MD/SMD 800A Frame and Internal Accessories 6/39
Accessory Locations
ND/SND 1200A Frame and Internal Accessories 6/43
Suffix for Internal Accesories 6/157
PD/SPD 1600A Frame and Internal Accessories 6/47
Technical Data 6/160
RD 2000A Frame and Internal Accessories 6/50
Unusual Operating Conditions 6/161
STD 3200A Frame and Internal Accessories 6/52
MagneticTrip Only—ETI Motor Circuit Protector 6/55
Adjustable Instantaneous MagneticTrip Settings 6/57
Molded Case Switch—Circuit Disconnect 6/60
Sensitrip III Digital Solid State Sentron Series 6/61
WL Power Circut Breakers - Insulated Case 6/63
Electronic and Communications Accessories 6/67
Pressure and Compression Connectors 6/69
Breaker Modifications 6/72
Internal Accessories - Feature Combinations 6/74
External Accessories 6/75
General Technical
Enclosed Circuit Breakers 6/80
Series Rated Combination Guide 6/88
Unusual Operating Conditions 6/99
Typical Specifications 6/100
Superseded Circuit Breakers 6/101
Molded Case Circuit Breakers
introduction
OEM Circuit Breakers ■ As Frame and Trip Unit shipped Connecting Breakers for DC
In this issue of the Speedfax, Siemens assembled and with the trip unit made Application
introduces the modular and flexible non-removable, in compliance with UL
design of Siemens VL molded case 489 requirements that to be reverse Most Siemens thermal magnetic trip
circuit breakers (MCCB) for OEM fed the circuit breaker must not have MCCBs are applicable on direct current
applications. This family of MCCB’s an interchangeable trip unit. (dc) systems. Generally, for 250 V dc
allow the OEM customer the flexibility systems a two pole breaker is used,
These two options are described in the with one pole on each leg of the supply
of last minute changes, with a following
minimum level of stock due to product circuit. For three pole breakers applied
modularity. The VL family of MCCB’s Components Ordered Separately on 500 V dc systems, it is important
also offer the widest range of field to connect the power supply “zig-zag”
To get the components for a 3 pole,
installable accessories in the industry. through the breaker as shown in the
400 Amp standard interrupting circuit
lay contact for alarms such as Ground figure below. This assures that the
breaker, you would order the frame
Fault Warning and a latching alarm relay Voltage between phases on the breaker
(JD63F400), the trip unit (JD63T400)
contact for trip indication. terminals is uniformly distributed.
and six lugs (TA2J6500). This option is
normally useful only if you stock and
use large volumes of product and wish
to reduce your inventory cost. You may
stock, for example, a smaller number of
frames (JD63F400) and a variety of trip
units (JD63T300, JD63T350, etc.) and
assemble breakers as you need them.
Frame, Trip Unit and Lugs Ordered
Together
If you order the catalog number
JD63B400, you will receive a frame, a
trip unit and 6 lugs in separate packages.
Interruption Ratings (UL/CSA) By suffixing this number with “L” (e.g.
N 35kA @ 480Vac Voltage JD63B400L), you will receive frame,
H 65kA @ 480Vac trip unit and lugs assembled in one
container. Pursuant to UL 489, a product
L 100kA @ 480Vac ordered thus will have the markings
“LINE” and “LOAD”, and may not be 500V DC Wiring Configuration
Ratings 30-1600A “reverse fed” (with power flowing from
the “OFF” end of the breaker toward the
Voltage 600Vac “ON” end).
6
690Vac (IEC)
Non-Interchangeable Trip Breakers
Standards UL, CSA, NOM, IEC, CE Marked If you place an “X” after the frame size
designator (e.g. JXD63B400), you will
receive a frame and trip unit assembled,
Ordering with the trip unit made non-removable. If
In the FD through RD frames, you may you suffix an “L” to this catalog number
BREAKERS
CIRCUIT
order molded case circuit breakers three (e.g. JXD63B400L), you will recieve the
basic ways: breaker, non-removable trip unit and
lugs assembled. Unless you anticipate
■ As separately ordered frames, trip units
6/2
Molded Case Circuit Breakers
reference
Catalog Numbering System
If used on 250A frame and above means non-interchangeable trip
breaker with factory assembled frame and trip. Solid state trip and
current limiting (S or C in first character) are non-interchangeable
only, and the “X” is omitted.
X D
6
FD Frame — 070, 080, 090, 100, 110, 125, 150, 175, 200, 225, 250
JD Frame — 200, 225, 250, 300, 350, 400
LD Frame — 250, 300, 350, 400, 450, 500, 600
LMD Frame — 500, 600, 700, 800
MD Frame — 500, 600, 700, 800
ND Frame — 900, 100 (1000A), 120 (1200A)
PD Frame — 120 (1200A), 140 (1400A), 160 (1600A)
RD Frame — 160 (1600A), 180 (1800A), 200 (2000A)
TD Frame — 2000, 2500, 3200
BREAKERS
CIRCUIT
Suffix
L — where applicable indicates a breaker shipped with line/loads lugs installed
A — used with a switch to show automatic self protection
Y — 400 Hertz
H — 100% rated
NOTE:
Applicable Standards Solderless Lugs for use with UL869 — Service Equipment
UL489 — Molded Case Circuit Breakers aluminum wire NEMA AB-1 — Molded Case Circuit
and Circuit Breaker Enclosures. UL943 — Ground Fault Interrupters (for Breakers and Molded Case Switches
UL486A — Wire Connectors and personnel protectors) CSA–C22.2 No. 5,
Solderless Lugs for use with copper wire UL1087 — Molded Case Switches C22.2 No. 14
UL486B — Wire Connectors and UL50 — Cabinets and Boxes
Note: (B) Molded case circuit breakers are to be connected with 60 or
(A) Molded case circuit breakers are designed and tested 75°C wire for circuit breakers having a rated ampacity of
in accordance to applicable portions of UL489 and CSAC22.2 125 amperes or less. Circuit breakers having a rated ampacity
No 5 and meet application requirements of the National greater than 125 amperes shall only be cabled with 75°C
Electric Code. Unless marked otherwise, circuit breakers are cable unless otherwise indicated on the circuit breaker
80% duty rated. label. Exceptions to this rule are outlined in the article
110-14 C(1)(2) of the 2002 National Electric Code and Canadian
Electrical Code.
