Controledge Hc900 Io Modules Specifications: 51-52-03-41, November 2019
Controledge Hc900 Io Modules Specifications: 51-52-03-41, November 2019
Controledge Hc900 Io Modules Specifications: 51-52-03-41, November 2019
Specifications
51-52-03-41, November 2019
Terminal Blocks
20-screw Barrier style and Euro style terminal blocks are available for use with all ControlEdge HC900 I/O Modules.
Red terminal blocks are used for high voltage connections for added safety while black terminal blocks are used for low
voltage connections. A 36-terminal Euro style block is available with the 16 AI, the 8 and 16 AO as well as the 32 DC DI and
32 DC DO module types. See page 27.
Digital Input, 120/240 Vac (16 channel 125 Vdc) T3C@ Ta = 60 deg. C
T4 @ Ta = 40 deg. C
Digital Input Vdc (32 channel) T3C@ Ta = 60 deg. C
T4 @ Ta = 40 deg. C
Digital Output, Relay type (8 channel) T5
Digital Output, 24 Vdc, (16 channel) T4
Digital Output, 120/240 Vac (8 channel) T4
Digital Output Vdc (32 channel) T6
Pulse/Frequency/Quadrature (4 channel) T5
Universal IO Module (16 channel) T4
Power Supply
P01 Power Supply (900P01-xxxx)
The P01 power supply provides 5VDC and 24VDC to satisfy the power requirements of a
rack with a controller and local I/O, a rack with a scanner, and remote I/O. The 60-watt
capacity allows for almost any mix of I/O modules in one rack. See Module Specifications
starting on page 6. A tool-secured door covers the high voltage connections; test jacks
behind the door allow for quick verification of proper operation. An internal non-replaceable
fuse limits supply current under certain fault conditions.
A B C D E
Max Max Calculate 5V
Enter Current @ Current @ current Calculate 24V current
Module type Quantity 5V 24 V ( D = A * B) ( E = A * C)
SIL CPU
Controller C30S CPU ( ) 820 mA 0 mA ( ) ( 0 )
Controller C50S CPUL ( ) 930 mA 0 mA ( ) ( 0 )
Controller C70S CPU ( ) 1150 mA 0 mA ( ) ( 0 )
Controller C75S ( ) 1500 mA 0 mA ( ) ( 0 )
I/O Scanner 1 Port (1 per I/O 670 mA 0 mA
rack) - SIL ( ) ( ) ( 0 )
I/O Scanner 2 Port (1 per I/O 770 mA 0 mA
rack) - SIL ( ) ( ) ( 0 )
Non-SIL CPU
Controller C30 CPU ( ) 820 mA 0 mA ( ) ( 0 )
Controller C50 CPU ( ) 930 mA 0 mA ( ) ( 0 )
Controller C70 CPU ( ) 1150 mA 0 mA ( ) ( 0 )
Controller C70R CPU ( ) 1500 mA 0 mA ( ) ( 0 )
I/O Scanner 1 Port (1 per I/O 670 mA 0 mA
rack) ( ) ( ) ( 0 )
I/O Scanner 2 Port (1 per I/O 770 mA 0 mA
rack) ( ) ( ) ( 0 )
Power Status Module (PSM) ( ) 22 mA 0 mA ( ) ( 0 )
Analog Input (8 pts) ( ) 40 mA 25 mA ( ) ( )
Analog Input (16 pts) ( ) 75 mA 50 mA ( ) ( )
Analog Output (4 pts) * ( ) 40 mA 200 mA ( ) ( )
Analog Output (8 pts) *** ( ) 225 mA 350 mA ( ) ( )
Analog Output (16 pts) *** ( ) 350 mA 700 mA ( ) ( )
AC Digital Input (16 pts) ( ) 130 mA 0 mA ( ) ( 0 )
DC Digital Input (16 pts) ( ) 130 mA 0 mA ( ) ( 0 )
AC/DC Digital Input (16 pts) ( ) 130 mA 0 mA ( ) ( 0 )
Contact Input (16 pts) ( ) 130 mA 40 mA ( ) ( )
DC Digital Input (32 pts) ( ) 215 mA 0 mA ( ) ( 0 )
AC Digital Output (8 pts) ( ) 220 mA 0 mA ( ) ( 0 )
DC Digital Output (16 pts) ( ) 340 mA 0 mA ( ) ( 0 )
DC Digital Output (32 pts) ( ) 235 mA 0 mA ( ) ( 0 )
Relay Output (8 pts) ( ) 110 mA 100 mA ( ) ( )
Pulse/Frequency/Quadrature** ( ) 110 mA 250 mA ( ) ( )
Universal IO Module (16 pts) ( ) 10 mA 100 mA ( ) ( )
6 ControlEdge 900 Platform Modules
** Type K thermocouple (mid-range) has a working range from 75 to 1800 °F, 25 to 982 °C. Input measurements below
75°F or 25°C may cause the input to default to the programmed failsafe value. Use type K low or full ranges if
measurements are required outside the mid- working range.
