03 - 01 - Major Alarm& Safety of 50DF With UNIC 3
03 - 01 - Major Alarm& Safety of 50DF With UNIC 3
03 - 01 - Major Alarm& Safety of 50DF With UNIC 3
UNIC C3
WÄRTSILÄ W50DF
SF alarm true 3s all all SF generated in CCM. Value not used in exh.
gas temp. average calculation.
SF gas trip true 3s all Gas, SF generated in CCM.
Transfer(D to G)
SP alarm 560 C 5s Run all Cyl. temp. too high.
SP load reduction 580 C 10 s Run all High cyl. temp. load reduction. Only for Ship
(CB Close) Power
SP shutdown 580 C 3s Run all High cyl. temp. shutdown. Only for Power Plant
SP pilot trip true 0s Start, Run Diesel, Gas Pilot injection v/v check failed