Kurimat Solar GTO - 501-600
Kurimat Solar GTO - 501-600
Kurimat Solar GTO - 501-600
0 Deg F
+HDW &RQVXPSWLRQ 3HUFHQW 'HVLJQ
120 Deg F
59 Deg F
, /HYLQH +$
*HQHUDWRU 2XWSXW 3HUFHQW 'HVLJQ
5HY $
*(1(5$/(/(&75,&02'(/3*)$*$6785%,1(
(IIHFW RI &RPSUHVVRU ,QOHW 7HPSHUDWXUH RQ
'/1 &RPEXVWRU
([KDXVW 7HPSHUDWXUH GHJ )
3HUFHQW 'HVLJQ
([KDXVW )ORZ
+HDW
&RQVXPSWLRQ
2XWSXW
&RPSUHVVRU ,QOHW 7HPSHUDWXUH GHJ )
, /HYLQH +$
5HY $
*(1(5$/(/(&75,&02'(/3*)$*$6785%,1(
(IIHFW RI ,QOHW *XLGH 9DQH RQ ([KDXVW )ORZ DQG 7HPSHUDWXUH
([KDXVW 7HPSHUDWXUH )
30 Deg F
59 Deg F 0 Deg F
90 Deg F
120 Deg F
0 Deg F
([KDXVW )ORZ 3HUFHQW 'HVLJQ
30 Deg F
59 Deg F
90 Deg F
120 Deg F
, /HYLQH +$
*HQHUDWRU 2XWSXW 3HUFHQW
5HY $
GENERAL ELECTRIC GAS TURBINE
ALTITUDE CORRECTION CURVE
ALTITUDE VS ATMOSPHERIC PRESSURE
AND
ALTITUDE VS CORRECTION FACTOR
FOR GASTURBINE OUTPUT, FUEL CONSUMPTION, AND EXHAUST FLOW
NOTES:
1. Exhaust Temperature, Heat Rate, and Thermal Efficiency are not affected by altitude.
2. Correction Factor = P(atm)/14.7
15.5 1.00
15.0 0.95
Correction Factor
14.5 0.90
Atmospheric Pressure (PSIA)
14.0 0.85
Correction Factor
13.5 0.80
13.0 0.75
12.5 0.70
12.0 0.65
Atmospheric Pressure
11.5 0.60
11.0 0.55
10.5 0.50
0 1000 2000 3000 4000 5000 6000 7000 8000 9000
Altitude (Feet)
Gajipara H. N. 416HA662
6/30/99 Rev-B
*HQHUDO(OHFWULF0606$QG06*DV7XUELQHV
&RUUHFWLRQV 7R 2XWSXW $QG +HDW 5DWH
,62 63(&,),& +80,',7<
+($7 5$7(
&255(&7,21 )$&725
32:(5 287387
+$
5(9 %
'$ -$48(:$<
Tab 21
GE Energy
Rev. : A
Page : 1/5
OPERATION AND MAINTENANCE MANUAL
OPERATION
OPERATION PRINCIPLE
1. INTRODUCTION..................................................................................................................... 2
2. OPERATION PRINCIPLE....................................................................................................... 2
3. OPERATION MONITORING .................................................................................................. 2
3.1. DATE, TIME AND METERS ................................................................................................ 3
3.2. OPERATION PHASES ........................................................................................................ 3
3.3. ALARMS AND TRIPS .......................................................................................................... 4
3.4. SPECIAL NOTES AND ABNORMALITIES.......................................................................... 4
3.5. INSTRUCTIONS .................................................................................................................. 4
3.6. PARAMETER READOUTS.................................................................................................. 4
4. LOCKOUTS/TAGOUTS ......................................................................................................... 5
5. SERVICING AND MAINTENANCE ........................................................................................ 5
Rev. : A
Page : 2/5
OPERATION AND MAINTENANCE MANUAL
OPERATION
1. INTRODUCTION
This document contains a standard text applicable to all gas turbine types and is intended
as a guide for the operator.
The experience acquired during daily operation of the installation will enable the operating
staff to further supplement and refine the control procedures described below.
2. OPERATION PRINCIPLE
The operation of Gas Turbines under optimum economic conditions in terms of availability
and reliability requires the implementation of a work structure with the following main
elements:
x Operation monitoring: for monitoring the day-to-day operation.
x Lockout/tagout (LOTO): for safety of the personnel during interventions.
x Servicing and maintenance: based on the operation monitoring and the different
maintenance programmes, allows the machine to be maintained in a proper operational
and reliable state.
3. OPERATION MONITORING
After commissioning of the turbine, it is imperative to record all events that mark out the
life of the turbine.
The events may be recorded manually or automatically, on paper or on data carrier. The
wealth of information that these records represent for operation and maintenance will
become apparent during their use.
The following data shall be recorded :
x Date, time and meters.
x Operation phases.
x Alarms and trips.
x Special notes.
x Instructions.
x Parameter readouts.
Rev. : A
Page : 3/5
OPERATION AND MAINTENANCE MANUAL
OPERATION
Relevant data :
x Date of the day.
x Time of the operation: start-up, shutdown…
x Daily meter readouts: number of start-ups, number of ignitions, number of emergency
shutdowns…, number of flame hours according to the fuel used…
x Climatic conditions :
¾ External ambient temperature.
¾ External atmospheric pressure.
x Weather conditions :
¾ Wind, rain, storm, snow, frost, humidity...
x Start-up :
¾ State of liquids: level readouts, e.g. fuel oil tank; readout of totaliser flowmeters…
¾ State of alarms.
¾ State of LOTO removals.
¾ Meter readings before and after start-up: flame hours, number of start-ups, number
of trips…
¾ Reason of start-up: power generation, compressor wash…
¾ Type of fuel at start-up.
¾ Time of start-up command.
¾ Time of ignition.
¾ Time of reaching nominal speed.
¾ Time of coupling.
x Operation :
¾ Change in base load/peak load operation - average power output.
¾ Gas - fuel oil (for multi-fuel turbines) or domestic fuel - heavy fuel transfers.
x Shutdown :
¾ Meter readings before and after shutdown.
¾ Time of shutdown command.
¾ Time of opening of the generator circuit breaker.
¾ Time of extinction of the flames.
All right reserved copyright - Droits de reproduction réservés
OMMO_1_ALL GT_EN_V2 Revision: A Date: 07/2008
GE Energy
Rev. : A
Page : 4/5
OPERATION AND MAINTENANCE MANUAL
OPERATION
3.5. INSTRUCTIONS
Rev. : A
Page : 5/5
OPERATION AND MAINTENANCE MANUAL
OPERATION
4. LOCKOUTS/TAGOUTS
Repair, servicing and maintenance interventions must be carried out in accordance with
the personnel and equipment safety procedures and regulations.
The operator must establish and observe work permit and equipment lockout/tagout
procedures.
The information collected during operation monitoring allows to define the scheduling of
the interventions or to complete the maintenance programmes defined in the next
maintenance part.
See document on operational inspections.
Rev. : A
Page : 1/4
OPERATION AND MAINTENANCE MANUAL
OPERATION
OPERATIONAL INSPECTIONS
1. INTRODUCTION..................................................................................................................... 2
2. CLEANLINESS OF THE EQUIPMENT .................................................................................. 2
3. FLUID LEVELS....................................................................................................................... 3
4. CONDITION OF FILTERS ...................................................................................................... 3
5. INSTRUMENTATION.............................................................................................................. 4
6. ELECTRIC MOTORS AND DRIVEN EQUIPMENT ................................................................ 4
7. LIGHTING AND SIGNALLING ............................................................................................... 4
Rev. : A
Page : 2/4
OPERATION AND MAINTENANCE MANUAL
OPERATION
1. INTRODUCTION
This document describes the inspections that are performed when the gas turbine is
operating or during short shutdowns. They are linked to the daily monitoring of the turbo-
generator set and are independent of the combustion, hot gas path and major inspections
during which the turbine is immobilised.
The following standard text applies to all gas turbine types and is intended as a guide for
the operator.
Optional equipment is often identified by the symbol () in the text.
