All DRG, Bom & Qap.-Salon

Download as pdf or txt
Download as pdf or txt
You are on page 1of 21
At a glance
Powered by AI
The document discusses the ordering of equipment for an 11kV solar power project in Somalia, including specifications of a VCB panel and components within it.

An 11kV, 630A, 25kA/1sec indoor cubicle mounted VCB panel along with associated equipment like CTs, PTs, meters, relays etc. is being ordered.

Routine tests like dimensional checks, ratio testing, operation checks and HV testing will be conducted on the VCB, CTs, PTs and complete panel.

BILL 

OF MATERIAL 
EQUIPMENT   OUTDOOR TYPE 11KV,630A,25kA/1 Sec, ICOG VCB PANEL QTY.:01 SET

PROJECT SOMALIYA SOLAR PROJECT

CUSTOMER SOLON INDIA PVT LTD ,SECUNDERABAD, A. P, – 500 026 ( INDIA )

JOB NO
JOB NO. J‐268/2014‐15

PANEL SR. NO. HTS/JL/J‐268/01/01/2015
Rev.00
MANUFACTURER  H.T. SWITCHGEARS, PUNE‐ 411 023 (INDIA) Date: 12.01.2015

SR.  TAG               DESCRIPTION       MAKE  QTY 


NO NO. TOTAL
1 VACUUM CIRCUIT BREAKER
1.1 52 DRAW OUT TYPE ,VCB TYPE VMAX
11KV , 3 PHASE ,50 Hz, 25kA /1 SEC
TRIPPING(02 Nos) & CLOSING COIL : - 110 VDC
SPRING CHARGING MOTOR : - 230 VAC
AUX CONTACT 4 NO + 3 NC ABB 1
LIMIT SWITCHES FOR TEST/SERVICE
HORIZONTAL DRAWOUT WITH SERVICE,TEST & ISOLATED
POSITIONS ,SPRING CHARGED MECH.WITH FOLLWING
ACCESSORIES
a) MECHANICAL SAFETY INTEROCKS
b) AUTOMATIC SAFETY SHUTTERS
c) MANUAL TRIP WITH FRONT DOOR OPEN
d) MECHANICAL ON/OFF INDICATOR
e) SPRING CHARGE/DISCHARGE INDICATORS
f) MANUAL SPRING CHARGE FACILITY
g) TRIP FREE MECHANISM
h) 'OPERATION COUNTER

2 CURRENT TRANSFORMER
2.1 CT1,CT2,CT3 11KV, EPOXY RESIN CAST, CT
CORE-1 : CL 0.5,10VA PRAGATI/ 3
CORE -2 :- CL 5P10 , 10 VA AE
CT RATIO : 140/ 1-1 A ,
WOUND PRIMARY TYPE /AS PER MAN.DESIGN
STC‐ 25 KA/1SEC, 
INSULATION- 12 / 28 / 75 KVP
CLASS OF INSULATION- B
AS PER IEC 60044.1
SECONDARY TERMINALS ON- P1 SIDE
FREQUENCY- 50HZ, INDOOR TYPE

3 POTENTIAL TRANSFORMER
3.1 PT1,PT2,PT3 PT, EPOXY RESIN CAST, DRAW OUT TYPE
INDOOR TYPE, SINGLE PHASE ,SINGLE POLE PRAGATI/ 3
INSULATED EARTH TYPE AE
WITH INBUILT H.V.FUSE 3.15A
AS PER IEC 600 44.2
RATIO:-
11 KV / 110V /110V
√3 / √3 / √3
SEC: 50VA, CL 0.5
TER :- 50 VA ,3P
INSULATION- 12 / 28 / 75 KVP
CLASS OF INSULATION
INSULATION- B
FREQUENCY- 50HZ
V.F.:- 1.2CONT. & 1.9 FOR 8 HRS.

