Scalance XC 200
Scalance XC 200
Scalance XC 200
___________________
Introduction
2
___________________
Safety notices
SIMATIC NET
___________________
Description of the device 3
___________________
Mounting 4
Industrial Ethernet switches
SCALANCE XC-200
___________________
Connecting up 5
___________________
Maintenance and
troubleshooting 6
Operating Instructions
___________________
Technical specifications 7
___________________
Dimension drawings 8
___________________
Certifications and approvals 9
07/2016
C79000-G8976-C442-01
Legal information
Warning notice system
This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent
damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert
symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are
graded according to the degree of danger.
DANGER
indicates that death or severe personal injury will result if proper precautions are not taken.
WARNING
indicates that death or severe personal injury may result if proper precautions are not taken.
CAUTION
indicates that minor personal injury can result if proper precautions are not taken.
NOTICE
indicates that property damage can result if proper precautions are not taken.
If more than one degree of danger is present, the warning notice representing the highest degree of danger will
be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to
property damage.
Qualified Personnel
The product/system described in this documentation may be operated only by personnel qualified for the specific
task in accordance with the relevant documentation, in particular its warning notices and safety instructions.
Qualified personnel are those who, based on their training and experience, are capable of identifying risks and
avoiding potential hazards when working with these products/systems.
Proper use of Siemens products
Note the following:
WARNING
Siemens products may only be used for the applications described in the catalog and in the relevant technical
documentation. If products and components from other manufacturers are used, these must be recommended
or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and
maintenance are required to ensure that the products operate safely and without any problems. The permissible
ambient conditions must be complied with. The information in the relevant documentation must be observed.
Trademarks
All names identified by ® are registered trademarks of Siemens AG. The remaining trademarks in this publication
may be trademarks whose use by third parties for their own purposes could violate the rights of the owner.
Disclaimer of Liability
We have reviewed the contents of this publication to ensure consistency with the hardware and software
described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the
information in this publication is reviewed regularly and any necessary corrections are included in subsequent
editions.
1 Introduction ............................................................................................................................................. 5
2 Safety notices ....................................................................................................................................... 11
2.1 Recommendations on network security ..................................................................................12
3 Description of the device ....................................................................................................................... 17
3.1 Product overview ....................................................................................................................17
3.1.1 Accessories .............................................................................................................................18
3.2 Device views ...........................................................................................................................20
3.2.1 Device view of a SCALANCE XC206-2 (ST/BFOC) ...............................................................20
3.2.2 Device view of a SCALANCE XC206-2 (SC)..........................................................................21
3.2.3 Device view of a SCALANCE XC206-2SFP ...........................................................................22
3.2.4 Device view of a SCALANCE XC208 .....................................................................................23
3.2.5 Device view of a SCALANCE XC216 .....................................................................................24
3.2.6 Device view of a SCALANCE XC224 .....................................................................................25
3.3 SELECT / SET button .............................................................................................................26
3.4 LED display .............................................................................................................................29
3.4.1 Overview .................................................................................................................................29
3.4.2 "RM" LED ................................................................................................................................29
3.4.3 "SB" LED .................................................................................................................................30
3.4.4 "F" LED ...................................................................................................................................30
3.4.5 LEDs "DM1" and "DM2" ..........................................................................................................30
3.4.6 LEDs "L1" and "L2" .................................................................................................................31
3.4.7 Port LEDs ................................................................................................................................32
3.5 C-PLUG ..................................................................................................................................33
3.5.1 Function of the C-PLUG..........................................................................................................33
3.5.2 Replacing the C-PLUG ...........................................................................................................35
3.6 Near Field Communication .....................................................................................................36
4 Mounting ............................................................................................................................................... 37
4.1 Safety notices for installation ..................................................................................................37
4.2 Types of installation ................................................................................................................39
4.3 Mounting on DIN rails .............................................................................................................40
4.4 Installation on a standard S7-300 rail .....................................................................................41
4.5 Installation on a standard S7-1500 rail ...................................................................................42
4.6 Wall mounting .........................................................................................................................44
4.7 Changing the position of the securing bar ..............................................................................45
4.8 General notes for SFP transceivers........................................................................................46
SCALANCE XC-200
Operating Instructions, 07/2016, C79000-G8976-C442-01 3
Table of contents
5 Connecting up....................................................................................................................................... 47
5.1 Safety when connecting up .................................................................................................... 47
5.2 Wiring rules ............................................................................................................................ 49
5.3 Power supply.......................................................................................................................... 50
5.4 Signaling contact .................................................................................................................... 52
5.5 Serial interface ....................................................................................................................... 53
5.6 Functional ground .................................................................................................................. 55
6 Maintenance and troubleshooting.......................................................................................................... 57
6.1 Downloading new firmware using TFTP without WBM and CLI ............................................ 57
6.2 Restoring the factory settings ................................................................................................ 58
7 Technical specifications ........................................................................................................................ 59
7.1 Technical specifications SCALANCE XC206-2 (ST/BFOC) .................................................. 59
7.2 Technical specifications SCALANCE XC206-2 (SC) ............................................................. 61
7.3 Technical specifications SCALANCE XC206-2SFP .............................................................. 63
7.4 Technical specifications of the SCALANCE XC208 .............................................................. 65
7.5 Technical specifications of the SCALANCE XC216 .............................................................. 67
7.6 Technical specifications of the SCALANCE XC224 .............................................................. 69
7.7 Mechanical stability (in operation).......................................................................................... 70
7.8 Cable lengths ......................................................................................................................... 71
7.9 Switching properties ............................................................................................................... 72
8 Dimension drawings .............................................................................................................................. 73
8.1 Dimension drawings SCALANCE XC-200 ............................................................................. 73
9 Certifications and approvals .................................................................................................................. 77
Index .................................................................................................................................................... 83
SCALANCE XC-200
4 Operating Instructions, 07/2016, C79000-G8976-C442-01
Introduction 1
Purpose of the Operating Instructions
These operating instructions support you when installing and connecting up devices of the
SCALANCE XC-200 product group.
Designations used
SCALANCE XC-200
Operating Instructions, 07/2016, C79000-G8976-C442-01 5
Introduction
Additional documentation
In addition, note the Operating Instructions of the pluggable transceivers.
You will find the supplementary documentation here:
● On the data medium that ships with some products:
– Product CD / product DVD
– SIMATIC NET Manual Collection
● On the Internet pages of Siemens Industry Online Support
(https://support.industry.siemens.com/cs/ww/en/ps/15247)
Documentation on configuration
You will find detailed information on configuring the devices in the following configuration
manuals:
● SCALANCE XB-200/XC-200/XP-200 Web Based Management
● SCALANCE XB-200/XC-200/XP-200 Command Line Interface
You will find the configuration manuals here:
● on the data medium that ships with some products:
– Product CD / product DVD
– SIMATIC NET Manual Collection
● On the Internet pages of Siemens Industry Online Support
(https://support.industry.siemens.com/cs/ww/en/ps/15247).
Further documentation
In the system manuals "Industrial Ethernet / PROFINET Industrial Ethernet" and "Industrial
Ethernet / PROFINET passive network components", you will find information on other
SIMATIC NET products that you can operate along with the devices of this product line in an
Industrial Ethernet network.
There, you will find among other things optical performance data of the communications
partner that you require for the installation.
You will find the system manuals here:
● On the data medium that ships with some products:
– Product CD / product DVD
– SIMATIC NET Manual Collection
● On the Internet pages of Siemens Industry Online Support under the following entry IDs:
– 27069465 (http://support.automation.siemens.com/WW/view/en/27069465)
Industrial Ethernet / PROFINET Industrial Ethernet System Manual
– 84922825 (http://support.automation.siemens.com/WW/view/en/84922825)
Industrial Ethernet / PROFINET - Passive network components System Manual
SCALANCE XC-200
6 Operating Instructions, 07/2016, C79000-G8976-C442-01
Introduction
Catalogs
You will find the article numbers for the Siemens products of relevance here in the following
catalogs:
● SIMATIC NET Industrial Communication / Industrial Identification, catalog IK PI
● SIMATIC Products for Totally Integrated Automation and Micro Automation, catalog
ST 70
● Industry Mall - catalog and ordering system for automation and drive technology, Online
catalog
(https://mall.industry.siemens.com/goos/WelcomePage.aspx?regionUrl=/de&language=e
n)
You can request the catalogs and additional information from your Siemens representative.