The experience acquired during day-to-day operation of the installation will enable the
operating staff to further supplement and refine the recommendations contained in this
document.
Rev. : A
Page : 3/4
OPERATION AND MAINTENANCE MANUAL
OPERATION
3. FLUID LEVELS
4. CONDITION OF FILTERS
Regular monitoring of the filters for loss of charge allows a schedule to be drawn up for
appropriate replacement of the cartridges. The main filters are located on the following
circuits :
x Lube oil.
x High pressure oil and control oil ().
x Gas, liquid and atomization () fuels.
x Starting diesel or standby diesel generator () oil.
x Turbine air intake.
Rev. : A
Page : 4/4
OPERATION AND MAINTENANCE MANUAL
OPERATION
5. INSTRUMENTATION
Lighting lamps and signalling devices such as alarms or motor status indicators must be
operational at all times. Rapid replacement of defective bulbs is part of compliance with
the operating regulations.
Rev. : A
Page : 1/7
OPERATION AND MAINTENANCE MANUAL
OPERATION
1. INTRODUCTION..................................................................................................................... 2
2. PARAMETER READOUTS .................................................................................................... 2
2.1. PERFORMANCES............................................................................................................... 2
2.2. GENERATOR TEMPERATURES........................................................................................ 2
2.3. COMPRESSOR TEMPERATURES AND TURBINE COOLING.......................................... 2
2.4. TURBINE EXHAUST TEMPERATURES............................................................................. 2
2.5. TURBINE AND AUXILIARIES FLUID PRESSURES AND LEVELS.................................... 3
2.6. TURBINE AND AUXILIARIES TEMPERATURES ............................................................... 3
2.7. SHAFT LINE VIBRATION.................................................................................................... 3
2.8. TURBINE CONTROL........................................................................................................... 3
2.9. START-UP AND SHUTDOWN ............................................................................................ 3
2.10. EXTERNAL ENVIRONMENT .............................................................................................. 3
3. ANALYSIS OF THE PARAMETERS...................................................................................... 4
3.1. PERFORMANCES............................................................................................................... 4
3.2. GENERATOR TEMPERATURES........................................................................................ 4
3.3. COMPRESSOR TEMPERATURES AND TURBINE COOLING.......................................... 4
3.4. TURBINE EXHAUST TEMPERATURES............................................................................. 4
3.5. TURBINE AND AUXILIARIES FLUID PRESSURES AND LEVELS.................................... 5
3.6. TURBINE AND AUXILIARIES TEMPERATURES ............................................................... 5
3.7. SHAFT LINE VIBRATION.................................................................................................... 5
3.8. TURBINE CONTROL........................................................................................................... 5
3.9. START-UP AND SHUTDOWN ............................................................................................ 6
3.9.1. START-UP ........................................................................................................................... 6
3.9.2. SHUT DOWN....................................................................................................................... 6
3.10. EXTERNAL ENVIRONMENT .............................................................................................. 6
4. VIBRATION READOUTS ....................................................................................................... 7
4.1. NOTE ................................................................................................................................... 7
4.2. VIBRATION READOUTS..................................................................................................... 7
4.3. ANALYSIS ........................................................................................................................... 7
Rev. : A
Page : 2/7
OPERATION AND MAINTENANCE MANUAL
OPERATION
1. INTRODUCTION
This document contains a standard text that is applicable to all gas turbine types and is
intended as a guide for the operator.
The experience acquired during the day-to-day operation of the plant will enable the
operating staff to further supplement and refine the readout procedures described below.
In order to maintain the performance and the reliability of the gas turbine, the operating
parameters must be read out and analyzed. This information, which is available on the
control screens or on site, can be divided into two families: the operating parameters and
the vibration readouts.
The readouts are performed manually or automatically with a frequency that depends on
the operational requirements. The following frequency is recommended:
x For the operating parameters: 1 to 4 readouts every 24 hours.
x For the vibration readouts: 1 to 4 readouts per month.
2. PARAMETER READOUTS
One method for reading out the parameters consists in classifying them into the following
categories :
2.1. PERFORMANCES
Active power, reactive power, generator voltage, generator current, excitation voltage and
current, ambient temperature, atmospheric pressure, loss of charge of air filter etc…
All generator temperatures: hot air, cold air, stator bars, return oil of bearings etc...
Rev. : A
Page : 3/7
OPERATION AND MAINTENANCE MANUAL
OPERATION
Turbine fluid pressures, differential pressures of filters and filter in service in case of
duplicated elements, and levels: lube oil, high pressure oil, atomization air, cooling water,
compressor outlet (CPD), liquid fuel supply, injectors (), gas supply, inter-valve (),
injection water () etc…
Turbine fluid temperatures: lube oil in tank and collector (LTTH, LTOT), return oil of
bearings, atomization air, cooling water, compressor outlet (CPD), liquid fuel (), gas (),
injection water (), etc…
Turbine control signal (FSR), position of gas valves (VSR – VGC) or fuel oil flow control
valve (), etc…
Battery charger current and voltage, main transformer temperature and oil level, etc…
Rev. : A
Page : 4/7
OPERATION AND MAINTENANCE MANUAL
OPERATION
The parameter readouts taken during the first commissioning period serve as reference.
All subsequent readouts will be compared against the original readouts.
3.1. PERFORMANCES
The power output of the gas turbine varies with changes in the atmospheric conditions.
The analysis must be based on measurements carried out at full load with temperature
control (base load). The performances of the machine must therefore be corrected prior to
any comparison. A decrease in active power is generally linked to fouling of the
compressor. An ON line or OFF line wash allows to recover the largest part of the
kilowatts. Loss of charge of the air filter also reduces the machine performance. The
cartridge replacement frequency primarily depends on the air quality of the site.
The cooling temperatures must not exceed the limit values and two thermocouples
located in the same zone must have similar temperature values; example: zone after
second wheel: the difference between thermocouples TTWS 2A0-1 and TTWS 2AO-2
must be less than 75°C.
In the event of a fault, check the measuring circuit and implement the appropriate
corrective action.
The exhaust temperature is limited by the control system as a function of the compression
ratio of the axial compressor.
Any drift of the measurement system or control system must be analyzed and corrected
as soon as possible.
The exhaust temperature measurement is performed by multiple thermocouples mounted
on the circumference of the exhaust and in the same measuring plane.
A major temperature difference between the exhaust thermocouples indicates a fault in
the measuring circuit or a combustion fault and must be analyzed and corrected as soon
as possible.
Rev. : A
Page : 5/7
OPERATION AND MAINTENANCE MANUAL
OPERATION
The pressure values often provide an indication of the proper functioning of the systems.
Regular monitoring of the differential pressures of the filters allows to identify the fouling
condition of the cartridges and to schedule the replacement intervals.
If the turbine runs on fuel oil, the injector pressure of each chamber at the outlet of the
flow divider is read out. The maximum permissible pressure difference between these
pressures is 6% of the median value. If the difference exceeds this value, the machine
must be shut down and the difference corrected before it is restarted.
Like the pressures, the temperatures reflect the proper functioning of the systems. It is
sometimes necessary to monitor temperature differences; example: difference between oil
supply and return values of the bearings.
The vibration values read out after the first run-ups of the turbo-generator set represent
the vibration signature of the shaft line. This signature is machine-specific.
The vibration values must be compared against the vibration signature.
Rev. : A
Page : 6/7
OPERATION AND MAINTENANCE MANUAL
OPERATION
3.9.1. START-UP
The parameters listed below allow to confirm the proper functioning of the starting system
and its operating conditions by comparing them against the original readouts :
x Turbine speed (TNH), control signal (FSR) and exhaust temperature (TTXM) as a
function of the start-up time.
x Start-up time. The start-up time must always be timed with respect to the same
conditions; example: from the start command when the machine is turning until the
100% speed level.
() Depending on the turbine model, the starting system contains one or more of the
following components: electric motor, diesel motor, torque converter, static frequency
converter.
Measurement of the shutdown time allows to validate the rotating conditions of the shaft
line. The timing must also be performed under the same conditions; example: from 99%
speed level until activation of the turning gear.
