PROJECT NAME

PROJECT NUMBER
BUILDING NAME
BUILDING NO.
PREPARED BY
CHECKED BY

ELECTRIC WATER HEATERS CALCULATIONS

Occupancy : Hotel

Heater Tag : EWH-01


From 2011 ASHRAE Handbook Table 10 page 50.20
Demand
Fixture
US GPH No. Off Total GPH
Basins, 2 372 744
Private Lavatory
Basins, 8 137 1096
Public Lavatory
Bathtubs 20 15 300
Dishwashers 125 0
Foot Basins 3 0
kitchen Sink 30 32 960
Laundry, 28 0
Stationary tubs
Pantry Sink 10 4 40
Showers 75 369 27675
Slop Sink 30 0
Hydrotherapeutic Showers 0 0
Hubbard baths 0 0
Leg Baths 0 0
Arm Baths 0 0
Sitz Baths 0 0
Continuous-Flow baths 0 0
Circular Wash Sinks 20 0
Semicircular Wash sinks 10 0
Possible Max. Demand (GPH) = 30815
Demand Factor = 0.25
Storage Factor = 0.8
Probable Max.Demand (GPH)= Demand Factor * Possible Max. Demand 9244.5
Tout = 140 °F 60 °C
Tin = 54 °F 12 °C
T rise = 86 °F 48 °C
m = Probable Max.Demand (L/S) 9.72
p = Density of water(Kg/L) 1
ƞ = Electric Efficiency (%) 96
Cp = Specific heat of water (kJ/(kg.K)) 4.18
P (kW) = Thermal Power Demand = (m x Cp x Trise) 1951.00
Pi (kW) = Electric Power Input = (m x Cp x Trise)/n 2033.00
Storage Tank Capacity (Gallons) = Prob. Max.Demand * Storage Factor 7396

WATER HEATER
Storage Tank Capacity (Liters) = Prob. Max.Demand * Storage Factor 27992

WATER HEATER
Heater Tag : EWH-01

From 2011 ASHRAE Handbook Table 10 page 50.20


Apartment Industrial Office Private
Club Gymnasium Hospital Hotel School
House Plant Building Residence
Basins,
Private Lavatory 2 2 2 2 2 2 2 2 2

Basins,
Public Lavatory 4 6 8 6 8 12 6 0 15

Bathtubs 20 20 30 20 20 0 0 20 0

Dishwashers 15 100 0 100 125 60 0 15 60

Foot Basins 3 3 12 3 3 12 0 3 3

kitchen Sink 10 20 0 20 30 20 20 10 20

Laundry,
Stationary tubs 20 28 0 28 28 0 0 20 0

Pantry Sink 5 10 0 10 10 0 10 5 10

Showers 30 150 225 75 75 225 30 30 225

Slop Sink 20 20 0 20 30 20 20 15 20

Hydrotherapeuti
c Showers 0 0 0 400 0 0 0 0 0

Hubbard baths 0 0 0 600 0 0 0 0 0

Leg Baths 0 0 0 100 0 0 0 0 0

Arm Baths 0 0 0 35 0 0 0 0 0

Sitz Baths 0 0 0 30 0 0 0 0 0

Continuous-
Flow baths 0 0 0 165 0 0 0 0 0

Circular Wash
Sinks 0 0 0 20 20 30 20 0 30

Semicircular
Wash sinks 0 0 0 10 10 15 10 0 15

Demand Factor 0.3 0.3 0.4 0.25 0.25 0.4 0.3 0.3 0.4

Storage
Capacity Factor 1.25 0.9 1 0.6 0.8 1 2 0.7 1