6/3
VL Molded Case Circuit Breakers
Reference
Interrupting Class
N — Normal
H — High
L — Very High
C — Trip Unit Only
Frame Family
G — Type GG L — Type LG
E — Type EG M— Type MG
D — Type DG N— Type NG
F — Type FG P — Type PG
J — Type JG
Breaker Type
G — Global (UL, IEC, CE, CSA, NOM) M — Motor Circuit Protector
T — Trip Unit Only (Global) S — Molded Case Switch
H — 100% rated J — 240V only rated, Non-interchangeable only
X — Non-Interchangeable Y — 100% rated, Non-interchangeable
N — Naval
Number of Poles
1, 2, 3, 4, 5 (4P w/ neutral protection)
Trip Unit
B — Thermal Magnetic, standard 40° C ambient L — Magnetic Only, Motor Circuit Protector - Low
C — Thermal Magnetic, calibrated for 50° C ambient (non-UL) instantaneous range
D — Electronic w/ LCD, LSI, 3P or 4P (neutral protected) M — Magnetic Only, Motor Circuit Protector - Standard
E — Electronic w/ LCD, LSIG, 3P/4W (selectable residual or instantaneous range
return type ground fault protection) N — Electronic LI, 3P or 4P (neutral protected)
F — Frame only, without trip unit P — Electronic LSI, 3P or 4P (neutral protected)
H — Magnetic only, Motor Circuit Protector - High S — Molded Case Switch
instantaneous range U — Electronic, LSIG, 3P/4W or 4P, residual ground fault protection
X — Electronic, LIG, 3P/4W or 4P, residual ground fault protection
A1 — 1 Alarm (includes 1NO & 1NC switch with a 2 Aux./1 Alarm Base, for frames EG to JG) Note: A1 and A3 include 1NO and 1NC switch for
A2 — 2 Aux (1NO & 1NC switch with a 3 Aux. Base, for frames EG to JG) alarm purposes, only one of these switches may
A3 — 2 Aux + 1 Alarm (2NO & 2NC switches with a 2 Aux./1 Alarm Base, for frames EG to JG) be used as there is only one space for an alarm.
A3 — 2 Aux + 2 Alarm (2NO & 2NC switches with a 2 Aux./2 Alarm Base, for frames LG to PG)
A4 — 4 Aux (2NO & 2NC switches with a 4 Aux. Base, for frames LG to PG)
Shunt Trips
RB — 24 VDC RM — 48-60 VAC
RC — 48-60 VDC RN — 110-127 VAC
RD — 110-127 VDC RS — 208-277 VAC
RE — 250 VDC RV — 380-600 VAC
6/4
Molded Case Circuit Breakers
Selection / Application
Reference Guide
Thermal-Magnetic Trip Breakers
Load Center Breakers Panelboard Breakers
QP, QPH, HQP, BQD,
QT QPP QPPH HQPP HQPPH QPJ BL BLH HBL BQD6
Page 1-23 1-22, 1-27 1-22, 1-27 1-22, 1-27 1-27 1-27 6-13 6-13 6-13 6-16
Poles 1, 2 1, 2, 3 1, 2, 3 1, 2, 3 2 2,3 1, 2, 3, 1, 2, 3 1, 2, 3 1, 2, 3
Amperes, Continuous 15–50 15–125 15–125 15–125 100–200 150–200 15–125 15–125 15–100 15–100
1-Pole
120/240 120/240 120/240 120/240 120/240 120/240 120/240 120/240 120/240 277
Volts (60 Hertz) 2-Pole
3-Pole — 240 240 240 240 240 240 240 240 480/277
AC 120V 10,000 10,000 22,000 65,000 — — 10,000 22,000 65,000 65,000
Ratings 240V 10,000 10,000 22,000 65,000 100,000 10,000 10,000 22,000 65,000 65,000
CSA/UL Interrupting Rating —
277V — — — — — — — — — 14,000
Symmetrical RMS Amperes
347V — — — — — — — — — 10,000a
480/277V — — — — — — — — — 14,000
600/347V — — — — — — — — — 10,000a
Volts — 2-Pole — — — — — — — — — 250
DC
Interrupting Rating — DC Amperes — — — — — — — — — 14,000e
15–50A — 2.87 2.87 — — 7.00 3.56 3.56 — 4.50
15–30A — — — — — — — 3.75 — —
Height
15–60A 3.12 — — — — — — — — —
Dimensions in 55–125A — 3.12 3.12 3.12 3.12 3.00 3.75 — 3.75 4.50
inches 1-Pole 1.00 1.00 1.00 1.00 — — 1.00 1.00 1.00 1.00
Width 2-Pole 2.00 2.00 2.00 2.00 4.00
2.00 2.00 2.00 2.00
3-Pole 2.00 3.00 3.00 3.00 — 3.00 3.00 3.00 3.00 3.00
Depth 2.06 2.37 2.37 2.37 2.37 2.34 2.37 2.37 2.69 2.23
Overcurrent Thermal and Fixed Magnetic Trip
Devices Molded Case Switch — — — — — — — — —
Undervoltage Trip — — — — — — — — —
Accessories & Shunt Trip — —
Modifications Auxiliary Switch — — — — —
Alarm Switch — — — — — — — — —
Type 1 — Indoor Surface — — — — —
Individual Type 1 — Indoor, Flush — — — — — —
Enclosures
6
Type 3R — Outdoor-Rainproof — — — — — —
BREAKERS
CIRCUIT
QP, QPH, HQP BL, BLH, HBL BQD, BQD6
For inches / millimeters conversion, see Application Data Single pole breakers available in ratings 15–70A only. Fits only Siemens EQIII load centers. Breaker is 2 or 3
section. 125A, 2-pole 120/240V AC only. poles wide.
14,000A IR at 277/480V AC only.
BQD6 CSA cerified 10,000A @ 600Y/347V 15–70A only. Not applicable to types QPP and QPPH.
Types QPP, QPPH, HQPP and HQPPH are special 2-pole Single pole circuit breakers available in ratings 15-70A only,
configurations for load center mains. Amperage range = 125A available as a 2-pole only.