For analysis of the environmental parameters of the gas turbine, reference shall be made
to the documents of the manufacturers.
Rev. : A
Page : 7/7
OPERATION AND MAINTENANCE MANUAL
OPERATION
4. VIBRATION READOUTS
4.1. NOTE
This standard text applies to all gas turbine types and is intended as a guide.
The experience acquired during operation of the plant will enable the operating staff to
further supplement and refine the vibration measurements.
The vibration measurements discussed in this chapter are carried out with a portable
device. The measuring frequency may be monthly or bimonthly. It is important to specify
the following:
x The type of value measured: displacement or speed.
x The units : µm or mm/s.
x The amplitude: single or double.
The readouts are related to the following auxiliaries: motor pump units, motor fans,
auxiliary gearbox. Displacement measurements on lifting lugs or on the bases of the
different modules provide information on the strength of the anchorages in the civil
engineering structures.
It is advisable to mark the exact location of the measurements on the equipment to allow
the results to be compared in time (for instance, by applying paint marks).
To characterize the vibration, it is preferable to make 3 measurements in the same plane:
x Along the vertical axis, (V : vertical).
x Along the horizontal axis parallel to the axis of rotation, (A : axial or L : longitudinal).
x Along the horizontal axis perpendicular to the axis of rotation. (H : horizontal or
T : transverse).
4.3. ANALYSIS
Increased vibrations are often an indication of degradation of the rotating parts of the
machine, of their attachments or of their alignment.
Refer to the supplier documents for the acceptable limits and the corrective actions.
In certain cases the vibration frequency and phase values are read out to allow for a more
precise diagnostic.
Rev. : A
Page : 1/23
OPERATION AND MAINTENANCE MANUAL
OPERATION
OPERATION SEQUENCES
1. INTRODUCTION ................................................................................................................. 2
1.1. FOREWORD........................................................................................................................ 2
1.2. OPERATING SEQUENCES ................................................................................................ 2
1.3. SCREEN SHOTS................................................................................................................. 2
2. OPERATOR RESPONSIBILITY.......................................................................................... 3
3. TURNING GEAR OPERATION (COOLDOWN CONTROL) ............................................... 3
3.1. INITIAL CONDITIONS ......................................................................................................... 3
3.2. SEQUENCES ...................................................................................................................... 4
3.3. FINAL CONDITIONS ........................................................................................................... 5
4. NORMAL START-UP .......................................................................................................... 5
4.1. INITIAL CONDITIONS ......................................................................................................... 5
4.2. SEQUENCES ...................................................................................................................... 6
4.3. FINAL CONDITIONS ........................................................................................................... 9
5. SYNCHRONIZING............................................................................................................. 10
5.1. INITIAL CONDITIONS ....................................................................................................... 10
5.2. SEQUENCES .................................................................................................................... 11
5.3. FINAL CONDITIONS ......................................................................................................... 11
6. LOAD PICK UP ................................................................................................................. 12
6.1. INITIAL CONDITIONS ....................................................................................................... 12
6.2. SEQUENCES .................................................................................................................... 13
6.3. FINAL CONDITIONS ......................................................................................................... 13
7. LEAD / LAG MOTORS...................................................................................................... 14
7.1. INITIAL CONDITIONS ....................................................................................................... 14
7.2. SEQUENCES .................................................................................................................... 14
7.3. FINAL CONDITIONS ......................................................................................................... 15
8. NORMAL SHUTDOWN ..................................................................................................... 16
8.1. INITIAL CONDITIONS ....................................................................................................... 16
8.2. SEQUENCES .................................................................................................................... 16
8.3. FINAL CONDITIONS ......................................................................................................... 17
9. EMERGENCY SHUTDOWN.............................................................................................. 18
9.1. INITIAL CONDITIONS ....................................................................................................... 18
9.2. SEQUENCES .................................................................................................................... 18
9.3. FINAL CONDITIONS ......................................................................................................... 18
10. ON-LINE COMPRESSOR WASH ..................................................................................... 19
10.1. INITIAL CONDITIONS ....................................................................................................... 19
10.2. SEQUENCES .................................................................................................................... 19
10.3. FINAL CONDITIONS ......................................................................................................... 20
11. OFF-LINE COMPRESSOR WASH.................................................................................... 21
11.1. INITIAL CONDITIONS ....................................................................................................... 21
11.2. SEQUENCES .................................................................................................................... 22
11.3. FINAL CONDITIONS ......................................................................................................... 23
Rev. : A
Page : 2/23
OPERATION AND MAINTENANCE MANUAL
OPERATION
1. INTRODUCTION
1.1. FOREWORD
After on-site installation, the first commissioning of the gas turbine is carried out with the
participation of General Electric Engineers and according to the specific commissioning
procedures.
The present document, which relates to the operation of the gas turbine, only addresses
the normal operating procedures.
Each technical intervention on the gas turbine must be backed up by a work permit.
Strict adherence to the work permit procedures guarantees the safety of the personnel as
well as observance of the initial functional configuration of equipments.
The sequences described in the tables below include initial conditions, sequences and
final conditions. The sequences are represented in four columns:
x The first column, titled Input, lists the manually initiated actions and significant
thresholds in sequences execution
x The second column describes the main events
x The third column, titled Output, lists the principal motors
x The last column, title Status, specifies the status of the relevant component or
sequence:
¾ 0 means that the motor stops
¾ 1 means that the motor runs
¾ 2min means that the sequence lasts 2 minutes
The screen shots included in this document are carried out without equipment of control
connected to the gas turbine. The posted physical values are thus not representative of
operating parameters.
Example: -18°C for the exhaust temperature.
These sights only facilitate the understanding of the text.
Rev. : A
Page : 3/23
OPERATION AND MAINTENANCE MANUAL
OPERATION
2. OPERATOR RESPONSIBILITY
The operator is a person, authorized by his employer, who is familiar with the operation
of a turbo-generator used for electrical power generation.
His role consists in conducting the installation in accordance with the relevant
operational, system and personal safety procedures.
Rev. : A
Page : 4/23
OPERATION AND MAINTENANCE MANUAL
OPERATION
3.2. SEQUENCES
Rev. : A
Page : 5/23
OPERATION AND MAINTENANCE MANUAL
OPERATION
The shaft line rotates at low speed and the gas turbine is available for start-up.
Deselecting the turning gear sequence will stop the shaft line rotation if the turbine is
cold.
4. NORMAL START-UP
If the shaft is already turning, following the start command, the starting frequency
converter starts, the turning motor stops and the sequence proceeds as described below.
When the gas turbine has been at standstill for more than two days without barring, it is
recommended to start the auxiliaries first and keep the machine at turning speed for few
minutes, as described in the above chapter “cool down control”. After few minutes
running, the normal start up sequence may be initiated.
Rev. : A
Page : 6/23
OPERATION AND MAINTENANCE MANUAL
OPERATION
4.2. SEQUENCES
Rev. : A
Page : 7/23
OPERATION AND MAINTENANCE MANUAL
OPERATION
Rev. : A
Page : 8/23
OPERATION AND MAINTENANCE MANUAL
OPERATION
Rev. : A
Page : 9/23
OPERATION AND MAINTENANCE MANUAL
OPERATION
Lubrication of the shaft line is ensured by one of the two AC lube oil pump.
Gas turbine is at nominal speed, generator excited at nominal voltage, turbo-generator
set ready to be synchronized to the grid for electrical power supply.
Rev. : A
Page : 10/23
OPERATION AND MAINTENANCE MANUAL
OPERATION
5. SYNCHRONIZING
RESYNC push button has the same function as automatic synchronizing. It must be used
to allow automatic re-synchronizing.
Rev. : A
Page : 11/23
OPERATION AND MAINTENANCE MANUAL
OPERATION
5.2. SEQUENCES
Rev. : A
Page : 12/23
OPERATION AND MAINTENANCE MANUAL
OPERATION
6. LOAD PICK UP
Manual : Action on + / - Speed push buttons allows the operator to adjust the load.
