HSE UK Alarm RRF-appendix-1
HSE UK Alarm RRF-appendix-1
HSE UK Alarm RRF-appendix-1
Assessment /
Review etc..
NOTE 1
Instrumented
alarm function
providing risk
reduction
identified
NOTE 2
Determine integrity
requirements (e.g.
SIL Assessment)
Redesign to reduce
integrity
SIL2 or higher ?
Y requirements on
SIAF NOTE 3
N
Implement /
manage alarm
N in accordance
SIL1? with good
practice, e.g.
OG-46 &
Y BS EN 62682 NOTE 4
RP Implement /
N manage SIAF to
to automate or
BS EN 61511
redesign?
BS EN 62682 NOTE 6
NOTE 5
Y
Redesign and
implement SIF to
good practice (e.g.
BS EN 61511) NOTE 7
End
2 The alarm presentation This requirement (along with criteria 3 & 4 and the
arrangement should more general requirements of overall SIS integrity
make the claimed alarm and independence) will generally require that the
very obvious to the alarm is annunciated on an annunciator which is
operator and suitably independent from other protection layers
distinguishable from and has the top priority reserved for SIAF’s.
other alarms.
A typical approach would be to use an independent
hardwired annunciator, i.e. outside of the basic
process control system (BPCS), although other
solutions may be possible.
3 The alarm should be The operator should be able to very quickly
classified at the highest distinguish between safety critical (i.e. ≥SIL1)
priority in the system. alarms and other alarms.
Operator Response within Instrumented Safety Functions in the Chemical, Oil & Gas, and
Specialist Industries
Figure 2: Response Time Considerations
Time pressure is a crucial factor that can influence operator performance when responding to safety-critical alarms. COMAH establishments
should be asked to demonstrate, on a case-by-case basis, that all sub-tasks associated with responding to an alarm (see below) can be
completed effectively within the actual time available for response i.e. from when the alarm is activated to when the process goes beyond the
point of no return. This is especially important when risk reduction is claimed for operator response as part of a SIL1 system (SIAF).
Alarm Activated
The operator must be available to respond. Operators should know how to respond and understand the The extent and nature of
Claims of continuous manning, or that operators consequences of failing to respond. They should be trained the action required, and
can be alerted by other means (e.g. alarm and assessed in managing the specific failure that the alarm any associated ‘what-ifs’
pagers), should be challenged. indicates (1) and be regularly re-assessed and re-trained should be fully explored.
(using simulators if possible).
Alarms should be: For example, carrying out
obvious and distinguishable from other Decision-making associated with a SIL1 operator response the required action might
should be kept to a minimum. The response should be involve communication
alarms (2)*
simple, obvious and invariant (6). The operator should have with a field operator, who is
classified at the highest priority (3) then required to travel to a
remain on view whilst active (4) access to a clear, written response for each SIL1 alarm (5)
e.g. a hard-copy grab-card, readily available at point-of-use. remote part of the plant to
These cards may also include confirmatory and follow-up identify and operate a
The operator interface should be designed to manual valve.
support management of the plant failure (7) actions in the event that initial response has been
unsuccessful.
Time
* Numbers in brackets denote the relevant ‘human reliability’ criteria from EEMUA 191, as summarised in Table 2 above.
All criteria relating to operator performance should be actively monitored and audited (8)