SCALANCE XC-200
Operating Instructions, 07/2016, C79000-G8976-C442-01 7
Introduction
WARNING
Do not use any parts that show evidence of damage
If you use damaged parts, there is no guarantee that the device will function according to
the specification.
If you use damaged parts, this can lead to the following problems:
• Injury to persons
• Loss of the approvals
• Violation of the EMC regulations
• Damage to the device and other components
Use only undamaged parts.
Security information
Siemens provides products and solutions with industrial security functions that support the
secure operation of plants, systems, machines and networks.
In order to protect plants, systems, machines and networks against cyber threats, it is
necessary to implement – and continuously maintain – a holistic, state-of-the-art industrial
security concept. Siemens’ products and solutions only form one element of such a concept.
Customer is responsible to prevent unauthorized access to its plants, systems, machines
and networks. Systems, machines and components should only be connected to the
enterprise network or the internet if and to the extent necessary and with appropriate security
measures (e.g. use of firewalls and network segmentation) in place.
Additionally, Siemens’ guidance on appropriate security measures should be taken into
account. For more information about industrial security, please visit
http://www.siemens.com/industrialsecurity (http://www.siemens.com/industrialsecurity)
Siemens’ products and solutions undergo continuous development to make them more
secure. Siemens strongly recommends to apply product updates as soon as available and to
always use the latest product versions. Use of product versions that are no longer supported,
and failure to apply latest updates may increase customer’s exposure to cyber threats.
To stay informed about product updates, subscribe to the Siemens Industrial Security RSS
Feed under
https://support.industry.siemens.com/cs/ww/en/ps/15247/pm
(https://support.industry.siemens.com/cs/ww/en/ps/15247/pm).
SCALANCE XC-200
8 Operating Instructions, 07/2016, C79000-G8976-C442-01
Introduction
Trademarks
The following and possibly other names not identified by the registered trademark sign ® are
registered trademarks of Siemens AG:
SIMATIC NET, SCALANCE, C-PLUG, OLM
SCALANCE XC-200
Operating Instructions, 07/2016, C79000-G8976-C442-01 9
Introduction
SCALANCE XC-200
10 Operating Instructions, 07/2016, C79000-G8976-C442-01
Safety notices 2
Read the safety notices
Note the following safety notices. These relate to the entire working life of the device.
You should also read the safety notices relating to handling in the individual sections,
particularly in the sections "Installation" and "Connecting up".
WARNING
EXPLOSION HAZARD
Do not open the device when the supply voltage is turned on.
Safety notices when using the device according to Hazardous Locations (HazLoc)
If you use the device under HazLoc conditions you must also keep to the following safety
notices in addition to the general safety notices for protection against explosion:
This equipment is suitable for use in Class I, Division 2, Groups A, B, C and D or non-
hazardous locations only.
This equipment is suitable for use in Class I, Zone 2, Group IIC or non-hazardous locations
only.
SCALANCE XC-200
Operating Instructions, 07/2016, C79000-G8976-C442-01 11
Safety notices
2.1 Recommendations on network security
NOTICE
Information security
Connect to the device and change the standard password for the user set in the factory
"admin" and "" before you operate the device.
General
● You should make regular checks to make sure that the device meets these
recommendations and/or other security guidelines.
● Evaluate your plant as a whole in terms of security. Use a cell protection concept with
suitable products (http://www.industry.siemens.com/topics/global/en/industrial-
security/network-security/Pages/Default.aspx).
● When the internal and external network are disconnected, an attacker cannot access
internal data from the outside. Therefore operate the device only within a protected
network area.
● For communication via non-secure networks use additional devices with VPN functionality
to encrypt and authenticate the communication.
● Terminate management connections correctly (WBM. Telnet, SSH etc.).
Physical access
● Restrict physical access to the device to qualified personnel because the plug-in data
medium can contain sensitive data.
● Lock unused physical interfaces on the device. Unused interfaces can be used to gain
access to the plant without permission.
SCALANCE XC-200
12 Operating Instructions, 07/2016, C79000-G8976-C442-01
Safety notices
2.1 Recommendations on network security
● The option of VLAN structuring provides protection against DoS and unauthorized
access. Check whether this is practical or useful in your environment.
● Use a central logging server to log changes and accesses. Operate your logging server
within the protected network area and check the logging information regularly.
Passwords
● Define rules for the assignment of passwords.
● Regularly change your passwords to increase security.
● Use passwords with a high password strength.
● Make sure that all passwords are protected and inaccessible to unauthorized persons.
● Do not use the same password for different users and systems.
SCALANCE XC-200
Operating Instructions, 07/2016, C79000-G8976-C442-01 13
Safety notices
2.1 Recommendations on network security
SCALANCE XC-200
14 Operating Instructions, 07/2016, C79000-G8976-C442-01
Safety notices
2.1 Recommendations on network security
Interfaces security
● Disable unused interfaces.
● Use IEEE 802.1X for interface authentication.
● Use the function "Locked Ports" to block interfaces for unknown nodes.
● Use the configuration options of the interfaces, e.g. the "Edge Type".
● Configure the receive ports so that they discard all untagged frames ("Tagged Frames
Only").
Available protocols
The following list provides you with an overview of the open protocol ports.
The table includes the following columns:
● Protocol
● Port
● Port status
– Open
The port is always open and cannot be closed.
– Open (when configured)
The port is open if it has been configured.
● Factory setting
– Open
The factory setting of the port is "Open".
– Closed
The factory setting of the port is "Closed".
● Authentication
Specifies whether or not the protocol is authenticated.
● Encryption
Specifies whether or not the transfer is encrypted.
SCALANCE XC-200
Operating Instructions, 07/2016, C79000-G8976-C442-01 15
Safety notices
2.1 Recommendations on network security
SCALANCE XC-200
16 Operating Instructions, 07/2016, C79000-G8976-C442-01
Description of the device 3
3.1 Product overview
Article numbers
Type designation
The type designation of a SCALANCE XC-200 is made up of several parts that have the
following meaning:
Interface Property
SFP Pluggable transceiver port with 100/1000 Mbps
SCALANCE XC-200
Operating Instructions, 07/2016, C79000-G8976-C442-01 17
Description of the device
3.1 Product overview
3.1.1 Accessories
The following accessories are available for SCALANCE XC-200:
C-PLUG
Cable
SCALANCE XC-200
18 Operating Instructions, 07/2016, C79000-G8976-C442-01
Description of the device
3.1 Product overview
Note
Restriction for pluggable transceivers
If you use pluggable transceivers of the types LH, LH+, ELH or ELH200, the maximum
ambient temperature is reduced to 60 °C.
Spare parts
The following spare parts are available for SCALANCE XC-200:
SCALANCE XC-200
Operating Instructions, 07/2016, C79000-G8976-C442-01 19
Description of the device
3.2 Device views
SCALANCE XC-200
20 Operating Instructions, 07/2016, C79000-G8976-C442-01
Description of the device
3.2 Device views
SCALANCE XC-200
Operating Instructions, 07/2016, C79000-G8976-C442-01 21
Description of the device
3.2 Device views
SCALANCE XC-200
22 Operating Instructions, 07/2016, C79000-G8976-C442-01
Description of the device
3.2 Device views
SCALANCE XC-200
Operating Instructions, 07/2016, C79000-G8976-C442-01 23
Description of the device
3.2 Device views
SCALANCE XC-200
24 Operating Instructions, 07/2016, C79000-G8976-C442-01
Description of the device
3.2 Device views
SCALANCE XC-200
Operating Instructions, 07/2016, C79000-G8976-C442-01 25
Description of the device
3.3 SELECT / SET button
Position
The "SELECT/SET" button is located on the front of the device.