Rev. : A
Page : 13/23
OPERATION AND MAINTENANCE MANUAL
OPERATION
6.2. SEQUENCES
Rev. : A
Page : 14/23
OPERATION AND MAINTENANCE MANUAL
OPERATION
Some motors and associated driven components like pumps, fans, boosters, are
redundant and running in a lead/lag philosophy which means that the operating motor is
the “lead” motor, the other been in standby. The operator has the choice to select the
motor to run by #1 Lead or #2 Lead, and to change over to the standby motor at any
time, to balance the running hours. Changeover is manual, or automatic in case of failure
of the active motor.
Auto Rotate : Enable / Disable : if Enable is selected, the automatic change over occurs
at each starting sequence of the gas turbine. If Disable is selected, the lead motor
selected by the operator remain the same at each gas turbine starting up.
Prior to any manual changeover, check that the relevant motor and associated system
are available.
7.2. SEQUENCES
Rev. : A
Page : 15/23
OPERATION AND MAINTENANCE MANUAL
OPERATION
Suppose two redundant motors and associated driven components M1 and M2. M1 is the
lead motor, M2 is the standby motor. If M1 fails, M2 starts automatically, a corresponding
alarm will inform the operator. The speedtronic logic will keep in memory that M1 is “lead”,
the operator must select “M2 lead” to confirm unavailability of M1.
Rev. : A
Page : 16/23
OPERATION AND MAINTENANCE MANUAL
OPERATION
8. NORMAL SHUTDOWN
8.2. SEQUENCES
Rev. : A
Page : 17/23
OPERATION AND MAINTENANCE MANUAL
OPERATION
The shaft line is rotating at turning gear speed to allow the cooling cycle to be carried out.
The compartments fans remain in operation according to the compartments temperature.
The cooling water pump remains in operation according to lube oil temperature.
Deselecting the turning gear sequence is forbidden during the first hours of cooling.
Normal restart is possible at any time.
Rev. : A
Page : 18/23
OPERATION AND MAINTENANCE MANUAL
OPERATION
9. EMERGENCY SHUTDOWN
This action can be initiated with the gas turbine loaded, starting or in normal shutdown
condition:
x Either by pressing an emergency shutdown pushbutton.
x Or through the operation of an electrical or mechanical protection.
9.2. SEQUENCES
Rev. : A
Page : 19/23
OPERATION AND MAINTENANCE MANUAL
OPERATION
10.2. SEQUENCES
Rev. : A
Page : 20/23
OPERATION AND MAINTENANCE MANUAL
OPERATION
Rev. : A
Page : 21/23
OPERATION AND MAINTENANCE MANUAL
OPERATION
A B C D E
Turbine speed
20
10
0
0 6 12 18 24 30 36 42 48 54 60 66 72 78 84 90
Time
Rev. : A
Page : 22/23
OPERATION AND MAINTENANCE MANUAL
OPERATION
11.2. SEQUENCES
Rev. : A
Page : 23/23
OPERATION AND MAINTENANCE MANUAL
OPERATION
Rev. : A
Page : 1/6
OPERATION AND MAINTENANCE MANUAL
OPERATION
SPECIAL SEQUENCES
1. GENERAL............................................................................................................................... 2
2. STARTING MODE .................................................................................................................. 2
3. FAULTY IGNITION ................................................................................................................. 2
3.1. NORMAL IGNITION............................................................................................................. 2
3.2. FAULTY IGNITION .............................................................................................................. 3
4. INLINE FILTER CHANGEOVER ............................................................................................ 3
5. OVERSPEED TEST................................................................................................................ 4
5.1. INITIAL CONDITIONS ......................................................................................................... 4
5.2. SEQUENCE......................................................................................................................... 4
5.3. FINAL CONDITIONS ........................................................................................................... 4
6. OIL PUMP RESTART TEST................................................................................................... 5
6.1. INITIAL CONDITIONS ......................................................................................................... 5
6.2. SEQUENCE......................................................................................................................... 5
6.3. FINAL CONDITIONS ........................................................................................................... 5
7. PROLONGED SHUTDOWN................................................................................................... 6
Rev. : A
Page : 2/6
OPERATION AND MAINTENANCE MANUAL
OPERATION
1. GENERAL
This document completes the normal operation sequences and contains specific
instructions for special sequences.
The following standard text applies to all gas turbines type 6FA (60 -80MW). Optional
equipment is often identified by the symbol () in the text.
The text is intended as a guide for the operator. The experience acquired during the day-
to-day operation of the plant will enable the operating staff to further supplement and
refine the recommendations contained in this document.
2. STARTING MODE
The operator usually starts the gas turbine in automatic mode by selecting “Auto“ on the
main screen, or “Remote” for remote operation. Mode Select “Crank” and “Fire” are
available for specific sequence test.
“Crank” allows normal starting sequence of the gas turbine up to firing speed but without
firing. This mode is used to test the starting means system.
“Fire” allows normal starting sequence of the gas turbine including firing, but without
accelerating the shaft line. This mode is used to test the firing sequence.
Both “Crank” and “Fire” mode select may be used to demonstrate or to test manually
cranking and/or firing after main maintenance activity on the gas turbine and are not used
during normal operation.
3. FAULTY IGNITION
Rev. : A
Page : 3/6
OPERATION AND MAINTENANCE MANUAL
OPERATION
Rev. : A
Page : 4/6
OPERATION AND MAINTENANCE MANUAL
OPERATION
5. OVERSPEED TEST
The overspeed protection circuit must be inspected once a year by simulation and with the
turbine in standstill position.
Real testing of the protection is not necessary if the simulation yields satisfactory results,
including the turbine trip circuits.
If a real test is scheduled, the following conditions must be fulfilled.
5.2. SEQUENCE
Choose the overspeed test control screen
Select the protection module
Increase the speed until a trip occurs. The speed increase must be maintained without
interruption until the trip occurs.
Rev. : A
Page : 5/6
OPERATION AND MAINTENANCE MANUAL
OPERATION
6.2. SEQUENCE
Input Description Output State
Close the plunger valve and slowly open the test valve.
Main pump test 88QA 1
The main oil pump starts.
Slowly close the test valve and then open the plunger
Main pump test valve. Select again the lead pump on the speedtronic 88QA 0
screen. The main standby pump stops.
Main pump test Acknowledge the alarms on the control cabinets.
Rev. : A
Page : 6/6
OPERATION AND MAINTENANCE MANUAL
OPERATION
7. PROLONGED SHUTDOWN
For particular operating reasons, the turbo-generator set may be shut down for a relatively
long period of time, more than one week, provided it can be started up, at short notice, to
generate power for the grid.
In this standby situation, the following instructions must be observed:
x Keep the electric auxiliaries and the control cabinets energized.
x Keep the heating systems (cabinet, compartments, generator…) and the air
conditioning system in automatic mode.
x The lube oil heating system automatically starts, with the oil pump, to keep the viscosity
at a value that is compatible with the turbine start-up.
x Keep the pipe tracing systems in automatic mode.
x Start up the gas turbine two to four times a month with few minutes at turning gear
before starting, fire and synchronize to the grid at low load to validate all sequences.
Shut down the turbine and observe the 24-hour turning sequence.
g
Revised, May 2007
GE Energy
These instructions do not purport to cover all details or variations in equipment nor to provide for every
possible contingency to be met in connection with installation, operation or maintenance. Should further
information be desired or should particular problems arise which are not covered sufficiently for the purchaser's
purposes the matter should be referred to the GE Company.
The totally enclosed, water- to- air- cooled (TEWAC) generator is designed for operation with air as the
cooling medium. Fans located at the ends of the generator rotor circulate the ventilating air. The
separately excited rotating field is supported by end shield- mounted bearings located at each end of the
generator frame (see Figure 1).
2
Description Totally Enclosed Water- to- Air- Cooled 6FA Generator with Brushless Excitation GEK 103823b
The frame containing the stator core and winding, the pedestals that support the rotor, and the coolers
mounted in a plenum chamber on top of the outer frame are assembled on a flat concrete foundation.