125–225A, width = 4 in. Not applicable to type HQPP.
6/5
Molded Case Circuit Breakers
Selection / Application
Reference Guide
Thermal-Magnetic Trip Breakers
General Purpose Breakers
BQ BQH HBQ QJ2 QJH2 QJ2-H HQJ2-H CQD NGG
Page 6-17 6-17 6-17 6-19 6-19 6-19 6-19 6-20 6-21
Poles 1, 2, 3 1, 2, 3 1, 2, 3 2, 3 2, 3 2, 3 3 1, 2, 3 1, 2, 3
1-Pole 15–70 15–70 15–50 — — — — 15–100 15–100
Amperes, Continuous 2-Pole 15–125 15–100 15–70 — 15–100 15–125
60–225 60–225 60–225
3-Pole 15–100 15–100 15–100 100–225 15–100 15-125
1-Pole — — — — 277 347
120/240 120/240 120/240
Volts (60 Hertz) 2-Pole —
240 240 240 480/277 600/347
3-Pole 240 240 240 240
AC
120V 10,000 22,000 65,000 — — — — 65,000 65,000
Ratings
CSA/UL Interrupting Rating — 240V 10,000 22,000 65,000 10,000 22,000 42,000 100,000 65,000 65,000
Symmetrical RMS Amperes 480/277V — — — — — — — 14,000 25,000
600/347V — — — — — — — 10,000 18,000
Volts — 2-Pole — — — — — — — 250 250
DC
Interrupting Rating — DC Amperes — — — — — — — 14,000 14,000
15–50A 3.75 3.75 4.00 — — — — 4.50 —
Height 55–125A 4.00 4.00 4.00 — — — — 4.50 —
Dimensions in 60–225A — — — 7.00 7.00 7.00 7.00 — —
inches 1-Pole 1.00 1.00 1.00 — — — — 1.00 1.00
Width 2-Pole 2.00 2.00 2.00 3.00 3.00 3.00 — 2.00 2.00
3-Pole 3.00 3.00 3.00 4.50 4.50 4.50 4.50 3.00 3.00
Depth 2.37 2.37 2.37 2.34 2.34 2.53 2.53 2.87 2.90
Overcurrent Thermal and Fixed Magnetic Trip
Devices Molded Case Switch — — — — — — —
Undervoltage Trip — — — — — — — —
Shunt Trip
Accessories & Auxiliary Switch
Modifications Alarm Switch — — — — —
Mechanical Interlock — — — — —
Fungus Proofing (ref. page 106)
Type 1 — Indoor Surface —
Individual
6
6/6
6
Molded Case Circuit Breakers
Selection / Application
Reference Guide
Thermal-Magnetic Trip Breakers
General Purpose Breakers
FD6A, HFD6, HHFD6,
ED2 ED4 ED6 HED4 CED6 FXD6A HFXD6 HHFXD6 CFD6
Page 6-23 6-23 6-23 6-24 6-24 6-26 6-27 6-27 6-27
Poles 1, 2, 3 1, 2, 3 1, 2, 3 1, 2, 3 2, 3 2, 3 2, 3 2, 3 2, 3
Amperes, Continuous 15–100 15–125 15–125 15–125 15–125 70–250 70–250 70–250 70–250
Volts 50/60HZ 1-Pole 120 277 347 277 — — — — —
2-Pole
240 480 600 480 600 600 600 600 600
3-Pole
120V 10,000 — — — — — — — —
240V 10,000 65,000 65,000 100,000 200,000 65,000 100,000 200,000 200,000
277V — 22,000 — 165,000 — — — — —
AC CSA / UL
347V — — 30,000 — — — — — —
480V — 18,000 25,000 142,000 1200,000 35,000 165,000 100,000 200,000
Ratings Interrupt Rating 600V — — 18,000 — 1100,000 18,000 125,000 125,000 100,000
Symmetrical RMS Icu — 65,000 — 200,000 65,000 100,000 200,000 —
Amperes 220/240V
Ics — — 17,000 — — 33,000 150,000 100,000 —
IEC 947-2 Icu — 35,000 — 200,000
35,000 165,000 100,000 —
380/415V
50/60HZ Ics — — 19,000 — — 18,000 133,000 150,000 —
Icu — — 18,000 — — 20,000 142,000 165,000 —
500V
Ics — — 15,000 — — 10,000 121,000 133,000 —
2-Pole, 250V DC Interrupting Ratings 5,000 30,000 30,000 30,000 30,000 30,000 30,000 — 30,000
DC
3-Pole, 500V DC Interrupting Ratings — — 18,000 — 50,000 18,000 25,000 — 50,000
Height 6.34 6.34 6.34 6.34 9.26 9.50 9.50 11.00 14.12
1-Pole 1.00 1.00 1.00 1.00 — — — — —
Dimensions in Width 2-Pole 2.00 2.00 2.00 2.00 2.00 4.50 4.50 4.50 4.50
inches
3-Pole 3.00 3.00 3.00 3.00 3.00 4.50 4.50 4.50 4.50
Depth 4.00 4.00 4.00 4.00 4.00 4.00 4.00 4.00 4.00
Thermal and Fixed Magnetic Trip — — — —
Overcurrent Thermal and Adjustable Magnetic Trip — — — — —
Devices Adjustable Magnetic Trip Only
Motor Circuit Protector — — — — —
Molded Case Switch — — —
Undervoltage Trip
Shunt Trip
6
Auxiliary Switch
Alarm Switch
Accessories & Mechanical Interlock — — — — —
Modifications
Rear Connection Studs
Electric Motor Operator
Plug-In Mounting Assembly
Fungus Proofing (ref. page 106)
BREAKERS
Type 1 — Indoor Surface
CIRCUIT
Type 1 — Indoor, Flush — —
Type 3R — Outdoor-Rainproof
Individual Type 7 — Flammable Gas Atmosphere — —
Enclosures
Type 9 — Combustion Dusttight — —
Type 5, 12 — Lint, Fine Dust, Oils, Coolants
Type 12K — Semi-Dusttight
6/7
Molded Case Circuit Breakers
Selection / Application
Reference Guide
Thermal-Magnetic Trip Breakers General Purpose Breakers
JD6-A, HJD6-A, HHJD6-A, LD6, HLD6, HHLD6,
JXD2-A JXD6-A HJXD6-A HHJXD6-A CJD6 LXD6 HLXD6 HHLXD6 CLD6
Page 6-29 6-29 6-30 6-30 6-30 6-33 6-33 6-34 6-34
