132KVF 1

Download as pdf or txt
Download as pdf or txt
You are on page 1of 29

01 02 03 04 05 06 07 08 09 10 11 12 13 14

APPR.
CHECK

A A
NAME
DATE

B B

Job No: GA13011


REVISION

C C

Name of Project 109MW Main HFO Power Plant Project - Bangladesh


REV.

Title 132kV Feeder Control & Protection Panel


D D
Revision: 00

E E
APPR.

CONSULTATN: MATRIX SOLUTIONS PVT LTD - BANGALORE, INDIA shall be


F F
added in title block
CHECK

Magnus Power Private Limited - Bangalore, India


NAME

Project 109MW Main HFO Power Plant Project - Bangladesh


DATE

G G

PO No: MPPL/CLC/PO-05/13-14

Supplier GE India Industrial Pvt.Ltd.

Drawing 132kV Feeder Control & Protection Panel


REVISION

H H
Title

SIZE: A3 JOB No: GA13011 SHEET

g
Project : 109MW Main HFO Power Plant Title : Title Sheet Date 16.08.13
Title : 132kV Feeder Control & Protection Panel
Drawn RJS GE Rev Sheet 01
Project - Bangladesh Checked
Approved
DCS
MVG Digital Energy Drg.No GA13011-01 00 Next Sheet 02
01 02 03 04 05 06 07 08 09 10 11 12 13 14
Sheet Next Sheet Description Rev. Revision Note Sheet Next Sheet Description Rev. Revision Note
APPR.

01 02 Title Sheet 00
CHECK

A A
02 03 List of Drawings 00
03 04 Panel Details - General Arrangement 00
NAME

04 05 Panel Details - Internal View 00


10 11 Bill of Meterial 00
DATE

11 15 Bill of Meterial 00
B B
15 20 Symbols 00
20 30 Protection Block Diagram 00
30 40 Trip Matrix 00
40 41 DC Distribution & DC Fail Circuit 00
REVISION

41 70 AC Distribution Circuit 00
C C
70 71 Annunciation Circuit 00
71 72 Annunciation Circuit 00
72 80 Isolator Indication & Control Circuit 00
REV.

80 81 CB Manual Closing Circuit 00


81 83 CB Tripping Circuit 00
D D
83 110 CB Position Recognition Circuit 00
110 111 Distance Protection CT/PT Circuit 00
111 120 Distance Protection DC Circuit 00
120 121 Backup protection CT/PT Circuit 00
121 130 Backup protection DC Circuit 00
E E
130 150 Line VT Circuit 00
150 151 86A Trip Relay Circuit 00
151 210 86B Trip Relay Circuit 00
210 211 Distance Protection Circuit 00
APPR.

211 220 Distance Protection Circuit 00


F F
220 221 Backup Protection Circuit 00
CHECK

221 250 Backup Protection Circuit 00


250 Nil Spare Contact Details 00
NAME
DATE

G G
REVISION

H H
g GE
Title : 132kV Feeder Control & Protection Panel Project : 109MW Main HFO Power Plant Title : List of Drawings Date 16.08.13 Rev Sheet 02
Drawn RJS
Project - Bangladesh Checked
Approved
DCS
MVG Digital Energy Drg.No GA13011-01 00 Next Sheet 03
01 02 03 04 05 06 07 08 09 10 11 12 13 14
A 800 A
=LE1 +RP1
Equipment Name Description
g =LE1 +RP1 -CL
FC
132kV Feeder Protection Relay Panel
Annunciator
PB1, PB2, PB3 Push Button for Annunciation Accept, Reset, Lamp Test
1 5 9 13 17 21 21 Distance Protection Unit
B 2 6 10 14 18 22 50/51 Backup Protection Unit B
3 7 11 15 19 23 195, 295 Trip Coil Supervision Relay TC1 & TC2
4 8 12 16 20 24 86A, 86B Master Trip Relays
80A,80B DC Supervision Relays
86AX Group-A High Speed Trip Relays, Type:RXMS
86BX
MIMIC shall be revised as per
Group-B High Speed Trip Relays, Type:RXMS
86RST Push Button for Lockout Relay Reset
latest SLD
21 D60
TS1 Test Switch for Distance Protection Relay
TS2 Test Switch for Backup Protection Relay
C H5 C
O N C
H4
CS-Q2 **NOTE: For Cubicle Details Board arrangement refer Drg.No GA13011-CD
T N C
H1 PB1 PB2 PB3
CS-Q0 Indicates Blank Plate
H2
O N C
CS-Q1
The following protections shall be provided instead of back up protection unit.
1. Directional over current protection (67ABC) fed from 132kV Bus PT protection core (132kV/Rt3 / 110V/Rt3)
D D
2. Directional earth fault protection (67N) fed from 132kV Bus PT Open delta core (132kV/Rt3 / 110V/3)
2000

50/51
3. Instantaneous over current relay (50)
2100

F650
Vector surge relay (dv/dt, df/dt) also to be provided
E E
The following general comments shall be taken care and accordingly all sheets shall have to be corrected
1. Control supply shall be 110V DC Instead of 220V DC.
2. Utility and Auxiliary supply (i.e. for space heaters and illumination lamps inside the panels) shall be 230V AC.
86A 86B
195
3. Painting thickness shall be 85 microns, with RAL 7035 with 7 tank process
295
F
4. Please check and correct the base frame height as per cubical drawings, M/s GE shall have to maintain all the F
86RST

panels of uniform height with 15 mm thickness anti vibration pad and 100 mm base channel.
86AX

86BX

80A

80B
TS1

TS2
G G
100
132kV Feeder Control & Protection Panel
H H
g GE
Title : 132kV Feeder Control & Protection Panel Project : 109MW Main HFO Power Plant Title : Panel
Details Date 16.08.13 Rev Sheet 03
Drawn RJS
Project - Bangladesh General Arrangement Checked
Approved
DCS
MVG Digital Energy Drg.No GA13011-01 00 Next Sheet 04
01 02 03 04 05 06 07 08 09 10 11 12 13 14
A A
800 800 800
+B.01
EQUIPMENT NAME DESCRIPTION
TH Thermostart
EAD1 DLS Door limit switch
B B
CFL Cubical fluorescent lamp
HT Heater
+B.07
TH PS
C C
+B.14 +C.14
GE INTERNAL 100 X100
+B.20
D D
+B.22
2000

CUSTOMER WIREWAY 100 X 100


E E
+B.32

GE WIREWAY 60 X 60
F F
+B.40 +C.40
G +B.10 EARTH BAR +C.10 G
PLANE-A PLANE-B PLANE-C
PANEL REF: =LE1 +RP1
H H
g GE
Title : 132kV Feeder Control & Protection Panel Project : 109MW Main HFO Power Plant Title : PanelDetails Date 16.08.13 Rev Sheet 04
Drawn RJS
Project - Bangladesh Internal View Checked
Approved
DCS
MVG Digital Energy Drg.No GA13011-01 00 Next Sheet 10
01 02 03 04 05 06 07 08 09 10 11 12 13 14
Panel Reference : =LE1 +RP1
APPR.