Flange connections are provided for the customer’s cooling water lines to the air coolers. Mechanical
power is derived from the turbine, which also supplies the bearing lubricating oil.
The generator is designed for continuous operation. Temperature detectors installed in the generator
permit the measurement of the winding and air temperatures. The generator is constructed to withstand,
without harm, all normal conditions of operation, as well as transient conditions such as system faults,
load rejection and lack of synchronization.
A. Stator Frame
The stator frame consists of a casing of welded plate construction, reinforced internally by web plates
in the radial direction, and by braces, key bars and ventilating ducts in the axial direction.
The key bars that support the stator core are welded directly to the fixed web plates. Radial and
tangential magnetic vibration of the core is transmitted to the frame but is isolated from the
foundation.
B. Stator Core
The stator core is made up of segmented, annealed, insulated punchings (see Figure 2) of high-
quality, silicon steel. These punchings are assembled in an interleaved manner on keys machined on
the key bars and are separated into packets by space blocks to provide ventilation ducts. The
punchings are stamped from thin steel sheets and contain open- end slots for the armature bars with
dovetail slots for the wedges that hold the armature bars in place. Other dovetail slots at the back of
the punching are for assembly and locking of the segments on the key bars. The assembled punchings
are clamped into a stiff cylindrical core by pressure applied through end flanges by means of the
stator key bars. Pressure is applied to the teeth by nonmagnetic steel fingers located under the end
flanges (see Figure 3). In order to reduce end heating caused by the end leakage flux and its
associated electrical losses, the end packets of punchings are stepped back at the ends of the stator
core to increase the gap between the punchings and the rotor. The punching insulation is a
thermosetting varnish designed to maintain its insulating value at temperatures above the normal
operating range.
3
GEK 103823b Description Totally Enclosed Water- to- Air- Cooled 6FA Generator with Brushless Excitation
4
Description Totally Enclosed Water- to- Air- Cooled 6FA Generator with Brushless Excitation GEK 103823b
C. Stator Winding
The stator winding is composed of insulated bars assembled in the stator slots, joined at the ends to
form coils and connected in the proper phase belts by bus rings. Each phase is split into groups of
coils 180 apart. The stator bars are composed of insulated copper conductors (strands) transposed by
the Roebel method so that each strand occupies every radial position in the bar for an equal length
along the bar. This arrangement minimizes the circulating current loss that otherwise would be
present under load conditions due to the distribution of magnetic flux in the coil slot (see Figure 4 for
details of the transposed bar).
High- voltage insulating system is provided according to the proven ELIN Vacuband System. With
this system, several half- overlapped, continuous layers of mica tape are applied to the bars. The
number of layers depends on the machine voltage. The bars are dried under vacuum and impregnated
with epoxy resin. Good penetration is reached by an impregnation pressure phase (VPI- System).
After impregnation, the bars are calibrated to the required shape in molds and cured in an oven. This
high-voltage insulation is obtained void free and characterized by its excellent electrical, mechanical
and thermal properties.
An outer covering of protective tape is applied to the core portion of the bar to protect the bar from
abrasion in the slot. This protective tape is impregnated with a controlled- resistivity material to
prevent slot discharge sparking and vibration sparking. The end arms of the bars are graded with a
nonlinear voltage grading material.
5
GEK 103823b Description Totally Enclosed Water- to- Air- Cooled 6FA Generator with Brushless Excitation
The stator coil ends are covered with an outer layer of tape to bind and protect the mica insulation,
after which they are sprayed with epoxy paint. These end turns are securely laced with treated glass
cord to the binding bands, which are molded fiberglass rings supported from the stator core flanges
(see Figure 3). The armature bars are held in the coil slots by wedges driven into dovetail slots.
Temperature detectors are provided to measure the inlet air temperature. The leads from the detectors
are brought out through the generator frame and connected to terminal boards for connection to
temperature meters or relays. The locations of the resistance temperature detectors and the
arrangement of connections at the terminal board are shown on the connection outline drawing. A
description of the detectors and circuit is given in the instructions for “Resistance Temperature
Detectors.”
E. Generator Leads
The main armature leads are brought out of either the upper or lower portion of the stator frame at the
exciter end, depending on the product line.
The leads exit through insulated terminal plates, bolted to the base or frame, which clamp and support
the leads. The leads are suitable for connection to bus bars. The neutral tie is formed within the base
and connected to the neutral grounding transformer and resistor.
F. Air Coolers
Generator air coolers are mounted horizontally in the plenum chamber on top of the frame. Water
inlet, outlet and vent pipe connections are made externally on either side of the unit to suit station
arrangement. Gaskets between the frame and the cooler water box make seals. The method of sealing
is such that the water boxes and covers can be removed to clean a cooler without opening the
generator air ventilation circuit. See instructions in MAINTENANCE.
G. Stator Ventilation
The rotor fans provide the ventilation of the generator. They are the radial flow type assembled near
the ends of the rotor. The entrance condition of the air to the fans is controlled by an inlet nozzle.
Cooling air is forced by the fans into the air gap and also around and behind the stator core. The
stator is divided axially into sections by the web plates and outer wrapper so that in some sections
cold air is forced from the outside of the core toward the air gap through the radial air ducts, while in
other sections it passes from the air gap toward the outside of the core through the radial ducts. The
cooling air is conducted through tubes or ducts to the proper section, and hot air is directed to the
outlet of the generator.
The arrangement of alternate inward and outward air flow in the stator core results in a substantially
uniform cooling of the core and windings, thus avoiding excessive local heating and reducing stresses
caused by temperature differentials.
6
Description Totally Enclosed Water- to- Air- Cooled 6FA Generator with Brushless Excitation GEK 103823b
The construction of the generator rotor is illustrated in Figure 5 and Figure 6. The rotor is machined from
a single alloy- steel forging that has passed extensive tests to assure that the forging meets the required
physical and metallurgical properties.
7
GEK 103823b Description Totally Enclosed Water- to- Air- Cooled 6FA Generator with Brushless Excitation
Longitudinal slots, machined radially in the body, contain the field coils. The field coils are held in the
slots against centrifugal force by steel wedges. These wedges are fitted into dovetail openings machined
in the rotor slots.
The rotor fans, provided for the ventilation of the generator, are assembled near the ends of the rotor. The
rotor is cooled externally by the air flowing along the gap over the rotor surface and internally by air that
passes under the rotor end windings and axially under the rotor winding, through the sub slot channels
and radially outward through holes in the coils and wedges.
The end turns are held in place against centrifugal force by heavy retaining rings machined from
high-strength, corrosion- resistant, alloy- steel forgings that are shrunk and key- locked onto the rotor
body.
The axial movement of the field winding is restricted by the centering ring, which is held in place by
a shrink fit onto the retaining ring.
B. Brushless Excitation
A description of the brushless exciter may be found in the “Exciter Section” of the instruction book.
The bearing at the exciter end of the generator is insulated from the generator frame to prevent the
flow of shaft currents.
The lubricating oil is retained within the end shield by seal rings on the bearing assembly and by oil
deflectors on either side of the bearing.
D. Air Shields
The end shields are bolted to the frame to limit the amount of air leakage.
Inner air shields are located between the ends of the armature windings and the outer air shields to
separate the fan discharge air from the air entering the fans. Air seal fan nozzle rings are attached to
the inner air shields to prevent the fan discharge air from leaking into the fan inlet.
8
Description Totally Enclosed Water- to- Air- Cooled 6FA Generator with Brushless Excitation GEK 103823b
9
GEK 103823b Description Totally Enclosed Water- to- Air- Cooled 6FA Generator with Brushless Excitation
g GE Energy
General Electric Company
www.gepower.com
10
GEI 85803F
Reviewed, March 2001
Reformatted, February 1992
GE Power Systems
Generator
Shaft-Grounding Brushes
I. INTRODUCTION
Shaft-grounding brushes are supplied on turbine-generator units to prevent damage to bearings by electrical
discharge through the oil films. Because of their small oil film thickness, bearings most susceptible to dam-
age are the centrifugal oil pump thrust bearing (or the worm drive for the main oil pump) and the turbine
thrust bearing. Damage to the main turbine generator bearings, hydrogen seals, gears, and other equipment
has also occurred and can be prevented by shaft grounding brushes.
