buildings. LRV
higher than 80% are hardly achievable for external cladding, given the fact that materials get
dirty with time, so they were left out of this investigation. Nonetheless, these values can be
increased if necessary and according to the specification of project.

60
Daylight Optimization in an office building through atrium improvements

7 Conclusions
This thesis investigated the current daylight conditions in the adjacent rooms of an atrium in
an office building located in Gothenburg, Sweden. This building is located in a dense urban
cluster. The simulations were guided by two main questions: 1) The parameters that could
influence daylight conditions the most in the adjacent rooms, and 2) The atrium design that
would best suit the study case. Firstly, the geometry was speculated as the most influential
parameter, followed by the idea that the light reflectance values would have a limited impact
on the AR. Considering the questions and hypotheses mentioned above, it could be concluded
that:

 The actual atrium configuration does not allow daylight to penetrate properly into
the adjacent rooms, as the atrium and the floor plans are deep;
 The current atrium configuration allows only the grids on the 10th and 11th floors to
comply with BREEAM and LEED thresholds for daylight. As for Miljögyggnad, the
top three floors managed to achieve the bronze category in the certification system;
 There is a great difference in the DF, sDA and UDI values among the eleven floors,
which can be explained by the portion of the sky that is more visible from the top
ones, while the bottom floors rely on the internally reflected component (IRC);
 The geometrical alterations proved to dramatically increase the daylight quantity in
the AR, specially the cases from group c, that increased the sDA values from 34,5%
to 77%;
 Cases c presented the best performance, confirming that opening the atrium towards
the southeast orientation is the best strategy to increase the sDA. For these cases, all
the tower positions resulted in the same daylight outcome in the AR;
 Cases b did not perform as well as the ones from groups a and c. The wing that is
being suppressed lies adjacently to the investigated rooms, therefore the sky view
across some of the rooms remained similar;
 By opening the wing towards the northwest in cases a, the sDA and area of DF above
1% were higher than in the volumetric changes from group b, proving that there is
an enormous potential if daylight is fetched from the north orientation as well;
 The combination of wings and the counter/clockwise additions did not perform as
well as the tower options. However, the differences were not significant, hence
giving the architects flexibility in design options;
 The wing splaying options showed a lower performance in terms of daylight quantity
if compared to the wing suppression cases, however they offered an interesting
volumetric effect for the rooms located on the atrium perimeter;
 The area of DF above 1% as a function of the area losses were also analyzed and
according to the results, the cases presented in the b family were the ones which
gained the largest floor area, but showed the worst daylight performance;
 Conversely, the c types were the modifications which presented the highest area
losses among the wing suppression cases. Option c3 lost up to 11% of the original
floor area;

61
Daylight Optimization in an office building through atrium improvements

 Option a2+3 showed the best cost effectiveness while increasing the daylight
quantity in the AR, as it kept the exact same floor area;
 Case abc displayed a great amount of area of DF above 1% while splaying all the
wings at the same time, nonetheless the area losses represented 23% of the original
floor space;
 Looking at the sDA and ADF per floor, it could be seen that the cases included in
group a demonstrated a better daylight uniformity between floors, while the b cases
had higher values at the top floors and the c cases presented great daylight uniformity
conditions in most of the floors;
 Option c1 was the only one to score eight floors towards the BREEAM and LEED
compliance, whereas leaving just one floor behind the achievement of the bronze
category in Miljöbyggnad;
 An LRV increase from 30% to 70% escalated the sDA from 33% to 42% on case c.
These results show the potential of this strategy, but rather limited if applied without
any change in the geometry;
 A closer look into the LRV effect on each floor showed that the increase is relatively
substantial on the bottom floors. On the other hand, they are not sufficient to allow
the compliance with the regulations and some of the certification systems;
 Overall, pulling down wing c was the most effective strategy, as the sDA and area
above DF 1% doubled.

