Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Occupancy Type.: Jba Consulting Engineers Job No. by Date Checked Date Sheet of Job Title

Download as xls, pdf, or txt
Download as xls, pdf, or txt
You are on page 1of 2

jba Consulting Engineers Job No.

Job Title By Date


Checked Date
Sheet of

Occupancy Type. RES

G.P.H. PER OCCUPANCY TYPE


APT. IND. OFFICE PRI.

QTY. FIXTURE TYPE HOUSE CLUB GYM HOSP. HOTEL PLANT BLDG. RES. SCH. G.P.H.
0 Lavatory/Bidet/Bar Sink 2 2 2 2 2 2 2 2 2 0
0 Basins, public lavatory 4 6 8 6 8 12 6 0 15 0
0 Bathtubs 20 20 30 20 20 0 0 20 0 0
0 Dishwashers (1) 15 100 0 100 150 100 0 15 75 0
0 Foot basins 3 3 12 3 3 12 0 3 3 0
0 Kitchen sink 10 20 0 20 30 20 20 10 20 0
0 Laundry, stationary tubs 20 28 0 28 28 0 0 20 0 0
0 Laundry Tray/Sink 5 10 0 10 10 0 10 5 10 0
0 Showers 30 150 225 75 75 225 30 30 225 0
0 Slop sink 20 20 0 20 30 20 20 15 20 0
0 Hydrotherapeutic showers 0 0 0 400 0 0 0 0 0 0
0 Hubbard baths 0 0 0 600 0 0 0 0 0 0
0 Leg baths 0 0 0 100 0 0 0 0 0 0
0 Arm baths 0 0 0 35 0 0 0 0 0 0
0 Sitz baths 0 0 0 30 0 0 0 0 0 0
0 Continuous-flow baths 0 0 0 165 0 0 0 0 0 0
0 Circular wash sinks 0 0 0 20 20 30 20 0 30 0
0 Semicircular wash sinks 0 0 0 10 10 15 10 0 15 0
0 TOTAL DEMAND - - - - - - - - - 0
Demand Factor 0.30 0.30 0.40 0.25 0.25 0.40 0.30 0.30 0.40 0.30
Storage Capacity (2) 1.25 0.90 1.00 0.60 0.80 1.00 2.00 0.70 1.00 0.70

Req'd. Heating Capacity 0 GPH 0 0 GPH Water Tempature


Req'd. Storage Capacity 0 GPH 1 0 GAL. C.W. 60 Deg.
H.W. 140 Deg.
Electric Heat Req'd. 0 KW
Gas Heat Req'd. 0 MBH Duration of Peak load
2 HR's
What size Water Heater tank would you like to us 0 GAL
Gallons Per Hour Recovery 0 GPH W.H. Efficiencies
80 %
Electric Heat Req'd. 0 KW
Gas Heat Req'd. 0 MBH
jba Consulting Engineers Job No.
Job Title By Date
Checked Date
Sheet of

Sizing hot system per Capita (Per preson)

Apt Size No. of Apts No. Per/Apt Person/Apt


2 - Bedrooms 0 0 0
3 - Bedrooms 0 0 0
0 0 Persons

Determine the low, Meduin, or High usage factor (LMH)


Table 2.1 - A.S.P.E. Water Heating Manual
LMH = low Demand

Table 2.2 - A.S.P.E. Water Heating Manual


LMH Peak 5 min. Peak 15 min. Peak 30 min. Max. H
low 0.04 1 1.7 2.8
Max. 2 H Max. 3H Max. Day Avg. Day
low 4.5 6.1 20 14

Est. DHW consumption


LMH Current No Demand System Load
of People Factor Category
low 0 14 0 gal/day

Generation and Storage System


System Load (GPH)
Peak load H Min

LMH Current No Demand Periods System


of People Peak /H Loads
low 0 2.8 2 0 GPH

Equipment Rating
Temp Rise 80 Degree F
Boiler Eff. 80 %
System Load Conversion Temp Rise 1/Boiler Eff Heater Input
0 8.33 80 1.25 0 BTU

System Storage
Demand Cat. 2H
LMH Current No Demand System
of People Category Loads
low 0 4.5 0 Gal. Storage