MEC20 Manual
MEC20 Manual
MEC20 Manual
MICROPROCESSOR
ENGINE/GENERATOR CONTROLLER
(WITH REMOTE COMMUNICATION, EXPANSION OUTPUT MODULE &
EAP 110 REMOTE ANNUNCIATOR OPTIONS)
th
9087A – 198 Street, Langley, BC Canada V1M 3B1 Telephone (604) 888-0110
Telefax (604) 888-3381 E-Mail: info@thomsontechnology.com www.thomsontechnology.com
MEC 20 MICROPROCESSOR ENGINE/GENERATOR CONTROLLER
CONTENTS
1. INTRODUCTION 1
2. INSTALLATION 5
2.7. OUTPUTS 8
3. DESCRIPTION 14
9. OPERATING INSTRUCTIONS 41
12. SPECIFICATIONS 87
15. NOTES 92
1. INTRODUCTION
1.82 05/03/30 Revised Idle Control Logic for Digital Inputs #1,2
Increased High Temperature Analog Shutdown High Limit
1.81 03/03/04 Changed Oil Pressure Sender Manufacturer requiring revised
pressure/resistance calibration data
New Oil Pressure Sender Thomson p/n-003654, Manufacturer-
Datcon, p/n 102227.
Discontinued Oil Pressure Sender Thomson p/n-000772,
Manufacturer- Isspro, p/n R9279C
Note: The oil pressure senders are not interchangeable with the
software versions.
1.8 02/09/09 Added Programmable Output Feature “EPS Supplying Load”
Added Digital Input Feature “No-Load Test”
Added New Digital Fault Names
Basin Rupture
ATS in Bypass
Fuel Leak
Vent Damper Fail
High Fuel Level
Low Fuel Press
Bat Charger Fail
Fail to Sync
HighIntkManfTemp
Added Independent Programming features for AMF Outputs
Added references for EAP 110 Remote Annunciator
Misc. Display & Menu changes
There were also minor changes that are reflected in the manual.
1.6 01/07/18 Added Ready to load programmable output and new Isspro Oil
Pressure sender curves; increased standard digital & analog fault
features.
1.4 99/12/09 Added new digital faults labels and blank selections.
1.3 98/02/09 New version with communication features, expansion relay module
capability, deletion of “horn” programming, deletion of cooldown
shutdown programmability, deletion of “common fail”
programmability and revised password number.
Rev 13 05/03/30 Added descriptive information for new software version 1.82
Rev 12 03/03/04 Changed Oil pressure/resistance calibration data and new software
version 1.81.
Rev 11 02/09/09 Added descriptive information for new software version 1.8
Rev 10 02/02/15 Added descriptive information for new software version 1.7
Rev 2 98/02/18 New version with communication features; expansion relay module
capability and revised password number.
Contact Thomson Power Systems, to obtain applicable instruction manuals. Soft copy
of most current version is available at www.thomsontechnology.com.
accuracy for all voltage monitoring, current monitoring and timing functions as well as
providing many standard features which were previously only available as expensive
add-on optional features.
The MEC 20 provides the following advanced features:
• Up to 28 alarm/shutdown fault circuits utilizing analog and digital inputs.
• Standard model meets or exceeds CSA C282, NFPA 110 Level 1 generator set
control requirements.
• RS 422 remote communication port.
• Expansion output module communication port for individual output fault contact
capability.
• Backlit LCD display screen with alpha-numeric readout for display and programming.
• Digital 3-phase voltage, 3-phase current, KVA and frequency metering for generator
output.
• Non-volatile memory retains logic and set points if control power is lost.
• Direct 3-phase voltage sensing inputs on generator supply from 120Vac up to
600Vac (nominal).
• Security password-protected programming levels.
• Self diagnostic features continuously verify processing, I/O and memory circuits.
• Superior EMI/RFI noise immunity and surge performance features as per IEEE
C62.41 requirements.
• Dual microprocessor design provides independent speed sensing circuitry for higher
performance.
CAUTION
contents subject to damage by
STATIC ELECTRICITY
This equipment contains static-sensitive parts. Please observe the following anti-static
precautions at all times when handling this equipment. Failure to observe these
precautions may cause equipment failure and/or damage.
• Do not touch any components on the printed circuit board with your hands
or any other conductive equipment.
2. INSTALLATION
NOTE:
Installations should be done according to all
applicable electrical regulation codes as
required.
The following installation guidelines are provided for general information only pertaining
to typical site installations. For specific site installation information, consult Thomson
Power Systems as required. Note: Factory installations of THOMSON POWER
SYSTEMS supplied control panels that have been tested and proven may deviate from
these recommendations.
CAUTION!!!
All installation and/or service work performed must be done by qualified
personnel only. Failure to do so may cause personal injury or death.
battery to the control panel should conform to the following guidelines to avoid possible
controller malfunction and/or damage.
2.2.1. Avoid wiring from the engine starter terminals - wiring should go directly
from the battery terminals to the engine control panel (to avoid voltage drop in
the starter cables and starter motor commutator noise). Note: Unit mounted
control panels with short wiring runs may utilize connections from the starter
terminals provided that the specific application is tested satisfactorily.
CAUTION!!!
The battery charger must be turned off before battery cables are removed
from the battery (i.e. for servicing). Failure to do so may subject the
control panel to an overvoltage condition in which damage may result.
2.2.2. Wiring from battery to engine control panel should be two - #14 AWG
(2.5mm2) wires (i.e. do not use the engine block as one of the common
conductors).
2.2.3. Under noisy environments (i.e. gas engines with high voltage ignitions,
etc.), wiring from battery should be a twisted pair of #14 AWG (2.5mm2) wires.
must be “dry” (i.e. non-powered) and one side must be connected to the common DC
negative conductor.
MEC 20 A B C N MEC 20 L1 L2 N
VA VA
VB VB
VC VC
No Connection
VN VN
GRD GRD
GRD GRD
FIGURE #1 FIGURE #2
3Ø, 4W 208/380/480/600VAC DIRECT SENSING 1Ø, 3W 120/240VAC DIRECT SENSING
SOLIDLY GROUNDED NEUTRAL SYSTEM SOLIDLY GROUNDED NEUTRAL SYSTEM
MEC 20 A B C N MEC 20 A B C
VA
120 VA
VB
VB 120
120
VC GRD 120
VC
120 VN
VN
No Connection
GRD
GRD
GRD
GRD
GRD
FIGURE #3 FIGURE #4
3Ø, 4W WYE PT's 3Ø, 3W DELTA PT's
CAUTION!!!