General conclusions
 Atria with asymmetrical shape do not follow the well index equation, therefore it is
more complicated to predict their behavior in terms of daylight performance;
 Researches, such as the one carried out by Saratsis et al. (2017), pointed out that
building with different heights is more beneficial than creating an atrium or
courtyard surrounded by walls with the same height. This thesis confirms the
hypotheses presented by the authors’ work, since it showed that a semi-enclosed
atrium with different geometry configurations yielded better daylight conditions in
the adjacent rooms;
 Opening the geometry towards different cardinal orientations can also increase the
useful daylight illuminance. Opening an atrium towards the north direction is
beneficial as the light coming from this orientation is uniform and no shading devices
are needed. On the other hand, the south orientation can take advantage of the
sunlight to increase the level of illuminance in an office building, even though a
shading system is extremely important in this case to avoid overheating and glare;
 Changing the geometry in the early stages of design revealed to have a great impact
on the daylight performance of the AR. Conversely, the LRV strategy may not be
qualified as a primary approach in deep atria, since it does not have the potential to
dramatically increase the natural light levels in the atrium perimeter rooms.

62
Daylight Optimization in an office building through atrium improvements

Future studies and limitations


This thesis project focused on finding an atrium optimum solution for the study case located
in Gothenburg. The investigation was limited to the perimeter office rooms along the atrium
as the main objective was to assess the daylighting improvements fostered by the atrium
modifications. The number of ambient bounces utilized in the simulations was four. It is
important to mention that a higher number of bounces would not only boost the uniformity,
but also the DF values. Although it is known that not all the construction is valued for leasing
purposes, all the area that is being lost or added was considered as an asset to be traded,
because it simplified the calculations for this thesis project.

Investigations regarding the daylight quality in the AR could be further developed in future
studies, as well as a proper shading system design for the AR that were exposed towards more
daylight and sunlight in the upper floors. It would be also interesting to assess the energy
demand and verify how the new atrium configurations would affect the thermal conditions in
the AR. Most importantly, future investigations could also address the potential of the whole
building area to comply with the Swedish regulations and the certifications systems
mentioned in this thesis.

63
Summary
Atria has been implemented as an architectural feature since ancient times in order to provide
an inner space that protects the building users from the outdoor climate, encourages
interaction and brings a good level of daylight into the atrium itself and the adjacent rooms.
Daylighting has proven to decrease the energy demand and the electrical lighting need of the
buildings. However, the relation among the atrium shape, its walls reflectance values and the
daylight quantity on the adjacent rooms follow a rather complex relation, that can be
simplified by the wall index for square and rectangular atria.

The literature revealed that the geometry is the most influential characteristic for the daylight
conditions both on the ground level and adjacent rooms. In addition, many authors have
investigated different atrium types, which can be divided into enclosed, semi-enclosed,
attached and linear. The studies showed that the deeper the atrium, the worse the daylight
conditions on the adjacent rooms. However, this type of atrium might be a good strategy in
warm climates, since less floors have access to direct solar radiation, thus demanding less
cooling. Shallower atria are prone to receive more daylight, but their adjacent rooms are more
exposed to the outdoor climate, which results in more heat losses in cold regions.

Contemporary buildings have been incorporated atria often in their design, but their projects
rarely analyze how the atrium should be designed in order to take the best advantage of the
climatic conditions to fetch as much daylight as possible. Therefore, this thesis aimed to
investigate which parameters influenced the daylight conditions in the adjacent rooms of a
triangular atrium of a building located in Gothenburg. The methodology proposed consisted
of dividing the building into four different wings, so the geometrical modifications could be
separated into different orientations. Different light reflectance values of the inner walls were
tested in the original atrium shape. The evaluation was conducted only in the perimeter of the
atrium and many different metrics such as daylight factor, daylight autonomy and useful
daylight illuminance were utilized to measure the daylight improvements. Furthermore, the
area losses and gains were also evaluated.

Results showed that suppressing the wings, regardless of the orientation, increased the
daylight factor values, as most of the floors had their sky view angle substantially increased.
The spatial daylight autonomy simulations also revealed that even with the presence of an
urban obstacle in the southeast direction, the sunlight could substantially contribute to the
increase on the daylight conditions in the adjacent rooms (AR). A diverse range of shapes
were tested in order to compensate for the area losses when one of the wings were pulled
down. The outcome of the investigation demonstrated that the daylight in the AR is slightly
influenced by how the new shapes are built around the atrium, however the largest differences
in the natural light conditions were felt depending on the orientation of the wing that was
being suppressed. The light reflectance values (LRV) of the inner facades were also changed
from 30% to 70%. The outcome of the simulations demonstrated that the LRV had a limited
impact on the AR due to the height of the atrium. Nonetheless, this strategy could successfully
increase the daylight situation in the AR if combined with an appropriate geometrical
alteration.

