MEE 515 - HVAC - Lecture 7 (Chapter 10)
MEE 515 - HVAC - Lecture 7 (Chapter 10)
MEE 515 - HVAC - Lecture 7 (Chapter 10)
Where:
P=static pressure, lbf/ft2 or N/m2
𝑙𝑏𝑚 𝑘𝑔
𝜌 = 𝑚𝑎𝑠𝑠 𝑑𝑒𝑛𝑠𝑖𝑡𝑦 𝑎𝑡 𝑎 𝑐𝑟𝑜𝑠𝑠 𝑠𝑒𝑐𝑡𝑖𝑜𝑛, 𝑜𝑟
𝑓𝑡 3 𝑚3
𝑉 = 𝐴𝑣𝑒𝑟𝑎𝑔𝑒 𝑣𝑒𝑙𝑜𝑐𝑖𝑡𝑦 𝑎𝑡 𝑎 𝑐𝑟𝑜𝑠𝑠 𝑠𝑒𝑐𝑡𝑖𝑜𝑛, 𝑓𝑡\sec 𝑜𝑟 𝑚\sec.
𝑔 = 𝑙𝑜𝑐𝑎𝑙 𝑎𝑐𝑐𝑒𝑙𝑒𝑟𝑎𝑡𝑖𝑜𝑛 𝑜𝑓 𝑔𝑟𝑎𝑣𝑖𝑡𝑦, 𝑓𝑡/ sec 2 𝑜𝑟 𝑚/ sec 2
𝑔𝑐 = 𝑐𝑠𝑡. = 32.17 𝑙𝑏𝑚 − 𝑓𝑡 Τ(𝑙𝑏𝑓 − 𝑠𝑒𝑐2)=1.0(kg−m)/(N−s2)
𝑧 = 𝑒𝑙𝑒𝑣𝑎𝑡𝑖𝑜𝑛 𝑓𝑡 𝑜𝑟 𝑚
𝑤 = 𝑤𝑜𝑟𝑘, 𝑓𝑡 − 𝑙𝑏𝑓 𝑙𝑏. 𝑚 𝑜𝑟 𝐽Τ𝐾𝑔
𝑙𝑓 = 𝑙𝑜𝑠𝑡 ℎ𝑒𝑎𝑑, 𝑓𝑡 𝑜𝑟 𝑚
Fluid Flow Basics
→Conservation of mass: one-dimensional flow
𝑚 = 𝜌1𝑉ത 1𝐴1 = 𝜌2𝑉ത 2𝐴2
Where:
ത
𝜌𝑉𝐷 ത
𝑉𝐷
𝑅𝑒 = =
𝜇 𝜐
Laminar zone →𝑓 = 𝑓 𝑅𝑒
Transition zone →𝑓 = 𝑓 𝑅𝑒; 𝑒Τ𝐷
Turbulent zone →𝑓 = 𝑓 𝑒Τ𝐷
Fluid Flow Basics
• Absolute roughness (e) for common pipes and conduits
1 𝑁−𝑠
2
= 103𝑐𝑒𝑛𝑡𝑖𝑝𝑜𝑖𝑠𝑒
𝑚
Example 10-1
• Compare the lost head for water and a 30 percent ethylene glycol
solution flowing at the rate of 110 gallons per minute (gpm) in a 3 in.
standard (Schedule 40) commercial steel pipe 200 ft in length. The
temperature of the water is 50 F.
Fluid Flow Basics
c) System Characteristic:
Behavior of a piping system:
𝑇𝑜𝑡𝑎𝑙 ℎ𝑒𝑎𝑑 = 𝑓 𝑣𝑜𝑙𝑢𝑚𝑒 𝑓𝑙𝑜𝑤 𝑟𝑎𝑡𝑒
𝑔𝑐 𝑃01 −𝑃02
• 𝐻𝑝 = ഥ 2)
+ 𝑧1 − 𝑧2 + 𝑙𝑓 ≈ 𝑉ത 2
gρ(≈𝑉
• 𝐻𝑝 represents the total head required to produce the change in static, velocity and elevation head
and to offset lost head
Fluid Flow Basics
Parallel circuits:
Series circuits:
2
𝑃1 𝑉ത1 𝑃2 𝑃02
+ = =
𝜌 2𝑔𝑐 𝜌 𝜌
Flow Measurement
Traverse the pipe or duct and to integrate either graphically or numerically
to find the average velocity in the duct
For control purposes: A centerline value is sufficient
Example 10-2
• A pitot tube is installed in an air duct on the center line. The velocity
pressure as indicated by an inclined gage is 0.32 in. of water, the air
temperature is 60 F, and barometric pressure is 29.92 in. of mercury.