When installing or performing any service work on CT circuits, always de-energize
the system before proceeding with any work. Never open circuit an energized CT
as extreme high voltages may result which may cause serious injury or death.
2.7. OUTPUTS
All outputs from the MEC 20 are relay driven contacts. Relay contacts have a
10A/240Vac resistive, 8A/24Vdc (3 Amp inductive 0.4pf), rating and are isolated Form A
& Form C types. Interposing relays are recommended between the MEC 20 outputs and
end devices to prevent internal damage due to possible excessive current draw and/or
damage should an external fault occur. Note: These outputs will require external
overcurrent protection (Maximum 10 Amp).
The use of AC or DC operated solenoids or relays in control systems can sometimes
cause high voltage spikes on the DC power supply, which may cause electronic devices
to fail. Transient suppression devices are recommended for all inductive devices
sharing wiring or if physically located near engine/generator control panels. For DC
operated relays or solenoids, use a suitably rated counter EMF Diode (or commonly
known as “freewheeling” diode). For AC operated relays or solenoids, use a suitably
rated metal oxide varistor (MOV) or capacitor/resistor suppressor.
Communication cable from the controllers’ com port must be suitably routed to protect it
from sources of electrical interference. Guidelines for protection against possible
electrical interference are as follows:
• Use high quality, 8 conductor shielded cable only with drain wire grounded at the
controller end only.
• Route the communication cable at least 3M (10”) away from sources of electrical
noise such as variable speed motor drives, high voltage power conductors, UPS
systems, transformers, rectifiers etc.
• Use separate, dedicated conduit runs for all communication cables. Do not
tightly bundle communication cables together in the conduit. Conduit should be
ferromagnetic type near sources of possible electrical interference. The entire
length of conduit should be grounded to building earth ground.
• When communication cables must cross over low or high voltage AC power
conductors, the communication cables must cross at right angles and not in
parallel with the conductors.
For additional information on protection against electrical interference, contact Thomson
Power Systems factory.
0.00 mm
152.4 mm
7.62 mm
137.16 mm
152.4 mm
4 HOLES
4.75 MM
DIAMETER
(3/16" DRILL)
7.62 mm 0.00 mm
137.16 mm
G:\ENGINEER\PRODUCTS\MEC20\MEC20_14.VSD
DRAWING SCALE .75:1
268 mm.
C TOP
126 mm. 126 mm.
9 HOLES
80 mm. 6 mm. DIAMETER
(1/4" DRILL)
32 mm.
CUTOUT
20 mm.
166 mm.
8 mm. 8 mm.
24 mm. 24 mm.
OUTLINE OF PRINTED CIRCUIT
BOARD UNDER PANEL DOOR 49 mm. 49 mm.
G:\ENGINEER\PRODUCTS\MEC20_07.VSD
FIGURE #6
MEC 20 PCB
MEC 20 REAR COVER
PEM STUD
#8-32 × 1" #8-32 × 3/8" MACHINE SCREW
HIGH VOLTAGE
MYLAR BARRIER #8-32 INTERNAL TOOTH LOCK WASHER
(mounts on bottom
right hand corner, as
viewed from rear)
FIGURE #7
Notes:
1. Ensure that all lockwashers are installed as shown above.
2. The high voltage mylar barrier (P/N TMW;10805;1) must be installed as shown
when the MEC 20 is installed onto the door of a control panel.
3. When the MEC 20 is installed on a door without 1” PEM studs, 1” machine
screws must be used.
11.5 in
C TOP
9 HOLES
1/4" DIAMETER
CUTOUT
7.5 in
4 STUDS #8/32
1/4"
1/4"
5.5 in
C
3.5 in
10.875 in
6.875 in
3. DESCRIPTION
The MEC 20 controller consists of three parts; a Lexan faceplate, which is mounted externally
on the enclosure door, a printed circuit board (PCB) which is mounted inside the enclosure
door, and a rear cover for the PCB.
connected to the main PCB via plug-in ribbon cable. The main features of the Lexan
faceplate are described as follows with reference to FIGURE #10.
FIGURE #10
LCD viewing window. The LCD display is mounted on the main PCB that
is visible through the lexan faceplate viewing window.
EXIT push-button. The EXIT function is used to scroll backwards through
the status menus or programming prompts to the previous item. The EXIT
function is used to “exit” the programming menu by holding this button
down for approximately 2 seconds while in the programming mode.
DECREMENT push-button. The DECREMENT function is used to change
a programming value while in the programming mode. When this push-
button is held down, the displayed value will be “decremented” to a lower
value as desired. Note: The longer the push-button is held down, the
faster the value will be decremented.
INCREMENT push-button. The INCREMENT function is used to change
a programming value while in the programming mode or to select a
desired programming menu loop. When this push-button is held down,
the displayed value will be “incremented” to a higher value as desired.
Note: The longer the push-button is held down, the faster the value will
be incremented.
ENTER push-button. The ENTER function is used to scroll forwards
through the status menus or programming prompts to the next item. The
ENTER function is used to “enter” a programming mode as well as
accepting changed programming values. Note: In the programming
mode, the longer the ENTER push-button is held down, the faster the
next menu prompts will appear.
RUN push-button and LED light viewing window. The RUN function is
used to initiate a manual start signal to the engine-generator set. Refer to
the operating instructions for detailed information.
OFF push-button and LED light viewing window. The OFF function is
used to initiate a stop signal to the engine-generator set. Refer to the
operating instructions for detailed information.
AUTO push-button and LED light viewing window. The AUTO function is
used to initiate automatic operation of the engine-generator set. Refer to
the operating instructions for detailed information.
LOAD TEST push-button and LED light viewing window. The LOAD
TEST function is used to initiate load test of the engine-generator set
when connected to an associated transfer switch. Refer to the operating
instructions for detailed information.
EMERGENCY STOP push-button and LED light viewing window. The
EMERGENCY STOP function is used to initiate an emergency stop signal
to the engine-generator set. Refer to the operating instructions for
detailed information.