SL. No. Device Device Type Technical Manufacturer Qty GE Item Code Sheet Ref.
Designation Description Designation Data
CHECK

A A
01 =LE1 +RP1 132kV Feeder Protection Panel Dimensions: (WXDXH) 800 X 800 X 2100mm (Base Frame: 100mm (H)) GE 01 03
Relay Panel With Swing Frame &
Paint: Powder Coated
Protective Glass Door Exterior & Interior : RAL7035
NAME

Base Frame: Black


02 CL Circuit Label Black PVC White Letter on Black Background GE 01 03
03 FC Annunciatior MP Based 24 Windows ALAN 01 70, 71
DATE

4 Rows x 5 Columns
B B
Color of Trip Window: Red
Color Of Non Trip Window: White
With Inbuilt DC/AC Fail Annunciation
Auxiliary Supply :220V DC / 230V AC
04 21 Distance Protection relay Numerical Model No : D60-J03-HKH-F8L-H6D-M67-PXX-UXX-WXX GE 01 211
Communication Protocol: IEC61850
Communication Port: Front RS232 & Rear RS485 & 10/100 Base-T
Protection Functions : Distance, VT Fuse Fail, Under Voltage, Over Voltage
REVISION

BOM shall be revises as per Recording Functions: Disturbance Recorder and Event Logger
C C
05 50/51 Bay Control / Protection Unit our commentsNumerical Model No : F650-B-F-B-F-1-G-0-HI-6E GE 01 221
Communication Protocol: IEC61850
Communication Port: Front USB & Rear 10/100 Base Tx
Protection Functions : Non Dir O/C & E/F
REV.

06 86A Master Trip Relay for Line Differential Protection Latching Type Model No : RXMVB2 ABB 01 150
86B Master Trip Relay for Backup Protection Contacts: 6 N/O + 2 N/C ER 01 151
Flag: HR
Auxiliary Supply : 220V DC
D D
07 86AX Group-A High Speed Trip Relay Electro Mechanical Model No : RXMS ABB 01 150
86BX Group-B High Speed Trip Relay Contacts: 6 N/O SR 01 151
Auxiliary Supply : 220V DC
08 86RST Push Button for Lockout relay Reset 2 N/O, 2 N/C ABB 01 150, 151
09 195 Trip Circuit Supervision Relay for CB Close & Trip Coil-1 Static Model No : RXTCS ABB 01 81
E 295 Trip Circuit Supervision Relay for CB Trip Coil-2 Contacts: 2 C/O + 1 N/O + 1 N/C S/R 01 E
Indication: LED
Auxiliary Supply : 220V DC
10 80A DC Source-1 Supervision Relay Static Model No : TSR ABB 01 40
80B DC Source-2 Supervision Relay Contacts: 2 C/O S/R 01 40
Indication: LED
APPR.

Auxiliary Supply : 220V DC


11 PB1 Pushbutton for Anuunciation Accept Momentry contact type Size: 22.5mmDia TEKNIC 01 70
F Colour: Red F
CHECK

Contacts: 2 N/O+2 N/C


PB2 Pushbutton for Anuunciation Reset Momentry contact type Size: 22.5mmDia TEKNIC 01 70
Colour: Yellow
Contacts: 2 N/O+2 N/C
NAME

PB3 Pushbutton for Anuunciation Test Momentry contact type Size: 22.5mmDia TEKNIC 01 70
Please clarify. not Colour: Blue
Contacts: 2 N/O+2 N/C
clear
DATE

G 12 TS1 Test switch for Line Differential Protection Relay Model No : ERMLG ER 01 110 G
TS2 Test switch for Backup Protection Unit Contacts: 2 N/O+2 N/C 01 120
13 CS-Q0 Control switch for Circuit Breaker Spring return No of position 3, Trip-Neutral-close TEKNIC 01 72
CS-Q1 Control switch for Disconnector Spring return No of position 3, Open-Neutral-close TEKNIC 01 72
CS-Q2 Control switch for Disconnector 01
REVISION

H H
g GE
Title : 132kV Feeder Control & Protection Panel Project : 109MW Main HFO Power Plant Title : Bill of Material Date 16.08.13 Rev Sheet 10
Drawn RJS
Project - Bangladesh Checked
Approved
DCS
MVG Digital Energy Drg.No GA13011-01 00 Next Sheet 11
01 02 03 04 05 06 07 08 09 10 11 12 13 14
Panel Reference : =LE1+ RP1
APPR.

SL. No. Device Device Type Technical Manufacturer Qty GE Item Code Sheet Ref.
Designation Description Designation Data
CHECK

A A
14 H1 Position Indicator for Circuit Breaker LED Size: 30mm Dia DOM0 01 72
TV22/30 CRQ RG.V220 Auxiliary Supply : 220V DC
NAME

H2 Position Indicator for Disconnector LED Size 30mm Dia DOM0 01 72


H4 Position Indicator for Disconnector TV22/30 CRT RG.V220 Auxiliary Supply : 220V DC 01
DATE

Position Indicator for Earth Switch LED Size: 30mm Dia DOM0 01 72
H5
B TV22/30 CRT RG.V220 Auxiliary Supply : 220V DC B
Semaphore indicators shall be provided
in mimic , as per M/s Magnus
Internally mounted equipments
SL. No. Device requirement
Device Type Technical Manufacturer Qty GE Item Code Sheet Ref.
Designation Description Designation Data
REVISION

01 MCB-01 MCB for DC1 Incoming Circuit Rating: 10A GE 01 40


MCB-02 MCB for DC2 Incoming Circuit Rating: 10A 01 40
C MCB-03 MCB for Main Protection Circuit Rating: 6A 01 40
C
MCB-04 MCB for Backup Protection Circuit Rating: 6A 01 40
MCB-05 MCB for CB Close & TC1 Tripping Circuit Rating: 10A 01 40
MCB-06 MCB for CB TC2 Tripping Circuit Rating: 10A 01 40
MCB-07 MCB for Annunciation Circuit Rating: 6A 01 40
REV.

MCB-08 MCB for Isolation Control Circuit Rating: 6A 01 40


No. of Poles : 2P
Aux Contact: 1 C/O
Aux Supply: 110V DC
02 MCB-11 MCB for Single Phase AC Circuit Rating: 16A GE 01 41
D No. of Poles : 2P D
Aux Contact: 1 C/O
Aux Supply: 230V AC
03 CFL Compact Fluorescent Lamp with fitting 11W, 230VAC PHILLIPS 01 41
Contacts: 2 N/O + 2 N/C
04 DS Door Limit switch for CFL Contacts: 1 N/C REPUTED 01 41
05 PS Power Socket 3 Pin Rating: 5/15A ANCHOR 01 41
E E
06 HT Space heater 60W, 240VAC SOFIA 01 41
07 TH Thermostat for Space Heater Capillary Range: 30-110 Deg C, 240V AC AI 01 41
08 HS Control Switch for Space Heater Stayput Model No : 1C160 SWITRON 01 41
No of position: 2, Off-On
APPR.