Figure 3-1 Position of the button "SELECT/SET", for example on the SCALANCE XC208
NOTICE
Previous settings
If you reset, all the settings you have made will be overwritten by factory defaults.
NOTICE
Inadvertent reset
An inadvertent reset can cause disturbances and failures in the configured network.
SCALANCE XC-200
26 Operating Instructions, 07/2016, C79000-G8976-C442-01
Description of the device
3.3 SELECT / SET button
Requirement
● The device is in operation.
● The function "Reset to Factory Defaults" is enabled for the "SELECT / SET" button.
Note
Reset despite disabled "SELECT/SET" button
If you have disabled the "Restore Factory Defaults" function for the "SELECT/SET" button
in the configuration, this does not apply during the startup phase, see section "Restoring
the factory settings (Page 58)".
If the function has been disabled in the configuration, it is only disabled on completion of
the startup phase.
Procedure
To reset the device to the factory defaults during operation, follow the steps below:
1. Switch to display mode A.
Display mode A is active if the LEDS "DM1" and "DM2" are unlit.
If the "DM1" and "DM2" LEDs are lit or flashing, you will need to press the "SET/SELECT"
repeatedly until the "DM1" and "DM2" LEDs go off.
If you do not press the "SELECT/SET" button for longer than 1 minute, the device
automatically changes to display mode A.
2. Hold down the "SELECT/SET" button for 12 seconds.
After 9 seconds,the "DM1" and "DM2" LEDs start to flash for 3 seconds. At the same
time, the port LEDs go on one after the other.
After you have held down the button for 12 seconds, the device restarts and the factory
defaults are restored.
If you release the button before the 12 seconds have elapsed, the reset is canceled.
SCALANCE XC-200
Operating Instructions, 07/2016, C79000-G8976-C442-01 27
Description of the device
3.3 SELECT / SET button
SCALANCE XC-200
28 Operating Instructions, 07/2016, C79000-G8976-C442-01
Description of the device
3.4 LED display
3.4.1 Overview
The following figure shows the arrangement of the LEDs based on the example of the
SCALANCE XC208.
SCALANCE XC-200
Operating Instructions, 07/2016, C79000-G8976-C442-01 29
Description of the device
3.4 LED display
SCALANCE XC-200
30 Operating Instructions, 07/2016, C79000-G8976-C442-01
Description of the device
3.4 LED display
SCALANCE XC-200
Operating Instructions, 07/2016, C79000-G8976-C442-01 31
Description of the device
3.4 LED display
If there is a connection problem and the type of transmission is fixed (autonegotiation off),
the desired status, in other words the set transmission speed (1000 Mbps, 100 Mbps, 10
Mbps) continues to be displayed. If there is a connection problem and autonegotiation is
active, the port LED goes off.
SCALANCE XC-200
32 Operating Instructions, 07/2016, C79000-G8976-C442-01
Description of the device
3.5 C-PLUG
3.5 C-PLUG
NOTICE
Do not remove or insert a C-PLUG during operation
A C-PLUG may only be removed or inserted when the device is turned off.
Note
The device can also be operated without a C-PLUG.
SCALANCE XC-200
Operating Instructions, 07/2016, C79000-G8976-C442-01 33
Description of the device
3.5 C-PLUG
How it works
Operating mode
In terms of the C-PLUG, there are three modes for the device:
● Without C-PLUG
The device stores the configuration in internal memory.
This mode is active if no C-PLUG is inserted.
● With unwritten C-PLUG
If an unwritten C-PLUG (factory status or deleted with Clean function) is used, the local
configuration already existing on the device is automatically stored on the inserted C-
PLUG during startup.
This mode is active as soon as an unwritten C-PLUG is inserted.
● With written C-PLUG
A device with a written and accepted C-PLUG uses the configuration data of the C-PLUG
automatically when it starts up. The requirement for acceptance is that the data was
written by a compatible device type.
If there is configuration data in the internal memory of the device this is overwritten.
This mode is active as soon as a written C-PLUG is inserted.
Response to errors
Inserting a C-PLUG that does not contain the configuration of a compatible device type and
inadvertently removing the C-PLUG, or general malfunctions of the C-PLUG are indicated by
the diagnostic mechanisms of the device.
● Fault LED
● Web Based Management (WBM)
● SNMP
● Command Line Interface (CLI)
● PROFINET diagnostics
The user then has the choice of either removing the C-PLUG again or selecting the option to
reformat the C-PLUG.
SCALANCE XC-200
34 Operating Instructions, 07/2016, C79000-G8976-C442-01
Description of the device
3.5 C-PLUG
NOTICE
Do not remove or insert a C-PLUG during operation
The C-PLUG may only be removed or inserted when the device is turned off.
Replacing a C-PLUG.
Removing a C-PLUG
SCALANCE XC-200
Operating Instructions, 07/2016, C79000-G8976-C442-01 35
Description of the device
3.6 Near Field Communication
Inserting a C-PLUG
Position
Figure 3-2 Position of NFC on the SCALANCE XC-200 in the bottom left corner of the LED display.
SCALANCE XC-200
36 Operating Instructions, 07/2016, C79000-G8976-C442-01
Mounting 4
4.1 Safety notices for installation
Safety notices
When installing the device, keep to the safety notices listed below.
WARNING
WARNING
If the device is installed in a cabinet, the inner temperature of the cabinet corresponds to
the ambient temperature of the device.
WARNING
EXPLOSION HAZARD
Replacing components may impair suitability for Class 1, Division 2 or Zone 2.
WARNING
WARNING
The device may only be operated in an environment with pollution degree 1 or 2 (see IEC
60664-1).
SCALANCE XC-200
Operating Instructions, 07/2016, C79000-G8976-C442-01 37
Mounting
4.1 Safety notices for installation
WARNING
WARNING
To comply with EC Directive 2014/34/EU (ATEX 114) or the conditions of IECEx, this
enclosure or cabinet must meet the requirements of at least IP54 in compliance with EN
60529.
WARNING
If the cable or conduit entry point exceeds 70 °C or the branching point of conductors
exceeds 80 °C, special precautions must be taken. If the equipment is operated in an air
ambient in excess of 60 ℃, only use cables with admitted maximum operating temperature
of at least 80 ℃.
Further notes
NOTICE
Warming and premature aging of the network component due to direct sunlight
Direct sunlight can heat up the device and can lead to premature aging of the network
component and its cabling.
Provide suitable shade to protect the network component against direct sunlight.
SCALANCE XC-200
38 Operating Instructions, 07/2016, C79000-G8976-C442-01
Mounting
4.2 Types of installation
Types of installation
The SCALANCE XC-200 can be installed in the following ways:
● DIN rail
● S7-300 standard rail
● S7-1500 standard rail
● Wall mounting
Installation clearance
Keep to the minimum clearances so that the convection ventilation of the device is not
blocked.
● Below at least 10 cm
● Above at least 10 cm
Installation location
Mount the devices vertically so that the LED display is at the top left.
SCALANCE XC-200
Operating Instructions, 07/2016, C79000-G8976-C442-01 39
Mounting
4.3 Mounting on DIN rails
Installation
Note
Note the position of the securing bar, see also section “Dimension drawings SCALANCE XC-
200 (Page 73)“.
When supplied, the securing bar is in the wall mounting position. To change the position of
the securing bar, refer to the section “Changing the position of the securing bar (Page 45)“.
Figure 4-1 DIN rail mounting with securing bar in the wall mounting position.