11
READY LED light viewing window. The READY LED illuminates when the
engine-generator set is set for automatic operation and no shutdown or
alarm faults have been activated.
12
SPEED SIGNAL LED light viewing window. The SPEED SIGNAL LED
illuminates when the engines speed signal is detected (i.e. the engine is
turning over).
13
ALARM LED light viewing window. The ALARM LED illuminates (flashes)
when any pre-programmed alarm fault has been activated.
14
SHUTDOWN LED light viewing window. The SHUTDOWN LED
illuminates (flashes) when any pre-programmed shutdown fault has been
activated.
J6
R115 TB1
EXP
RJ45
IN
CONTRAST
IC
J7 IB
IA
COM
RJ45 VN
WATCHDOG VC
REMOTE START
CRANK VB
RUN
VA
COM FAIL
TB3 18 38
FIGURE #11
WARNING!!!
Voltage sensing circuits are capable of lethal voltages while
energized. Current transformer (CT) secondary circuits are capable
of generating lethal voltages when open circuited with their primary
circuit energized. Standard safety procedures should be followed
and be performed by qualified personnel only. Failure to do so may
cause personal injury and/or death.
3.2.2.1. WATCHDOG
This LED flashes on and off at irregular intervals which indicates that the
microprocessor is functioning normally.
3.2.2.3. CRANK
This LED is illuminated whenever the MEC 20 is initiating an engine
cranking signal.
3.2.2.4. RUN
This LED is illuminated whenever the MEC 20 has called the engine to
run.
MAGNETIC OVERSPEED
PICKUP SHUTDOWN
RPM FAULT LOSS OF SPEED RUN
DISPLAY LOGIC ALARM/SHUTDOWN 10A/240Vac, 8A/24Vdc
RESISTIVE
OVERCRANK
SHUTDOWN
AUTO PUSHBUTTON
SWITCH NOT IN AUTO CRANK
LOGIC
ALARM 10A/240Vac, 8A/24Vdc
RESISTIVE
ENGINE TEMPERATURE LOW ENGINE TEMP.
SENDER ALARM
TEMP. FAULT HIGH ENGINE TEMP.
DISPLAY LOGIC ALARM
HIGH ENGINE TEMP. COMMON FAIL
SHUTDOWN CONTACT
10A/240Vac, 8A/24Vdc
RESISTIVE
ENGINE OIL PRESSURE
SENDER LOW OIL PRESSURE
PRESS. FAULT ALARM
DISPLAY LOGIC
LOW OIL PRESSURE
SHUTDOWN
PROGRAMMABLE
2 CONTACT #1
LOW BATTERY 10A/240Vac, 8A/24Vdc
BATTERY VOLTAGE ALARM RESISTIVE
– + VOLTAGE DC
FAULT HIGH BATTERY
VOLT
LOGIC VOLTAGE ALARM
DISPLAY
WEAK BATTERY
ALARM
PROGRAMMABLE
3 PHASE AC UNDERVOLTAGE 2 CONTACT #2
AC
VOLTAGE OVERVOLTAGE 10A/240Vac, 8A/24Vdc
VOLT/ FAULT
V FREQ. LOGIC UNDERFREQUENCY
RESISTIVE
DISPLAY OVERFREQUENCY
3 PHASE AC
AC PROGRAMMABLE
CURRENT FAULT
CURRENT OVERCURRENT 2 CONTACT #3
LOGIC 10A/240Vac, 8A/24Vdc
DISPLAY
RESISTIVE
DIGITAL INPUT
CONTACTS (N/O or N/C)
LOW OIL PRESSURE
1
SHUTDOWN
HIGH ENGINE TEMP.
2 PROGRAMMABLE
SHUTDOWN
2 CONTACT #4
LOW COOLANT 10A/240Vac, 8A/24Vdc
3
LEVEL SHUTDOWN RESISTIVE
LOW FUEL LEVEL
4
ALARM
FIGURE #12
4.2.1. OVERCRANK
The overcrank fault circuit is initiated when the engine fails to start after the
selected crank time or number of crank cycles. The overcrank fault circuit is
internally programmed as a latching shutdown fault and is not user
programmable. Refer to the programming instructions for further information.
4.2.2. OVERSPEED
The overspeed fault circuit is initiated when the engine’s speed has increased
above the overspeed setpoint. The overspeed fault circuit is internally
programmed as a latching shutdown fault. The overspeed shutdown fault circuit
is programmable for the percentage of nominal engine speed (i.e. overspeed
setpoint) and for the transient time delay period. The programming prompts for
overspeed are located in the main menu programming loop. Refer to the
programming instructions for further information.
Note: Up to six custom ”user defined” fault label names may be specified for the MEC
20 controller at time of purchase. The six custom fault label names cannot be changed
once shipped from the factory.
Refer to Section 11.4 Digital Fault Programming Menu for the factory default
settings.
Note: Fault Input #5 - #10 must be customer configured unless specified at
time of order.
All faults require a customer connected contact to the MEC 20 input terminal as
indicated. All fault circuits may be user field programmed for different control
functions or alternate fault names.
⊇
Note: For CSA C282 applications the controller will be factory supplied with
Low coolant level shutdown in place of Battery charger input fail alarm. Refer to
the programming instructions for further information on digital fault circuits.
Note: Shutdown functions for Low Oil Pressure and High Engine Temperature
may alternatively be provided via analog pressure and temperature sender inputs
if programmed accordingly in the analog fault programming menu. Refer to
Section 11.3 for further information.
analog fault circuits. Each analog fault input circuit is activated via specific analog signal
type. Refer to Section 11.3 Analog Fault Programming Menu for the factory default program
settings for each analog fault provided.
WARNING!!!
The analog protection circuits for voltage, frequency, current,
engine oil pressure, engine temperature and engine speed will be
set at factory default settings only. Final settings will be required to
be set by the commissioning authority. Failure to do so may result
in severe equipment failure or damage.
alarm signal as programmed by the user. The engine temperature analog input
provides the following control functions:
alarm and/or shutdown signal as programmed by the user. The engine oil
pressure analog input provides the following control function:
control functions. All programmable outputs may be user field programmed for the
desired control function. The following programmable features are provided:
once an engine start signal is issued. Refer to the programming instructions for
further information.