09 TB Terminal Block Disconnecting / Non Disconnecting ELMEX 01


F set F
CHECK

10 EAD1 DC Bell Electronic 220V DC ALAN


01 70
for TRIP annunciation alarm
NAME
DATE

G G
REVISION

H H
g GE
Title : 132kV Feeder Control & Protection Panel Project : 109MW Main HFO Power Plant Title : Bill of Material Date 16.08.13 Rev Sheet 11
Drawn RJS
Project - Bangladesh Checked
Approved
DCS
MVG Digital Energy Drg.No GA13011-01 00 Next Sheet 15
01 02 03 04 05 06 07 08 09 10 11 12 13 14
APPR.

SYMBOLS
CHECK

A A
CURRENT TRANSFORMER RELAY COIL NON DISCONNECTING TYPE TERMINAL
NAME
DATE

B B
I MINIATURE CIRCUIT BREAKER NORMALLY OPEN CONTACT DISCONNECTING TYPE TERMINAL
REVISION

C C
REV.

DOOR LIMIT SWITCH


ISOLATING LINK NORMALLY CLOSED CONTACT
D D
THERMOSTAT
3 PIN POWER SOCKET WITH SWITCH COMBINATION OF NO & NC
CONTACT WITH COMMON TERMINAL CAPILARY TYPE
E E
APPR.

F FLUORESCENT LIGHT HEATER F


PUSH BUTTON
CHECK
NAME

SPRING RETURN TYPE CONTROL SWITCH


DATE

1 2
G G
PANEL BOUNDARY RELAY BOUNDARY
1 2
STAYPUT TYPE CONTROL SWITCH
REVISION

H H
g GE
Title : 132kV Feeder Control & Protection Panel Project : 109MW Main HFO Power Plant Title : Symbols Date 16.08.13 Rev Sheet 15
Drawn RJS
Project - Bangladesh Checked
Approved
DCS
MVG Digital Energy Drg.No GA13011-01 00 Next Sheet 20
01 02 03 04 05 06 07 08 09 10 11 12 13 14
APPR.

132kV LINE TO TOWER


CHECK

A A
132kV, 3 WINDING PT.
CL: 0.2, 50VA
RATIO: 132KV 110V CL: 0.2, 50VA
NAME

3 3 CL: 3P, 50VA


DATE

145kV, 3P, 1250A,


B 40KA B
ISOLATOR WITHOUT
Isolator earth switch shall
M
EARTH SWITCH
be shown. =LE1+RP1
P1 21

DC1
DC2
Distance Protection Unit-D60
REVISION

CORE-1
132kV CT ANSI IEC CODE IEC SYMBOL
Refer GA drawing for our comments
C C
CL: PS, 15VA 21
400-350/1-1-1A 27 U< =PTUV
59 U> =PTOV and revise accordingly
REV.

50/51
Backup Protection Unit-F650
CORE-2
132kV CT ANSI IEC CODE IEC SYMBOL
CL: 5P20, 15VA 51 I> =PTOC
D D
400-350/1-1-1A 51N Io > =PTOC
50 I>> =PIOC
50N Io >> =PIOC
67 I> =PTOC
CORE-3
132kV CT
CL: 0.2 =1MTP
E 400-350/1-1-1A E
EM-MAIN
Energy Meter
3xCT
METERING
3xVT
CORE-4
132kV CT EM-CHECK
APPR.

CL: 0.2, 15VA


Energy Meter
400-350/1-1-1A
3xCT
F METERING F
3xVT
CHECK

P2
NAME

145kV, 3P, 1250A


40KA, M/s GE Shall have to provide the formula of 132kV Side CT and 11kV side CT for calculating the
DATE

SF6 CB
Knee point voltage and I mag at Vk/2.
G G
145kV, 3P, 1250A,
40KA M
ISOLATOR WITHOUT
EARTH SWITCH
132kV BAY
H H
REVISION
g GE
Title : 132kV Feeder Control & Protection Panel Project : 109MW Main HFO Power Plant Title : Protection Block Diagram Date 16.08.13 Rev Sheet 20
Drawn RJS
Project - Bangladesh Checked
Approved
DCS
MVG Digital Energy Drg.No GA13011-01 00 Next Sheet 30
01 02 03 04 05 06 07 08 09 10 11 12 13 14
APPR.
CHECK

A A
CB-52
IED ANSI CC TC1 TC2 Block CL 86A 86B
NAME

50N X X X
50/51 51N X X X
67 X X X
DATE

21 X X X
B 21 59 X B
X X
86A X X X X
86B X X X
195TCS O O
-Ext
295TCS O O
Legend :
O - Supervision
REVISION

X - Action
C 86A & 86B - Lock Out Relay C
TC - Trip Coil
CC - Close Coil
Supervision for 86A and 86B relays shall also have to be provided.
REV.

D D
E E
APPR.

F F
CHECK
NAME
DATE

G G
REVISION

H H
g GE
Title : 132kV Feeder Control & Protection Panel Project : 109MW Main HFO Power Plant Title : Trip Matrix Date 16.08.13 Rev Sheet 30
Drawn RJS
Project - Bangladesh Checked
Approved
DCS
MVG Digital Energy Drg.No GA13011-01 00 Next Sheet 40
01 02 03 04 05 06 07 08 09 10 11 12 13 14
DCDB =LE1 +RP1
APPR.

MCB 01 - 10A
I
80A
TB3
+ J1 J3 TSR
CHECK

A 220V DC A
3 4 11 21
Source-1 J2 J4
Supply -
MCB 05 - 10A

1 2
MCB 03 - 6A

MCB 07 - 6A

MCB 08 - 6A

16 15
NAME

1 3 1 3 1 3 1 3 17
To + I I I I 26 25
Adjacent
DATE

- 2 4 2 4 2 4 2 4 To Annun. Ckt.
Panel
B 27 Sh.71 B
K102

K101

K702

K701
L102

L101
J2

J1

DC Supply auto To Distance To CB Closing & To Annu.Ckt. To Isolator control Ckt.


Protn.Ckt. TC1 Tripping Ckt Sh.70 Sh.72
changeover scheme shall Sh.111 Sh.80
be provided for selecting
supply-1/ supply-2/
REVISION

C
independent sources. C
REV.

MCB 02 - 10A
I
80B
TB3
220V DC + J21 J53 TSR
D 3 4 11 21 D
Source-2 J22 J54
Supply -

MCB 06 - 10A
1 2

MCB 04 - 6A
16 15
1 3 1 3 17
To + I I 26 25
Adjacent 2 4 2 4
Panel - To Annun. Ckt.
27 Sh.71

K202

K201

J102

J101
E E
To Backup Protection Ckt. To CB Closing &
Sh.121 TC2 Tripping Ckt
Sh.80
L111
To Annun. Ckt.
L157 Sh.71
APPR.