ControlEdge 900 Platform Modules 9
RTD °F °C °F °C
Platinel -94 to 1382 -70 to 750 3.0 1.7
Platinel (low) 32 to 2516 0 to 1380 1.5 0.8
100 Pt. (high) RTD*** –300 to 1500 –184 to 816 1.8 1.0
100 Pt. (mid) RTD*** -300 to 1200 -184 to 649 1.4 0.8
100 Pt. (low) RTD*** -300 to 600 -184 to 316 0.9 0.5
500 Pt. RTD*** -300 to 1200 -184 to 649 0.9 0.5
1000 Pt RTD***** -40 to 500 -40 to 260 0.8 0.4
100 JIS -328 to 932 -200 to 500 1.3 0.7
100 JIS (low) 0 to 212 -18 to 100 0.5 0.3
Cu10 -4 to 482 -20 to 250 2.0 1.0
YSI405 50 to 100 10 to 37.8 0.05 0.03
Input Type Range Reference Accuracy
Ohms, 200 0 to 200 +/- 0.4 ohms
Ohms, 500 0 to 500 +/- 1.0 ohms
Ohms, 1000 0 to 1000 +/- 2.0 ohms
Ohms, 2000 0 to 2000 +/- 4.0 ohms
Ohms, 4000 0 to 4000 +/- 8.0 ohms
Milliamperes 4 to 20 mAdc ± 0.2% F.S. (mA)****
0 to 20 mAdc ± 0.2% F.S. (mA)****
Millivolts 0 to 10 mVDC ± 0.17% F.S. (mV)
0 to 50 mVDC ± 0.1% F.S. (mV)
0 to 100 mVDC ± 0.1% F.S. (mV)
-10 to 10 mVDC ± 0.2% F.S. (mV)
-50 to 50 mVDC ± 0.1% F.S. (mV)
-100 to 100 mVDC ± 0.1% F.S. (mV)
-500 to 500 mVDC ± 0.1% F.S. (mV)
Volts 1 to 5 VDC ± 0.1% F.S. (mV)
0 to 1 VDC ± 0.1% F.S. (mV)
0 to 2 VDC ± 0.1% F.S. (mV)
0 to 5 VDC ± 0.1% F.S. (mV)
0 to 10 VDC ± 0.2% F.S. (mV)
-1 to 1 VDC ± 0.1% F.S. (mV)
-2 to 2 VDC ± 0.1% F.S. (mV)
-5 to 5 VDC ± 0.1% F.S. (mV)
-10 to 10 VDC ± 0.2% F.S. (mV)
Slidewire ≤ 250 ohms
250 to 1250 ohms
1250 to 4000 ohms
4000 to 6500 ohms
Carbon 0 to 1250 mVDC ± 0.1% F.S. (mV)
Oxygen -30 to 510 mVDC ± 0.1% F.S. (mV)
*** Conforms to IEC751
****Tolerances for these input types include that of the external Dropping Resistors.
A DIP switch on the module selects the use of 24V from External Power Source requirements:
Rack PS (internal) power or external loop power via a
Voltage Vin: 18 to 36 Vdc
separate 24V DC power source. The as-shipped (default)
switch setting is external power. Current 350 mA per module
14 ControlEdge 900 Platform Modules
A DIP switch on the module selects the use of 24V from rack PS (internal) power or external loop power via a separate 24V
DC power source. The as-shipped (default) switch setting is external power.
*excluding controllers scan time and excluding transmission time from module to backplane
ControlEdge 900 Platform Modules 17
A green blinking status LED on the module indicates when the module is being scanned. An amber blinking status LED
indicates when channels are forced and a red status LED when module diagnostics exist.
*excluding controllers scan time and excluding transmission time from module to backplane
22 ControlEdge 900 Platform Modules
Channels Used Only channels 1 and 2 can be used for quadrature pulses A and
B respectively.
Index pulse is provided in addition.
Input Voltage Range Differential: -6 VDC to +6 VDC
Single-ended: 0 VDC to 24 VDC
ON Voltage Level Differential: 0.2 VDC minimum
Single-ended: 3.0 VDC minimum
OFF Voltage Level Differential: -0.2 VDC maximum
Single-ended: 1 VDC maximum
Common Mode Voltage +/- 12VDC
Input Sensitivity +/- 200mV
Hysteresis +/- 50mV
Module powered encoder 5V DC, 0.50A
Frequency 200 KHz maximum
Minimum Pulse Width 2.25 µsec
Quadrature Counter 32 bits signed
Quadrature Modes For variable resolution there are three count modes for the
Pulse/Quadrature input:
X1: rising edges of signal A are counted (increment); falling
edges of signal A (decrement)
X2: rising & falling edges of signal A are counted
X4: rising & falling edges of signals A & B are counted
Quadrature LEDs Two LEDs indicate UP and DOWN direction of counting.