5.2.5. OVERCURRENT
The designated programmable output relay will energize when the overcurrent
fault circuit is activated. The output will remain energized until the fault condition
has been manually reset (if programmed as a latching type fault) or until the
overcurrent level drops below the setpoint.
5.2.7. PREHEAT
The designated programmable output relay will energize during the start delay
timer period and cranking period until the engine starts and reaches crank
disconnect speed. The preheat output is typically used for an engine starting aid
such as glow plugs. Note: An external pilot relay is required to switch the high
current glow plug load.
The Generator Ready To Load output is typically used in an Auto Mains Failure
(AMF) application. Refer to Section 9.3.5 for further details on sequence of
operation.
5.2.12. AIRFLAP
The designated programmable output relay will energize when the engine’s
speed exceeds the overspeed setpoint level. The output will remain energized
until the engine’s speed drops below the low speed setpoint (typically 5% of rated
speed). Note: An external pilot relay will be required if the main air flap solenoid
current rating exceeds the MEC 20 contact rating.
NOTE:
This control feature is only operative if a remote
transfer switch is interconnected with remote
testing capability.
The designated programmable output relay will energize when a load test
operating mode is selected via the front keypad push-button. Once initiated, the
engine will receive a start signal from the transfer switch and upon the generator
reaching nominal voltage and frequency levels, a load transfer will be initiated.
The generator set will remain running on load until a different operating mode is
selected or the generator set develops an alarm or shutdown condition.
Notes:
1) The MEC 20’s standard programmable output contact is factory supplied with
the ATS LOADTEST function programmed. When the “Utility Ready to Load” and
“Generator Ready to Load” outputs are programmed, the “Load Test”
programmable output is not required as the engine starting logic is internally
initiated.
2) When both “Utility Ready to Load” and “Generator Ready to Load”
programmable outputs are programmed and utilized in a AMF control
configuration, the ATS Output is not utilized (i.e. engine start signal is internally
generated).
The MEC 20 communication port utilizes a RS422 data transmission signal which is directly
interconnected to the CIM module via 8 conductor, shielded cable with plug-in RJ45 connectors.
Refer to FIGURE #14 & 15 for detailed information on direct connected or remote connected PC
applications with CIM module.
CIM
Communication
Interface Module
+- G
Phone To expansion
output module J6
MEC 20
no connection
GRD
(optional) GRD Engine
Port 2A Port 3B Controller
J7
GRD
8 conductor
RS 232 Signal Shielded Cable c/w
15M (50')** DC Power RJ45 connectors
maximum 8-35Vdc
cable length
305M (1000')**
THS maximum
2000 cable length
null modem
connector Personal **Communication cable wiring must be suitably routed
Computer to protect it from sources of electrical interference.
Refer to installation section for further information.
G:\ENGINEER\PRODUCTS\MEC20\MEC20_20.VSD
CIM
Communication
Interface Module
+- G
Phone To expansion
output module J6
MEC 20
GRD
(optional) GRD Engine
Port 2A Port 3B Controller
J7
GRD
no connection
8 conductor
Shielded Cable c/w
DC Power RJ45 connectors
8-35Vdc
305M (1000')**
maximum cable
length
G:\ENGINEER\PRODUCTS\MEC20\MEC20_21.VSD
The MEC 20 RS422 communication port allows multiple MEC 20 controllers to be directly
interconnected together to form a single network system. Up to 10 MEC 20 controllers may be
interconnected to a single CIM module. Each MEC 20 controller is programmed with an unique
communication address number for the remote communication system to reference. The
network system may be connected to a local PC or to a remote PC via telephone system and
CIM module. Refer to FIGURE #15 for a typical MEC 20 network system with CIM module.
CIM
Communication
Interface Module 8 conductor
+- G
Shielded Cable c/w
Phone
RJ45 connectors MEC 20
GRD
J6 Engine
Port 2A Port 3B Controller
GRD J7 #1
no connection
DC Power
MEC 20
8-35Vdc
J6 Engine
305M (1000')**
maximum cable Controller
THS
length GRD J7 #2
G:\ENGINEER\PRODUCTS\MEC20\MEC20_22.VSD
NOTES:
1
ALL CONTACTS RATED MAXIMUM 0.5A, 120Vac/1.0A, 30Vdc RESISTIVE
2 PROGRAMMABLE MODULE ADDRESS (REMOVE JUMPER FOR STANDARD C282/NFPA FAULTS,ADD JUMPER FOR
ADDITIONAL FAULTS)
3
CONTACT LOGIC IS INDIVIDUALLY PROGRAMMABLE VIA PIN JUMPERS (CONTACT TO OPEN OR CLOSE WHEN FAULT
ACTIVATED)
4
PROGRAMMABLE CONTACT - USER CONFIGURED FUNCTION VIA MEC 20 SOFTWARE (REFER TO MEC 20
LITERATURE)
5
"GRD" CONNECTION TO BE MADE TO COMMON CHASSIS/ENCLOSURE GROUND BOND SYSTEM
6 C282 OR NFPA 110 STANDARD FAULTS EXCLUDE ANALOG FAULTS OVER/UNDER VOLTAGE, OVER/UNDER
FREQUENCY, OVERCURRENT, SPARE DIGITAL FAULT INPUTS #5-#12 AND PROGRAMMABLE OUTPUT #6 (I.E. MUST
SPECIFY SECOND EXPANSION MODULE TO OBTAIN CONTACTS FOR THESE FAULTS).
G:\ENGINEER\PRODUCTS\MEC 20\MEC20_15.VSD
The expansion module outputs are relay contacts which may be individually configured for
normally open or normally closed contact position. Contact configuration is via circuit board
mounted jumper pins and clips. Refer to FIGURE #18 for jumper pin location and configuration
settings. Each output contact is rated maximum 0.5A 120Vac, 1.0A 30Vdc resistive.
Each expansion module also provides one programmable contact for desired control function.
The programmable contact on the first expansion module (in the system) is referenced as
“Programmable Output #5”. On the second expansion module, the programmable contact is
referenced as “Programmable Output #6”. Refer to Section 9.0 of this manual for programming
functions and procedures for the programmable contact feature.