Poles 2, 3 2, 3 2, 3 2, 3 2, 3 2, 3 2, 3 2, 3 2, 3
Amperes, Continuous 200-400 200-400 200-400 200-400 200-400 450-600 250-600 250-600 450-600
Volts 50/60HZ 2-Pole
240 600 600 600 600 600 600 600 600
3-Pole
240V 65,000 65,000 100,000 200,000 200,000 65,000 100,000 200,000 200,000
CSA / UL 480V — 35,000 065,000 100,000 150,000 35,000 165,000 100,000 150,000
AC
Interrupt Rating 600V — 25,000 035,000 150,000 100,000 25,000 135,000 150,000 100,000
Ratings Symmetrical RMS Icu — 65,000 100,000 200,000 — 65,000 100,000 200,000 —
Amperes 220/240V
Ics — 33,000 050,000 100,000 — 33,000 150,000 100,000 —
IEC 947-2 Icu — 40,000 065,000 100,000 — 40,000 165,000 100,000 —
380/415V
50/60HZ Ics — 20,000 033,000 150,000 — 20,000 133,000 150,000 —
Icu — 30,000 042,000 165,000 — 30,000 142,000 165,000 —
500V
Ics — 15,000 021,000 133,000 — 15,000 121,000 133,000 —
2-Pole 250V DC Interrupting Ratings 30,000 30,000 030,000 — 30,000 30,000 130,000 — 130,000
DC
3-Pole, 500V DC Interrupting Ratings — 25,000 035,000 — 50,000 25,000 135,000 — 150,000
Height 11.00 11.00 11.00 11.00 17.86 11.00 11.00 11.00 17.86
Dimensions in 2-Pole
Width 7.50 7.50 7.50 7.50 7.50 7.50 7.50 7.50 7.50
inches 3-Pole 1 1 1 1 1 1 1 1 1
Depth 14.00 14.00 14.00 14.00 14.00 14.00 14.00 14.00 14.00
Thermal and Adjustable Magnetic Trip
Overcurrent Adjustable Magnetic Trip Only
Devices Motor Circuit Protector — — — — — —
Molded Case Switch — — — —
Undervoltage Trip
Shunt Trip
Auxiliary Switch
Alarm Switch
Accessories & Mechanical Interlock
Modifications
Rear Connection Studs
Electric Motor Operator
Plug-In Mounting Assembly
6
6/8
Molded Case Circuit Breakers
Selection / Application
Reference Guide
Thermal-Magnetic Trip Breakers
General Purpose Breakers
LMD6, HLMD6, MD6, HMD6, ND6, HND6,
LMXD6 HLMXD6 MXD6 HMXD6 CMD6 NXD6 HNXD6 CND6
Page 6-37 6-37 6-40 6-41 6-41 6-44 6-45 6-45
Poles 2, 3 2, 3 2, 3 2, 3 3 2, 3 2, 3 3
Amperes, Continuous 500-800 500-800 500-800 500-800 400-800 800-1200 800-1200 800-1200
Volts 50/60 HZ 2-Pole
600 600 600 600 600 600 600 600
3-Pole
240V 65,000 100,000 65,000 100,000 200,000 65,000 100,000 200,000
CSA / UL 480V 50,000 165,000 50,000 165,000 100,000 50,000 165,000 100,000
AC 600V 25,000 125,000 25,000 150,000 165,000 25,000 150,000 165,000
Ratings Interrupt Rating Icu 65,000 100,000 65,000 100,000 200,000 65,000 100,000 200,000
Symmetrical RMS 220/240V
Amperes Ics 33,000 150,000 33,000 150,000 100,000 33,000 150,000 100,000
IEC 947-2 Icu 40,000 165,000 40,000 165,000 100,000 40,000 165,000 100,000
380/415V
50/60HZ Ics 20,000 133,000 20,000 133,000 150,000 20,000 133,000 150,000
Icu 30,000 142,000 30,000 142,000 165,000 30,000 142,000 165,000
500V
Ics 15,000 121,000 15,000 121,000 133,000 15,000 121,000 133,000
2-Pole 250V DC Interrupting Ratings 30,000 130,000 30,000 130,000 130,000 30,000 130,000 130,000
DC
3-Pole, 500V DC Interrupting Ratings 25,000 150,000 25,000 150,000 150,000 25,000 150,000 150,000
Height 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00
Dimensions in 2-Pole — —
Width 7.50 7.50 9.00 9.00 9.00 9.00
inches 3-Pole 9.00 9.00
Depth 4.59 4.59 6.19 6.19 6.19 6.19 6.19 6.19
Thermal and Fixed Magnetic Trip — — — — — — — —
Thermal and Adjustable Magnetic Trip
Overcurrent
Devices Adjustable Magnetic Trip Only
Motor Circuit Protector — — — — —
Molded Case Switch — —
Undervoltage Trip
Shunt Trip
Auxiliary Switch
Alarm Switch
Accessories & Mechanical Interlock
Modifications
Rear Connection Studs
Electric Motor Operator —
6
Plug-In Mounting Assembly — —
Fungus Proofing (ref. page 6/73)
Type 1 — Indoor Surface —
Type 1 — Indoor, Flush — — — — — — —
Individual Type 3R — Outdoor-Rainproof — —
Enclosures
Type 5, 12 — Lint, Fine Dust, Oils, Coolants — —
Type 7 — Flammable Gas Atmosphere — — — — — — — —
BREAKERS
Type 9 — Combustion Dusttight — — — — — — —
CIRCUIT
Type 12K — Semi-Dusttight — —
6/9
Molded Case Circuit Breakers
Selection / APplication
Reference Guide
Thermal-Magnetic Trip Breakers General Purpose Breakers
PD6 , HPD6, RD6 , HRD6,
PXD6 HPXD6 CPD6 RXD6 HRXD6
Page 6-48 6-48 6-48 6-51 6-51
Poles 3 3 3 3 3
Amperes, Continuous 1200-1600 1200-1600 1200-1600 1600-2000 1600-2000
Volts 50/60 HZ 3-Pole 11,600 111,600 111,600 11,600 111,600