Removal
To remove the device from a DIN rail, follow the steps below:
1. Disconnect all connected cables.
2. If necessary, loosen the knurled screw with your hand or a screwdriver.
SCALANCE XC-200
40 Operating Instructions, 07/2016, C79000-G8976-C442-01
Mounting
4.4 Installation on a standard S7-300 rail
3. Lever the securing bar down using a screwdriver as far as it will go.
4. Pull the device away from the bottom of the DIN rail with the bar pulled.
Note
Note the position of the securing bar, see also section “Dimension drawings SCALANCE XC-
200 (Page 73)“.
When supplied, the securing bar is in the wall mounting position. To change the position of
the securing bar, refer to the section “Changing the position of the securing bar (Page 45)“.
Figure 4-2 S7-300 mounting rail installation with the securing bar in the wall mounting position.
SCALANCE XC-200
Operating Instructions, 07/2016, C79000-G8976-C442-01 41
Mounting
4.5 Installation on a standard S7-1500 rail
Removal
To remove the device from a standard rail, follow the steps below:
1. Disconnect all connected cables.
2. If necessary, loosen the knurled screw with your hand or a screwdriver.
3. Lever the securing bar down using a screwdriver as far as it will go.
4. Remove the device from the mounting rail with the bar pulled.
Note
Note the position of the securing bar, see also section “Dimension drawings SCALANCE XC-
200 (Page 73)“.
When supplied, the securing bar is in the wall mounting position. To change the position of
the securing bar, refer to the section “Changing the position of the securing bar (Page 45)“.
Figure 4-3 S7-1500 mounting rail installation with the securing bar in the wall mounting position.
SCALANCE XC-200
42 Operating Instructions, 07/2016, C79000-G8976-C442-01
Mounting
4.5 Installation on a standard S7-1500 rail
4. When you tighten the knurled screw. you cannot release the securing bar (torque 0.5
Nm). The device is additionally fixed.
5. Connect the electrical connecting cables, refer to the section "Connecting up (Page 47)".
Removal
To remove the device from a standard rail, follow the steps below:
1. Disconnect all connected cables.
2. If necessary, loosen the knurled screw with your hand or a screwdriver.
3. Lever the securing bar down using a screwdriver as far as it will go.
4. Remove the device from the mounting rail with the bar pulled.
SCALANCE XC-200
Operating Instructions, 07/2016, C79000-G8976-C442-01 43
Mounting
4.6 Wall mounting
Preparation
Note the position of the securing bar, see also section “Dimension drawings SCALANCE XC-
200 (Page 73)“.
When supplied, the securing bar is in the wall mounting position. You do not need to prepare
the device any further.
If the securing bar is in the rail mounting position, note the section “Changing the position of
the securing bar (Page 45)“.
Tools
To mount the device on a wall, you require the following:
● 2 wall plugs
● 2 fillister head screws
Note
Depending on the mounting surface, use suitable fittings.
Assembly
Note
The wall mounting must be capable of supporting at least four times the weight of the device.
SCALANCE XC-200
44 Operating Instructions, 07/2016, C79000-G8976-C442-01
Mounting
4.7 Changing the position of the securing bar
To change the securing bar from the rail mounting position to the wall mounting position
follow the steps below:
1. If necessary, loosen the knurled screw with your hand or a screwdriver.
2. Move the securing bar down as far as it will go.
– Use the levering aid and level the securing bar down using a screwdriver into this
position.
– Push the securing bar down using your hand.
3. Hold the securing bar in this position.
– Hold the securing bar with the screwdriver.
– Use the gap on the rear of the device and fix the securing bar briefly with a pin.
4. Tighten the knurled screw (torque 0.5 Nm).
The securing bar is fixed in the wall mounting position.
5. Remove the pin.
SCALANCE XC-200
Operating Instructions, 07/2016, C79000-G8976-C442-01 45
Mounting
4.8 General notes for SFP transceivers
WARNING
Use only approved SFP transceivers
If you use SFP transceivers that have not been approved by Siemens AG, there is no
guarantee that the device will function according to its specifications.
If you use unapproved SFP transceivers, this can lead to the following problems:
• Damage to the device
• Loss of the approvals
• Violation of the EMC regulations
Use only approved pluggable transceivers.
Note
Plugging and pulling during operation
You can plug and pull pluggable transceivers with the device in operation.
SCALANCE XC-200
46 Operating Instructions, 07/2016, C79000-G8976-C442-01
Connecting up 5
5.1 Safety when connecting up
Safety notices
When connecting up the device, keep to the safety notices listed below.
WARNING
The equipment is designed for operation with Safety Extra-Low Voltage (SELV) by a
Limited Power Source (LPS).
This means that only SELV / LPS complying with IEC 60950-1 / EN 60950-1 / VDE 0805-1
must be connected to the power supply terminals. The power supply unit for the equipment
power supply must comply with NEC Class 2, as described by the National Electrical Code
(r) (ANSI / NFPA 70).
If the equipment is connected to a redundant power supply (two separate power supplies),
both must meet these requirements.
NOTICE
Failure of the data traffic due to contamination of optical plug-in connections
Optical sockets and plugs are sensitive to contamination of the end face. Contamination
can lead to the failure of the optical transmission network.
Close unused optical sockets and plugs as well as pluggable transceivers and slots with the
supplied protective caps.
Remove the protective caps only immediately before you use the plug-in connection.
WARNING
EXPLOSION HAZARD
Do not connect or disconnect cables to or from the device when a flammable or
combustible atmosphere is present.
SCALANCE XC-200
Operating Instructions, 07/2016, C79000-G8976-C442-01 47
Connecting up
5.1 Safety when connecting up
Safety notices when using the device according to Hazardous Locations (HazLoc)
If you use the device under HazLoc conditions you must also keep to the following safety
notices in addition to the general safety notices for protection against explosion:
WARNING
EXPLOSION HAZARD
Do not connect or disconnect while the circuit is live or unless the area is known to be free
of ignitible concentrations.
WARNING
Take measures to prevent transient voltage surges of more than 40% of the rated voltage.
This is the case if you only operate devices with SELV (safety extra-low voltage).
WARNING
Safety notice for connecting with a LAN ID (Local Area Network)
A LAN or LAN segment with all the interconnected devices should be contained completely
in a single low voltage power distribution in a building. The LAN is designed either for
“Environment A” according to IEEE802.3 or "Environment 0" according to IEC TR 62102.
Do not connect any electrical connectors directly to the telephone network (telephone
network voltage) or a WAN (Wide Area Network).
WARNING
EXPLOSION HAZARD
Do not press the SELECT/SET button when there is an explosive atmosphere.
SCALANCE XC-200
48 Operating Instructions, 07/2016, C79000-G8976-C442-01
Connecting up
5.2 Wiring rules
Note
Wire end ferrules
Use crimp shapes with smooth surfaces, such as provided by square and trapeze shaped
crimp cross sections.
Crimp shapes with wave-shaped profile are unsuitable.
SCALANCE XC-200
Operating Instructions, 07/2016, C79000-G8976-C442-01 49
Connecting up
5.3 Power supply
WARNING
Incorrect power supply
When the device is connected to a redundant power supply (two separate power supplies),
both must meet these requirements.
Never operate the device with AC voltage or DC voltage higher than 32 V DC.
CAUTION
Damage to the device due to overvoltage
The connector of the external power supply is not protected against strong electromagnetic
pulses that can, for example, result from lightning strikes or switching large loads.
One of the tests used to attest the immunity of devices of the IE switches SCALANCE XC-
200 to electromagnetic interference was the "surge immunity test" according to EN61000-4-
5. This test requires overvoltage protection for the power supply lines. A suitable device is,
for example, the Dehn Blitzductor BVT AVD 24, article number 918 422 or a comparable
protective element.
Manufacturer: DEHN+SOEHNE GmbH+Co. KG, Hans-Dehn-Str.1, Postfach 1640, D92306
Neumarkt, Germany
Operate the SCALANCE XC-200 with suitable overvoltage protection.