Note: The communication cable between the MEC 20 and the expansion module must be
ordered separately.
JMP FOR
NORMALLY
JMP OPEN CONTACT
1-10,
16
JMP FOR NORMALLY
CLOSED CONTACT
TB1
B+ B- GRD 1 20
K1 K2 K3 K4 K5 K6 K7 K8 K9 K10
JMP1 JMP2 JMP3 JMP4 JMP5 JMP6 JMP7 JMP8 JMP9 JMP10
21
JMP11 K11
JMP12 K12
JMP13 K13
JMP14 K14
JMP15 K15
JMP16 K16
32
J1
RJ45
(IN)
J2
RJ45
(OUT)
DIAGNOSTIC LED'S
JMP 17
G:\ENGINEER\PRODUCTS\MEC20\MEC20_16.VSD
Diagnostic LED’s are provided on each expansion module as shown in FIGURE #17. Their
functions are described as follows:
WATCHDOG - This LED flashes on and off at a very high rate which indicates that the expansion
module microprocessor is functioning normally.
MESSAGE - This LED flashes on and off at irregular intervals which indicates that the expansion
module is correctly receiving all data messages from the MEC 20.
Two expansion modules may be connected to a single MEC 20 controller to provide a maximum
of 32 output contacts. Two modules are interconnected together using a single communication
cable to the MEC 20 controller. Refer to FIGURE #19 for interconnection details. The first
expansion module addresses standard C282/NFPA110 MEC 20 fault circuits1 and the second
expansion module addresses all additional fault circuits. To select which faults are addressed
by each expansion module, jumper pins and clips are provided on the circuit boards. Refer to
FIGURE #18 for jumper pin location and configuration settings.
8 conductor Shielded
Expansion Expansion Cable c/w RJ45 connectors
Module #2 Module #1
(C282/NFPA Standard
(Additional Fault Circuits)
Fault Circuits)
J6
MEC 20
GRD GRD Engine
Controller
J7
J17 on J17 off GRD
To remote
communication
300M (~1000') system (optional)
maximum cable
length
1
C282 or NFPA 110 standard faults exclude analog faults Over/Under voltage, Over/Under Frequency, Overcurrent, spare digital inputs #5-#12 and
programmable output #6 (i.e. must specify second expansion module to obtain contacts for these faults).
G:\ENGINEER\PRODUCTS\MEC20\MEC20_17.VSD
For complete information on the EAP 110 contact Thomson Power Systems to obtain the
specific product documentation available.
Refer to FIGURE #20 for the EAP 110 remote annunciator connection diagram.
Expansion
Port Controller
Communication
Cable**
No
Connection J7
Ext 1
Ext 2
Ext 3
Ext 4
Com
B+ B- 1000' maximum cable Port B+ B-
length
External Alarm
Sensing contacts
(optional use as
required) +
-
12-24V Engine
**8 conductor Shielded Twisted Cable c/w RJ45 connectors. Communication cable wiring must be Cranking Battery
suitably routed to protect it from sources of electrical interference. Refer to instruction manual for
further information.
9. OPERATING INSTRUCTIONS
GENERATOR KVA
GENERATOR FREQUENCY/HOURMETER
PROGRAM MENU
NOTE:
The operating status screen may be momentarily
replaced with a time delay countdown screen when
a start or stop sequence is initiated. The display
will automatically return to the previous menu
following expiry of the timing sequence.
function has expired, the LCD display will automatically change to either the next
timing sequence countdown display or return to the original system status menu.
LCD DISPLAY
ENGINE START
DELAY 45 SEC
Displays specific time delay function currently in operation
Displays current time in seconds or minutes that are left in the specific timing
sequence.
NOTE:
During a timer countdown sequence, a different
display screen may be selected by pressing the
“ENTER” push-button.
Displays the average generator current as follows:
3-phase system: AVERAGE LINE CURRENT--Phases A,B,C
1-phase system: AVERAGE LINE CURRENT--Phases A,B
Displays generator frequency in hertz (HZ). The frequency is
displayed with a resolution of 1/10 of a hertz.
LCD DISPLAY
KVA
532.31
Displays generator voltage as follows:
3-phase system: LINE TO LINE VOLTAGE--Phases A to B
1-phase system: LINE TO LINE VOLTAGE--Phases A to B
Displays generator voltage as follows:
3-phase system: LINE TO LINE VOLTAGE--Phases B to C
1-phase system: LINE TO NEUTRAL VOLTAGE--Phases A-N
Displays generator voltage as follows:
3-phase system: LINE TO LINE VOLTAGE--Phases C-A
1-phase system: LINE TO NEUTRAL VOLTAGE--Phases B-N
LCD DISPLAY
Amps a b c
408 451 415
Displays generator load current as follows:
3-phase system: PHASE A CURRENT
1-phase system: PHASE A CURRENT
Displays generator load current as follows:
3-phase system: PHASE B CURRENT
1-phase system: PHASE B CURRENT
Displays generator load current as follows:
3-phase system: PHASE C CURRENT
1-phase system: not applicable
Displays generator frequency in hertz (HZ). The frequency is displayed
with a resolution of 1/10 of a hertz.
Displays unit operating hours
BATTERY 27.0Vdc
SPEED 1800rpm
Displays battery voltage in DC volts. The voltage is displayed with a
resolution of 1/10 of a volt.
Displays engine speed in revolutions per minute (RPM).
LCD DISPLAY
PROGRAMMING MENU NO
YES
PASSWORD
LCD DISPLAY
PROGRAM MENU?
NO
Displays two messages that may be toggled between YES and NO by pressing
the INCREMENT push-button. Their functions are described as follows:
NO Programming sub-menus are disabled when NO is displayed.
YES Programming sub-menus are enabled when YES is displayed and a
valid password number is entered.
9.3.1. GENERAL
The MEC 20 Engine-generator controller is designed to start and stop an engine
from either a local (“manual”) or remote (“automatic”) command. When this
command is issued, the controller issues a run and crank output signal. The
controller then monitors engine speed and when crank disconnect speed is
reached, the crank signal is terminated. While the engine accelerates to normal
speed, the controller continuously monitors the engines speed signal. Should the
engine speed exceed the maximum predetermined setpoint, the overspeed
shutdown fault circuit will activate, terminating the run signal. In addition to
overspeed shutdown, the engine controller also monitors many other engine
protection circuits and should they be activated, the engine will be stopped
and/or alarm initiated. The engine will automatically stop for any shutdown
condition, or when the remote and/or local start signal is removed. The engine
controller operation includes time delay circuits for normal operating conditions
such as start delays, cooldown and cranking periods.