4 PROTECTION RELAYS
50,50N,51,51N  NUMERICAL MICROPROSESSOR BASED DIRECTIONAL
4.1 27,59,  ‐NON DIRECTIONAL 'RELAY WITH FOLLOWING PROTECTION ALSTOM 1
50 ‐Definite time overcurrent protection
/ p
50N ‐ Neutral/Ground Definite time overcurrent protection
51 ‐ IDMT overcurrent protection
51N ‐Neutral/Ground IDMT overcurrent protection
CONT. 2
2

SR.  TAG               DESCRIPTION       MAKE  QTY 


NO NO. TOTAL
27‐UNDER VOLTAGE
59‐ OVER VOLTAGE
DI‐8, DO‐8
AUX VOLTAGE ‐110 VDC PT SECONDORY 110VAC
AUX. VOLTAGE ‐110 VDC ,PT SECONDORY 110VAC
WITH RS‐485 MODBUS COMMUNICATION
TYPE:‐  P14DB/Eqv. 

4.2 86 MASTER TRIP RELAY,  HAND RESET  TYPE
TYPE - PQ8 Nch2j ABB 1
COIL VOLTAGE 110 V DC, FLUSH MOUNTED
5 NO + 2NC CONTACTS,

4.3 95‐1,95‐2 TRIP CIRCUIT SUPERVISION RELAY ABB 2


FLUSH MOUNTED , AUX. VOLTAGE 110 V DC,
1 NO + 2 NC + 2 C/O, S/R CONTACTS,
TYPE - TCS

4.5 63AB,CD,EF AUX. RELATY FOR T/F WTI/OTI/BZ ABB 3


FLUSH MOUNTING TYPE, 2 ELEMNT ,S/R CONTACTS
ELECTROMECHANICAL TYPE, TYPE TYPE   CV2D2J
ELECTROMECHANICAL TYPE, TYPE TYPE ‐ CV2D2J

4.6 APR AUX. RELAY FOR ANTI PUMPING L ,TYPE:‐ CRM /RN4 ABB / RELPOL 1


AUX.VOLTAGE‐ 110V DC., DIN RAIL MOUNTED
OUTPUT CONTACTS‐ 2 C/O

4.7 52X AUX CONTACTOR FOR VCB CONTACT ABB / SEIMENS 1


 MULTIPLICATION , 'AUX.VOLTAGE‐ 110V DC., 
OUTPUT CONTACTS‐ 2NO+2NC,DIN RAIL MOUNTED
NC' ADD ON BLOCK
NC' ADD ON BLOCK  2

5 METERING
5.1 V TAUT BAND VOLTMETER,96 X 96 mm M.C.TYPE AE/ RISHABH 1
RANGE : - 0 - 12KV, P.T. RATIO : 11000/110 V AC

5.2 VSS VOLTMETER SELECTOR SWITCH SALZER/ 1


4 POSITION OFF - RY - YB - BR KAYCEE

5.3 A TAUT BAND AMMETER 96 X 96 MM  M.C.TYPE
SCALE 0‐140A, C.T. RATIO: 140/1A AE/RISHABH 1

5.4 ASS AMMETER SELECTOR SWITCH SALZER/ 1


4 POSITION OFF - R - Y - B KAYCEE

5.5 MFM  MULTIFUNCTION METER , SIZE 96 x 96 MM


DIGITAL TYPE , 3PHASE, 4 WIRE ,CLASS‐0.5 RISHABH /AE/ 1
C.T. RATIO : 140/ 1A, PTR 110 V AC CONZERV
IMPORT / EXPORT WITH RS 485 COMMUNICATION PORT (SCHNIEDER)
AUX SUPPLY 110 V AC
TYPE:- EM6400/Eqv.