Assuming that fully developed turbulent flow exists where the
average velocity is approximately 82 percent of the center-line value,
compute the volume and mass flow rates for a 10 in. diameter duct.
Flow Measurement The orifice introduces an appreciable loss in total
pressure->discharge coefficient:
𝑄ሶ 𝑎𝑐𝑡𝑢𝑎𝑙
• The orifice: square edged orifice: 𝐶=
𝑄ሶ 𝑖𝑑𝑒𝑎𝑙
High High
Fluid Volute,
Impeller Kinetic Static
Diffuser
Energy Pressure
Centrifugal Pumps
Pumps • Single-suction (one inlet side)
• Double-suction (two inlet sides)
If the static pressure of the fluid entering a pump approaches the vapor pressure of
the liquid too closely, vapor bubbles will form in the impeller passages.
noise and probable damage of the pump (cavitation)
NPSHR (required net positive suction head): Pressure excess of the vapor
pressure required to prevent cavitation. f( speed, capacity).
Centrifugal Pumps:
NPSHA: available net positive suction head
NPSHA>NPSHR cavitation
Centrifugal Pumps:
𝑇𝑜𝑡𝑎𝑙 𝑑𝑦𝑛𝑎𝑚𝑖𝑐 ℎ𝑒𝑎𝑑
𝐸𝑓𝑓𝑖𝑐𝑖𝑒𝑛𝑐𝑦
Pump performance: f(Qcapacity, impeller diameter)
𝑆ℎ𝑎𝑓𝑡 𝑝𝑜𝑤𝑒𝑟
𝑁𝑃𝑆𝐻𝑅
Example 10-3
• Suppose the pump of Fig. 10-11 is installed in a system as shown in Fig. 10-12.
The pump is operating at 3500 rpm with the 6 in. impeller and delivering 200
gpm. The suction line is standard 4 in. pipe that has an inside diameter of
4.026 in. Compute the NPSHA, and compare it with the NPSHR. The water
temperature is 60 F.
Centrifugal Pumps:
The pump foundation, usually concrete, should be sufficiently rigid to
support the pump base plate Maintain alignment between the
pump and motor
The pump foundation should weigh at least 212 times the total pump
and motor weight for vibration and sound control
Expansion joints are required on both the suction and discharge sides
of the pump to isolate expansion and contraction forces
Combined System and Pump Characteristic
Combined System and Pump Characteristic
Example 10-4
• A water piping system has been designed to distribute 150 gpm, and the total
head requirement is 36 ft. Select a pump, using the data of Fig. 10-11, and
specify the power rating for the electric motor.
Affinity Laws
Modify the performance of a pump by changing the rotational speed or
impeller diameter.
affinity laws for pumps:
1) For constant impeller diameter 2) For Constant rotating speed
Example 10-5
• The 1750 rpm pump with 7 in. impeller of Fig. 10-11 is operating in a system
as shown as point 1 of Fig. 10-16. It is desired to reduce the pump speed
until the flow rate is 100 gpm. Find the new pump head, shaft power, and
efficiency.
Piping System Fundamentals
Closed-Loop Systems:
• A closed-loop system has no more than one interface with a compressible gas or
flexible surface such as an open or closed expansion tank
• There is no motivation of flow by static head in a closed system and the entire
system is filled with liquid.