240V 65,000 100,000 200,000 65,000 100,000
CSA / UL 480V 50,000 165,000 100,000 50,000 165,000
600V 25,000 150,000 165,000 25,000 150,000
AC
Ratings Interrupt Rating Icu 65,000 100,000 200,000 65,000 100,000
Symmetrical RMS 220/240V
Ics 33,000 150,000 100,000 33,000 150,000
Amperes
IEC 947-2 Icu 40,000 165,000 100,000 40,000 165,000
380/415V
50/60HZ Ics 10,000 117,000 125,000 10,000 117,000
Icu 30,000 142,000 165,000 30,000 142,000
500V
Ics 18,000 121,000 117,000 18,000 121,000
2-Pole 250V DC Interrupting Ratings 30,000 130,000 130,000 30,000 130,000
DC
3-Pole, 500V DC Interrupting Ratings 25,000 150,000 150,000 25,000 150,000
Circuit breakers require Connect-all Height 16.00 16.00 16.00 16.00 16.00
Dimensions in mounting block. Dimensions shown Width 19.00 19.00 19.00 19.00 19.00
inches
are for circuit breaker only. Depth 16.19 16.19 16.19 16.19 16.19
Overcurrent Thermal and Adjustable Magnetic Trip
Devices Molded Case Switch — — —
Undervoltage Trip
Shunt Trip
Auxiliary Switch
Accessories & Alarm Switch
Modifications Mechanical Interlock
Electric Motor Operator
Fungus Proofing (ref. page 106)
Mounting Block (required)
Type 1 — Indoor Surface
Type 1 — Indoor, Flush — — — — —
Type 3R — Outdoor-Rainproof — — — — —
Individual Type 7 — Flammable Gas Atmosphere — — — — —
Enclosures
6
6/10
Molded Case Circuit Breakers
Selection / Application
Reference Guide
Electronic Trip Breakers
Solid State Trip Cicuit Breakers
SJD6 SHJD6 SCJD6 SLD6 SHLD6 SCLD6 SMD6 SHMD6 SCMD6
Page 6-31 6-31 6-31 6-35 6-35 6-35 6-42 6-42 6-42
Poles 3 3 3 3 3 3 3 3 3
Amperes, Continuous 200-400 200-400 200-400 300-600 300-600 300-600 600-800 600-800 600-800
Volts 50/60 HZ 3-Pole 600 600 600 600 600 600 600 600 600
Ratings AC
Interrupt Rating 240V 65,000 100,000 200,000 65,000 100,000 200,000 65,000 100,000 200,000
Symmetrical RMS CSA / UL 480V 35,000 165,000 150,000 35,000 165,000 150,000 50,000 165,000 100,000
Amperes 600V 25,000 135,000 100,000 25,000 135,000 100,000 25,000 150,000 165,000
Height 11.00 11.00 17.86 11.0 11.00 17.86 10.00 16.00 16.00
Dimensions in Width 3-Pole 17.50 17.50 17.50 17.50 17.50 17.50 19.00 19.00 19.00
inches
Depth 14.00 14.00 14.00 14.00 14.00 14.00 16.19 16.19 16.19
Overcurrent Solid State Trip
Devices
Undervoltage Trip —
Shunt Trip
Auxiliary Switch
Alarm Switch
Accessories & Mechanical Interlock — — — — — —
Modifications
Rear Connection Studs
Electric Motor Operator
Plug-In Mounting Assembly
Fungus Proofing (ref. page 106)
Type 1 — Indoor Surface — —
Type 1 — Indoor, Flush — — — — — — — — —
Type 3R — Outdoor-Rainproof — —
Individual Type 7 — Flammable Gas Atmosphere — — — — —
Enclosures
Type 9 — Combustion Dusttight — — — —
Type 5, 12 — Lint, Fine Dust, Oils, Coolants
Type 12K — Semi-Dusttight — — —
6
BREAKERS
CIRCUIT
6/11
Molded Case Circuit Breakers
Selection / Application
Reference Guide
Electronic Trip Breakers
Insulated Case
Solid State Trip Circuit Breakers Circuit Breakers
SND6 SHND6 SCND6 SPD6 SHPD6 STD6 SHTD6 SHHTD6 SBA SBS SBH
Page 6-46 6-46 6-46 6-49 6-49 6-53 6-53 6-53 6-64 6-64 6-64
Poles 3 3 3 3 3 3 3 3 3 3 3
Amperes, Continuous 800-1200 800-1200 800-1200 1200-1600 1200-1600 2000-3200 2000-3200 2000-3200 400-2000 400-500 2000-5000
Volts 50/60HZ 3-Pole 600 600 600 600 600 600 600 600 600 600 600
240V 65,000 100,000 200,000 65,000 100,000 65,000 100,000 200,000 65,000 150,000 200,000
CSA / UL 480V 50,000 165,000 100,000 50,000 165,000 35,000 165,000 150,000 65,000 100,000 150,000
Ratings AC
Interrupt Rating 600V 25,000 150,000 165,000 25,000 150,000 25,000 135,000 100,000 50,000 85,000 100,000
Symmetrical RMS Icu — — — — — — — — — 100 —
Amperes 380/415V
EC 947-2 Ics — — — — — — — — — 100 —
50/60HZ Icu — — — — — — — — — 165 —
690V
Ics — — — — — — — — — 165 —
Height 16.00 16.00 16.00 16.00 16.00 27.5 27.5 27.5 — — —
Dimensions in Width 19.00 19.00 19.00 19.00 19.00 14.12 14.12 14.12 — — —
inches
Depth 16.19 16.19 16.19 16.19 16.19 11.38 11.38 11.38 — — —
Overcurrent
Devices Solid State Trip
Undervoltage Trip
Shunt Trip
Auxiliary Switch
Alarm Switch
Accessories & Mechanical Interlock —
Modifications
Rear Connection Studs —
Electric Motor Operator — — — — — — —
Plug-In Mounting Assembly — — — — — — — — —
Stored Energy Mechanism — — — — — — — —