11 12
11 12
F F
11 12
CHECK

11 12
11 12
NAME

11 12
11 12
11 12
DATE

G G
REVISION

H H
g GE
Project : 109MW Main HFO Power Plant Title : DC Distribution & DC Fail Circuit Date 16.08.13
Title : 132kV Feeder Control & Protection Panel
Drawn RJS
Rev Sheet 40
Project - Bangladesh Checked
Approved
DCS
MVG Digital Energy Drg.No GA13011-01 00 Next Sheet 41
01 02 03 04 05 06 07 08 09 10 11 12 13 14
APPR.

ACDB =LE1 +RP1


MCB 11 - 16A
CHECK

A I A
TB3
PH H1 H11
230V AC 3 4
Supply NU H2 H12
NAME

1 2
DS H13 CFL
DATE

B HS HT B
H15A H15
1 2
PS
230V AC Supply E
To Adjacent Panel
As Applicable
REVISION

C C
REV.

D D
E E
APPR.

F F
CHECK
NAME
DATE

G G
REVISION

H H
g GE
Project : 109MW Main HFO Power Plant Title : AC Distribution Circuit Date 16.08.13
Title : 132kV Feeder Control & Protection Panel
Drawn RJS
Rev Sheet 41
Project - Bangladesh Checked
Approved
DCS
MVG Digital Energy Drg.No GA13011-01 00 Next Sheet 70
01 02 03 04 05 06 07 08 09 10 11 12 13 14
=LE1 +RP1
APPR.

FROM SH.40
FC 24 WAYS

L101+

L102-
PB1 PH
CHECK

A L105 A
ACCEPT A NU
1-3 1-4
PB2 AD
L107
RESET
NAME

R AD
1-3 1-4
PB3
L109 E
TEST T
DATE

1-3 1-4 +Ve


B B
-Ve
AN EAD1
L113
AN TRIP ALARM
AT
AT
21 SH.211
REVISION

L111
Distance Protection Unit-D60 COM
C (M4) Cont Op 4 DIST PROTN. OP. C
Seal In OFF 4b L121 DISTANCE
50/51 Sh.221 1C
Distance Protection Operated 4c PROTECTION
Backup Protection Unit-F650 OPERATED
T
REV.

F04 B/U Protn. Optd. F


Seal In OFF 27 L123 BACKUP
2C
=BACKUP PROTECTION OPTD. 28 O/C & E/F PROTN.
OPERATED
T
D D
(M5) Cont Op 5 PSB OP.
Seal In OFF 5b L125 POWER SWING
3C BLOCKING
Power Swing Blocking Operated 5c
OPERATED
T
(M6) Cont Op 6
Seal In
VT FUSE FAIL
OFF 6b L127
VT All protections required as
4C FUSE
E
VT Fuse Fail 6c FAIL commented shall have to E
NT
present in annunciator.
195 CB
L131
5C TRIP COIL-1
21 23
SH.81 FAULTY
NT
APPR.

CB-52 295 CB
L133 6C
21 23 TRIP COIL-2
F FAULTY F
SH.81
NT
CHECK

26
X1 -S3 X1 L135 CB
31 7 8 32 27 7C SPRING
NAME

CHARGED
NT
-S12
X1 X1 L137 8C
CB mention description as
DATE

G 33 13 14 34 28
REMOTE G
INDICATION
NT CB Control on remote
X1 -K2 SF6
21 24 9C PRESSURE
29
X1 L141 BLOCKING
22 30
NT
29
-F2
X1 X0 SF6 GAS
10C REPLENISHMENT
11 11 13
REVISION

H 18 H
X0 X1 L143 ALARM
12 12 19
NT
30
Drg No: 1HYB903940-3 Sh.3 TO SH.71
g GE
Project : 109MW Main HFO Power Plant Title : Annunciation Circuit Date 16.08.13
Title : 132kV Feeder Control & Protection Panel
Drawn RJS
Rev Sheet 70
Project - Bangladesh Checked
Approved
DCS
MVG Digital Energy Drg.No GA13011-01 00 Next Sheet 71
01 02 03 04 05 06 07 08 09 10 11 12 13 14
=LE1 +RP1
APPR.

FROM SH.70
CHECK

A FC 24 WAYS A
31
L145 11C SPARE
NAME

32
NT
Spare 33
L147
DATE

12C SPARE
B 34 B
NT
35
L151 13C SPARE
36
NT
45
REVISION

L153 14C SPARE


46
C Spare C
NT
47
L155 15C SPARE
48
REV.

NT
L157 PANEL
21 From Sh.40 16C
SH.211 MCB TRIP
D Distance Protection Unit-D60 D
Critical Failure NT
B1a
L161 MAIN
CRITICAL FAILURE B2b 17C PROTECTION
RELAY FAULTY
50/51 Sh.221 NT
Backup Protection Unit-F650
Power Supply Ok BACKUP
H14 PROTECTION
L163 18C
RELAY FAULTY
E POWER SUPPLY OK H15 E
NT
80A
L165 19C DC
SUPPLY-1/2
26 27
SH.40 FAIL
80B NT
APPR.

26 27
49
SH.40 L167 20C SPARE
F 50
F
NT
CHECK

37
Annunciation windows shall also covers 50 LBB,
38
86 L171
21C
SPARE
LBB,86A/86B Operated.
NAME

NT
39
L173
SPARE
DATE

40 22C
G Spare G
NT
41
L175
SPARE
42 23C
NT
43
L177 SPARE
44 24C
REVISION

H H
NT
g GE
Title : 132kV Feeder Control & Protection Panel Project : 109MW Main HFO Power Plant Title : Annunciation Circuit Date 16.08.13 Rev Sheet 71
Drawn RJS
Project - Bangladesh Checked
Approved
DCS
MVG Digital Energy Drg.No GA13011-01 00 Next Sheet 72
01 02 03 04 05 06 07 08 09 10 11 12 13 14
=LE1 +RP1
APPR.

From Sh.40
+ -
K701

K702

ISOL-89-A CB-52
CHECK

A TB4 A
71 89A-b -S1
K3 TB3 TB3 TB1 X1 X1
NAME

72 24 23 437 110 109


K5 89A-a FOR
Drg No: 1HYB903940-3 Sh.3
73 26 25
CONTROL
TB1 CIRCUIT
DATE

B Semaphore indicators may please be used instead of 74 410 220V DC SUPPLY 438
CB-52 B
LED indications, Same may have to be provided as per 75 418
CS-Q1
M/s Magnus requirement.
-S1
TB1 X1 X1
440 114 113
FOR
O K705 TB4 TB1 Drg No: 1HYB903940-3 Sh.3
REMOTE OPEN INTERLOCK
1 2 76 432 CIRCUIT
REVISION

C K707
REMOTE CLOSE
3 4 441
C 77 430 C
K703 +Ve FROM L/R SWITCH
78 431
Drg No: 1HYD990161-303 Sh.2
ISOL-89-L CB-52
REV.