Shaft-to-ground voltages occur on a turbine-generator shaft in three ways. First, charge separation in wet-
steam stages of condensing turbines can cause a buildup of electrostatic voltage (dc) between shaft and sta-
tionary parts. Second, on units with static excitation systems, the output of the three-phase full wave bridge
rectifiers is not pure dc, but contains a 360 Hertz ripple of appreciable magnitude. Under certain conditions
this ripple can cause currents to flow through the capacitive circuit consisting of the field insulation, the bear-
ing oil films, and the distributed capacitance of the excitation system transformers and rectifiers. Finally,
asymmetries in the generator magnetic circuit induce a stiff source of shaft voltage between the collector and
turbine ends of the generator.
B. Current flow due to static excitation voltage ripple flows harmlessly to ground, bypassing the bearings.
C. The brushes ground the shaft at the turbine end of the generator so the voltage from magnetic asymmetry
does not impact the turbine end generator bearing and the turbine bearings and other low clearance com-
ponents.
The grounding-brush assembly consists of a bracket or yoke carrying one or more constant-pressure
brush-holders and is located at the turbine end of the generator shaft. Note that the outboard bearing (and
seal housing on hydrogen-cooled generators) are deliberately insulated from ground to prevent the flow
of currents due to a loop-type voltage along shaft and through bearings which may be produced by minor
dissymmetry in the generator stator magnetic paths. Therefore, the grounding brushes must never be lo-
cated at the outboard end of the generator. The brushes used in this grounding assembly are like those
used on collector rings. The bracket or yoke should be electrically connected to the same station ground
as the turbine and generator casings.
These instructions do not purport to cover all details or variations in equipment nor to provide for every possible
contingency to be met in connection with installation, operation or maintenance. Should further information be desired or
should particular problems arise which are not covered sufficiently for the purchaser’s purposes the matter should be
referred to the GE Company.
1991 GENERAL ELECTRIC COMPANY
GEI 85803F Shaft-Grounding Brushes
In operation, the voltage from shaft to ground should be checked at least once per week to insure that
the shaft-grounding brush assembly is functioning properly. The method of checking voltage is de-
scribed in the following paragraphs.
II. INSTRUMENTATION
In order to obtain meaningful data, high-impedance instruments must be used, preferably those having an
impedance of at least one megohm. The reason for this is to prevent loading down the source voltage through
its own internal impedance. Electronic voltmeters, digital voltmeters, and oscilloscopes in general will satis-
fy the requirement for high impedance.
Another consideration is the wave shape of the shaft-to-ground voltage, which may depart considerably from
a sine wave. Even under the best conditions when the voltage appears as a basic square wave, there may be
high-voltage spikes on the order of microseconds in duration due to rectifier commutation. Since even a
short-duration spike of sufficient magnitude can initiate the flow of current through a bearing, it is the peak
value of voltage, rather than the average or RMS value, that is of interest. As an example, if the shaft voltage is
40V peak to peak, a comparison of the shaft voltages measurement by different instruments typically could
be as follows:
Thus the reading taken on a rms reading voltmeter should be multiplied by a factor of about 7 to correlate with
peak-to-peak voltage observed on an oscilloscope. The factor 7 is probably typical, but it might be less if the
wave shape contained no spikes. An oscilloscope or peak reading voltmeter is recommended if available.
The voltmeter or oscilloscope should be connected solidly to ground on one terminal, the other terminal to an
insulated probe containing a metal-graphite or bronze brush. To read shaft voltage, press the probe firmly
against the shaft at a point adjacent to the grounding brush assembly, but preferably not in the track of the
grounding brush.
The dc component of shaft-to-ground voltage is usually below 2 volts, and this dc component is not greatly
affected by the type of meter used. Be sure to connect the meter to get an upscale reading.
The 0-to-peak voltage is of greatest interest. If the true 0-to-peak voltage is 6 volts or less, the indication is
that the grounding brush assembly is functioning satisfactorily. A 0-to-peak voltage above 6 volts indicates
that maintenance is required.
IV. MAINTENANCE
Whenever an unsatisfactory indication is obtained on the shaft-to-ground voltage check, the following steps
should be taken:
A. Remove the brushes from their holders, one at a time. Clean brush and holder so brush may move freely.
2
Shaft-Grounding Brushes GEI 85803F
C. Use a soft brush seating stone or a canvas-padded board to remove excess film from shaft.
E. Check spring force. It should be at least 3 3/4 pounds (1.7 kg); an even higher force may be advisable
in some instances. Machines using a shaft voltage monitor should use a spring force of 7 1/2 pounds (3.4
kg).
F. Replace brushes before the pigtail is in contact with top of brush box.
G. Check for corrosion or damage on the bracket mounting surface. Clean the surface if necessary.
H. If replacing brush holder, check gap between brush holder and shaft. Gap typically should be adjusted
to 0.12 to 0.25 inch.(3.0 to 6.4mm)
During turbine inspections, all bearings and hydrogen seal rings should be carefully checked for any
signs of electrical pitting, which will appear to be an etched or frosted surface, but at a magnification
of 25x will show numerous individual small pits or craters. The thrust bearings deserve particular atten-
tion during inspection. The amount of taper on tapered land thrust bearings should be checked with a
micrometer or feeler gauge in addition to making a visual inspection for pitting.
Some idea of the importance of keeping the shaft grounded can be gained by considering that a failure
of one or more bearings might be expected within a year if the shaft voltage is allowed to rise to approxi-
mately 50 volts 0-to-peak. As the shaft-to-ground voltage is reduced, bearing life is increased, and it is
expected that the bearings will suffer no damage from shaft currents as long as the shaft-to-ground volt-
age is held to 6 volts 0-to-peak or less.
3
GE Power Systems
GE Power Systems
Generator
These instructions do not purport to cover all details or variations in equipment nor to provide for
every possible contingency to be met in connection with installation, operation or maintenance. Should
further information be desired or should particular problems arise which are not covered sufficiently for
the purchaser’s purposes the matter should be referred to the GE Company.
© 1998 GENERAL ELECTRIC COMPANY
GEK 106933a Horizontal Duplex Air Coolers
I. GENERAL
The generator uses two coolers (heat exchangers) to transfer the heat from the generator ventilating air to
water. Each cooler consists of two independent sections. Each section, in turn, consists of a pair of water
headers (water boxes) and tube sheets with a bank of finned tubes, supported by a steel frame. The cooling
water circulates in the tubes in each section with two or more passes as determined by the arrangement
of partitions in the water boxes. The air flows through the finned tube bank. When practical, the coolers
will be constructed to achieve a “counterflow” between the air and the water. Counterflow will attempt to
achieve a uniform difference in the temperature between the air and the water throughout the cooler.
The frame is of welded steel construction and is fabricated to a box-like structure. An air-seal gasket
assembly seals between the cooler and the generator base as well as between the cooler and the foun-
dation, thereby forcing all of the air to flow through the tube bank for maximum cooling.
B. Tubes
The tubing is at least 13 mm ( inch) nominal diameter to reduce the chance of the tubes plugging un-
der normal operation. Typically the tubes are 16 mm (0.63,) O.D, 1.25 mm (0.049,) thick, (18 BWG)
condenser quality tube as described by A.S.T.M Specification B-111. The extended surface on the out-
side of the tube consists of a continuous plate fin with a shoulder formed at the tube holes for stacking
as required.
C. Tube Sheets
Both ends of the tubes are expanded into the tube sheets. Standard condenser tube expanders that roll
to a depth of approximately 19 mm (0.75,) are satisfactory for re-rolling any tube joint which may
loosen and leak. The tube sheet at the water connection end of the cooler is held rigidly to the end of
the cooler frame. This end of the cooler is called the "fixed end". A seal plate fastened to the cooler
frame laterally restrains the tube sheet at the opposite end. This end of the cooler is called the "floating
end". This assembly arrangement allows movement in the axial direction for the differential expansion
between the tube bank and the cooler frame. The edges of the tube sheets provide a surface for making
an airtight seal. If the surfaces become excessively marred, the scratches should be blended smooth to
minimize air leakage.