Overall, pulling down the southeast oriented wing showed to be the most powerful strategy,
not only to yield good daylight conditions in the AR, but also to comply with the regulations
and some of the certification systems assessed in the thesis.
References
Acosta, I., Varela, C., Molina, J.F., Navarro, J., Sendra, J.J., 2018. Energy efficiency and
lighting design in courtyards and atriums: A predictive method for daylight factors. Appl.
Energy 211, 1216–1228.

AGi32, 2018, viewed 2.11.18,


<https://docs.agi32.com/AGi32/Content/references/Perez_All-Weather_Sky_Model.htm>.

Aldawoud, A., 2013. The influence of the atrium geometry on the building energy
performance. Energy Build. 57, 1–5.

Alraddadi, T.A., 2004. The Effect of the Stepped Section Atrium on Daylighting
Performance. Archit. Sci. Rev. 47, 303–310.

Arkitema Architects, 2018, viewed 5.8.18, <https://arkitema.com/se>.

Baker, N.V., Fanchiotti, A., Steemers, K., 1993. Daylighting in Architecture: A European
Reference Book, 1 edition. ed. Routledge.

Bian, Y., Ma, Y., 2017. Analysis of daylight metrics of side-lit room in Canton: A
comparison between daylight autonomy and daylight factor. Energy Build. 138, 347–354.

Boubekri, M., Anninos, W.Y., 1996. Daylighting Efficiency of an Atrium: Part 1-The Four-
Sided Type. Archit. Sci. Rev. 39, 75–81.

Boverket, 2015. Mandatory provisions on the amendment to the Board’s building


regulations.

BREEAM-SE, 2018, viewed 1.31.18, <https://www.breeam.com/>.

BREEAM-SE, 2013. English manual for new construction and refurbishment. Sweden
Green Building Council.

Building Performance Simulation for Design and Operation. Chapter 9, “Daylight


performance predictions”, pp. 235-276, Christoph Reinhart. January 2011. Publisher: Spon
Press.

Calcagni, B., Paroncini, M., 2004. Daylight factor prediction in atria building designs. Sol.
Energy 76, 669–682.

Cammarano, S., Pellegrino, A., Verso, V.R.M.L., Aghemo, C., 2015. Daylighting Design
for Energy Saving in a Building Global Energy Simulation Context. Energy Procedia 78,
364–369.

Capeluto, I.G., 2003. The influence of the urban environment on the availability of
daylighting in office buildings in Israel. Build. Environ. 38, 745–752.

Chen, H., Wei, P., 2013. Utilization of Natural Daylight in Office Buildings. Int. J. Smart
Grid Clean Energy 2, 301–306.
Daysim, 2018, viewed 2.11.18, <http://daysim.ning.com/>

DeKay, M., Brown, G.Z., 2014. Sun, Wind, and Light: Architectural Design Strategies,
third edition. ed. Wiley, Hoboken.

Du, J., Sharples, S., 2011. Assessing and predicting average daylight factors of adjoining
spaces in atrium buildings under overcast sky. Build. Environ. 46, 2142–2152.

Du, J., Sharples, S., 2010. Daylight in atrium buildings: Geometric shape and vertical sky
components. Light. Res. Technol. 42, 385–397.

Dubois, M.-C., Flodberg, K., 2013. Daylight utilization in perimeter office rooms at high
latitudes: Investigation by computer simulation. Light. Res. Technol. 45, 52–75.

Erlendsson, Ö., 2014. Daylight optimization: A parametric study of atrium design. Royal
Institute of Technology KTH, Stockholm.

European Committee for Standardization, 2011. European Standard EN 12464-1.

Ghasemi, M., Noroozi, M., Kazemzadeh, M., Roshan, M., 2015. The influence of well
geometry on the daylight performance of atrium adjoining spaces: A parametric study. J.
Build. Eng. 3, 39–47.

