Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Sunshine Nuvoco - Vista P.R 11026299 MCC - Panel 6 5 23

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

SUNSHINE CORPORATION

SHYAM MARKET, ROOM C-12, 1ST FLOOR, PANDRI RAIPUR (C.G)


Ph- 0771-4901856, MOBILE: 9302186863 , 98271-86862
E-MAIL I.D –sunshinecorporation_ryp@yahoo.com

QU/SSC/NVCL/09/2023 06/05/2023

TO,
M/S NUVOCO VIST CORPORATION LTD.
RISDA , BALODABAZAR,
RAIPUR, (C.G)

SUB: QUOTATION OF OUT DOOR TYPE 1000A MCC PANEL AS PER YOUR PR NO 1102006299 Dt.4/5/23

KIND ATT: DEEPAK KUMAR JI


DEAR SIR,
WITH REFERENCE TO YOUR REQUIREMENT OF 400A & 630A PDB AS PER YOUR PR NO 1103004346 Dt.4/5/23 , WE ARE PLEASED TO GIVE
OUR MINIMUM PRICE OFFER FOR SAME
AS PER BELOW MENTIONED TECHNICAL DETAIL

1000A MCC PANEL FOR PONTOON ROOM PUMP. PANEL WILL BE SUITABLE FOR 415V AC 3PHASE 4 WIRE POWER
SUPPLY SYSTEM, OUT DOOR INSTALLATION, NON DRAW OUT TYPE FEEDER ( ANNEXURE -1)
FEEDER DETAIL QNTY. MAKE
S.
No. INCOMER 1
MAIN INCOMER ACB 1000A, 50 KA, 3P,EDO MICROPROCESSOR BASED RELAY L&T/SCHNEIDER
1 (DRAW OUT TYPE) 1
2 MULTIFUNCTION METER 1 L&T/SCHNEIDER
3 LED INDICATION LAMP FOR R ,Y AND B PHASE 220VAC 3 L&T/SCHNEIDER
4 ON/OFF/TRIP LED INDICATION LAMP, 220VAC 3 L&T/SCHNEIDER
5 SPRING CHARGE/TRIP CKT HEALTHY LED INDICATION LAMP 2 L&T/SCHNEIDER
6 MICRO SWITCH FOR COMMON I/C OF O/L & S/C 1 L&T/SCHNEIDER
7 SPRING CHARGE I/C MICRO SWITCH 1 L&T/SCHNEIDER
8 TNC SWITCH 25A (1 TRIP+1 CLOSE) 1 L&T/SCHNEIDER
9 MCB SP-6A 5 L&T/SCHNEIDER
10 RESIN CAST CT RATIO (1000/5) A 3 VENTEX
11 ANALOGUE TYPE AMPERE METER (0-1000A) SEC.CURRENT 5A 1 RISHAB
12 AMMETER SELECTOR SWITCH (ASS) 6A 1 L&T
13 ANALOGUE TYPE VOLTMETER (0-500)V 1 RISHAB
14 VOLTMETER SELECTOR SWITCH (VSS) 6A 1 L&T
15 MICROPROCESSOR BASED PROTECTION RELAYS 1 L&T ;MCX61
16 TAPE WOUND CT (1000/5A) 3 VENTEX
17 CT SHORTING TERMINAL 8 ELMEX
18 AUXILIARY CONTACTOR 3NO+1NC 2 L&T/SCHNEIDER
DIGITAL TYPE EARTH LEAKAGE RELAY 30 MA TO 30A, LEAKAGE CURRENT DISPLAY, AUX ELMEASUER
19 SUPPLY (110-240 VAC & 110 VDC) 1
20 CBCT FOR EARTH LEAKAGE RELAY 1 ELMEASUER