5.6 ANN ALARM ANNUNCIATOR  


WITH INBUILD TEST/ACCEPT/RESET PUSH BUTTON PROTON/ 1
LEGENDS AS PER DRAWING ALAN
16 WINDOW, AUX. SUPPLY : 110 V DC

5.7 H HOOTER ,  96X96MM PROTON  1


FLUSH MOUNTED TYPE  ,AUX. SUPPLY 110V DC,

4.8 TTB TEST TERMINAL BLOCK


SUITABLE FOR 3 PHASE, 4 WIRE SYSTEM, DAV 1
BACK CONNECTED COMPLETE WITH BAKELITE
COVER AND SEALING ARRANGEMENT
6 CONTROL SWITCHES
6.1 BCS BREAKER CONTROL  SWITCH  SALZER / 1
SPRING RETURN TYPE , T‐N‐C,16 A,  KAYCEE
1 NO IN EACH POSITION,PISTAL GRIP

CONT. 3
3

SR.  TAG               DESCRIPTION       MAKE  QTY 


NO NO. TOTAL
6.2 LR LOCAL REMOTE SELECTOR SWITCH  SALZER / 1
LOCKABLE WITH 02 NO + 2 NC ELEMENT  KAYCEE

7 INDICATING LAMPS
INDICATING LAMPS
7.1 IND  LAMPS,  DIA 22.5 ,LED TYPE 110V DC  L&T / DAV
IL1 VCB ON  (RED) 1
IL2 VCB OFF (GREEN) 1
IL3 VCB AUTO TRIP (AMBER) 1
IL4 TRIP CIRCUIT HEALTHY COIL‐1 (WHITE) 1
IL5 TRIP CIRCUIT HEALTHY COIL‐2  (WHITE) 1
IL6 VCB SPRING CHARGED (BLUE) 1
IL7 VCB TEST POSITION(RED) 1
IL8 VCB SERVICE POSITION(GREEN)
VCB SERVICE POSITION(GREEN) 1

7.2 IND  LAMPS,  DIA 22.5 ,LED TYPE 63.5VAC L&T / DAV


R R‐PHASE  (RED) 1
Y Y‐PHASE (YELLOW) 1
B B‐PHASE (BLUE) 1

8 COMMON FOR SWITCHGEARS
8.1 ‐‐‐‐‐‐‐‐ 11 KV EPOXY  INSULATORS MOULD TECH / AS PER REQUIREMNET
SIZE 75X130 mm HEIGHT, CREEPAGE‐250 mm BBI

8.2 MCB  MCB , DP, 16 A FOR DC ON/OFF L&T / ABB 1


MCB , DP, 10 A FOR AC ON/OFF 1
MCB , SP, 06 A FOR CLOSING, INDICATION & 5
SPRING CHARGING

8.3 F CONTROL FUSE FOR PT SEC
2 AMP TYPE NS
2 AMP TYPE NS DAV + C&S
DAV + C&S 6
NEUTRAL LINK DAV 2

8.4 ‐‐‐‐‐‐‐‐ TERMINAL ,   CONNECTWELL/


FOR CT / PT DISCONNECTED   TYPE  ELMEX AS PER REQUIREMNET
END PLATES FOR ABOVE AS PER REQUIREMNET
FOR CONTROL CIRCUIT CST 2.5 AS PER REQUIREMNET
END PLATES FOR ABOVE AS PER REQUIREMNET

8
8.5 PL PANEL LAMP HOLDER 
O ANCHOR
C O 1

‐‐‐‐‐‐‐‐ 3 PIN SOCKET WITH  03 SWITCHS ANCHOR 1


1) FOR SPACE HEATER
2) FOR PANEL LAMP HOLDER  
3) FOR SOCKET

8.6 SPH  SPACE HEATER , 60W , 230 V AC WITH SWITCH GIRISH EGO 1


8.7 TH TH RMOSTAT
THERMOSTAT  SAI GO
SAI EGO 1
8.8 ‐‐‐‐‐‐‐‐ WIRING , PVC COPPER FLEXIBLE WIRE‐ FRLS POLYCAB AS PER REQUIREMNET
CONTROL  2.5 SQ.MM. GREY FOR D.C 
CONTROL   1.5 SQ.MM. BLACK  FOR A.C 
CT ‐ PT 4 SQ. MM COLOUR CODE R/Y/B
GREEN FOR EARTHING  GRADE 1.1 KV