D. Water Boxes
The water boxes are bolted to the tube sheets with bolts or studs and nuts. The water boxes on the
floating tube sheet end of the cooler have provisions for installing eyebolts. The eyebolts facilitate
handling the cooler in the horizontal position for assembly into the foundation or roof openings. Refer
to the generator’s mechanical outline drawing for the size and location of the water connection flanges
and any extension pieces that may be required to pass through the foundation.
Joints between the water boxes and the tube sheets are furnished with gaskets. Normally, any gasket
leakage can be corrected by tightening the water box bolts (nuts). The leakage should be checked at the
test pressure normally shown on the cooler nameplate. The standard generator cooler the test-pressure
is 8.64 bars (125 psig or 8.8 kg/cm2).
2
Horizontal Duplex Air Coolers GEK 106933a
F. Air Removal
Since the coolers and cooler sections are usually connected in parallel, there is a possibility that one of
the cooler sections may become partially or completely air bound, which will impair heat transfer and
accelerate corrosion.
To assist in avoiding this condition, vent connections are provided in the connection end water box
of each cooler section. If the water pressure inside the cooler is above atmospheric pressure, the pip-
ing should consist of a line from each vent connection with a valve cracked slightly open to permit
continuous discharge of coolant into a funnel or other visible drain. The continuous flow of coolant
indicates that the cooler is properly vented. In closed systems, such as condensate or ethylene-glycol
based coolant mixtures; provision must be made to properly handle the vented coolant.
It is recommended that the coolers be operated with a relatively low water pressure, 15 to 30 psig
(1.05 to 2.11 kg/cm2). The primary advantage of low-pressure operation is that water leakage into the
generator will be minimized in the event of a tube failure. The coolant supply pressure must be checked
periodically to assure that it is within the design operating pressure.
G. Coolant Flow
The coolant flow rate to the coolers must be throttled to provide an even distribution of flow to each
cooler section. This can be accomplished by balancing the pressures at the inlet and outlet flanges of
each cooler section. Calibrated pressure gauges can be mounted on each flange and the cooler isolation
valves adjusted to obtain a balanced flow distribution.
It is recommended that a flow meter be installed to measure the total flow to the coolers or, if possible,
two meters - one for each cooler assembly. Coolant systems designed with no provision for flow mea-
surement run the risk of exceeding cooler tube and nozzle velocity limits. Excessive coolant velocities
accelerate tube erosion and shorten the life of the coolers.
An alternate piping scheme where the two individual cooler sections are connected in series and the
cooler assemblies connected in parallel may offer some advantage in some installations. Such a scheme
requires more valves (to allow isolation when required) but uses less total flow with a somewhat-higher
pressure drop. Contact GE Product Service for assistance in evaluating this alternative.
H. Servicing or Repairs
Except for the rolled joints between the tubes and the tube sheet, all of the joints on the waterside of
cooler section are outside of the generator circulating air space. This design permits normal servicing
or repairs, such as: plugging leaking tubes, re-rolling tubes, tightening or replacing gaskets, pressure
testing and cleaning tubes, without removing the cooler section from the generator.
NOTE
I. Leaky Tubes
A cooler tube leak is found by performing a pressure decay test on each suspected tube. To locate a
leaky tube, remove both water boxes of the faulty section. Test each tube separately by plugging one
end and inserting a close-fitting nozzle at the other end. The nozzle connection should be provided
3
GEK 106933a Horizontal Duplex Air Coolers
with a gauge and a valve, so that as soon as the tube is under static pressure, the supply can be shut
off and any reduction in pressure noted on the gauge. A leaky tube can be plugged by driving tapered
plugs (brass, maple or phenolic are best) into both ends. When the number of plugged tubes prevents
the cooler from accomplishing the required cooling, the cooler should be replaced.
The above method for locating leaky tubes will not identify tube-to-tube sheet leaks. These leaks are
usually caused by improper tube expansion and are usually discovered during the factory hydro test.
If the above pressure decay test fails to locate a suspected cooler leak, it probably is a tube connection
leak and must be located visually with the cooler removed from the unit.
A rise in generator temperature over a period of time, under the same water and load conditions, may
indicate the need for tube cleaning. Each heat exchanger consists of two separate cooler sections that
allows for the isolation of any section for cleaning or repair. It is important that the piping to the coolers
be designed and installed so that the valves are located such that the necessary water connections can
be removed and access gained for the desired work while still permitting operation of the other cooler
sections. The interior of the tubes can be cleaned with compressed air. In extreme cases, it may be
necessary to use a brass brush or scraper plug.
Normally, the airside or finned surface should not become dirty. If this does happen, the cooler should
be removed and cleaned with a stream of water. If there is an oily deposit which water or detergents
will not remove, apply an air blast saturated with a solvent suitable for removing the film. The same
solvent used to clean the generator winding is recommended. Refer to CLEANING and CLEANING
FLUIDS instructions found elsewhere in the instruction book.
K. Inspection
The best time for the annual inspection and cleaning of the cooler is prior to the warm season. The
need for additional cleaning may be indicated by a gradual increase in the generator temperatures not
attributable to some other cause.
L. Correspondence
For identification purposes, all correspondence should reference the catalog number, serial number
and cooler manufacturer that are stamped on the cooler nameplate. The generator and turbine number
should also be included.
4
Horizontal Duplex Air Coolers GEK 106933a
5
GEK 106933a Horizontal Duplex Air Coolers
GE Power Systems
General Electric Company
One River Road, Schenectady, NY 12345
518 • 385 • 2211 TX: 145354
6
GEK 46135A
Revised, April 1991
GE Power Systems
Generator
Oil Recommendations
I. RESPONSIBILITY OF OPERATOR
Temperature and pressure of the oil to and from the bearings shall be within the limits specified.
The oil purity shall be sustained by checking for water leaks, draining sludge and closely adhering to the
regulation set forth by the oil vendor for sampling, purifying and oil replacement.
It is generally recognized that the lubricating oil should be a petroleum derivative free from water, sediment,
inorganic acids or any materials which in the service specified will prove injurious to the oil or the equipment,
and there should be no tendency toward permanent emulsification nor rapid oxidation with the formation
of sludge.
The responsibility of supplying the proper oil for the lubricating system rests with the oil vendor and the unit
operator. This responsibility includes specifications for flushing, purifying, inspection and treatment of the
oil during operation and maintenance to insure satisfactory performance of the equipment in service.
In the normal operation of generator, particularly during the starting and stopping periods, a certain amount
of water may find its way into, and become entrained in, the lubrication system. This water may come from
leaks in the oil cooler or from atmospheric condensation.
To meet this condition, it is essential that the oil have a preferred metal–wetting ability to coat the ferrous
metals of the system with a film of oil. Otherwise, the entrained moisture may be taken to, and deposited on,
the ferrous metal parts of the oil system and quickly start rusting.
It is recommended that the oil shall successfully pass the Referee Tests for rust prevention.
In the servicing of lubricants, it is expected the operator will be governed by the specific recommendations
of the vendor from whom the oil is obtained. However, the opinion of the turbine–generator manufacturer
is often sought and in those cases, the following comments on water washing and clay filters are offered as
a general guide.
These instructions do not purport to cover all details or variations in equipment nor to provide for every possible
contingency to be met in connection with installation, operation or maintenance. Should further information be desired or
should particular problems arise which are not covered sufficiently for the purchaser’s purposes the matter should be
referred to the GE Company.
1991 GENERAL ELECTRIC COMPANY
GEK 46135A Oil Recommendations
It is recommended that the purification system be such as to remove all water and other foreign matter.
V. WATER WASHING
The following action taken by Section 1 of Technical Committee C, D–2 of A.S.T.M. at their June 24, 1946
meeting is endorsed:
“The committee went on record against water washing oils containing rust and oxidation in-
hibitors since experience indicates such practice may cause some reduction in inhibitor con-
tent. The only exception to this recommendati on might be in the case of contamination of
the rust and oxidation inhibited turbine oil with corrosive materials which are water soluble.