Drawout Construction — — — — — — — —
Fungus Proofing (ref. page 106)
Type 1 — Indoor Surface — — — — — — —
Type 1 — Indoor, Flush — — — — — — — — — — —
Type 3R — Outdoor-Rainproof — — — — — — — — —
Individual —
Type 7 — Flammable Gas Atmosphere — — — — — — — — — —
Enclosures
6
6/12
Molded Case Circuit Breakers
SELECTION / APPLICATION
Panelboard Mounting Circuit Breakers
Type BL–Low Tab Bolt-on (10,000A IR)
Non-Interchangeable Trip
1-Pole 2-Pole 2-Pole 3-Pole
120/240V AC 240V AC 240V AC
Continuous 120/240V AC Common Trip Common Trip Common Trip
Current Rating Catalog Catalog Catalog Catalog
@ 40° C Number Number Number Number
015 B115 30.00 B215 68.00 B215R ■ 181.00 B315 227.00
020 B120 30.00 B220 68.00 B220R ■ 181.00 B320 227.00
025 B125 30.00 B225 68.00 B225R ■ 181.00 B325 227.00
030 B130 30.00 B230 68.00 B230R ■ 181.00 B330 227.00
035 B135 30.00 B235 68.00 B235R ■ 181.00 B335 227.00
040 B140 30.00 B240 68.00 B240R ■ 181.00 B340 227.00
045 B145 ■ 30.00 B245 68.00 B245R ■ 181.00 B345 227.00
050 B150 30.00 B250 68.00 B250R ■ 181.00 B350 227.00
060 B160 30.00 B260 68.00 B260R ■ 181.00 B360 227.00
070 B170 65.00 B270 133.00 B270R ■ 240.00 B370 278.00
080 — B280 181.00
B280R ■ 273.00 B380 314.00
090 — B290 181.00 B290R ■ 273.00 B390 314.00
100 — B2100 181.00 B2100R ■ 273.00 B3100 314.00
110 — B2110 ■ 364.00 — —
125 — B2125 385.00 — —
6
040 B140HH 118.00 B240HH302.00 — B340HH522.00
050 B150HH ■ 118.00 B250HH302.00 — B350HH522.00
060 —— B260HH302.00 — B360HH522.00
070 ——-- B270HH ■ 494.00 — B370HH558.00
080 ——-- B280HH ■ 558.00 — B380HH656.00
090 ——-- B290HH ■ 558.00 — B390HH656.00
100 ——-- B2100HH558.00 — B3100HH656.00
BREAKERS
CIRCUIT
Types BL/BLH/HBL
Internal Accessories (Factory installed only; require one additonal pole width)
Auxiliary Switches
Control Voltage Shunt Trip 1A and 1B
AC DC Suffix Suffix
120V — ...00S01 ■ ...01 ■
24V — ...00S07 ■ ...01 ■
■ Built to order. Allow 3–4 weeks for delivery. CSACertified / UL Listed for 3 phase 240V grounded B
CSA Certified / UL Listed for frequent switching at 10,000 AIR. Modifications - page 6/73
applications (SWD). 120V AC fluorescent lighting. HACR rated. Accessories - page 6/75 to 6/80
For 400 cycle CSA Certified/ UL Listed devices, add “Y”
suffix to catalog number. Add 25% to list price. 5000A
interrupting rating — Built To Order.
6/13
Molded Case Circuit Breakers
Selection
Panelboard Mounting Circuit Breakers
Ordering Instructions
All BL circuit breakers are supplied with load side connectors.
All standard circuit breakers are calibrated for 40° C maximum ambient application.
1 #14–#6 AWG Cu
25-35
1 #12-#6 AWG AI
1 #8–#6 AWG Cu
40-50
1 #8-#4 AWG AI
BL, BLH, HBL Fixed in Breaker
1 #8–#4 AWG Cu
55-70 BL/BLH/HBL
1 #8-#2 AWG AI
1 #4–#1/0 AWG Cu
80-100
1 #2-#1/0 AWG AI
1 #2–#1/0 AWG Cu
110-125
1 #1/0-#2/0 AWG AI
6
BREAKERS
CIRCUIT
6/14
Molded Case Circuit Breakers
SELECTION
Special Application Panelboard Mounting Breakers
GFCI Personnel Protection (Class A) (5MA)
Complete Breaker UL Interrupting Ratings (KA)
Unenclosed (RMS Symmetrical Amperes) 1˝
BLF 15
20
BF215
BF220
349.00
349.00
—
—
10
10
—
—
2-Pole
30 BF230 349.00 — 10 —
40 BF240 ■ 349.00 — 10 —
50 BF250 ■ 349.00 — 10 —
60 BF260 ■ 349.00 — 10 —
BLHF 15
20
BF115H 581.00
BF120H 581.00
22
22
—
—
—
—
1-Pole 22 — —
30 BF130H ■ 581.00
BLHF 15
20
BF215H ■ 633.00
BF220H ■ 633.00
—
—
22
22
—
—
2˝
2-Pole
30 BF230H ■ 633.00 — 22 —
40 BF240H ■ 633.00 — 22 —
50 BF250H ■ 633.00 — 22 —
60 BF260H ■ 633.00 — 22 —
BLE 15
20
BE215 ■
BE220
468.00
468.00
—
—
10
10
—
—
2-Pole
30 BE230 468.00 — 10 —
120/240V AC
40 BE240 ■ 468.00 — 10 —
50 BE250 ■ 468.00 — 10 —
60 BE260 ■ 468.00 — 10 —
BLEH 20
30
BE120H ■ 581.00
BE130H ■ 581.00
22
22
—
—
—
—
1-Pole
6
20 BE220H ■ 848.00 — 22 —
2-Pole
30 BE230H ■ 848.00 — 22 —
40 BE240H ■ 848.00 — 22 —
50 BE250H ■ 848.00 — 22 —
60 BE260H ■ 848.00 — 22 —
BREAKERS
1-Pole 20 B120AF 279.00 10 — —
CIRCUIT
BAFH 15
20
B115AFH 553.00
B120AFH 553.00
22
22
—
—
—
—
1-Pole
HID Lighting
BL 15
20
B115HID ■ 38.00
B120HID 38.00
10
10
—
—
—
—
1-Pole
30 B130HID ■ 38.00 10 — —
BL 15
20
B215HID ■ 81.00
B220HID 81.00
—
—
10
10
—
—
2-Pole
30 B230HID ■ 81.00 — 10 —
Switching Neutrals
BG 15 BG215 ■ 105.00 10 —
—
—
—