• There are two main groups of components: thermal and hydraulic
• The thermal components are the source, chiller or boiler, the load, cooling or
heating coils, and the expansion tank
• The hydraulic components are the distribution system, the pump, and the
expansion tank
• The expansion tank serves both the thermal and hydraulic functions
• Actual systems will have additional components such as isolation and control
valves, flow meters, expansion joints, pump and pipe supports…
Piping System Fundamentals
Pipe Sizing Criteria:
• Piping systems often pass through or near occupied spaces where noise generated by the
flowing fluid may be objectionable
• A common recommendation sets a velocity limit of 4 ft/sec or 1.2 m/s for pipes 2 in. and
smaller
• For larger sizes a limit on the head loss of 4 ft per 100 ft of pipe is imposed
• This corresponds to about 0.4 kPa/m in SI units
• These criteria should not be treated as hard rules but rather as guides.
• Noise is caused by entrained air, locations where abrupt pressure drops occur, and
turbulence in general
• If these factors can be minimized, the given criteria can be relaxed
• Open systems such as cooling tower circuits are remote from occupied spaces. Therefore,
somewhat higher velocities may be used in such a case.
• A reasonable effort to design a balanced system will prevent drastic valve adjustments and
will contribute to a quieter system.
Piping System Fundamentals
Pipe Sizing:
• After the piping layout has been completed, the problem of sizing the pipe consists
mostly of applying the design criteria discussed earlier
• Where possible the pipes should be sized so that drastic valve adjustments are not
required
• To facilitate the actual pipe sizing and computation of head loss, charts for pipe and
copper tubing have been developed
• These figures are based on 60 F (16 C) water and give head losses that are about
10% high for hot water
• Examination of the charts shows that head loss may be obtained directly from the
flow rate and nominal pipe size or from flow rate and water velocity
• When the head loss and flow rate are specified, a pipe size and velocity may be
obtained
Piping System Fundamentals
Piping System Fundamentals
Piping System Fundamentals
Pipe Sizing:
• Pipe fittings and valves also introduce losses in head. These losses are usually
allowed for by use of a resistance coefficient K, which is the number of
velocity heads lost because of the valve or fitting:
ഥ2
𝑉 𝐿
𝑙𝑓 = 𝑘 , 𝑘= 𝑓
2𝑔 𝐷
• The ratio L/D is the equivalent length, in pipe diameters, of straight pipe that
will cause the same pressure loss as the valve or fitting under the same flow
conditions.
Piping System Fundamentals
Example 10-6
• Compute the lost head for a 150 ft run of standard pipe, having a diameter of
3 in. The pipe run has three standard 90-degree elbows, a globe valve, and a
gate valve. One hundred gpm of water flows in the pipe.
Valves, strainers and other devices
Coefficient Cv: equal to the flow rate of water at 60F in gpm, which will give a
pressure loss of 1 lbf/in2 (2.31 ft of water).
gpm
• The expansion tank must be installed so that the assumptions made in deriving the
equations valid
• This generally means that the expansion tank is not insulated and is connected to the main
system by a relatively long, small-diameter pipe so that water from the system does not
circulate into the expansion tank
Example 10-9
• Compute the expansion tank volume for a chilled water system that contains 2000
gal of water. The system is regulated to 10 psig at the tank with an operating
temperature of 45 F. It is estimated that the maximum water temperature during
extended shutdown would be 100 F and a safety relief valve in the system is set for
35 psig. Assume standard barometric pressure and steel pipe.
Steam heating systems
Water vapor (steam) is distributed to the various terminal units, where it is
condensed, giving up latent heat, and the condensate is returned to the boiler. The
motive force for the steam is the pressure maintained in the boiler.
A condensate pump returns the liquid to the boiler.
Steam systems are very efficient in transporting energy.
P-T dependence helpful for control Used to heat water, which is distributed and used
in water to air coils
Steam heating systems
In HVAC applications: P≤15psig [103 kPa]
• Piping circuit, more complicated: two phases : liquid and vapor.
Sizing system Components
After the steam distribution laid out
→various elements of the system can be sized, including the boiler.
→Boiler capacity (lbm/hr):
Criteria:
max ΔP=boiler pressure-pressure at the end of the system
4psi→15psi boiler pressure