When the “OFF” push-button on the front keypad is depressed, the controllers
RUN output will be immediately terminated which will initiate the engine to stop.
The automatic stop sequence will be initiated by removal of the remote start
signal. Once the start signal is removed, a cooldown delay function will be
initiated. Once the cooldown time delay period expires (typically programmed for
5 minutes), the controllers RUN output will be immediately terminated which will
initiate the engine to stop.
• Engine starts following expiry of the Engine Start Delay timer (Utility
Ready To Load output stays energized)
• Once the engine has started and the generator output rises above the
programmed voltage and frequency limits, a warm-up timer is
initiated.
• Once the warm-up timer expires the Utility Ready to Load output de-
energizes and the NEUTRAL Delay timer is initiated.
• Once the NEUTRAL DELAY timer expires the Gen Ready to Load
output energizes to signal the transfer switch to transfer to the
generator supply. Note: The neutral delay function is only operative
with an electrically-held type transfer switch mechanism (i.e. electrical
contactor type).
• Once the Return Delay timer expires, the Generator Ready to Load
output de-energizes and the Neutral Delay timer is initiated.
• Once the Neutral Delay timer expires the Utility Ready to Load output
energizes to signal the transfer switch to transfer to the utility supply.
Note: If the generator has a shutdown during the Return or Neutral
Delay periods, the timers are bypassed, and the Utility Ready to Load
output immediately energizes.
NOTE:
The following sequence as described is
applicable only if both “Utility Ready to
Load” and Gen Ready to Load” outputs are
programmed and used.
• When the MEC Load Test pushbutton is pressed, the controller’s logic
will internally simulate receiving a remote start input.
• Once the engine has started and the generator output rises above the
programmed voltage and frequency limits, a warm-up timer is
initiated.
• Once the warm-up timer expires the Utility Ready to Load output de-
energizes and the Neutral Delay timer is initiated.
• Once the Neutral Timer expires the Gen Ready To Load output
energizes to signal the transfer switch to transfer to the generator
supply. Note: if a generator shutdown occurs during a Load Test
Operation, the Load Test mode will be de-activated.
• Once the Neutral Delay timer expires The Utility Ready To Load
output energizes to signal the transfer switch to transfer to the
utility supply.
• Once the external exercise timer contact closes, the engine will start
and come-up to normal operating speed and voltage. The MEC will
issue an alarm of a No Load Test condition. The connected transfer
switch will remain on the utility and the generator will not transfer on
load. Note: should the utility supply fail, the generator will
automatically transfer on load.
• The engine will continue to run as long as the external exercise timer
contact remains closed.
• Once the external exercise timer contact opens, the engine will
continue to run for its cooldown time as programmed, then it will
automatically stop.
UTILITY (MAINS) 7
220/380V
N U V W
MF 5 UTILITY (MAINS)
MEC 2 / MEC 20 MAINS CONTROL
5
FAILURE FUSES (5A)
C/W AMF RELAY
16
W
REMOTE
START 17
V
2
35 U
PROGRAMMABLE
OUTPUT #3 U
3
G-AUX(b) UTILITY (MAINS) 5
36 A CONTACTOR
U 6
S1a
1 URTL 220V U
G 5
S1 V
MANUAL 8
OVERRIDE W LOAD
8
SWITCH
(OPTIONAL) N
U
220V
1 GRTL S1b
20 A
PROGRAMMABLE
G GENERATOR
21 5
OUTPUT #4 G U-AUX(b) CONTACTOR
4
VA
VB
VC
U V
GENERATOR SUPPLY
5
CONTROL
FUSES (5A)
N G W
NOTES: 220/380V 7
FIGURE 21
9.4.1.1. RUN
In this position, the engine will start and operate continuously providing no
shutdown circuits are active. All protective circuits will be operative in this
mode. There will be no cooldown cycle at the end of a manual run
sequence.
9.4.1.2. OFF
This position immediately stops the engine and locks it out from
operation. The OFF position also allows any shutdowns to be reset.
9.4.1.3. AUTO
In this position, starting and stopping of the engine will be controlled by a
remote contact. When the remote start signal is removed the engine will
continue to run for the cooldown period (if selected) then stop. Re-
selecting the Off position will stop the engine immediately, even if the
cooldown period is not complete.
9.4.1.4. LOADTEST
NOTE:
The control feature is only operative if used in the
AMF application or if one of the programmable
output contacts is configured for “ATS Test” and a
remote transfer switch is interconnected with
remote testing circuitry.
NOTE:
To initiate a reset command, the engine must come
to a complete stop and the controller’s switch must
be placed in the Off position.
PROGRAM MENU?
YES
Select the Program Menu by scrolling through the display menus using the “ENTER”
push-button. When displayed, use the INCREMENT push-button to select the YES
prompt and push the ENTER button
PASSWORD
0
Use the INCREMENT or DECREMENT push-buttons to ramp the displayed number up
or down to the desired password access number. Press the ENTER push-button when
the correct number is displayed.
NOTE:
If an invalid number is entered,
programming access will be denied. To exit
the programming mode, press the EXIT
push-button for more two seconds until the
display changes.
The MAIN MENU message will be displayed immediately upon entering the
programming mode. To select the desired programming menu, press the INCREMENT
push-button to scroll through the available menu types and once displayed, press the
ENTER push-button to select the specific program menu.
NOTE:
If the programming mode is terminated
before the last change had been entered,
the programming parameter will remain
unchanged.
To exit the programming mode, press the EXIT push-button and hold for two seconds.
The controller will automatically exit the Program Mode when an internal timer set for
999 seconds, expires from when a key press was last received by the controller.
Note: The display menu will automatically revert to a low power “sleep” mode following
the expiry of the 999 second internal timer.
Note: If preheat and /or prelube functions are utilized, the engine start delay
time should be set as required for these functions.
