Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

08-Electric Water Heater

Download as xls, pdf, or txt
Download as xls, pdf, or txt
You are on page 1of 3
At a glance
Powered by AI
The document provides information on water heater calculations and specifications for a hotel project including probable maximum demand, electric power input, thermal power demand, and storage tank capacity.

The heater tag EWH-01 and the probable maximum demand calculation of 9244.5 GPH are provided for the hotel water heater project.

The probable maximum demand, density of water, electric efficiency, specific heat of water, and temperature rise are used to calculate the electric power input of 2033 kW and thermal power demand of 1951 kW.

PROJECT NAME

PROJECT NUMBER
BUILDING NAME
BUILDING NO.
PREPARED BY
CHECKED BY

ELECTRIC WATER HEATERS CALCULATIONS

Occupancy : Hotel

Heater Tag : EWH-01


From 2011 ASHRAE Handbook Table 10 page 50.20
Demand
Fixture
US GPH No. Off Total GPH
Basins, 2 372 744
Private Lavatory
Basins, 8 137 1096
Public Lavatory
Bathtubs 20 15 300
Dishwashers 125 0
Foot Basins 3 0
kitchen Sink 30 32 960
Laundry, 28 0
Stationary tubs
Pantry Sink 10 4 40
Showers 75 369 27675
Slop Sink 30 0
Hydrotherapeutic Showers 0 0
Hubbard baths 0 0
Leg Baths 0 0
Arm Baths 0 0
Sitz Baths 0 0
Continuous-Flow baths 0 0
Circular Wash Sinks 20 0
Semicircular Wash sinks 10 0
Possible Max. Demand (GPH) = 30815
Demand Factor = 0.25
Storage Factor = 0.8
Probable Max.Demand (GPH)= Demand Factor * Possible Max. Demand 9244.5
Tout = 140 °F 60 °C
Tin = 54 °F 12 °C
T rise = 86 °F 48 °C
m = Probable Max.Demand (L/S) 9.72
p = Density of water(Kg/L) 1
ƞ = Electric Efficiency (%) 96
Cp = Specific heat of water (kJ/(kg.K)) 4.18
P (kW) = Thermal Power Demand = (m x Cp x Trise) 1951.00
Pi (kW) = Electric Power Input = (m x Cp x Trise)/n 2033.00
Storage Tank Capacity (Gallons) = Prob. Max.Demand * Storage Factor 7396

WATER HEATER
Storage Tank Capacity (Liters) = Prob. Max.Demand * Storage Factor 27992

WATER HEATER
Heater Tag : EWH-01

From 2011 ASHRAE Handbook Table 10 page 50.20


Apartment Industrial Office Private
Club Gymnasium Hospital Hotel School
House Plant Building Residence
Basins,
Private Lavatory 2 2 2 2 2 2 2 2 2

Basins,
Public Lavatory 4 6 8 6 8 12 6 0 15

Bathtubs 20 20 30 20 20 0 0 20 0

Dishwashers 15 100 0 100 125 60 0 15 60

Foot Basins 3 3 12 3 3 12 0 3 3

kitchen Sink 10 20 0 20 30 20 20 10 20

Laundry,
Stationary tubs 20 28 0 28 28 0 0 20 0

Pantry Sink 5 10 0 10 10 0 10 5 10

Showers 30 150 225 75 75 225 30 30 225

Slop Sink 20 20 0 20 30 20 20 15 20

Hydrotherapeuti
c Showers 0 0 0 400 0 0 0 0 0

Hubbard baths 0 0 0 600 0 0 0 0 0

Leg Baths 0 0 0 100 0 0 0 0 0

Arm Baths 0 0 0 35 0 0 0 0 0

Sitz Baths 0 0 0 30 0 0 0 0 0

Continuous-
Flow baths 0 0 0 165 0 0 0 0 0

Circular Wash
Sinks 0 0 0 20 20 30 20 0 30

Semicircular
Wash sinks 0 0 0 10 10 15 10 0 15

Demand Factor 0.3 0.3 0.4 0.25 0.25 0.4 0.3 0.3 0.4

Storage
Capacity Factor 1.25 0.9 1 0.6 0.8 1 2 0.7 1