Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Water Heater Calculator

Download as xls, pdf, or txt
Download as xls, pdf, or txt
You are on page 1of 5
At a glance
Powered by AI
The document discusses fixture unit calculations and hot water demand for different types of buildings. It provides information on gallons per hour for various fixtures and factors used in related calculations.

The document discusses fixture unit calculations and hot water demand for different types of buildings such as industrial plants, office buildings, clubs, gyms, hospitals, hotels, schools, YMCAs and private residences.

The document provides information on gallons per hour requirements for various plumbing fixtures such as lavatories, showers, sinks, tubs etc. for different types of buildings.

JOB NO.

SHEET NO.
JOB NAME: DATE : 12-Mar-19
BUILDING: COMPUTED BY :
SUBJECT: CALCULATIONS OF DRAINAGE FIXTURE UNITS CHECKED BY :

INDUSTRIAL PLANT
Fixture Qty Gallons/Hour per fixture Total Gallons/Hour
Basin, private lavatory 0 2 0
Basin, public lavatory 0 12 0
Dishwasher (20 - 100) 0 40 0
Foot basin 0 12 0
Kitchen sink 0 20 0
Shower 0 225 0
Service sink 0 20 0
Circular wash sink 0 30 0
Semicircular wash sink 0 15 0

Total Gallons/Hour 0
* DEMAND FACTOR = 0.40 Demand GPH 0
* STORAGE CAPACITY FACTOR = 1.00 Gallons 0

Instructions:
1. Enter the quantity of each type of fixture in the QTY column.
2. Reference the Table sheet to determine the GPH per fixture for an Industrial Facility and enter value.
JOB NO.
SHEET NO.
JOB NAME: DATE :
BUILDING: COMPUTED BY
SUBJECT: CALCULATIONS OF DRAINAGE FIXTURE UNITS CHECKED BY :

OFFICE BUILDING
Fixture Qty Gallons/Hour per fixture Total Gallons/Hour
Basin, private lavatory 0 2 0
Basin, public lavatory 0 6 0
Kitchen sink 0 20 0
Pantry sink 0 10 0
Shower 0 30 0
Service sink 0 20 0
Circular wash sink 0 20 0
Semicircular wash sink 0 10 0

Total Gallons/Hour 0
* DEMAND FACTOR = 0.30 Demand GPH 0
* STORAGE CAPACITY FACTOR = 2.00 Gallons 0

Instructions:
1. Enter the quantity of each type of fixture in the QTY column.
2. Reference the Table sheet to determine the GPH per fixture for an Office Building and enter value.
12-Mar-19
Hot Water Demand per Fixture for Various Types of Build
(Gallons of water per hour per fixture, calculated ata final temperatur
Apartment
House Club Gymnasium Hospital
Basin, private lavatory 2 2 2 2
Basin, public lavatory 4 6 8 6
Bathtubc 20 20 30 20
Dishwasher a
15 50 - 150 -- 50 - 150
Foot basin 3 3 12 3
Kitchen sink 10 20 -- 20
Laundry, stationary tub 20 28 -- 28
Pantry sink 5 10 -- 10
Shower 30 150 225 75
Service sink 20 20 -- 20
Hydrotherapeutic shower -- -- -- 400
Hubbard bath -- -- -- 600
Leg bath -- -- -- 100
Arm bath -- -- -- 35
Sitz bath -- -- -- 30
Continuous-flow bath -- -- -- 165
Circular wash sink -- -- -- 20
Semicircular wash sink -- -- -- 10

DEMAND FACTOR 0.30 0.30 0.40 0.25


STORAGE CAPACITY FACTOR b
1.25 0.90 1.00 0.60

Source: ASHRAE Handbook 2007 HVAC Applications, Chapter 49, Section 17, Table 10
xture for Various Types of Buildings
ure, calculated ata final temperature of 140°F)
Industrial Office Private
Hotel Plant Building Residence School YMCA
2 2 2 2 2 2
8 12 6 -- 15 8
20 -- -- 20 -- 30
50 - 200 20 - 100 -- 15 20 - 100 20 - 100
3 12 -- 3 3 12
30 20 20 10 20 20
28 -- -- 20 -- 28
10 -- 10 5 10 10
75 225 30 30 225 225
30 20 20 15 20 20
-- -- -- -- -- --
-- -- -- -- -- --
-- -- -- -- -- --
-- -- -- -- -- --
-- -- -- -- -- --
-- -- -- -- -- --
20 30 20 -- 30 --
10 15 10 -- 15 --

0.25 0.40 0.30 0.30 0.40 0.40


0.80 1.00 2.00 0.70 1.00 1.00