All DRG, Bom & Qap.-Salon
All DRG, Bom & Qap.-Salon
All DRG, Bom & Qap.-Salon
OF MATERIAL
EQUIPMENT OUTDOOR TYPE 11KV,630A,25kA/1 Sec, ICOG VCB PANEL QTY.:01 SET
PROJECT SOMALIYA SOLAR PROJECT
CUSTOMER SOLON INDIA PVT LTD ,SECUNDERABAD, A. P, – 500 026 ( INDIA )
JOB NO
JOB NO. J‐268/2014‐15
PANEL SR. NO. HTS/JL/J‐268/01/01/2015
Rev.00
MANUFACTURER H.T. SWITCHGEARS, PUNE‐ 411 023 (INDIA) Date: 12.01.2015
2 CURRENT TRANSFORMER
2.1 CT1,CT2,CT3 11KV, EPOXY RESIN CAST, CT
CORE-1 : CL 0.5,10VA PRAGATI/ 3
CORE -2 :- CL 5P10 , 10 VA AE
CT RATIO : 140/ 1-1 A ,
WOUND PRIMARY TYPE /AS PER MAN.DESIGN
STC‐ 25 KA/1SEC,
INSULATION- 12 / 28 / 75 KVP
CLASS OF INSULATION- B
AS PER IEC 60044.1
SECONDARY TERMINALS ON- P1 SIDE
FREQUENCY- 50HZ, INDOOR TYPE
3 POTENTIAL TRANSFORMER
3.1 PT1,PT2,PT3 PT, EPOXY RESIN CAST, DRAW OUT TYPE
INDOOR TYPE, SINGLE PHASE ,SINGLE POLE PRAGATI/ 3
INSULATED EARTH TYPE AE
WITH INBUILT H.V.FUSE 3.15A
AS PER IEC 600 44.2
RATIO:-
11 KV / 110V /110V
√3 / √3 / √3
SEC: 50VA, CL 0.5
TER :- 50 VA ,3P
INSULATION- 12 / 28 / 75 KVP
CLASS OF INSULATION
INSULATION- B
FREQUENCY- 50HZ
V.F.:- 1.2CONT. & 1.9 FOR 8 HRS.
4 PROTECTION RELAYS
50,50N,51,51N NUMERICAL MICROPROSESSOR BASED DIRECTIONAL
4.1 27,59, ‐NON DIRECTIONAL 'RELAY WITH FOLLOWING PROTECTION ALSTOM 1
50 ‐Definite time overcurrent protection
/ p
50N ‐ Neutral/Ground Definite time overcurrent protection
51 ‐ IDMT overcurrent protection
51N ‐Neutral/Ground IDMT overcurrent protection
CONT. 2
2
4.2 86 MASTER TRIP RELAY, HAND RESET TYPE
TYPE - PQ8 Nch2j ABB 1
COIL VOLTAGE 110 V DC, FLUSH MOUNTED
5 NO + 2NC CONTACTS,
5 METERING
5.1 V TAUT BAND VOLTMETER,96 X 96 mm M.C.TYPE AE/ RISHABH 1
RANGE : - 0 - 12KV, P.T. RATIO : 11000/110 V AC
5.3 A TAUT BAND AMMETER 96 X 96 MM M.C.TYPE
SCALE 0‐140A, C.T. RATIO: 140/1A AE/RISHABH 1
CONT. 3
3
7 INDICATING LAMPS
INDICATING LAMPS
7.1 IND LAMPS, DIA 22.5 ,LED TYPE 110V DC L&T / DAV
IL1 VCB ON (RED) 1
IL2 VCB OFF (GREEN) 1
IL3 VCB AUTO TRIP (AMBER) 1
IL4 TRIP CIRCUIT HEALTHY COIL‐1 (WHITE) 1
IL5 TRIP CIRCUIT HEALTHY COIL‐2 (WHITE) 1
IL6 VCB SPRING CHARGED (BLUE) 1
IL7 VCB TEST POSITION(RED) 1
IL8 VCB SERVICE POSITION(GREEN)
VCB SERVICE POSITION(GREEN) 1
8 COMMON FOR SWITCHGEARS
8.1 ‐‐‐‐‐‐‐‐ 11 KV EPOXY INSULATORS MOULD TECH / AS PER REQUIREMNET
SIZE 75X130 mm HEIGHT, CREEPAGE‐250 mm BBI
8.3 F CONTROL FUSE FOR PT SEC
2 AMP TYPE NS
2 AMP TYPE NS DAV + C&S
DAV + C&S 6
NEUTRAL LINK DAV 2
8
8.5 PL PANEL LAMP HOLDER
O ANCHOR
C O 1
JUMPER 40 X 10 mmX 01 NOS. / PHASE FOR BUS PT AS PER REQUIREMNET
1 2 3 4 5 6 7 8
SR. COMPONENT CHARACTERISTIC QUANTUM REFERENCE ACCEPTANCE FORMAT OF INSPECTION AUTHORITY
NO. CHECK OF CHECK DOCUMENTS NORMS RECORD
1 2 3 4
1. M.S.SHEET QUALITY ,PHYSICAL FREE FROM MAJOR
PROPERTIES i.e. 100% ---- SURFACE DEFECTS ---- --- P --- ---
THICKNESS
2. BUSBAR - AL. QUALITY ,PHYSICAL
PROPERTIES I.e 100% AS PER BILL OF FREE FROM MAJOR ---- --- P --- ---
SIZE & THICKNESS MATERIAL SURFACE DEFECTS
3. VACUUM CIRCUIT DIMENSIONAL CHECK , 100% AS PER BILL OF ---- ROUTINE TEST P R --- ---
BREAKER ON /OFF OPERATION MATERIAL,SUPPLIERS CERTIFICATE OF
DRAWING SUPPLIER
4. CURRENT TRANSFORMER DIMENSIONAL CHECK , 100% AS PER BILL OF ---- ROUTINE TEST P R --- ---
POTENTIAL TRANSFORMER RATIO CHECK MATERIAL, SUPPLIERS CERTIFICATE OF
DRAWING SUPPLIER
5. METERS / RELAYS DIMENSIONAL CHECK , 100% AS PER BILL OF ---- ROUTINE TEST P R --- ---
OPERATION CHECK MATERIAL, SUPPLIERS CERTIFICATE OF
DRAWING SUPPLIER
6. COMPLETE PANEL ROUTINE TEST , APPROVED APPROVED HTS ROUTINE --- P P P
DIMENSIONAL CHECK 100% DRAWINGS DRAWINGS TEST CERTIFICATE
* FOLLOWING ROUTINE TESTS CARRIED OUT -
A Visual inspection & dimension check – --- --- W W
B Checking of C.T. Ratio by primary injection test – --- --- W W
C Checking of C.T. Polarity as per manufacturer marking – --- --- W W
D Checking of Voltage ratio of Potential Transformer – --- --- W W
E Checking of Mechanical & Electrical operation of VCB - --- --- W W
F H.V. Test 28 kV for 1 minute --- --- W W
G Megger test before & after H.V. – --- --- W W
H Checking of Relay by primary injection test – --- --- W W
Note : (1) No witness Test for Sr. No. 1,2,3,4 & 5 involved .
(2) Only Routine Test for complete Panel ( Sr.No.6)