10.3.20. OVERSPEED
Set overspeed shutdown point in percentage of nominal speed (i.e. 110% or
1980 RPM on a 1800 RPM engine).
NOTE:
The run output Fail-safe feature will be
factory programmed as enabled. The user
of this equipment may elect to change this
feature dependent upon site conditions and
does so at their discretion.
Delay timer will start when The Utility Ready To Load output de-energizes. Once
the Neutral Delay time period expires, The Generator Ready To Load output will
then be energized. The similar sequence will occur when transfer in the opposite
direction. The purpose of the Neutral Delay timer is to prevent out of phase
transfers, which may be caused by a fast transfer and the two sources of supply
are out of synchronism. The Neutral Delay timer ensures the load voltages
decay before the transfer is initiated.
Set to the desired time in seconds. The Neutral Delay timer is typically set for 3
seconds. Refer to Section 9.3 for further details on this timing function.
NOTE:
The Neutral Delay feature is only
effective when an electrically held
“contactor-type” transfer switch is
connected. Contact Thomson Power
Systems for further application
information on use with other types of
transfer switch mechanisms.
CAUTION!!!
The programming function selected must co-ordinate with
external control wiring prior to energizing the control system.
Failure to do so may cause severe equipment damage.
Note: Lube functions are disabled in Off and whenever the engine is above crank
disconnect speed.
10.4.1. LEVEL
This setting determines the actual analog signal setpoint at which the selected
fault type will be activated. Note: For AC voltage fault circuits, two levels (i.e.
pick-up & drop-out) must be programmed.
10.4.2. ACTION
This setting allows a fault circuit to be programmed as either an alarm or a
shutdown.
Once the desired fault label is selected, press the “enter” key to accept the
selection.
WARNING!!!
The digital fault label programming must match with the external
control wiring to the controller. Failure to do so may cause severe
equipment damage.
10.5.2. ACTION
This setting allows a fault circuit to be programmed as either an alarm or a
shutdown.
Note: All activated alarm and shutdown faults will energize the “common fail”
circuit and sound the alarm horn.
10.5.4. POLARITY
This setting allows the digital fault circuit to be set for Open to Fail or Close to
Fail sensing contacts.
NOTE:
A programmable output must also be
programmed for IDLE to enable correct
operation. Refer to Section 5.2.2 for
further details
The No Load Test digital input feature is typically used in an AMF application
where it is required to do an automatic timed No Load Test of the
engine/generator set. A contact from an external exercise clock timer is required
to be connected to the digital input circuit which is programmed for “No Load
Test”.
10.6.1. GENERAL
AC Voltage, AC current and battery voltage analog circuits are factory calibrated
before the product is shipped therefore these circuits should not require any field
calibration. Should field calibration be required refer to the applicable procedure
as described further in this section.
Engine oil pressure and engine temperature analog circuits are not factory
calibrated and therefore require field calibration before the equipment is placed
into service. Refer to Section 10.6.9 & 10.6.10 for detailed information on field
calibration procedures required.
WARNING!!!
Failure to field calibrate and validate the correct operation of the
engine oil pressure and engine temperature analog circuits on
the equipment may result in severe equipment failure or
damage.
Displays the generator’s phase voltages to be calibrated.
Displays the type of calibration function, either ZERO or SPAN.
Displays the calibration correction factor number (0-255) used to obtain the
correct voltage reading. Note: To correctly calibrate any of the voltage
sensors, the ZERO function must be calibrated before the SPAN function.
Displays the actual voltage measurement that will be the same value as shown
on the MEC 20 display menus for generator supply. This voltage reading may
be calibrated higher or lower by changing the correction factor number.
WARNING!!!
Voltage sensing circuits are capable of lethal voltages
while energized. Standard safety procedures should be
followed and be performed by qualified personnel only.
Failure to do so may cause personnel injury and/or death.
NOTE:
Once the span calibration setting has been
completed, re-confirm the zero calibration
points. If the zero calibration setpoint needs
further adjustment, the span calibration
point must also be re-calibrated.
CURRENT A ZERO
99 350A
Displays the generator’s load current (phase A, B or C) to be calibrated.
Displays the type of calibration function, either ZERO or SPAN.
Displays the calibration correction factor number (0-255) used to obtain the
correct current reading. Note: To correctly calibrate any of the current
sensors, the ZERO function must be calibrated before the SPAN function.
Displays the actual current measurement that will be the same value as shown
on the MEC 20 display menus for generator supply. This current reading may
be calibrated higher or lower by changing the correction factor number.
NOTE:
To accurately calibrate the MEC 20’s
current sensors, an external test AC
ammeter and current clamp is required, with
an accuracy of 0.5% or better.
Note: Zero calibration must be completed before span calibration.
NOTE:
Do not exceed the current rating of the CT.
Non-linear output of the CT will result when
the secondary current exceeds 5 amps and
will similarly effect the MEC 20 displayed
values.
WARNING!!!
Never open circuit an energized CT as extreme high
voltages may result which may cause serious injury or
death. Standard safety procedures should be followed and
be performed by qualified personnel only. Failure to do so
may cause personnel injury and/or death.
NOTE:
Once the span calibration setting has been
completed, re-confirm the zero calibration
points. If the zero calibration setpoint needs
further adjustment, the span calibration
point must also be re-calibrated.
ENGINE TEMP
127 95 ºC
Displays the type of calibration function.
Displays the calibration correction factor number (0-255) used to obtain the
correct Temperature or Pressure reading.
Displays the actual temperature or pressure measurement that will be the
same value as shown on the MEC 20 display menus. This reading may be
calibrated higher or lower by changing the correction factor number.
NOTE:
To accurately calibrate the MEC 20’s
temperature sensor, an external
temporary engine mounted temperature
gauge is required. The external
temperature gauge should be connected
as close as possible to the temperature
sender for the MEC 20.
The calibration procedure is to be done only at a single point, which is the normal
operating temperature of the engine.
WARNING!!!
Failure to field calibrate and validate the correct operation of the
pressure analog circuit on the equipment may result in severe
equipment failure or damage.
The calibration procedure is to be done only at a single point, which is the normal
operating pressure of the engine.