TB4
81 89A-b -S1
K7 TB3 TB3 TB1 X1 X1
82 24 23 437 118 117
D K9 89A-a FOR D
Drg No: 1HYB903940-3 Sh.3
83 26 25 CONTROL
TB1 CIRCUIT
84 410 220V DC SUPPLY 438
CB-52
85 418
CS-Q2 -S1
TB1 X1
440 122 121
E FOR E
O K715 TB4 TB1 Drg No: 1HYB903940-3 Sh.3
REMOTE OPEN INTERLOCK
1 2 86 432 CIRCUIT
C K717
REMOTE CLOSE
3 4 87 430 441
K713
+Ve FROM L/R SWITCH
88 431
Drg No: 1HYD990161-303 Sh.2
APPR.

ISOL-89-LE CB-52
F TB4 F
CHECK

91 89L-b -S1
K11 TB3 TB3 TB1 X1
92 24 23 440 122 121
K13 89L-a FOR
Drg No: 1HYB903940-3 Sh.3
NAME

93 26 25 INTERLOCK
TB4 TB1 CIRCUIT
94 410 220V DC SUPPLY 441
DATE

G G
95 418
Drg No: 1HYD990161-303 Sh.2
REVISION

H H
g GE
Project : 109MW Main HFO Power Plant Title : Control and Indication Circuit Date 16.08.13
Title : 132kV Feeder Control & Protection Panel
Drawn RJS
Rev Sheet 72
Project - Bangladesh Checked
Approved
DCS
MVG Digital Energy Drg.No GA13011-01 00 Next Sheet 80
01 02 03 04 05 06 07 08 09 10 11 12 13 14
=LE1 +RP1 CB-52
APPR.

TB4 X1+ Ve
J1
220V DC SUPPLY 55 01 TO CB LOCAL CLOSING &
J2 - Ve TC-1 CIRCUITS
CHECK

A SH.40 A
56 02
CS-Q0
To Sh.81
NAME

=SE +RP1
1TB4 1TB4 T K27 TB4 X1
REMOTE OPEN TC1
DATE

07 07 86A 86B 1 2 57 10
196
B K31B K31A C K31 B
REMOTE CLOSE
08 08 223 224 223 224 9 10 58 9
Sh.121 SH.150 SH.150
Drg No: GA13011-06 TB4
59 -S1
K15 X1 X1
60 102 101
K17 -S1
REVISION

61 104 103
C C
REV.

TB4 X1+ Ve
J101
220V DC SUPPLY 65 * TO CB
SH.40 J102 - Ve TC-2 CIRCUITS
66 03
D TB4 D
To Sh.81 67
T K29 X1
REMOTE OPEN TC2
3 4 68 11
Drg No: 1HYB903940-3 Sh.2
E E
APPR.

F F
CHECK
NAME
DATE

G G
REVISION

H H
g GE
Project : 109MW Main HFO Power Plant Title : Circuit Breaker Date 16.08.13
Title : 132kV Feeder Control & Protection Panel
Drawn RJS
Rev Sheet 80
Project - Bangladesh Manual Closing Circuit Checked
Approved
DCS
MVG Digital Energy Drg.No GA13011-01 00 Next Sheet 81
01 02 03 04 05 06 07 08 09 10 11 12 13 14
=SE +RP1 =LE1 +RP1 CB-52
APPR.

From Sh.80
CHECK

A 50/51 Sh.221 A
J1

J2

Backup Protection Unit-F650


F
F02 TC1 Trip
24
TS-2
NAME

Seal In OFF TB4 TC1


23 K1A K23 X1
=Trip Coil-1 Trip 22 15 16
Post Close Supvn.
03 12
21 Sh.211
DATE

Distance Protection Unit-D60


B B
M
Please ensure the
(M2) Cont Op 2 TC1 TRIP
Seal In OFF 2b TS-1
K1B
=Trip Coil-1 Trip 2c 15 16
mentioned terminal details
shall have to match with
113 114
Sh.150
12 13
Sh.150
132kV Breaker drawings.
REVISION

113 114
Sh.151
C 1TB4 1TB4 12 13 C
03 03 Sh.151
196
196X 04 04 195
Sh.121 RXTCS
REV.

Sh.121 A
13 14
TB4
11 K25
15
K26 04 * TC1
12 B Pre Close Supvn.
16 05 13
D To Annunciation Ckt. D
22 23 Sh.70
21
From Sh.80
27 28
50/51 Sh.221 26

J101

J102
Backup Protection Unit-F650
F03 TC2 Trip F
E Seal In OFF 25 TS-2 TB4 X1 TC2 E
K53A K53
=Trip Coil-2 Trip 26 Post Close Supvn.
17 18 13 14
21 Sh.211
Distance Protection Unit-D60
(M3) Cont Op 3 TC2 TRIP M
TS-1
APPR.

Seal In OFF 3b
K53B
=Trip Coil-2 Trip 3c 17 18
F F
115 116
CHECK

Sh.150
14 15
Sh.150
115 116
Sh.151
NAME

1TB4 1TB4 14 15
Sh.151
05 05
196
196X 06 06 295
DATE

Sh.121
G RXTCS G
Sh.121 A
13 14
K55 TB4
11
15 14 *
K56 TC2
12 B Pre Close Supvn.
16 15 15
To Annunciation Ckt.
22 23 Sh.70
21
REVISION

H H
27 28
26
Drg No: GA13011-06 Drg No: 1HYB903940-3 Sh.2
g GE
Project : 109MW Main HFO Power Plant Title : Circuit Breaker Tripping Circuit Date 16.08.13
Title : 132kV Feeder Control & Protection Panel
Drawn RJS
Rev Sheet 81
Project - Bangladesh Checked
Approved
DCS
MVG Digital Energy Drg.No GA13011-01 00 Next Sheet 83
01 02 03 04 05 06 07 08 09 10 11 12 13 14
=LE1+ RP1 CB-52
APPR.
CHECK

A 21 Sh.211 TB4 X1 A
Distance Protection Unit-D60
S1
34 33
NAME

S1
DATE

32 31
B B
Drg No: 1HYB903940 Sh.3
REVISION

C C
REV.

D D
E E
APPR.

F F
CHECK
NAME
DATE

G G
REVISION

H H
g GE
Title : 132kV Feeder Control & Protection Panel Project : 109MW Main HFO Power Plant Title : CB Position Recognition Circuit Date 16.08.13 Rev Sheet 83
Drawn RJS
Project - Bangladesh Checked
Approved
DCS
MVG Digital Energy Drg.No GA13011-01 00 Next Sheet 110
01 02 03 04 05 06 07 08 09 10 11 12 13 14
FROM 132kV LINE SIDE
APPR.

CTMB =LE1 +RP1


21 SH.211
CHECK

A Distance Protection Unit-D60 A


P1 P1 P1 TS-1 IA5 IA
TB1 A11 A12 IA1 Phase-A Current
NAME

21 22 F1c
IA CT 1A SRC-1
F1b
IB5 IB
A31
DATE

A32 IB1 Phase-B Current


23 24 F2c
B B
IB CT 1A SRC-1
F2b
IC5 IC
1S1 1S1 1S1 A51 A52 IC1 Phase-C Current
CORE-1 F3c
25 26
132kV CT IC CT 1A SRC-1
CL: PS, 15VA A71 F3b
A72
400-350/1-1-1A 1S2 1S2 1S2 27 28
REVISION

C C
P2 P2 P2
REV.