Note
The device can be disconnected from the power supply by pulling off the terminal block.
SCALANCE XC-200
50 Operating Instructions, 07/2016, C79000-G8976-C442-01
Connecting up
5.3 Power supply
Figure 5-1 Position of the power supply based on the example of the SCALANCE XC208 and the
assignment of the terminal block
Contact Assignment
L1+ 24 VDC
M1 Ground
M2 Ground
L2+ 24 VDC
SCALANCE XC-200
Operating Instructions, 07/2016, C79000-G8976-C442-01 51
Connecting up
5.4 Signaling contact
NOTICE
Damage due to voltage being too high
The signaling contact can be subjected to a maximum load of 100 mA (safety extra-low
voltage SELV, 24 VDC).
Higher voltages or currents can damage the device.
Figure 5-2 Position of the signaling contact based on the example of the SCALANCE XC208 and
the assignment of the terminal block
Contact Assignment
F1 Fault contact 1
F2 Fault contact 2
SCALANCE XC-200
52 Operating Instructions, 07/2016, C79000-G8976-C442-01
Connecting up
5.5 Serial interface
Signaling faults
● The signaling of errors by the signaling contact is synchronized with the fault LED "F",
see section ""F" LED (Page 30)".
All errors that the fault LED "F" indicates (freely configurable) are also signaled by the
signaling contact.
● If an internal fault occurs, the fault LED "F" lights up and the signaling contact opens.
● If you connect a communications node to an unmonitored port or disconnect it, this does
not cause an error message.
● The signaling contact remains open until one of the following events occurs:
– The problem is eliminated.
– The current status is entered in the fault mask as the new desired status.
Figure 5-3 Position and pin assignment of the serial interface (RJ-11 jack), for example on the
SCALANCE XC208 as well as the pin assignment D-sub socket.
SCALANCE XC-200
Operating Instructions, 07/2016, C79000-G8976-C442-01 53
Connecting up
5.5 Serial interface
Contact Pin assignment of the RJ-11 plug Pin assignment of the D-sub female con-
nector
1 - -
2 - TD (Transmit Data)
3 TD (Transmit Data) RD (Receive Data)
4 SG (Signal Ground) -
5 RD (Receive Data) SG (Signal Ground)
6 - -
7 -
8 -
9 -
Note
Pin assignment of the RJ-11 jack on the device
The RJ-11 jack on the device has a pinout to match the RJ-11 plug of the connecting cable.
SCALANCE XC-200
54 Operating Instructions, 07/2016, C79000-G8976-C442-01
Connecting up
5.6 Functional ground
Protective/functional ground
The connection of the reference potential surface with the protective ground system is
normally in the cabinet close to the power feed-in. This ground conducts fault currents to
ground safely and according DIN/VDE 0100 is a protective ground to protect people, animals
and property from too high contact voltages.
Apart from the protective ground, there is functional grounding in the cabinet. According to
EN60204-1 (DIN/VDE 0113 T1) electrical circuits must be grounded. The chassis (0 V) is
grounded at one defined point. Here, once again the grounding is implemented with the
lowest leakage resistance to ground in the vicinity of the power feed-in.
With automation components, functional ground also ensures interference-free operation of
a controller. Via the functional ground, interference currents coupled in via the connecting
cables are discharged to ground.
SCALANCE XC-200
Operating Instructions, 07/2016, C79000-G8976-C442-01 55
Connecting up
5.6 Functional ground
SCALANCE XC-200
56 Operating Instructions, 07/2016, C79000-G8976-C442-01
Maintenance and troubleshooting 6
6.1 Downloading new firmware using TFTP without WBM and CLI
Firmware
The firmware is signed and encrypted. This ensures that only firmware created by Siemens
can be downloaded to the device.
Note
This time only lasts a few seconds.
The bootloader of the device waits in this status for a new firmware file that you can
download by TFTP.
5. Connect a PC to port 0.1 via an Ethernet cable.
6. Assign an IP address to the device using DHCP or the Primary Setup Tool.
7. Open a Windows command prompt and change to the directory where the file with the
new firmware is located and then execute the following command :
tftp -i <IP address> put <firmware file>
Note
You can enable TFTP in Microsoft Windows as follows:
"Control Panel" > "Programs and Features" > "Turn Windows features on or off" > "TFTP
Client".
8. Once the firmware has been transferred completely to the device and validated, there is
an automatic restart on the device. This may take several minutes.
SCALANCE XC-200
Operating Instructions, 07/2016, C79000-G8976-C442-01 57
Maintenance and troubleshooting
6.2 Restoring the factory settings
NOTICE
Previous settings
If you reset, all the settings you have made will be overwritten by factory defaults.
NOTICE
Inadvertent reset
An inadvertent reset can cause disturbances and failures in the configured network.
Requirement
The device is in the startup phase.
NOTICE
Reset despite disabled "SELECT/SET" button
Using the "SELECT/SET" button, you can always reset the device parameters to the factory
defaults during the startup phase of the device. This applies also if the "Reset to Factory
Defaults" function was disabled in the configuration. This allows you to reset the device to
the factory defaults in an emergency.
If the function has been disabled in the configuration, it is only disabled on completion of
the startup phase.
Procedure
To reset the device to the factory defaults during the startup phase, follow the steps below:
1. Turn off the power to the device.
2. Now press the "SELECT/SET" button and reconnect the power to the device while
holding down the button.
3. Hold down the button until the red error LED "F" stops flashing and is permanently lit.
4. Now release the button and wait until the fault LED "F" goes off again.
5. The device starts automatically with the factory defaults.
SCALANCE XC-200
58 Operating Instructions, 07/2016, C79000-G8976-C442-01
Technical specifications 7
7.1 Technical specifications SCALANCE XC206-2 (ST/BFOC)
The following technical specifications apply to the SCALANCE XC206-2 (ST/BFOC).
Technical specifications
Attachment to Industrial Ethernet
Electrical connectors Quantity 6
Connector RJ-45 jack
Properties Half/full duplex, MDI-X pinning
Transmission speed 10 / 100 Mbps
Optical connectors Quantity 2
Connector ST/BFOC socket
Properties Full duplex acc. to 100Base-FX
Transmission speed 100 Mbps
Cable type Multimode glass FO cable
Transmitter output (optical)
• Minimum • -19 dBm
• Maximum • -14 dBm
Receiver input
• Sensitivity min. • -32 dBm
• Input power max. • -3 dBm
Cable cross-section Cable length Attenuation
• 50/125 μm • 0 ... 5 km • ≤ 1 dB/km at 1310 nm; 1200 MHz * km
• 62.5/125 μm • 0 ... 5 km • ≤ 1 dB/km at 1310 nm; 1200 MHz * km
Diagnostics interface
Serial interface Quantity 1
Connector RJ-11 jack
Electrical data
Power supply 1) Rated voltage 12 to 24 VDC
Voltage range (incl. tolerance) 9.6 to 31.2 VDC Safe Extra Low Voltage
(SELV)
Design Terminal block, 4 terminals
Properties Implemented redundantly
Current consumption 12 VDC 500 mA
24 VDC 250 mA
Effective power loss 6W
Fusing 2.5 A / 125 V
SCALANCE XC-200
Operating Instructions, 07/2016, C79000-G8976-C442-01 59
Technical specifications
7.1 Technical specifications SCALANCE XC206-2 (ST/BFOC)
Technical specifications
Signaling contact 1) Quantity 1
Design Terminal block, 2 terminals
Permitted voltage range 24 VDC
Load capability max. 100 mA
Permitted ambient conditions
Ambient temperature During operation up to 2000 m -40 °C to +70 °C
During storage -40 ℃ to +85 ℃
During transportation -40 ℃ to +85 ℃
Relative humidity During operation at 25 ℃ ≤ 95 % no condensation
Housing, dimensions and weight
Design compact
Housing material Basic housing Die cast aluminum, powder coated
Front cover Polycarbonate (PC-GF10)
Degree of protection IP20
Dimensions (W x H x D) 60 x 147 x 125 mm
Weight 540 g
Installation options • Wall mounting
• Installation on a DIN rail
• Mounting on an S7-300 standard rail
• Mounting on an S7-1500 standard rail
Mean time between failure (MTBF)
MTBF (EN/IEC 61709; 40 °C) > 46 years
Switching properties
Aging time 45 seconds
Max. number of learnable MAC 2048
addresses
Response to LLDP frames Blocking
Response to spanning tree BPDU Forwarding
frames
CoS acc. to IEEE 802.1Q Yes
QoS priority queues 4
1) Note the wiring rules (Page 49).