Grasshopper, 2018. Algorithmic Modelling for Rhino. Seattle: Robert McNeel and
Associates.

Guzenski, F., 2011. Impacto ambiental del sector de la construcción: Análisis comparativo
de cerriamentos externos aplicando el enfoque de ciclo de vida. Universidad Politécninca de
Madrid, Madrid.

Hung, W.Y., Chow, W.K., 2001. A Review on Architectural Aspects of Atrium Buildings.
Archit. Sci. Rev. 44, 285–295.

International Commission on Illumination (CIE), 2018., viewed 2.7.18,


<http://eilv.cie.co.at/term/279>.

Jenkins, D., 2004. Norman Foster Works 4. Prestel, Munich: New York.

Ladybug Tools, 2018, viewed 1.21.18, <http://www.ladybug.tools/about.html>.

Laouadi, A., 2004. Design with SkyVision: A Computer Tool to Predict Daylighting
Performance of Skylights. Presented at the Building for the Future: The 16th CIB World
Building Congress 2004, Toronto, Canada.

Laouadi, A., Atif, M.R., 2001. Prediction model of optical characteristics for domed
skylights under standard and real sky conditions 1101–1108.

Laouadi, A., Atif, M.R., Galasiu, A., 2002. Towards developing skylight design tools for
thermal and energy performance of atriums in cold climates. Build. Environ. 37, 1289–
1316.

Littlefair, P., 2002. Daylight prediction in atrium buildings. Sol. Energy 73, 105–109.
Liu, A., Navvab, M., Jones, J., 1991. Geometric shape index for daylight distribution
variations in atrium spaces. Presented at the 1991 Solar World Congress: proceedings of the
Biennial Congress of the International Solar Energy Society, Denver, Colorado, USA, 19-23
August 1991, Pergamon Press, Denver. USA.

Mangkuto, R.A., Rohmah, M., Asri, A.D., 2016. Design optimization for window size,
orientation, and wall reflectance with regard to various daylight metrics and lighting energy
demand: A case study of buildings in the tropics. Appl. Energy 164, 211–219.

Mardaljevic, J., Christoffersen, J., 2017. ‘Climate connectivity’ in the daylight factor basis
of building standards. Build. Environ., Advances in daylighting and visual comfort research
113, 200–209.

Matusiak, B., Aschehoug, O., Littlefair, P., 1999. Daylighting strategies for an infinitely
long atrium: An experimental evaluation. Light. Res. Technol. 31, 23–34.

Miljöbyggnad 3.0, 2015. Bedömningskriterier för nyproducerade byggnader. Sweden Green


Building Council.

Moberger, C., 2018, Västfastigheter, viewed 2.10.18


<http://vastfast.vgregion.se/sv/Vastfastigheter/Vastfastigheter-Projekt---
Sok/Vastfastigheter-Projekt---Sok/Platshallare---Distrikt-Goteborg/Per-Dubb/>.

Mohsenin, M., Hu, J., 2015. Assessing daylight performance in atrium buildings by using
Climate Based Daylight Modeling. Sol. Energy 119, 553–560.

Moosavi, L., Mahyuddin, N., Ab Ghafar, N., Azzam Ismail, M., 2014. Thermal performance
of atria: An overview of natural ventilation effective designs. Renew. Sustain. Energy Rev.
34, 654–670.

Murgul, V., 2015. Reconstruction of the Courtyard Spaces of the Historical Buildings of
Saint-Petersburg with Creation of Atriums. Procedia Eng. 117, 808–818.

Nabil, A., Mardaljevic, J., 2005. Useful daylight illuminance: a new paradigm for assessing
daylight in buildings. Light. Res. Technol. 37, 41–57.

Neufert, E., Neufert, P., 2012. Architects’ Data, 4th Edition. ed. John Wiley and Sons Ltd,
Chichester, West Sussex, UK; Ames, Iowa.

Programme, U.N.E., 2007. Buildings and climate change: status, challenges and
opportunities. UNEP.