TO 132kV BUS SIDE


D D
E111 E112 VA VAG
1 2 F5b
Phase Voltage
VA
E Line VT Supply F5c PT 63.5VAC SRC-1 E
CORE-3 E131 E132 VB VBG
RATIO : 132kV / 110V 3 4 F6b
Phase Voltage
3 3 VB
F6c PT 63.5VAC SRC-1
CLASS : 3P E151 E152
BURDEN : 50VA VC VCG
5 6 F7b
Phase Voltage
From Sh.130 VC
F7c PT 63.5VAC SRC-1
E171 E172
APPR.

7 8
F F
CHECK

To Backup Portn. Ckt.


Sh.120
NAME
DATE

G G
REVISION

H H
g GE
Project : 109MW Main HFO Power Plant Title : Distance Protection Unit CT/PT Circuit Date 16.08.13
Title : 132kV Feeder Control & Protection Panel
Drawn RJS
Rev Sheet 110
Project - Bangladesh Checked
Approved
DCS
MVG Digital Energy Drg.No GA13011-01 00 Next Sheet 111
01 02 03 04 05 06 07 08 09 10 11 12 13 14
=LE1 +RP1
APPR.

21 SH.211
Distance Protection Unit-D60
CHECK

A A
B
K101 HI+
5b Control Power
NAME

110V DC Supply LO+


From Sh.40 6b
K102 -
6a
Surge
8a
Filter
8b
DATE

To Sh.83
B B
REVISION

C C
REV.

D D
E E
APPR.

F F
CHECK
NAME
DATE

G G
REVISION

H H
g GE
Project : 109MW Main HFO Power Plant Title : Distance Protection Unit DC Circuit Date 16.08.13
Title : 132kV Feeder Control & Protection Panel
Drawn RJS
Rev Sheet 111
Project - Bangladesh Checked
Approved
DCS
MVG Digital Energy Drg.No GA13011-01 00 Next Sheet 120
01 02 03 04 05 06 07 08 09 10 11 12 13 14
CTMB =LE1 +RP1
APPR.

FROM 132kV LINE SIDE


50/51 SH.221
Backup Protection Unit-F650
CHECK

A A
P1 P1 P1 TS2 IA
TB1 C12 B
IA Phase-A Current
1
NAME

21 22
IA CT 1A
2
IB
C32
DATE

IB Phase-B Current
23 24 3
B B
IB1 CT 1A
4
IC
2S1 2S1 2S1 C52
CORE-2 IC Phase-C Current
25 26 5
132kV CT IC1 CT 1A
CL: 5P20, 15VA C72 6
400-350/1-1-1A 2S2 2S2 2S2 IN or IG
27 28
REVISION

IG Neutral/Ground Current
10
C IG1 CT 1A C
9
P2 P2 P2
TO 132kV BUS SIDE
REV.

E111 E113 A VAG


VA
1 2 5 Phase Voltage
VA PT 63.5VAC
6
E131 E133 VBG
D VB D
3 4 7 Phase Voltage
From
Sh.110 VB PT 63.5VAC
8
E151 E153 VCG
VC
5 6 9 Phase Voltage
VC PT 63.5VAC
10
E171 E173
7 8
E E
APPR.

F F
CHECK
NAME
DATE

G G
REVISION

H H
g GE
Title : 132kV Feeder Control & Protection Panel Project : 109MW Main HFO Power Plant Title : Backup Protection Unit Date 16.08.13 Rev Sheet 120
Drawn RJS
Project - Bangladesh CT/PTCircuit Checked
Approved
DCS
MVG Digital Energy Drg.No GA13011-01 00 Next Sheet 121
01 02 03 04 05 06 07 08 09 10 11 12 13 14
=LE1 +RP1
APPR.

50/51 SH.221
Backup Protection unit-F650
CHECK

A A
H
K201 +
110V DC Supply 10
NAME

K202 - Control Power


From Sh.40 18
DATE

To Sh.151
B B
REVISION

C C
REV.

D D
E E
APPR.

F F
CHECK
NAME
DATE

G G
REVISION

H H
g GE
Title : 132kV Feeder Control & Protection Panel Project : 109MW Main HFO Power Plant Title : Backup Protection Unit DC Circuit Date 16.08.13 Rev Sheet 121
Drawn RJS
Project - Bangladesh Checked
Approved
DCS
MVG Digital Energy Drg.No GA13011-01 00 Next Sheet 130
01 02 03 04 05 06 07 08 09 10 11 12 13 14
APPR.

CORE-1
CHECK

A RATIO : 132kV / 110V A


1MTP
3 3
CLASS : 0.2
BURDEN : 50VA
1TB2
NAME

1E11
1E31
To Metering Ckt.
DATE

Sh.211
B 1E51 B
1E71
Drg No: GA13011-07
CORE-2
RATIO : 132kV / 110V 1MTP
3 3
REVISION

CLASS : 0.2
BURDEN : 50VA
C C
2TB2 2E11
2E31
To Metering Ckt.
REV.

Sh.211
2E51
2E71
D D
Drg No: GA13011-07
CORE-3
RATIO : 132kV / 110V =LE1 +RP1
3 3
CLASS : 3P
BURDEN : 50VA
TB2 E111
E131
E To Distance E
Protn. Ckt.
E151 Sh.110
E171
APPR.

F F
CHECK

Shall be revised as per Comments on GA drawing


NAME
DATE

G G
REVISION

H H
g GE
Project : 109MW Main HFO Power Plant Title : Line VT Circuit Date 16.08.13
Title : 132kV Feeder Control & Protection Panel
Drawn RJS
Rev Sheet 130
Project - Bangladesh Checked
Approved
DCS
MVG Digital Energy Drg.No GA13011-01 00 Next Sheet 150
01 02 03 04 05 06 07 08 09 10 11 12 13 14
APPR.

=LE1 +RP1
CHECK

A A
NAME

21 Sh.211
Distance Protection Unit-D60 86AX
(M1) Cont Op 1 Protn. Trip M 11 21
DATE

1b 86A
Seal In OFF
B B
=PROTECTION TRIP 1c
86RST
REVISION

16 26
C C
REV.

D D
86B
E E
APPR.

F F
CHECK
NAME
DATE

G G
REVISION

H H
g GE
Title : 132kV Feeder Control & Protection Panel Project : 109MW Main HFO Power Plant Title : 86A Trip Relay Circuit Date 16.08.13 Rev Sheet 150
Drawn RJS
Project - Bangladesh Checked
Approved
DCS
MVG Digital Energy Drg.No GA13011-01 00 Next Sheet 151
01 02 03 04 05 06 07 08 09 10 11 12 13 14
APPR.

=LE1 +RP1
CHECK

A A
NAME

50/51 Sh.221
Backup Protection Unit-F650 86BX
F01 Protn. Trip F 11 21
DATE

Seal In OFF 21
B B
=PROTECTION TRIP 19
86RST
REVISION

18 28
C C
REV.