2 Wire 20 BG220 ■ 105.00 10
Common Trip 30 BG230 ■ 105.00 10 — —
BG
BG 15 BG315 ■ 158.00 —
—
10 —
—
3 Wire 20 BG320 ■ 158.00 10
Common Trip 30 BG330 ■ 158.00 — 10 —
6/15
Molded Case Circuit Breakers
Selection
BQD 100A Frame Panelboard Mounting Circuit Breakers
BQD
1-Pole 2-Pole 3-Pole
480Y/277V AC–
277V AC–125V DC 125/250V DC 480Y/277V AC
Continuous
Current Rating Catalog Catalog Catalog
@ 40°C Number Number Number
15 BQD115
105.00 BQD215 258.00 BQD315 459.00
20 BQD120
105.00 BQD220 258.00 BQD320 459.00
25 BQD125 105.00 BQD225 258.00 BQD325 459.00
30 BQD130 105.00 BQD230 258.00 BQD330 459.00
35 BQD135 105.00 BQD235 258.00 BQD335 459.00
40 BQD140 105.00 BQD240 258.00 BQD340 459.00
45 BQD145■ 105.00 BQD245 258.00 BQD345 459.00
50 BQD150 105.00 BQD250 258.00 BQD350 459.00 BQD, BQD6
60 BQD160 105.00 BQD260 258.00 BQD360 459.00
70 BQD170■ 221.00 BQD270 526.00 BQD370 625.00
80 BQD180■ 221.00 BQD280 526.00 BQD380 625.00
90 BQD190 221.00 BQD290 526.00 BQD390 625.00
100 BQD1100■ 221.00 BQD2100 526.00 BQD3100 625.00
BQD6 CSA Certified
1-Pole 2-Pole 3-Pole
347V AC 600/347V AC 600/347V AC
Continuous
Current Rating Catalog Catalog Catalog
@ 40°C Number Number Number
15 BQD6115 105.00 BQD6215 258.00 BQD6315 459.00
20 BQD6120 105.00 BQD6220 258.00 BQD6320 459.00 BQD, BQD6
25 BQD6125■ 105.00 BQD6225■258.00 BQD6325■ 459.00
30 BQD6130 105.00 BQD6230 258.00 BQD6330 459.00
35 BQD6135■ 105.00 BQD6235■258.00 BQD6335■ 459.00 Shipping Weights
40 BQD6140 105.00 BQD6240 258.00 BQD6340 459.00
Number of Number per Shipping
45 BQD6145■ 105.00 BQD6245■258.00 BQD6345■ 459.00
50 BQD6150 105.00 BQD6250 258.00 BQD6350 459.00 Poles Carton Weight (lbs.) (ea.)
60 BQD6160 105.00 BQD6260 258.00 BQD6360 459.00 1 1/12/48 1.6
70 BQD6170 221.00 BQD6270 526.00 BQD6370 625.00 2 1/6/24 1.2
3 1/4/16 2.0
Interrupting Ratings
RMS Symmetrical Amperes (KA) Lugs For 60/70°C Wire
Volts AC Volts DC BQD – Load End Only
Number
Breaker of 480/ 600/
6
Control Voltage Shunt Trip Shunt Trip and Auxiliary Switch Combinations
Catalog Catalog
V AC V DC Number Number
120 — BQDST120 569.00 BQDST120AAS▲ 802.00
240 — BQDST240▲ 569.00 BQDST240AAS▲ 802.00
277 — BQDST277▲ 569.00 BQDST277AAS▲ 802.00
480 — BQDST480▲ 569.00 BQDST480AAS▲ 802.00
600 — BQDST600▲ 569.00 BQDST600AAS▲ 802.00
— 12 BQDST12▲ 569.00 BQDST12DAS▲ 802.00
— 24 BQDST24▲ 569.00 BQDST24DAS▲ 802.00
— 48 BQDST48▲ 569.00 BQDST48DAS▲ 802.00
— 125 BQDST125▲ 569.00 BQDST125DAS▲ 802.00
Maximum Voltage Auxiliary Switch Alarm Switch Alarm and Auxiliary Switch Combination
Catalog Catalog Catalog
AC DC Number Number Number
240 125 BQDA1▲ 42.00BQDBA▲ BQDA1BA 483.00
240 125 BQDA2▲ 83.00—
For inches / millimeters conversion, SWD rated for switching 277V AC fluorescent lighting. HACR rated.
see Application Data section. HID rated at 277V AC.
■ Built to order. Allow 2–3 weeks for delivery. Not suitable for 3 phase delta 480V and 600V
Accessories pages 6/75 to 6/80
▲ Built to order. Allow 6–8 weeks for delivery. applications.
6/16
Molded Case Circuit Breakers
SELECTION
BQ 125A Frame
Ordering Instructions
All BQ circuit breakers are supplied with load side lugs. All standard circuit breakers are calibrated for 40°C maximum
ambient application.
6
090 — BQ2B090H 291.00 — BQ3B090H ■ 485.00
100 — BQ2B100H 291.00 — BQ3B100H 485.00
BREAKERS
030 HB1B030■ 101.00 HB2B030■247.00 — HB3B030■429.00
CIRCUIT
040 HB1B040■ 118.00 HB2B040■302.00 — HB3B040■522.00
050 HB1B050■ 118.00 HB2B050■302.00 — HB3B050■522.00
060 — - HB2B060■302.00 — HB3B060■522.00
070 — -- HB2B070■494.00 — HB3B070■558.00
080 — -- — — HB3B080■656.00
090 — -- HB2B090■558.00 — HB3B090■656.00
100 — -- HB2B100■558.00 — HB3B100 656.00
BQ/BQH/HBQ
Internal Accessories (Factory installed only)
Auxiliary Switches
Control Voltage Shunt Trip 1A and 1B
AC DC Suffix Suffix
120V ...00S01 ...A01■
■ Built to order. Allow 3–4 weeks for delivery. For 400 cycle CSA Certified / UL Listed devices, add “Y”
Interrupting Ratings page 6/6
suffix to catalog number. Add 25% to list price. 5000A
CSA Certified / UL Listed for frequent switching
interrupting rating.■ Accessories pages 6/75 to 6/80
applications (SWD). 120V AC fluorescent lighting. UL Listed for use on 3 phase grounded “B” systems– Modifications page 6/75
HCAR rated.