OUTGOING-1 : 1NO
A MCCB 125A
1 MCCB 125A,50KA, 3P 1 L&T/SCHNEIDER
2 EXTENDED ROM 1 L&T/SCHNEIDER
3 SPREADER TERMINALS 3 L&T/SCHNEIDER
4 ON/OFF/TRIP LED INDICATION LAMP, 220VAC 3 L&T/SCHNEIDER
5 MCCB TRIP COIL FOR EARTH LEAKAGE RELAY 1 L&T/SCHNEIDER
DIGITAL TYPE EARTH LEAKAGE RELAY 30 MA TO 30A,LEAKAGE CURRENT DISPLAY, AUX ELMEASUER
6 SUPPLY (110-240 VAC & 110 VDC) 1
7 CBCT FOR EARTH LEAKAGE RELAY 1 ELMEASUER
8 ELCB 63A,30MA ,4POLE 1 L&T/SCHNEIDER
OUTGOING-2 : 1 NO
B LIGTING FEEDER 40A X 1
1 INCOMER MCB 40A, 3P, 10 KA 1 L&T/SCHNEIDER
2 POWER CONTACTOR MNX 40 1 L&T/SCHNEIDER
3 TIMER 10 AMP 240 VAC BASE/DIN MOUNTING 1 L&T/SCHNEIDER
4 PUSH BUTTON START, STOP 2 L&T/SCHNEIDER
5 LED INDICATION ON, OFF 2 L&T/SCHNEIDER
6 SELECTOR SWITCH LOCAL/ REMOTE 1 KEYCEE/SCI
7 O/G MCB 10A, 1P, 10 KA 5 L&T/SCHNEIDER
8 TB 10A, 5 L&T/SCHNEIDER
9 ELCB 40A,30MA ,4POLE 1 L&T/SCHNEIDER

QU/SSC/NVCL/08/2023
DT. 06/07/2023 Page 1 of 4
SUNSHINE CORPORATION
SHYAM MARKET, ROOM C-12, 1ST FLOOR, PANDRI RAIPUR (C.G)
Ph- 0771-4901856, MOBILE: 9302186863 , 98271-86862
E-MAIL I.D –sunshinecorporation_ryp@yahoo.com