D D
E E
86A and 86 B shall have to be utilized for all major trips, 86AX/ 86BX shall
have to be utilized only for remote indications/ annunciations.
APPR.

F F
86A and 86B shall have to be provided with 2NO +2NC Spare contacts shall
CHECK

have to be provided for purchaser use other than the contacts used for
Control and relay panels.
NAME
DATE

G G
REVISION

H H
g GE
Title : 132kV Feeder Control & Protection Panel Project : 109MW Main HFO Power Plant Title : 86B Trip Relay Circuit Date 16.08.13 Rev Sheet 151
Drawn RJS
Project - Bangladesh Checked
Approved
DCS
MVG Digital Energy Drg.No GA13011-01 00 Next Sheet 210
01 02 03 04 05 06 07 08 09 10 11 12 13 14
Distance Protection Unit-D60-J03-HKH-F8L-H6D-M67-PXX-UXX-WXX
APPR.

CT Input Contact Input Contact Output Protection Functions


Contact Slot Ref Assignment Sheet Contact Slot Ref Assignment Sheet Contact Slot Ref Assignment Sheet IEC Code Assignment
CHECK

A Input Ref Input Ref output Ref A


1 F -F1 1 H -H1a CB-52 Close /Sh.83 1 M -M1 Protection Trip /Sh.150 21 Distance Protection Unit
2 F -F2 Line CT /Sh.110 2 H -H1c CB-52 Open /Sh.83 2 M -M2 TC1 Trip /Sh.81 27 Under Voltage Relay
3 F -F3 3 H -H2a Spare 3 M -M3 TC2 Trip /Sh.81 59 Over Voltage Relay
NAME

4 F -F4 Spare 4 H -H2c Spare 4 M -M4 Distance Protection Operated /Sh.70 PSB Operated
5 H -H3a Spare 5 M -M5 PSB Operated /Sh.70 27 VT Fuse Fail
PT Input 6 H -H3c Spare 6 M -M6 VT Fuse Fail /Sh.70
DATE

Assignment 7 H -H4a Spare 7 M -M7 Spare /Sh.250


Contact Slot Ref Sheet
B Input Ref 8 H -H4c Spare 8 M -M8 Spare /Sh.250 B
1 F -F5 9 H -H5a Spare
2 F -F6 Line PT /Sh.110 10 H -H5c Spare
3 F -F7 11 H -H6a Spare
4 F -F8 Spare 12 H -H6c Spare Monitoring Functions
13 H -H7a Spare /Sh.250 IEC Code Assignment
14 H -H7c Spare
15 H -H8a Spare 27 VT Fuse Fail
REVISION

16 H -H8c Spare Event logging


Distrubance recording
C C
Fault Report
Distance to fault location
REV.

D D
E E
APPR.

F F
CHECK
NAME
DATE

G G
REVISION

H H
g GE
Title : 132kV Feeder Control & Protection Panel Project : 109MW Main HFO Power Plant Title : Distance Protection Unit Date 16.08.13 Rev Sheet 210
Drawn RJS
Project - Bangladesh Checked
Approved
DCS
MVG Digital Energy Drg.No GA13011-01 00 Next Sheet 211
01 02 03 04 05 06 07 08 09 10 11 12 13 14
=LE1 +RP1
APPR.

21
Distance Protection Unit-D60
CHECK

A DSP Module Type 8L IO Module Type 6D A


(H1a) Cont Ip 1 CB-52 Close H (M1) Cont Op 1 Protn. Trip M
IA
IA5 1a 1b
2.0ms 166VDC Seal In OFF
IA Phase-A Current
F1b CB-52 Close /Sh.83 1b =PROTECTION TRIP /Sh.150 1c
NAME

CT 1A SRC-1
F1c IA1
(H1c) Cont Ip 2 CB-52 Open (M2) Cont Op 2 TC1 Trip
IB 1c 2b
IB5 2.0ms 166VDC Seal In OFF
CB-52 Open =TRIP COIL - 1 TRIP 2c
DATE

IB Phase-B Current /Sh.83 /Sh.81


F2b
B CT 1A SRC-1 B
F2c IB1 (H2a) Cont Ip 3 Spare (M3) Cont Op 3 TC2 Trip
IC 2.0ms 166VDC 2a Seal In OFF 3b
IC5
SPARE =TRIP COIL - 2 TRIP /Sh.81 3c
F3b IC Phase-C Current
IC1 CT 1A SRC-1 (H2c) Cont Ip 4 Spare (M4) Cont Op 4 Dist Protn.Op.
F3c 2c 4b
2.0ms 166VDC Seal In OFF
IG5 IN or IG
SPARE =DISTANCE PROTN OPERATED/Sh.70 4c
Neutral/Ground Current
REVISION

F4b IG
SRC-1
(H3a) Cont Ip 5 Spare (M5) Cont Op 5 PSB Op.
C F4c
IG1 CT 1A 3a 5b C
2.0ms 166VDC Seal In OFF
VAG
VA SPARE 3b Power Swing Blocking Operated /Sh.70 5c
F5b Phase Voltage
VA PT 63.5VAC SRC-1
F5c (H3c) Cont Ip 6 Spare (M6) Cont Op 6 VT Fuse Fail
VB VBG 3c 6b
2.0ms 166VDC Seal In OFF
REV.

F6b
Phase Voltage
VB SPARE VT FUSE FAIL /Sh.70 6c
F6c PT 63.5VAC SRC-1
VC VCG
F7b (H4a) Cont Ip 7 Spare (M7) Cont Op 7 Spare
Phase Voltage 4a 7b
VC 2.0ms 166VDC Seal In OFF
F7c PT 63.5VAC SRC-1
D SPARE SPARE 7c D
V aux /Sh.250
VX
F8b Auxiliary voltage
VX (H4c) Cont Ip 8 Spare (M8) Cont Op 8 Spare
F8c PT 63.5VAC SRC-1
2.0ms 166VDC 4c Seal In OFF 8b
SPARE SPARE /Sh.250 8c
B
1b
1a Critical failure (H5a) Cont Ip 9 Spare H
2.0ms 166VDC 5a
2b
E 3a 48v dc out put
SPARE 5b E
3b
HI+ (H5c) Cont Ip 10 Spare
5b Control power
6b
LO+
2.0ms 166VDC 5c
6a SPARE
Surge
8a
Filter
8b (H6a) Cont Ip 11 Spare
2.0ms 166VDC 6a
APPR.