26 ControlEdge 900 Platform Modules
Channels Used Any one of the channels can be used for Pulse Output.
However, the use of a particular channel for outputting pulses
will render the particular input channel unusable for either of
pulse, frequency or quadrature input.
Digital Output Type Open Collector, 5 to 24V, 30 mA max
Frequency Range 25 Hz – 10 KHz
Duty cycle Always 50%
Pulse Output Duration Selectable CONTINUOUS or NUMBERED PULSES.
Channels Used Any one of the channels can be used for Pulse Output.
However, the use of a particular channel for outputting pulses
will render the particular input channel unusable for either of
pulse, frequency or quadrature input.
Digital Output Type Open Collector, 5 to 24V, 30 mA max
Frequency Range 25 Hz – 10 KHz
Duty cycle Always 50%
Pulse Output Duration Selectable CONTINUOUS or NUMBERED PULSES.
ControlEdge 900 Platform Modules 27
Universal IO channel can be soft configured as AI, AO, DI or DO. Details of each IO type are listed in tables below.
Item Specification
Channels 161
24V DC(Typical)2,3
24V Field Supply Voltage 22V DC(Min)
27V DC(Max)
Max 4.2 Amps per module
Load
500 mA per channel
1.5 kVDC Module to Rack (Logic Side)
Isolation
1.5 kVDC Module to Module
Update Rate 10ms
ESCP (Electronic Short Circuit Protection per channel) 620 mA re-settable
Fuse (per channel) Internal, non-replacable (1 Amp)
Field Supply Fuse Internal, electronic fuse (10 Amps)
Detail Specifications – Analog Input
Parameter Specification
Input type Current (2, 3, or 4 wire devices)
Input Channels 16 Maximum per module
(line monitored)
A/D Converter Resolution 16 Bit
Input Range 4-20 mA
Crosstalk, dc to 60 Hz (channel-to-channel) 58dB
Input Impedance 250 Ω nominal
Maximum Input Voltage (any input referenced to 0 - 30V
common, no damage)
Hardware accuracy 0.1% of full-scale (23.5 ± 2°C)
0.2% of full-scale (23.5 ± 2°C) (For Redundant)
0.17% of full-scale (0 to +60°C)
0.34% of full-scale (0 to +60°C) (For Redundant)
Transmitter Field Power Conditioning Current limited to 24 mA
Input Filter First-order low-pass 1 kHz
Note:
1. 900U02 modules may not be installed such that the 900U02 is between two 900B16 modules. 900B16 may only be
installed in one adjacent slot.
2. Field power to be supplied by a local power supply providing tertiary protection from zone B severity levels. Generally
characterized by short wiring, isolation, surge suppressors etc.
3. For Marine applications ABS Type approved power supplies are required for field supply voltage.
4. Field supply voltage should be maintained higher than 22.5 V for AO higher AO loads (> 750 Ohms)
30 ControlEdge 900 Platform Modules
All terminal blocks support customer wiring entering the Shield terminal strips are also available to terminate the
block from the top or bottom when mounted in the shields of shielded cables at the controller.
controller. A locking swing out door provides easy access
for wiring and covers potential high voltage connections
during operation.
Number of 20 36*
terminals
Type Terminal blocks removable Terminal blocks removable
under instrument power. under instrument power.
(Field power disconnected) (Field power disconnected)
Gauge Wires Barrier and Euro: #14 to 26 Euro: #12 to 26 AWG, solid
AWG, solid or stranded or stranded
Terminal color High voltage: Red Black Terminal styles
(top) Barrier
Low Voltage: Black (middle) Euro
(bottom) 36-terminal Euro
Contacts High Voltage: Tin Coated Gold plated
Low Voltage: Gold Plated
Contact Style Post and socket Post and socket
Door Access Tool accessible Tool accessible
Cold Junction Yes (provided by AI N/A—thermocouples not
compensation for module) used
thermocouples
*Required with the following I/O modules: 16 HL AI, 8 AO, 16 AO, 32 DI, 32
DO and 16 AC/DC DI.
The Remote Termination Panel (RTP) provides an easy way to connect the ControlEdge HC900 controller to the field wiring.
The RTP integrates some of the typical externally connected components, reducing wiring and setup time. It also minimizes
the need for multiple wires under a single screw connection by expanding the connectivity of the shared terminals of the I/O
modules.
For more details on Installation Remote Termination Panels (RTPs), refer to “51-52-33-170 - HC900 Remote Terminal Panel
for Redundant UIO” manual.
Sales and Service
For application assistance, current specifications, pricing, or name of the nearest Authorized Distributor, contact one
of the offices below.
Singapore
Honeywell Pte Ltd.
Phone: +(65) 6580 3278
Fax: +(65) 6445-3033
South Korea
Honeywell Korea Co Ltd
Phone: +(822) 799 6114
Fax: +(822) 792 9015
Process Solutions
Honeywell