The committee sees no objection to water washing straight mineral turbine oils if such prac-
tice is desirable to remove corrosive materials, oil deterioration products, or potentially cor-
rosive contaminants. It is recommended that, where water washing is employed, the water
have a pH of 6.5–8 and a conductivity of 2–5 microhms.”
The following action taken by Section 1 of Technical Committee C, D–2 of A.S.T.M. at their June 24, 1946
meeting is endorsed:
“The committee went on record against the use of clay filters with rust and oxidation inhib-
ited turbine oils since experience indicates such filters will remove the rust inhibitor and
some types of oxidation inhibitor from present–day rust and oxidation turbine oils.”
A. Viscosity
The viscosity or body of an oil is the measure of its resistance to flow. Saybolt Universal Seconds (SSU)
are the number of seconds required for 60 milliliters of oil to flow through the orifice of the Saybolt vis-
cosimeter a t a specified temperature.
B. Flash Point
The flash point of an oil is the lowest temperature in degrees Fahrenheit at which sufficient vapors are
given off to form an inflammable mixture with air that will burn momentarily when a small flame is
applied.
C. Neutralization Value
The neutralization value is the weight in milligrams of potassium–hydroxide required to neutralize one
gram of the oil and expresses the total amount of mineral acid and of the organic compounds having acid
characteristics.
2
Oil Recommendations GEK 46135A
D. Rust Prevention
This test is to determine the rust preventing characteristics of the oil in the presence of water.
OPERATING CONDITIONS
Note:
1. Specific instructions for equipment prevail when they differ from this tabulation.
2. No reference is made under these Typical Oil Characteristics to the ASTM steam–emulsion number
since these recommendations are for inhibited oils. Experience has indicated that the steam–emul-
sion number has little or no value when used in testing of inhibited turbine oils. This is consistent
with the action of ASTM Designation: D–157–36 which is as follows:
“Results obtained on rust and oxidation–inhibited turbine oils cannot be interpreted in the same
manner as in the practice with uninhibited oils. Steam–emulsion numbers of such inhibited oils are
not reproducible and the existence of any correlation to emulsion in service is considered doubtful.”
3. The cooling water through the oil coolers is controlled to maintain 130°F ambient, lube oil inlet oil
at 80°F ambient and below. Above 80°F ambient, lube oil inlet temperature will increase 1 degree
for every 1 degree increase in ambient. The oil temperature rise through the bearing should be
25–35°F. The oil drain alarm setting should be maximum ambient ±100°F.
E. Oxidation
To determine the oxidation characteristics of the oil, the time measured in hours required to build up a
neutralization value of 2.0 mg. KOH per gram of oil in a sample of oil subjected to temperature of 95°C
in the presence of water, oxygen, and an iron–copper catalyst.
3
GE Power Systems
GE Energy
Operation
Totally Enclosed, Water-to-Air Cooled Generator with Brushless Excitation Gas
Turbine Drive
These instructions do not purport to cover all details or variations in equipment nor to provide for
every possible contingency to be met in connection with installation, operation or maintenance. Should
further information be desired or should particular problems arise which are not covered sufficiently for
the purchaser's purposes the matter should be referred to the GE Company.
© 1995 General Electric Company
GEK 95143b Operation
TABLE OF CONTENTS
I. INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
II. FINAL INSPECTION BEFORE STARTING THE GENERATOR FOR THE FIRST TIME . . 3
A. Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
B. Generator Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
C. Resistance Temperature Detectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
D. Insulation Resistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
E. Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
F. Rubbing and Vibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
G. Bearing Insulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
H. Exciter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
I. Air Coolers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2
Operation GEK 95143b
I. INTRODUCTION
A high-speed generator is a complex, precision built piece of equipment designed to operate in conjunction
with a turbine in a modern plant with a minimum of manual control. These machines are constructed to
operate continuously for long periods of time without shutdown. Proper operation of a high speed generator
requires close adherence to operating guides and procedures for the particular unit. Although operating
practices differ to some extent between various operators, there are many general operating rules that can
be applied universally. This instruction is included as a guide for operating a turbine-generator and does
not purport to cover all details or variations in operating procedures.
II. FINAL INSPECTION BEFORE STARTING THE GENERATOR FOR THE FIRST TIME
One of the most important periods in the life cycle of a turbine-generator is the initial start-up. During this
period each component part of the unit is checked and tested for proper installation and operation.
Before shipment, standard factory tests are performed on the generator, including the following:
• Mechanical inspection
• Mechanical balance
• Overspeed run
• Dielectric tests
To supplement the tests made in the factory, it is considered essential to repeat many checks just prior to
operating the unit in the power plant. The following inspections and preliminary checks should be made
just before the generator is started up for the first time.
A. Connections
B. Generator Voltage
See that the voltage on the generator nameplate corresponds with the line voltage.
The resistance temperature detectors should be checked to determine that they are indicating properly.
D. Insulation Resistance
The insulation resistance should be measured in accordance with instructions on INSULATION TEST-
ING.
3
GEK 95143b Operation
E. Clearances
As specified in the instructions for bringing the turbine up to speed, checks should be made to ensure
that there is no rubbing between the rotating and stationary parts of the generator, and that the operation
of the combined turbine and generator rotors is free from excessive vibration.
G. Bearing Insulation
The exciter-end bearing insulation should be checked with an insulation resistance meter in accordance
with instructions on BEARING INSULATION.
H. Exciter
I. Air Coolers
The air coolers should be checked as follows: the water supply to all cooler sections should be turned
on full. The cooler vents should be open to bleed all entrapped air. The cooler discharge lines should
be checked to ascertain that nearly an equal flow of water is discharging from each cooler section.
With the vents cracked open to provide for continuous venting, the water discharge may be throttled
to obtain the desired rate of flow. Excessive flow results in accelerated tube erosion and unbalanced
flow results in ineffective generator cooling. The coolant flow may be balanced by measuring the
differential pressure across the inlet and outlet nozzles at the connection end of each cooler section.
The discharge flow rate from the cooler vents and cold gas RTD temperatures are also good indicators
of balanced coolant flow.
Cooler water should be throttled on the discharge of the coolers to avoid air pockets and unstable oper-
ation with low flows. Where valves are located both before and after the coolers, care should be taken
to maintain a positive pressure on the coolers. If condensate is used for cooling, it may be necessary
to connect the discharge from the vent lines to the condenser in order to maintain an effective pressure
for venting.
The cooling water supply pressure should be checked to determine that this pressure is within the de-
signed operating pressure for the coolers.
Excessive flow results in accelerated tube erosion and unbalanced flow results in ineffective generator
cooling. The coolant flow may be balanced by measuring the differential pressure across the inlet and
outlet nozzles at the connection end of each cooler section. The discharge flow rate from the cooler
vents and cold gas RTD temperatures are also good indicators of balanced coolant flow.
When starting a turbine-generator, it is recommended that a start-up checklist be used to ascertain that no
items have been overlooked. The following items should be included on a checklist for starting a generator.
4
Operation GEK 95143b
This is a recommended list and does not purport to cover all items to be checked on a specific installation.
Refer to separate instruction for detailed operation of the exciter system.
Operator actions employing the regulator described below use datalink (digital regulators only) or remote
control switches/hardware.
The voltage regulator and exciter protective circuits must be set up according to detailed instructions con-
tained in a separate regulator instruction book prior to initial operation.
Two major starting methods are employed. The first is for turbine-generators which are started and brought
to operating speed using conventional starting motors. The second category has been included to cover the
unique generator requirements associated with LCI (Load Commutated Inverter) turbine-generator starting
systems. Refer to Turbine startup procedures for operational details related specifically to the LCI. Also
refer to separate instructions for detailed operation of the excitation system.
3. As the generator is brought up to speed, check the mechanical balance by taking shaft vibration
readings.
4. Regulate the cold liquid flow valves to obtain the rated flow condition. The cold gas temperature
inside the generator will then be a function of cold liquid temperature and the losses during the
start sequence.
***WARNING***