1
Sender resistance data shown are for Oil Pressure Sender p/n-003654
(Thomson p/n), Manufacturer- Datcon, p/n 102227. Datcon Sender must
be used with MEC software version 1.81 or greater (previous software
versions cannot be used).
Figure 22
XXX 1-255
SYSTEM FREQUENCY
SYSTEM PHASES
TEMPERATURE SCALE
PRESSURE SCALE
START DELAY
CRANK TIME
REST TIME
STARTER RE-ENGAGE
NUMBER OF CRANKS
BYPASS DELAY
COOLDOWN DELAY
NOMINAL RPM
CRANK DISCONNECT
XX PERCENT 0-100%
OVERSPEED
XX PERCENT 100-150%
OVERSPEED TRANSIENT
RUN OUTPUT
PROG OUTPUT #2
PROG OUTPUT #3
PROG OUTPUT #4
PROG OUTPUT #5
PROG OUTPUT #6
UNDER AC E* S Y Y* 5.0
VOLTAGE VOLTAGE
OVER AC E* S Y N 2.0
VOLTAGE VOLTAGE
UNDER AC E* S Y Y* 5.0
FREQUENCY FREQUENCY
OVER AC E* A Y N 2.0
FREQUENCY FREQUENCY
OVER AC E* 500 4990 A Y N 20.0
CURRENT CURRENT
WEAK DC E* 18.0 N/A A* Y N* 3.0
BATTERY VOLTAGE
LOW DC E* 25.6 N/A A* N N* 120.0
BATTERY VOLTAGE
VOLTAGE
HIGH DC E* 30.4 N/A A* N N* 10.0
BATTERY VOLTAGE
VOLTAGE
LOW TEMP E* 95°F N/A A* Y N* 5.0
ENGINE SENDER
TEMP
HIGH ENG TEMP E* 198°F N/A A Y Y 2.0
TEMP #1 SENDER
ALARM
HIGH ENG TEMP E* 206°F N/A S Y Y 2.0
TEMP #2 SENDER
SHUTDOWN
LOW OIL PRESS E* 30PSI N/A A Y Y* 2.0
PRESS#1 SENDER
ALARM
LOW OIL PRESS E* 20PSI N/A S Y Y* 2.0
PRESS#2 SENDER
SHUTDOWN
12. SPECIFICATIONS
• Power supply: 10 to 30Vdc, negative ground
• Operating temperature: -15°C to +50°C1
1
Extended temperature ratings are available using the VFD display option. Extended ratings are:
Operating -40°C to +70°C, Storage -50°C to +85°C
• Environmental (Faceplate): NEMA 12
• Vibration: 4g, 5-250Hz
• Power consumption: 5 watts (max.)
• Storage temperature: -20°C to +70°C1
• Humidity: 5 to 95% non-condensing
• Dimensions: 10.75”W x 6.75”H x 2.0”D
• AC Metering Accuracy: ± 1.0%, @ 25°C Volts, Amps
± 2% @25°C KVA
• Inputs:
Engine Speed Sensing 100 - 10,000Hz, 3.0 - 20Vac, rms
AC Voltage 120 - 600Vac (nominal), 0.1VA, 3 phase, 50/60Hz
AC Current 0 - 5Aac (nominal), 1.5VA, 3 phase
Engine Parameters Dedicated Senders (supplied loose)
Digital Fault Contacts Open or close to DC Negative
• Output contacts:
Run, Crank 10A/240Vac, 8A/24Vdc resistive (3A inductive, 0.4pf), Form
A
Programmable 10A/240Vac, 8A/24Vdc resistive (3A inductive, 0.4pf), Form
A
• Analog Oil Pressure Measurement:
Range: 15 PSI – 150 PSI (maximum)
Pressure Accuracy Operating range 15 - 59 PSI = +-6 PSI
Operating range 60 - 75 PSI = +-2 PSI
Operating range 76-150 PSI = +-7 PSI
• Analog Engine Temperature Measurement:
Range: 0-200°C (maximum)
Temperature Accuracy Operating range 0 - 30°C = +-8°C
Operating range 30 -100°C = +-2°C
Operating range 100 -200°C = +-8°C
18 IA
1 ØA GENERATOR OUTPUT
RUN
4 RUN CIRCUIT 19 CURRENT SENSING
RUN CIRCUIT (FUEL SOL., GOV.) IB
ØB TRANSFORMERS
MP1 5 Aac SECONDARY
4
SPEED SENSING IC (DELETE PHASE C
MAGNETIC PICKUP MP2
MEC 20 ØC FOR SINGLE PHASE
GRD IN SYSTEMS)
4 OIL PRESSURE SENDER 37
GRD
4
ENGINE TEMPERATURE 38 25
SENDER COMMON FAIL CONTACT
13 1 26 (OPERATES ON AN ALARM OR
REMOTE EMERGENCY STOP
(CLOSE TO INITIATE) SHUTDOWN CONDITION)
14
27
REMOTE FAULT RESET
15
(CLOSE TO INITIATE)
28
16
REMOTE START
PROGRAMMABLE
CONTACT 1 29
17 CONTACT #1
4 2
DIGITAL FAULT INPUT 1 30
CONTACTS #1 TO #12
2
31
3 PROGRAMMABLE
1 32 CONTACT #2
4
33
5
6 34
7 24 PROGRAMMABLE
1 35
CONTACT #3
8
36
9
22
10
PROGRAMMABLE
1 21
11 CONTACT #4
12 20
NOTES:
1 CONTACTS RATED MAXIMUM 10A/240Vac, 8A/24Vdc RESISTIVE
2 LOGIC IS SOFTWARE PROGRAMMABLE FOR OPEN OR CLOSE ON FAIL
3 GENERATOR SUPPLY MUST UTILIZE A SOLIDLY GROUNDED NEUTRAL SYSTEM – REFER TO
INSTRUCTION MANUAL FOR ALTERNATE CONNECTIONS
4
ENGINE MOUNTED COMPONENTS
5 "GRD" CONNECTION TO BE MADE TO COMMON CHASSIS/ENCLOSURE GROUND BOND SYSTEM
CAUTION!!!
Before opening the enclosure to perform any service task, it is imperative to isolate the
control system from any possible source of power. Failure to do so may result in serious
personal injury or death due to electrical shock.
15. NOTES