SCALANCE XC-200
60 Operating Instructions, 07/2016, C79000-G8976-C442-01
Technical specifications
7.2 Technical specifications SCALANCE XC206-2 (SC)
Technical specifications
Attachment to Industrial Ethernet
Electrical connectors Quantity 6
Connector RJ-45 jack
Properties Half/full duplex, MDI-X pinning
Transmission speed 10 / 100 Mbps
Optical connectors Quantity 2
Connector SC socket
Properties Full duplex acc. to 100Base-FX
Transmission speed 100 Mbps
Cable type Multimode glass FO cable
Transmitter output (optical)
• Minimum • -19 dBm
• Maximum • -14 dBm
Receiver input
• Sensitivity min. • -32 dBm
• Input power max. • -3 dBm
Cable cross-section Cable length Attenuation
• 50/125 μm • 0 ... 5 km • ≤ 1 dB/km at 1310 nm; 1200 MHz * km
• 62.5/125 μm • 0 ... 5 km • ≤ 1 dB/km at 1310 nm; 1200 MHz * km
Diagnostics interface
Serial interface Quantity 1
Connector RJ-11 jack
Electrical data
Power supply 1) Rated voltage 12 to 24 VDC
Voltage range (incl. tolerance) 9.6 to 31.2 VDC Safe Extra Low Voltage
(SELV)
Design Terminal block, 4 terminals
Properties Implemented redundantly
Current consumption 12 VDC 500 mA
24 VDC 250 mA
Effective power loss 6W
Fusing 2.5 A / 125 V
Signaling contact 1) Quantity 1
Design Terminal block, 2 terminals
Permitted voltage range 24 VDC
Load capability max. 100 mA
SCALANCE XC-200
Operating Instructions, 07/2016, C79000-G8976-C442-01 61
Technical specifications
7.2 Technical specifications SCALANCE XC206-2 (SC)
Technical specifications
Permitted ambient conditions
Ambient temperature During operation up to 2000 m -40 °C to +70 °C
During storage -40 ℃ to +85 ℃
During transportation -40 ℃ to +85 ℃
Relative humidity During operation at 25 ℃ ≤ 95 % no condensation
Housing, dimensions and weight
Design compact
Housing material Basic housing Die cast aluminum, powder coated
Front cover Polycarbonate (PC-GF10)
Degree of protection IP20
Dimensions (W x H x D) 60 x 147 x 125 mm
Weight 540 g
Installation options • Wall mounting
• Installation on a DIN rail
• Mounting on an S7-300 standard rail
• Mounting on an S7-1500 standard rail
Mean time between failure (MTBF)
MTBF (EN/IEC 61709; 40 °C) > 46 years
Switching properties
Aging time 45 seconds
Max. number of learnable MAC 2048
addresses
Response to LLDP frames Blocking
Response to spanning tree BPDU Forwarding
frames
CoS acc. to IEEE 802.1Q Yes
QoS priority queues 4
1) Note the wiring rules (Page 49).
SCALANCE XC-200
62 Operating Instructions, 07/2016, C79000-G8976-C442-01
Technical specifications
7.3 Technical specifications SCALANCE XC206-2SFP
Technical specifications
Attachment to Industrial Ethernet
Electrical connectors Quantity 6
Connector RJ-45 jack
Properties Half/full duplex, MDI-X pinning
Transmission speed 10 / 100 Mbps
Slots for pluggable transceivers Quantity 2
Connector SFP transceivers (LC port)
Transmission speed 100 / 1000 Mbps
Diagnostics interface
Serial interface Quantity 1
Connector RJ-11 jack
Electrical data
Power supply 1) Rated voltage 12 to 24 VDC
Voltage range (incl. tolerance) 9.6 to 31.2 VDC Safe Extra Low Voltage
(SELV)
Design Terminal block, 4 terminals
Properties Implemented redundantly
Current consumption 12 VDC Without SFP 400 mA
With SFP 2) 500 mA
24 VDC Without SFP 200 mA
With SFP 2) 250 mA
Effective power loss Without SFP 4.8 W
With SFP 2) 6W
Fusing 2.5 A / 125 V
Signaling contact 1) Quantity 1
Design Terminal block, 2 terminals
Permitted voltage range 24 VDC
Load capability max. 100 mA
Permitted ambient conditions
Ambient temperature 3) During operation up to 2000 m -40 °C to +70 °C
During storage -40 ℃ to +85 ℃
During transportation -40 ℃ to +85 ℃
Relative humidity During operation at 25 ℃ ≤ 95 % no condensation
Housing, dimensions and weight
Design compact
Housing material Basic housing Die cast aluminum, powder coated
Front cover Polycarbonate (PC-GF10)
Degree of protection IP20
SCALANCE XC-200
Operating Instructions, 07/2016, C79000-G8976-C442-01 63
Technical specifications
7.3 Technical specifications SCALANCE XC206-2SFP
Technical specifications
Dimensions (W x H x D) 60 x 147 x 125 mm
Weight 520 g
Installation options • Wall mounting
• Installation on a DIN rail
• Mounting on an S7-300 standard rail
• Mounting on an S7-1500 standard rail
Mean time between failure (MTBF)
MTBF (EN/IEC 61709; 40 °C) > 47 years
Switching properties
Aging time 45 seconds
Max. number of learnable MAC 2048
addresses
Response to LLDP frames Blocking
Response to spanning tree BPDU Forwarding
frames
CoS acc. to IEEE 802.1Q Yes
QoS priority queues 4
1) Note the wiring rules (Page 49).
2)Detected with the SFP992-1ELH. You will find the precise values in the operating
instructions of the pluggable transceivers, see the section "Introduction" Additional
documentation (Page 5).
3)Depending on which pluggable transceiver you use, the maximum ambient temperature
can change, see section "Accessories", Pluggable transceivers SFP (Page 18)".
SCALANCE XC-200
64 Operating Instructions, 07/2016, C79000-G8976-C442-01
Technical specifications
7.4 Technical specifications of the SCALANCE XC208
Technical specifications
Attachment to Industrial Ethernet
Electrical connectors Quantity 8
Connector RJ-45 jack
Properties Half/full duplex, MDI-X pinning
Transmission speed 10 / 100 Mbps
Diagnostics interface
Serial interface Quantity 1
Connector RJ-11 jack
Electrical data
Power supply 1) Rated voltage 12 to 24 VDC
Voltage range (incl. tolerance) 9.6 to 31.2 VDC Safe Extra Low Volt-
age (SELV)
Design Terminal block, 4 terminals
Property Implemented redundantly
Current consumption 12 VDC 350 mA
24 VDC 175 mA
Effective power loss 4.2 W
Fusing 2.5 A / 125 V
Signaling contact 1) Quantity 1
Design Terminal block, 2 terminals
Permitted voltage range 24 VDC
Load capability max. 100 mA
Permitted ambient conditions
Ambient temperature During operation up to 2000 m -40 °C to +70 °C
During storage -40 ℃ to +85 ℃
During transportation -40 ℃ to +85 ℃
Relative humidity During operation at 25 ℃ ≤ 95 % no condensation
Housing, dimensions and weight
Design compact
Housing material Basic housing Die cast aluminum, powder coated
Front cover Polycarbonate (PC-GF10)
Degree of protection IP20
Dimensions (W x H x D) 60 x 147 x 125 mm
Weight 520 g
SCALANCE XC-200
Operating Instructions, 07/2016, C79000-G8976-C442-01 65
Technical specifications
7.4 Technical specifications of the SCALANCE XC208
Technical specifications
Installation options • Wall mounting
• Installation on a DIN rail
• Mounting on an S7-300 standard rail
• Mounting on an S7-1500 standard rail
Mean time between failure (MTBF)
MTBF (EN/IEC 61709; 40 °C) > 48 years
Switching properties
Aging time 45 seconds
Max. number of learnable MAC ad- 2048
dresses
Response to LLDP frames Blocking
Response to spanning tree BPDU Forwarding
frames
CoS acc. to IEEE 802.1Q Yes
QoS priority queues 4
1) Note the wiring rules (Page 49).