8.9 ‐‐‐‐‐‐‐‐ AL BUSBAR , WITH HBT SLEEVED  SUDAL


JUMPER 75 X 10 mmX 01 NOS. / PHASE  AS PER REQUIREMNET

JUMPER 40 X 10 mmX 01 NOS. / PHASE FOR BUS PT AS PER REQUIREMNET

8.10 EARTH BUS : ‐ 50 X 06  mm  CU OMEGA AS PER REQUIREMNET

8.11 INDOOR TYPE, M.S. CUBICLE : 14 GAUGE, HTS 1


PROTECTION CLASS IP 4X
QUALITY ASSURANCE PLAN
EQUIPMENTOUTDOOR TYPE 11KV,630A,25kA/1 Sec, ICOG VCB PANEL QTY.:01 SET LEGEND FOR INSPECTION AUTHORITY
PROJECT SOMALIYA SOLAR PROJECT P = PERFORM 1. SUB - VENDOR
CUSTOMER SOLON INDIA PVT LTD ,SECUNDERABAD, A. P, – 500 026 ( INDIA ) R = REVIEW 2. HTS
JOB NO. J‐268/2014‐15 W= WITNESS 3. SUB CONTRACTOR-
PANEL SR. NHTS/JL/J‐268/01/01/2015 4. CLIENT -
MANUFACT H.T. SWITCHGEARS, PUNE‐ 411 023 (INDIA)

1 2 3 4 5 6 7 8
SR. COMPONENT CHARACTERISTIC QUANTUM REFERENCE ACCEPTANCE FORMAT OF INSPECTION AUTHORITY
NO. CHECK OF CHECK DOCUMENTS NORMS RECORD
1 2 3 4
1. M.S.SHEET QUALITY ,PHYSICAL FREE FROM MAJOR
PROPERTIES i.e. 100% ---- SURFACE DEFECTS ---- --- P --- ---
THICKNESS
2. BUSBAR - AL. QUALITY ,PHYSICAL
PROPERTIES I.e 100% AS PER BILL OF FREE FROM MAJOR ---- --- P --- ---
SIZE & THICKNESS MATERIAL SURFACE DEFECTS
3. VACUUM CIRCUIT DIMENSIONAL CHECK , 100% AS PER BILL OF ---- ROUTINE TEST P R --- ---
BREAKER ON /OFF OPERATION MATERIAL,SUPPLIERS CERTIFICATE OF
DRAWING SUPPLIER
4. CURRENT TRANSFORMER DIMENSIONAL CHECK , 100% AS PER BILL OF ---- ROUTINE TEST P R --- ---
POTENTIAL TRANSFORMER RATIO CHECK MATERIAL, SUPPLIERS CERTIFICATE OF
DRAWING SUPPLIER
5. METERS / RELAYS DIMENSIONAL CHECK , 100% AS PER BILL OF ---- ROUTINE TEST P R --- ---
OPERATION CHECK MATERIAL, SUPPLIERS CERTIFICATE OF
DRAWING SUPPLIER
6. COMPLETE PANEL ROUTINE TEST , APPROVED APPROVED HTS ROUTINE --- P P P
DIMENSIONAL CHECK 100% DRAWINGS DRAWINGS TEST CERTIFICATE
* FOLLOWING ROUTINE TESTS CARRIED OUT -
A Visual inspection & dimension check – --- --- W W
B Checking of C.T. Ratio by primary injection test – --- --- W W
C Checking of C.T. Polarity as per manufacturer marking – --- --- W W
D Checking of Voltage ratio of Potential Transformer – --- --- W W
E Checking of Mechanical & Electrical operation of VCB - --- --- W W
F H.V. Test 28 kV for 1 minute --- --- W W
G Megger test before & after H.V. – --- --- W W
H Checking of Relay by primary injection test – --- --- W W
Note : (1) No witness Test for Sr. No. 1,2,3,4 & 5 involved .
(2) Only Routine Test for complete Panel ( Sr.No.6)