OUTGOING-3 : 1NO
C 160 KW Y/D STARTER X 1 (CONTROL SUPPLY -110V AC)
1 INCOMER MCCB 630A,3P 1 L&T/SCHNEIDER
2 STAR CONTACTOR 200A 1 L&T/SCHNEIDER
3 DELTA & MAIN CONTACTOR 300A 2 L&T/SCHNEIDER
4 OVER LOAD RELAY (135-225) A 1 L&T/SCHNEIDER
5 EXTENDED ROM 1 L&T/SCHNEIDER
6 SPREADER TERMINALS 1 L&T/SCHNEIDER
7 STAR/DELTA TIMER , 3-120 SEC 1 L&T/SCHNEIDER
8 MCB 2P 6A 10KA FOR CONTROL 1 L&T/SCHNEIDER
9 PUSH BUTTON START, STOP AND E-STOP WITH 2NC AND 1 NO 3 L&T/SCHNEIDER
10 LED INDICATION MOTOR ON,OFF AND MOTOR TRIP (220 VAC) 3 L&T/SCHNEIDER
11 SELECTOR SWITCH LOCAL/ REMOTE 1 KEYCEE/SCI
12 CONTROL CONTACTOR 2NO+2NC 2 L&T/SCHNEIDER
13 TAP WOUND CT 630/5 A 3 VENTEX
14 AMPERE METER ANALOGUE (0-630)A SEC.CURRENT 5A 1 RISHAB
15 AMMETER SELECTOR SWITCH (ASS) 6A 1 L&T
DIGITAL TYPE EARTH LEAKAGE RELAY 30 MA TO 30A,LEAKAGE CURRENT DISPLAY, AUX ELMEASUER
16 SUPPLY (110-240 VAC & 110 VDC) 1
17 CBCT FOR EARTH LEAKAGE RELAY 1 ELMEASUER
18 REMOTE START/STOP PUSH BUTTON STATION 1 REPUTED
19 CONTROL TRANSFORMER (SUPPLY FOR REMOTE START/STOP 24VAC ) 1 REPUTED
OUTGOING-4 : 1NO.
D 75 KW DOL STARTER X 1 (CONTROL SUPPLY -110V AC)
1 INCOMER MCCB 250A,3P 1 L&T/SCHNEIDER
2 POWER CONTACTOR 225A 1 L&T/SCHNEIDER
3 OVER LOAD RELAY (90-150)A 1 L&T/SCHNEIDER
4 EXTENDED ROM 1 L&T/SCHNEIDER
5 SPREADER TERMINALS 1 L&T/SCHNEIDER
6 STAR/DELTA TIMER , 3-120 SEC 1 L&T/SCHNEIDER
7 MCB 2P 6A 10KA FOR CONTROL 1 L&T/SCHNEIDER
8 PUSH BUTTON START, STOP AND E-STOP WITH 2NC AND 1 NO 3 L&T/SCHNEIDER
9 LED INDICATION MOTOR ON,OFF AND MOTOR TRIP (220 VAC) 3 L&T/SCHNEIDER
10 SELECTOR SWITCH LOCAL/ REMOTE 1 KEYCEE/SCI
11 CONTROL CONTACTOR 2NO+2NC 2 L&T/SCHNEIDER
12 TAP WOUND CT 250/5 A 3 VENTEX
13 AMPERE METER ANALOGUE (0-250)A SEC.CURRENT 5A 1 RISHAB
14 AMMETER SELECTOR SWITCH (ASS) 6A 1 L&T
DIGITAL TYPE EARTH LEAKAGE RELAY 30 MA TO 30A,LEAKAGE CURRENT DISPLAY, AUX ELMEASUER
15 SUPPLY (110-240 VAC & 110 VDC) 1
16 CBCT FOR EARTH LEAKAGE RELAY 1 ELMEASUER
17 REMOTE START/STOP PUSH BUTTON STATION 1 REPUTED
18 CONTROL TRANSFORMER (SUPPLY FOR REMOTE START/STOP 24VAC ) 1 REPUTED
BUSBAR : 1NO.
50X10 COPPER BUSBAR EC GRADE COVERED WITH RYB & B COLOR
E CODED HEAT SHRINKABLE PVC SLEEVES O EPOXY BUSBAR SUPPORT 4
CONSTRUCTIONAL DETAIL OF PANEL
LENGTH- 2000 MM X HEIGHT 2200 MM X DEPTH-900 MM
APPROX.SIZE
FRONT OPEN ABLE DOORS
TYPE OUTDOOR INSTALLATION, FLOOR MOUNTED
POWER 415 V AC 50 HZ AC 3DUTY
CABLE ENTRY FROM BOTTOM, THROUGH REMOVABLE UNDRILLED GLAND PLATES
EARTHING M10 G.I STUD AT BOTH BOTTOM END
MADE FROM MAIN STRUCTUER 2 MM CRCA SHEET, DOORS 1.6 MM CRCA SHEET, GLAND
PANEL
PLATE-2MM CRCA SHEET POWDER COATED WITH RAL7035 SIEMENS GREY SHADE

QU/SSC/NVCL/08/2023
DT. 06/07/2023 Page 2 of 4
SUNSHINE CORPORATION
SHYAM MARKET, ROOM C-12, 1ST FLOOR, PANDRI RAIPUR (C.G)
Ph- 0771-4901856, MOBILE: 9302186863 , 98271-86862
E-MAIL I.D –sunshinecorporation_ryp@yahoo.com

RATES:
PARTICULARS RATE- EACH:
1000A MCC PANEL FOR PONTOON ROOM PUMP. PANEL WILL BE SUITABLE FOR 415V AC RS. 5,65,000.00
1 3PHASE 4 WIRE POWER SUPPLY SYSTEM, OUT DOOR INSTALLATION, NON DRAW OUT
EACH
TYPE FEEDER ( ANNEXURE -1)

TERMS & CONDITION:


1. TAXES: GST @ 18 % EXTRA
2. TRANSPORTATION: ON YOUR SCOPE.
3. PAYMENT: 45% ADVANCE & BALANCE AGAINST PERFORMA IN VOICE
4. OFFER VALIDITY: 30 DAYS.
5. INSPECTION : AT OUR SITE
6. DELIVERY: 5-6 WEEKS AFTER ADVANCE & P.O
7. PACKING EXTRA AS PER ACTUAL
8. ALL G.A & CONTROL DRAWING WILL BE GIVEN AFTER CONFIRMATION OF P.O ORDER WITH ADVANCE
9. THIS OFFER EXCLUDE ANY KIND OF SITE COMMISSIONING / SUPERVISION

WE ONLY BELIEVE IN DOING BUSINESS THE RIGHT WAY

THANKS & REGARD

SANJAY SOMANI

MAKE
: GENERAL SPECIFICATION OF PDB/PCC/MCC PANELS
No. Description Parameter
CRCA-Sheet SAIL/TATA
1 Main enclosure : 2 mm
thickness
Sheet SAIL/TATA
2 Gland plate : 3 mm
thickness
Sheet SAIL/TATA
3 Membrane & partition : 1.2 mm
thickness
Base channel :
4 BASE
MCC PANEL: BASE channel : 75MM HEIGHT
5 Cable entry: top / bottom Cable

6 Powder coating : Siemens gray shade RAL 7032 color RAPIDCOAT

MAKE
BUS BAR DETAILS

No. Description Parameter


1 Material : COPPER COPPER

2 Grade electrical
CURRENT
3 1A/ Sq MM UP TO 2000A
DENSITY

QU/SSC/NVCL/08/2023
DT. 06/07/2023 Page 3 of 4
SUNSHINE CORPORATION
SHYAM MARKET, ROOM C-12, 1ST FLOOR, PANDRI RAIPUR (C.G)
Ph- 0771-4901856, MOBILE: 9302186863 , 98271-86862
E-MAIL I.D –sunshinecorporation_ryp@yahoo.com

CURRENT
4 1.5A/ Sq MM ABOVE 2000A
DENSITY
BUS BAR SUPPORT : SMC/DMC INSULATOR AS PER RAMANUJ
5 INSULATOR
REQUIREMENT
6 HEAT SHRINKABLE PVC SLEEVE FOR COLOR GRADE COLOR CODE
Icw = 50 KA/
7 Rated S.C. current w/s capacity for 1 sec
Arms =45KA
8 System Insulation Voltage Ui = 670 V
9 System continuous Current Iu = 6000 A
10 System Impulse Voltage Imp = 12 KV
Clearance
11 Phase to phase/phase to neutral/phase to earth
above 35 mm

HARDWARE DETAILS
Description
ALL NUT BOLT HARDWARE WILL BE ZINC PASSIVATED CHROME

ALL THE NUT BOLT WILL BE TIGHTEN BY HIGH TENSILE SPRING WASHER

WIRING DETAILS
Description
WIRE : MULTISTRAND COPPER CABLE
ALL CONTROL WIRING WILL BE DONE BY 1.5 Sq MM FOR METERING &
CONTROL
ALL C.T & PROTECTION CKT WIRING WILL BE DONE BY 2.5 SQ MM
COPPER LUG (RING, PIN, FORK) WILL BE USED TO TERMINATION FOR
CABLE.
DIGITAL PRINTED FERRULE WILL BE USED FOR CABLE IDENTIFICATION

ACCESSORIES DETAILS
Description
ALL THE OPERABLE FEEDER DOOR WILL BE PROVIDED WITH CHROME
PLATED DOOR LOCK WITH KEY
ALL DOOR WILL BE PROVIDED WITH NEOPRENE GASKET, STICK WITH
ADHESIVE.
ALL BUS BAR WILL BE SHROUDED WITH ACRYLIC/HYLUM SHEET

EACH FEEDER/ DOOR WILL HAVE LEGEND PLATE FOR IDENTIFICATION

QU/SSC/NVCL/08/2023
DT. 06/07/2023 Page 4 of 4

You might also like