SCALANCE XC-200
66 Operating Instructions, 07/2016, C79000-G8976-C442-01
Technical specifications
7.5 Technical specifications of the SCALANCE XC216
Technical specifications
Attachment to Industrial Ethernet
Electrical connectors Quantity 16
Connector RJ-45 jack
Properties Half/full duplex, MDI-X pinning
Transmission speed 10 / 100 Mbps
Diagnostics interface
Serial interface Quantity 1
Connector RJ-11 jack
Electrical data
Power supply 1) Rated voltage 12 to 24 VDC
Voltage range (incl. tolerance) 9.6 to 31.2 VDC Safe Extra Low Voltage
(SELV)
Design Terminal block, 4 terminals
Properties Implemented redundantly
Current consumption 12 VDC 550 mA
24 VDC 275 mA
Effective power loss 6.6 W
Fusing 2.5 A / 125 V
Signaling contact 1) Quantity 1
Design Terminal block, 2 terminals
Permitted voltage range 24 VDC
Load capability max. 100 mA
Permitted ambient conditions
Ambient temperature During operation up to 2000 m -40 °C to +70 °C
During storage -40 ℃ to +85 ℃
During transportation -40 ℃ to +85 ℃
Relative humidity During operation at 25 ℃ ≤ 95 % no condensation
Housing, dimensions and weight
Design compact
Housing material Basic housing Die cast aluminum, powder coated
Front cover Polycarbonate (PC-GF10)
Degree of protection IP20
Dimensions (W x H x D) 120 x 147 x 125 mm
Weight 800 g
SCALANCE XC-200
Operating Instructions, 07/2016, C79000-G8976-C442-01 67
Technical specifications
7.5 Technical specifications of the SCALANCE XC216
Technical specifications
Installation options • Wall mounting
• Installation on a DIN rail
• Mounting on an S7-300 standard rail
• Mounting on an S7-1500 standard rail
Mean time between failure (MTBF)
MTBF (EN/IEC 61709; 40 °C) > 48 years
Switching properties
Aging time 45 seconds
Max. number of learnable MAC 2048
addresses
Response to LLDP frames Blocking
Response to spanning tree BPDU Forwarding
frames
CoS acc. to IEEE 802.1Q Yes
QoS priority queues 4
1) Note the wiring rules (Page 49).
SCALANCE XC-200
68 Operating Instructions, 07/2016, C79000-G8976-C442-01
Technical specifications
7.6 Technical specifications of the SCALANCE XC224
Technical specifications
Attachment to Industrial Ethernet
Electrical connectors Quantity 24
Connector RJ-45 jack
Properties Half/full duplex, MDI-X pinning
Transmission speed 10 / 100 Mbps
Diagnostics interface
Serial interface Quantity 1
Connector RJ-11 jack
Electrical data
Power supply 1) Rated voltage 12 to 24 VDC
Voltage range (incl. tolerance) 9.6 to 31.2 VDC Safe Extra Low Volt-
age (SELV)
Design Terminal block, 4 terminals
Property Implemented redundantly
Current consumption 12 VDC 750 mA
24 VDC 375 mA
Effective power loss 9W
Fusing 2.5 A / 125 V
Signaling contact 1) Quantity 1
Design Terminal block, 2 terminals
Permitted voltage range 24 VDC
Load capability max. 100 mA
Permitted ambient conditions
Ambient temperature During operation up to 2000 m -40 °C to +70 °C
During storage -40 ℃ to +85 ℃
During transportation -40 ℃ to +85 ℃
Relative humidity During operation at 25 ℃ ≤ 95 % no condensation
Housing, dimensions and weight
Design compact
Housing material Basic housing Die cast aluminum, powder coated
Front cover Polycarbonate (PC-GF10)
Degree of protection IP20
Dimensions (W x H x D) 120 x 147 x 125 mm
Weight 880 g
SCALANCE XC-200
Operating Instructions, 07/2016, C79000-G8976-C442-01 69
Technical specifications
7.7 Mechanical stability (in operation)
Technical specifications
Installation options • Wall mounting
• Installation on a DIN rail
• Mounting on an S7-300 standard rail
• Mounting on an S7-1500 standard rail
Mean time between failure (MTBF)
MTBF (EN/IEC 61709; 40 °C) > 41 years
Switching properties
Aging time 45 seconds
Max. number of learnable MAC ad- 2048
dresses
Response to LLDP frames Blocking
Response to spanning tree BPDU Forwarding
frames
CoS acc. to IEEE 802.1Q Yes
QoS priority queues 4
1) Note the wiring rules (Page 49).
SCALANCE XC-200
70 Operating Instructions, 07/2016, C79000-G8976-C442-01
Technical specifications
7.8 Cable lengths
SCALANCE XC-200
Operating Instructions, 07/2016, C79000-G8976-C442-01 71
Technical specifications
7.9 Switching properties
Switching properties
Switching technique Store and forward
Latency 10 microseconds
Full wire speed switching Frame length (bytes) Number of frames per second (at 100 Mbps)
64 148810
128 84459
256 45290
512 23496
1024 11973
1280 9615
1518 8127
Note
The number of SCALANCE XC-200 modules connected in a line influences the entire frame
delay. When a frame passes through the IE switch, this is delayed by the store-and-forward
function of the SCALANCE XC-200 by 10-130 microseconds (at 100 Mbps).
SCALANCE XC-200
72 Operating Instructions, 07/2016, C79000-G8976-C442-01
Dimension drawings 8
8.1 Dimension drawings SCALANCE XC-200
Note
Dimensions are specified in mm.
Front view SCALANCE XC206-2 (ST/BFOC), SCALANCE XC206-2 (SC), SCALANCE XC206-2SFP
and SCALANCE XC208
SCALANCE XC-200
Operating Instructions, 07/2016, C79000-G8976-C442-01 73
Dimension drawings
8.1 Dimension drawings SCALANCE XC-200
SCALANCE XC-200
74 Operating Instructions, 07/2016, C79000-G8976-C442-01
Dimension drawings
8.1 Dimension drawings SCALANCE XC-200
SCALANCE XC-200
Operating Instructions, 07/2016, C79000-G8976-C442-01 75
Dimension drawings
8.1 Dimension drawings SCALANCE XC-200
Figure 8-4 Drilling template with securing bar in the wall mounting position (as supplied)
SCALANCE XC-200
76 Operating Instructions, 07/2016, C79000-G8976-C442-01
Certifications and approvals 9
The SIMATIC NET products described in these Operating Instructions have the approvals
listed below.
Note
Issued approvals on the type plate of the device
The specified approvals apply only when the corresponding mark is printed on the product.
You can check which of the following approvals have been granted for your product by the
markings on the type plate.
Installation guidelines
The devices meet the requirements if you adhere to the installation and safety instructions
contained in this documentation and in the following documentation when installing and
operating the devices.
