with integrated Tan Delta diagnostics system

VLF 0.1 Hz integrated


14 kg
29 kVpeak TD diagnostics

334 mm
The HVA28TD is a truly compact and portable VLF test set system for testing medium
voltage cables. It performs VLF and DC testing, sheath testing with sheath fault
location mode and TD leakage current correction (guard terminal) is included.
Assessments of cable condition can also be carried out by use of Tan Delta Diagnostics.

MWT: the recently introduced Monitored Withstand Test (MWT), a combination of Withstand Testing and Tan Delta Diagnostics in
compliance with IEEE 400.2-2013, can be performed.
Performance - the HVA28TD offers outstanding features in terms of size, weight (14 kg) and performance (max. 10 µF).
Safety: the instrument has two independent earthing devices (electronic and mechanical discharging) and an integrated 12 kV feed-
back protection system to protect both operator and instrument.
Field use: a watertight and very rugged case with a protection class of IP67 makes additional transport boxes obsolete.
Connectivity: on site, no external PC is needed. All results can be downloaded later by USB or Bluetooth for further investigation and
easy report creation on the PC Software.
Unlimited operating time: Operating time of the HVA high voltage generators are not thermally limited and can be operated continuously.

www.b2hv.com | info@b2hv.com
www.b2hv.at
www.b2hv.at
Features
• Output voltage 29 kVpeak , 21 kVrms • Protection class IP67 (with closed lid) • Dual Discharge Device (DDD®), integrated
• Pure sinusoidal output voltage • Total protection: almost unbreakable, electronic and mechanical discharge devices
(load-independent) watertight, dustproof and corrosion • Easily exchangeable HV cable
• Internal TD measurement with proof case • Intuitive menu operation
high accuracy (1 x 10-4) • Large Colour display (4,3”) • Sheath Fault Locating (in combination
• Tan Delta measurement with • USB and Bluetooth connections with Earth Fault Locator) (not included)
various frequencies (0.01-0.1 Hz) • Cable testing according: • Vacuum Bottle Test
• Leakage Guard® - IEC60502-2:2015, IEEE 400.2-2004, • Insulation Testing
leakage current correction CENELEC HD 620/621,
• Output current 20 mA max. IEEE400.2-2013 etc.
• 0.5 μF @ 0.1 Hz @ 20 kV rms • Programmable test sequences
• Highest test capacity of 10 µF • Upgradable with Partial Discharge
• Ultra light and compact weight (14 kg) diagnostics system (optional)
• 12 kV transient protection (50 Hz)
HVA28TD
www.b2hv.com | info@b2hv.com
Type HVA28TD
Article number SH5002
Input voltage 100-240 V, 50/60 Hz, 400 VA
VLF sine wave 0-29 kV peak, 21 kV rms
DC ± 0-28 kV
dry system Output voltage VLF square wave 0-28 kV
accuracy ± 1%
resolution 0.1 kV
Output current 0-20 mA
Resistance range 0.1 MΩ-5 GΩ
0.01-0.1 Hz in steps of 0.01 Hz

Riedstrasse 1 | 6833 Klaus | AUSTRIA | T +43 (0)5523 57373 | info@b2hv.com


Output frequency

DHV1299 Rev06 - ENGLISH - Subject to alternations. Errors excepted. Illustrations are not binding.
default: 0.1 Hz (auto frequency)
Tan Delta accuracy ± 1 x 10-4
0.5 μF @ 0.1 Hz @ 20 kV rms
upgradeable to Output load 5.0 μF @ 0.01 Hz @ 20 kV rms
PD diagnostics 10.0 μF maximum Capacitance!1
system max. test voltage 10 kV
Sheath test
trip current 0.1-5.0 mA
max. test voltage 10 kV
Sheath fault location2
Pulse/Period 1:3 / 4 s, 1:5 / 4 s, 1:5 / 6 s, 1:9 / 6 s
AC (VLF) Symmetrical and load independent across full range,
Output Modes DC (plus or negative polarity), Burn-/Fault Condition or
Fault Trip Mode, Jacket/Sheath Testing
12 kV/50 Hz Feedback Protection | integrated electronic and mechanical
unlimited Safety
discharge devices - DDD®: Dual Discharge Device (internal)
operating time
Memory 50 Test Record Stored, USB almost unlimited
Voltage and Current (True rms and/or peak), Capacitance,
Metering
Resistance, Time, Flashover Voltage
Duty cycle Continuous! No thermal limitation for operating time.

IP67 HV-Cable
Software
4 m with alligator clamps
“b2 Control Center” (included)
Computer interfaces Bluetooth and USB flash drive
protection class Dimensions LxWxH 416 x 221 x 334 mm (Peli Case)
IP67 Weight 14 kg
temperature: storage -25°C to + 70°C, operating -20°C to + 55°C
Environment
humidity: 5-85 % non condensing
1
at lower frequency and voltage | 2 in combination with locating device (not in scope of supply)

Options Scope of delivery


• Partial Discharge diagnostics system • HVA28TD testing device incl. Tan Delta diagnostics
• PC Software - b2 ControlCenter
• HV cable 4 m
• Power and earthing cable
• Accessory bag