The HVA45 and HVA45TD are truly compact and portable VLF test sets that determine
the condition of medium voltage cables. Both test sets perform VLF and DC testing, as well
as sheath testing with sheath fault location possibilities. In order to meet international test
guides (e.g. IEEE 400.2-2013) the HVA45TD combines the small and lightweight VLF test set
with an integrated Tan Delta diagnostics unit. With the available +4 kV option you can
extend the possible output voltage of this test set even further.
+ 4 k
Performance: Outstanding features Connectivity: On-site, no external V
optio
considering size and weight vs. output load. PC is needed. All results can be later n
downloaded via USB or Bluetooth for
Duty cycle: No thermal limitation! further investigation and easy reporting
You can use the test set continuously. via the b2 ControlCenter.
YOUR BENEFITS
This makes them widely applicable for eliminates routine servicing and makes the
in-field use. test sets almost maintenance-free.
www.b2hv.com
1/4
HVA45 & HVA45TD
VLF high voltage test set
Datasheet
TECHNICAL DATA
Output characteristics with +4 kV option
VLF sine wave 0 ... 32.3 kVrms / 0 ... 45 kVpeak 0 ... 34.6 kVrms / 0 ... 49 kVpeak
DC -45 kV ... 45 kV
VLF square wave 0 ... 45 kV
Output voltage Sheath test 0 ... 15 kV (negative polarity)
Voltage setting resolution 0.1 kV
AC frequency range 0.01 Hz ... 0.1 Hz
Frequency setting resolution 0.01 Hz
AC 30 mArms max.
DC 45 mA max.
Output current
Sheath test trip current 0.1 ... 10 mA
Sheath fault location 25 mA max.
Duty cycle Continuous, no thermal limitation of operating time
10.0
9.0
8.0
5.0
4.0
3.0
2.0
1.0
DHV1453 Rev00 – © b2 electronics GmbH – Subject to change without notice.
0.0
0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34
Voltage [kVrms]
www.b2hv.com
2/4
HVA45 & HVA45TD
VLF high voltage test set
Datasheet
Metering
AC TrueRMS
Maximum display value 38 kVrms
Resolution 0.1 kVrms
Output voltage Accuracy ± 0.1 kVrms ± 1% of reading
measurement range DC
Maximum display value 55 kV
Resolution 0.1 kV
Accuracy ± 0.1 kV ± 1% of reading
AC TrueRMS
Maximum display value 69 mArms
Resolution 0.1 / 1 / 10 / 100 µArms
Output current Accuracy ± 1 µArms ± 1% of reading
measurement range DC
Max./min. display values ± 98 mA
Resolution 0.1 / 1 / 10 / 100 µA
Accuracy ± 1 µA ± 1% of reading
Load 10 nF ... 10 μF
TD range 0.1 ... 999 E-3
Resolution single: 0.1 E-3 / mean: 0.01 E-3
Tan Delta Accuracy ± 0.1 E-3
DHV1453 Rev00 – © b2 electronics GmbH – Subject to change without notice.
www.b2hv.com
3/4
HVA45 & HVA45TD
VLF high voltage test set
Datasheet
Further characteristics
AC supply 100 ... 240 V, 50/60 Hz, 1.200 VA
Backfeed protection: 12 kV at 50/60 Hz
Product safety DDD Dual Discharge Device
(integrated electronic and mechanical discharge device)
Operating
-20 ... +55 °C
temperature range
Environmental
Storage
conditions -25 ... +70 °C
temperature range
Humidity 5 ... 85%, non condensing
USB type A
Data transfer
Bluetooth
Built-in memory: up to 50 reports, 50 test sequences
Report management
USB flash drive: dependent on storage capacity
PC software b2 ControlCenter (included)
500 x 305 x 457 mm
Dimensions L x W x H
19.68 x 12.0 x 18.0 in
Weight 39 kg / 86 lbs