● "Industrial Ethernet / PROFINET Industrial Ethernet" System Manual
● "Industrial Ethernet / PROFINET - Passive network components" System Manual
You will find information on the system manuals in the section "Introduction (Page 5)", in
"Further documentation".
● "EMC Installation Guidelines" configuration manual
60612658 (http://support.automation.siemens.com/WW/view/en/60612658)
SCALANCE XC-200
Operating Instructions, 07/2016, C79000-G8976-C442-01 77
Certifications and approvals
WARNING
Personal injury and property damage can occur
The installation of expansions that are not approved for SIMATIC NET products or their
target systems may violate the requirements and regulations for safety and electromagnetic
compatibility.
Only use expansions that are approved for the system.
Note
The test was performed with a device and a connected communications partner that also
meets the requirements of the standards listed above.
When operating the device with a communications partner that does not comply with these
standards, adherence to the corresponding values cannot be guaranteed.
EC declaration of conformity
The SIMATIC NET products described in these operating instructions meet the requirements
and safety objectives of the following EC directives and comply with the harmonized
European standards (EN) which are published in the official documentation of the European
Union.
● 2014/34/EU (ATEX explosion protection directive)
Directive of the European Parliament and the Council of 26 February 2014 on the
approximation of the laws of the member states concerning equipment and protective
systems intended for use in potentially explosive atmospheres, official journal of the EU
L96, 29/03/2014, pages. 309-356
● 2014/30/EU (EMC)
EMC directive of the European Parliament and of the Council of February 26, 2014 on the
approximation of the laws of the member states relating to electromagnetic compatibility;
official journal of the EU L96, 29/03/2014, pages. 79-106
● 2011/65/EU (RoHS)
Directive of the European Parliament and of the Council of 8 June 2011 on the restriction
of the use of certain hazardous substances in electrical and electronic equipment
You will find the EC declaration of conformity for these products on the Internet pages of
Siemens Industry Online Support
(http://support.automation.siemens.com/WW/view/en/33118389/134200).
The EC Declaration of Conformity is available for all responsible authorities at:
Siemens Aktiengesellschaft
Division Process Industries and Drives
Process Automation
DE-76181 Karlsruhe
Germany
SCALANCE XC-200
78 Operating Instructions, 07/2016, C79000-G8976-C442-01
Certifications and approvals
WARNING
When using SIMATIC NET products in hazardous area zone 2, make absolutely sure that
the associated conditions in the following document are adhered to:
"SIMATIC NET Product Information Use of subasseblies/modules in a Zone 2 Hazardous
Area".
You will find this document
• on the data medium that ships with some devices.
• on the Internet pages of Siemens Industry Online Support
(http://support.automation.siemens.com/WW/view/en).
Enter the document identification number C234 as the search term.
The SIMATIC NET products meet the requirements of the EC directive 94/9/EC "Equipment
and Protective Devices for Use in Potentially Explosive Atmospheres”. and as of 20.04.2016
the EC directive 2014/34/EU.
ATEX classification:
II 3 G Ex nA IIC T4 Gc
KEMA 07ATEX0145 X
The products meet the requirements of the following standards:
● EN 60079-15 (electrical apparatus for potentially explosive atmospheres; Type of
protection "n")
● EN 60079-0 (Explosive atmospheres - Part 0: Equipment - General requirements)
You will find the current versions of the standards in the currently valid ATEX certificates.
IECEx
The SIMATIC NET products meet the requirements of explosion protection according to
IECEx.
IECEx classification:
Ex nA IIC T4 Gc
DEK 14.0025X
The products meet the requirements of the following standards:
● IEC 60079-15 (Explosive atmospheres - Part 15: Equipment protection by type of
protection "n")
● IEC 60079-0 (Explosive atmospheres - Part 0: Equipment - General requirements)
You will find the current versions of the standards in the currently valid IECEx certificates.
SCALANCE XC-200
Operating Instructions, 07/2016, C79000-G8976-C442-01 79
Certifications and approvals
You will find the current versions of the standards in the currently valid EC declaration of
conformity.
RoHS
The SIMATIC NET products described in these operating instructions meet the requirements
of the EC directive 2011/65/EC for the restriction of the use of certain hazardous substances
in electrical and electronic equipment:
Applied standard:
● EN 50581
FM
The product meets the requirements of the standards:
● Factory Mutual Approval Standard Class Number 3611
● FM Hazardous (Classified) Location Electrical Equipment:
Non Incendive / Class I / Division 2 / Groups A,B,C,D / T4 and
Non Incendive / Class I / Zone 2 / Group IIC / T4
SCALANCE XC-200
80 Operating Instructions, 07/2016, C79000-G8976-C442-01
Certifications and approvals
RCM
The product meets the requirements of the AS/NZS 2064 standard (Class A).
SCALANCE XC-200
Operating Instructions, 07/2016, C79000-G8976-C442-01 81
Certifications and approvals
CAUTION
SCALANCE XC-200
82 Operating Instructions, 07/2016, C79000-G8976-C442-01
Index
A G
Approvals, 77 Glossary, 7
Article numbers, 17 Grounding, 20, 21, 22, 23, 24, 25, 55
Attachment to Industrial Grounding screw, 20, 21, 22, 23, 24, 25
Ethernet, 59, 61, 63, 65, 67, 69
H
B Housing, 60, 62, 63, 65, 67, 69
Button, 57
I
C Installation, 60, 62, 63, 65, 67, 69
CE mark, 77 Installation on a DIN rail, 40
Command Line Interface (CLI), 34, 53, 57 Installation on a standard rail, 41, 42
Components of the product, 18 Wall mounting, 44
Configuration, 27 Installation on a DIN rail, 40
Connecting cable, 53 Installation on a standard rail, 41, 42
Connecting up
Grounding, 55
C-PLUG K
Configuration, 33
Knurled screw, 20, 21, 22, 23, 24, 25, 40, 41, 42
D L
Dimensions, 60, 62, 63, 65, 67, 69
LED display, 20, 21, 22, 23, 24, 25, 29
Display mode, 26, 30
Levering aid, 20, 21, 22, 23, 24, 25, 45
E M
Electrical data, 59, 61, 63, 65, 67, 69
MTBF, 60, 62, 64, 66, 68, 70
Environmental conditions, 19, 60, 62, 63, 65, 67, 69
N
F
Near Field Communication (NFC), 36
Factory defaults, 26, 58
Factory setting, 58
Factory settings, 26, 58
P
Fault mask, 28
Fault/error status, 30 Permitted ambient conditions, 60, 62, 63, 65, 67, 69
Firmware, 30, 57 Permitted environmental conditions, 19
PLUG, 33
Pluggable transceiver
SFP, 6, 18, 19, 19
SCALANCE XC-200
Operating Instructions, 07/2016, C79000-G8976-C442-01 83
Index
R
Redundancy manager, 28
Reset device, 26, 58, 58
Reset to Factory Defaults, 27, 58
S
S7-1500, 42
S7-300, 41
Safety notices
for installation, 37
general, 11
Use in hazardous areas, 11, 37, 47
when connecting up, 47
Securing
bar, 20, 21, 22, 23, 24, 25, 40, 41, 42, 73, 74, 75
SELECT / SET button, 26
SELECT/SET button, 20, 21, 22, 23, 24, 25, 31, 58
Serial interface, 53
SFP transceiver, 6, 18, 19, 19
Signaling contact, 18, 20, 21, 22, 23, 24, 25, 30, 52
SIMATIC NET glossary, 7
SIMATIC NET manual, 7
Spare parts, 19
Spring-loaded terminal, 18, 50, 52
Startup phase, 27, 30, 58
Switching properties, 60, 62, 64, 66, 68, 70
System manual, 6, 77
W
Web Based Management (WBM), 34, 57
Weight, 60, 62, 63, 65, 67, 69
Wiring rules, 50, 52
SCALANCE XC-200
84 Operating Instructions, 07/2016, C79000-G8976-C442-01