Radiance Settings, 2018, viewed 5.8.18,


<http://radsite.lbl.gov/radiance/refer/Notes/rpict_options.html>.

Radiance, 2018, viewed 1.22.18, <https://www.radiance-online.org/>.

Reinhart, C.F., LoVerso, V.R.M., 2010. A rules of thumb-based design sequence for diffuse
daylight. Light. Res. Technol. 42, 7–31.
Reinhart, C.F., Walkenhorst, O., 2001. Validation of dynamic RADIANCE-based daylight
simulations for a test office with external blinds. Energy Build. 33, 683–697.

Rhinoceros, version 5, 2018. Seattle: Robert McNeel and Associates.

Sadeghipour Roudsari, Mostapha, Pak, Michelle, 2013. Ladybug: a parametric


environmental plugin for grasshopper to help designers create an environmentally-conscious
design. In: Proceedings of the 13th International IBPSA Conference Held in Lyon, France
Aug 25–30th.

Samant, S., 2011. Atrium and its adjoining spaces: a study of the influence of atrium facade
design. Archit. Sci. Rev. 54, 316–328.

Samant, S., Yang, F., 2007. Daylighting in atria: The effect of atrium geometry and
reflectance distribution. Light. Res. Technol. 39, 147–157.

Saratsis, E., Dogan, T., Reinhart, C.F., 2017. Simulation-based daylighting analysis
procedure for developing urban zoning rules. Build. Res. Inf. 45, 478–491.

Sharples, S., Lash, D., 2007. Daylight in Atrium Buildings: A Critical Review. Archit. Sci.
Rev. 50, 301–312.

Sharples, S., Shea, A.D., 1999. Roof obstructions and daylight levels in atria: a model study
under real skies. Int. J. Light. Res. Technol. 31, 181–185.

Sørensen, N.L., Frandsen, A.K., Øien, T.B., 2015. Architectural Competitions and BIM.
Procedia Econ. Finance 21, 239–246.

Sweden Green Building Council, 2018, viewed 5.8.18, <https://www.sgbc.se/>.

Sweden Property Market View, 2017, viewed 2.22.18, <https://www.cbre.com/research-


and-reports/Sweden-Overall-Property-MarketView-Q2-2017>.

Tregenza, P., Wilson, M., 2013. Daylighting: Architecture and Lighting Design. Routledge.

USGBC, 2018, viewed 1.31.18, <https://new.usgbc.org/leed>.

Wang, L., Huang, Q., Zhang, Q., Xu, H., Yuen, R.K.K., 2017. Role of atrium geometry in
building energy consumption: The case of a fully air-conditioned enclosed atrium in cold
climates, China. Energy Build. 151, 228–241.

Ward, G and Shakespear R. (1998) Rendering with RADIANCE –The Art and Science of
Lighting Visualization, San Fransisco, CA: Morgan Kaufmann Publishers.

Wong, I.L., 2017. A review of daylighting design and implementation in buildings. Renew.
Sustain. Energy Rev. 74, 959–968.

Yi, R., Shao, L., Su, Y., Riffat, S., 2009. Daylighting performance of atriums in subtropical
climate. Int. J. Low-Carbon Technol. 4, 230–237.
Appendix A
ADF, DF median and dynamic daylight metrics for the remaining cases.

Figure A 1: ADF, sDA, DF median and UDI autonomous for cases a2, b2 and c2.
Figure A 2: ADF, sDA, DF median and UDI autonomous for cases a3, b3 and c3.
Figure A 3: ADF, sDA, DF median and UDI autonomous for cases a1+2, b1+2 and c1+2.
Figure A 4: ADF, sDA, DF median and UDI autonomous for case a2+3, b1+3 and c2+3.
Figure A 5: ADF, sDA, DF median and UDI autonomous for cases a1+2+3, b1+2+3 and c1+2+3.
Figure A 6: ADF, sDA, DF median and UDI autonomous for cases a3+2+1, b3+2+1 and c3+2+1.
Figura A 7: ADF, sDA, DF median and UDI autonomous for cases a,b, c and abc..
Dept of Architecture and Built Environment: Division of Energy and Building Design
Dept of Building and Environmental Technology: Divisions of Building Physics and Building Services