SPARE
REAR ETHERNET COM BOARD
F 100BaseT F
Tx (H6c) Cont Ip 12 Spare
CHECK

Rx 2.0ms 166VDC 6c
SPARE
(H7a) Cont Ip 13 Spare
NAME

2.0ms 166VDC 7a
SPARE /Sh.250 7b
(H7c) Cont Ip 14 Spare
DATE

G 7c G
2.0ms 166VDC
SPARE
(H8a) Cont Ip 15 Spare
2.0ms 166VDC 8a
SPARE
(H8c) Cont Ip 16 Spare
2.0ms 166VDC 8c
REVISION

H H
SPARE
g GE
Title : 132kV Feeder Control & Protection Panel Project : 109MW Main HFO Power Plant Title : Distance Protection Circuit Date 16.08.13 Rev Sheet 211
Drawn RJS
Project - Bangladesh Checked
Approved
DCS
MVG Digital Energy Drg.No GA13011-01 00 Next Sheet 220
01 02 03 04 05 06 07 08 09 10 11 12 13 14
Backup Protection Unit - F650-B-F-B-F-1-G-0-HI-6E
APPR.

CT Input Contact Input Contact Output


Current Slot Ref Assignment Sheet Contact Slot Ref Assignment Sheet Contact Slot Ref Assignment Sheet
CHECK

A Input Ref Input Ref output Ref A


1 B -B1 1 F -CC1 Spare 1 F -F1 Protection Trip /Sh.151
-B2 2 F -CC2 Spare 2 F -F2 TC1 Trip /Sh.81
2 -B3 3 F -CC3 Spare 3 F -F3 TC2 Trip /Sh.81
Line CT /Sh.120
-B4 4 F -CC4 Spare 4 F -F4 Backup Protection Optd. /Sh.70
NAME

3 -B5 5 F -CC5 Spare 5 F -F5 Spare


-B6 6 F -CC6 Spare 6 F -F6 Spare
4 -B9 7 F -CC7 Spare 7 F -F7 Spare
Spare
-B10 8 F -CC8 Spare 8 F -F8 Spare /Sh.250
DATE

9 F -CC9 Spare
B B
PT Input 10 F -CC10 Spare
Voltage Slot Ref Assignment Sheet 11 F -CC11 Spare
Input Ref 12 F -CC12 Spare
1 A -A5 13 F -CC13 Spare
-A6 14 F -CC14 Spare
2 -A7 /Sh.120 15 F -CC15 Spare
Line VT
-A8 16 F -CC16 Spare
3 -A9 17 G -CC1 Spare
REVISION

-A10 18 G -CC2 Spare


4 -A11 19 G -CC3 Spare
C Spare C
-A12 20 G -CC4 Spare
21 G -CC5 Spare
22 G -CC6 Spare
23 G -CC7 Spare
24 G -CC8 Spare
REV.

25 G -CC9 Spare
26 G -CC10 Spare
27 G -CC11 Spare
28 G -CC12 Spare
29 G -CC13 Spare
D 30 G -CC14 Spare D
31 G -CC15 Spare
32 G -CC16 Spare
E E
APPR.

F F
CHECK
NAME
DATE

G G
REVISION

H H
g GE
Title : 132kV Feeder Control & Protection Panel Project : 109MW Main HFO Power Plant Title : Backup Protection Unit Date 16.08.13 Rev Sheet 220
Drawn RJS
Project - Bangladesh Checked
Approved
DCS
MVG Digital Energy Drg.No GA13011-01 00 Next Sheet 221
01 02 03 04 05 06 07 08 09 10 11 12 13 14
=LE1 +RP1
APPR.

50/51
Backup Protection unit-F650
CHECK

A A
F
F-CC1 F F01 Protn. Trip
21
IA =Spare 01 Seal In OFF
20
B =PROTECTION TRIP
Phase-A Current /Sh.151 19
NAME

1
IA
IA CT 1A F-CC2 F02 TC1 Trip
2 24
=Spare 02 Seal In OFF
IB 23
=Trip Coil-1 Trip
DATE

/Sh.81 22
3
IB Phase-B Current
B B
F-CC3 F03 TC2 Trip
4 IB1 CT 1A 03 25
=Spare Seal In OFF
IC =Trip Coil-2 Trip 26
/Sh.81
5
IC Phase-C Current
F-CC4 F04 B/U Protn. Optd.
IC1 CT 1A 04 27
6 =Spare Seal In OFF
IN or IG =BACKUP PROTECTION OPTD. /Sh.70 28
REVISION

To Neutral/Ground Current
9
IG F-CC5 F05 Spare
Sh.120
C 05 29 C
IG1 CT 1A =Spare Seal In OFF
10
SPARE 30
F-CC6 F06 Spare
06 31
A =Spare Seal In OFF
REV.

VA VAG
5 Phase Voltage SPARE 32
VA PT 63.5VAC
6
F-CC7 F07 Spare
VB VBG
7 07 33
Phase Voltage =Spare Seal In OFF
D VB PT 63.5VAC SPARE 34 D
8
VC VCG
9 Phase Voltage F-CC8 F08 Spare
VC 08 35
PT 63.5VAC =Spare -Ve Seal In OFF
10
V aux 09 SPARE 36
VX /Sh.250
11 Aux Voltage
12
VX PT 63.5VAC F-CC9
=Spare 11
E H
E
13 F-CC10
To POWER SUPPLY OK 12
14 =Spare
Sh.71
15
+Ve
To +
10
Sh.121 CONTROL POWER F-CC11
-Ve -
18 =Spare 13
APPR.

F REAR ETHERNET COM BOARD F-CC12 F


14
CHECK

100BaseT =Spare
Tx
Rx
F-CC13
NAME

=Spare 15
F-CC14
DATE

16
G =Spare G
F-CC15
=Spare 17
F-CC16
=Spare 18
-Ve
H 10 H
REVISION g GE
Project : 109MW Main HFO Power Plant Title : Backup Protection Unit Date 16.08.13
Title : 132kV Feeder Control & Protection Panel Rev
Drawn RJS Sheet 221
Project - Bangladesh Checked
Approved
DCS
MVG Digital Energy Drg.No GA13011-01 00 Next Sheet 250
01 02 03 04 05 06 07 08 09 10 11 12 13 14
=LE1 +RP1
APPR.

21 Sh.211 From Sh.150


Distance Protection Unit-D60
CHECK

A A
(H7a) Cont Ip 13 Spare H
NAME

2.0ms 166VDC H7a


SPARE
DATE

M7) Cont Op 7 Spare M


B 7b B
Seal In OFF
SPARE 7c
(M8) Cont Op 8 Spare
Seal In OFF 8b
SPARE 8c
REVISION

C C
50/51 Sh.221
Backup Protection Unit-F650
REV.

F08 Spare F
35
Seal In OFF
=SPARE 36
D D
Test switches shall have to provide the the following,
CT Shorting facility
Trip Isolation facility
E Extension of DC circuit E
Feeding external current or voltage facility.
SH.150
And test switches shall be preferably M/s GE Make, when GE Make relays used.
APPR.

F F
SH.151
CHECK
NAME
DATE

G G
REVISION

H H
g GE
Title : 132kV Feeder Control & Protection Panel Project : 109MW Main HFO Power Plant Title : Spare Contact Details Date 16.08.13 Rev Sheet 250
Drawn RJS
Project - Bangladesh Checked
Approved
DCS
MVG Digital Energy Drg.No GA13011-01 00 Next Sheet Nil