5000A IR for this application.
6/17
Molded Case Circuit Breakers
Selection
DIN Rail Mounted Circuit Breakers
Type BQXD — BQ Breaker with DIN Rail Mounting - UL Listed only
1-Pole 2-Pole Interrupting Ratings (KA)
(RMS Symmetrical Amperes)
Continuous Volts AC
Current Catalog Catalog
Rating Number Number 120/240
15 BQ1B015QLD 30.00 BQ2B015QLD 68.00
20 BQ1B020QLD 30.00 BQ2B020QLD 68.00
25 BQ1B025QLD 30.00 BQ2B025QLD 68.00
30 BQ1B030QLD 30.00 BQ2B030QLD 68.00 10
35 BQ1B035QLD 30.00 BQ2B035QLD 68.00 2-Pole DIN Rail mtd
40 BQ1B040QLD 30.00 BQ2B040QLD 68.00
(UL listed only)
45 BQ1B045QLD 30.00 BQ2B045QLD 68.00
50 BQ1B050QLD 30.00 BQ2B050QLD 68.00
60 BQ1B060QLD 30.00 BQ2B060QLD 68.00
Shipping Weights
Shipping
Number of Number Per Weight (lbs.)
Poles Carton/Master Master
BQ
1 (15–50A) 6/72 23
1 (55–70A) 6/66 23
1 (15–70A, 22 and 65K A IR) 6/66 23
2 (15–50A) 3/36 24 Dimensions (inches)
2 (60–125A) 3/33 23 Breaker
2 (15–100A, 22 and 65K A IR) 3/33 24 Type Amperes L D1 D2
2 (15–100A, 240V) 3/33 23 BQ, BQH 15–50 33⁄4 23⁄8 3
3 (15–100A) 2/22 23 BQ, BQH 55–125 4 23⁄8 3
BQH and HBQ HBQ 15–125 4 23⁄8 3
BQXD 15–60 41⁄2 23⁄8 3
1 6/66 23
2 3/33 24
3 2/22 24
Enclosures
Circuit Cables Lug
Type Catalog Number Breaker Per Wire Range Catalog
1 EB3100S Amp. Rtg. Lug AWG Number
3R WB31006.00 Line Side
1 #14–#6 Cu
15–40 TC1Q1 13.90
1 #12–#6 Al
1 #8–#1 Cu
50–100 TA1Q1 12.20
BREAKERS
CIRCUIT
1 #6–#1/0 Al
Load Side
1 #14–#10 Cu
15–20
1 #14–#10 Al
1 #14–#6 Cu
25–35
1 #14–#6 Al
1 #8–#6 Cu Connectors are
40–50
1 #8–#4 Al Supplied with
1 #8–#4 Cu Circuit Breaker
55–70
1 #8–#2 Al
1 #4–#1/0 Cu
80–100
1 #2–#1/0 Al
1 #2–#1/0 Cu
110–125
1 #1/0–#2/0 Cu
For inches / millimeters conversion, Surfacemounted indoor. If flush mounting is required, Package of 6 connectors.
see Application Data section. replace suffix “S” in catalog number with suffix “F”. BQXD uses TA1Q1 or TC1Q1 lugs on both line and load
Discount Schedule B. ends.
Does not include circuitbreaker. Order circuit breaker
■ Built to order. Allow 3–4 weeks for delivery.
separately.
Terminals
are CSA Certified / UL Listed for 60°/75°C Neutral included in enclosure.
Enclosure will not accept circuit breakers with shunt trips
Accessories pages 6/75 to 6/80
conductors.
or auxiliary switches installed.
Connector has steel construction.
6/18
Molded Case Circuit Breakers
SELECTION / DIMENSIONS
QJ 225A Frame
Type QJ2 Ordering Information
2-Pole 3-Pole Load side TA1Q300 lugs are mounted and
included when circuit breaker is ordered.
Continuous 240V AC 240V AC For line and load lugs (TA1Q300) installed at
Current Rating Catalog Catalog no additional charge, add suffix “L” to catalog
@ 40°C Number Number number.
060 QJ22B060■374.00 QJ23B060 989.00 50°C Calibration - See page 6-72.
070 QJ22B070■377.00 QJ23B070 989.00 400HZ. - See page 6-72.
080 QJ22B080■377.00 QJ23B080 989.00
090 QJ22B090■377.00 QJ23B090 989.00
100
110
QJ22B100 377.00
QJ22B110■377.00
QJ23B100
QJ23B110
989.00
989.00
Shipping Weights
125 QJ22B125377.00 QJ23B125 989.00 QJ2, QJH2, QJ2H, HQJ2H
150 QJ22B150377.00 QJ23B150 989.00 Number of Number per Shipping
175 QJ22B175 377.00 QJ23B175 989.00 Poles Carton Weight (lbs.)
200 QJ22B200377.00 QJ23B200 989.00
225 QJ22B225377.00 QJ23B225 989.00 2 10 30
3 10 41
Type QJH2
6
Type HQJ2H
100 — HQJ23B100H 998.00
110 — HQJ23B110H 1998.00
125 — HQJ23B125H 998.00
150 — HQJ23B150H 1998.00
175 — HQJ23B175H 998.00
200 — HQJ23B200H 1998.00
225 — HQJ23B225H 998.00
BREAKERS
CIRCUIT
QJ2
Internal Accessories (Factory installed only) 3-pole only .
Add suffix to catalog number.
Auxiliary Switches Shunt Trip and
Control Voltage Shunt Trip 1A and 1B 2A and 2B 1A and 1B Auxiliary Switch
AC DC Suffix Suffix Suffix Suffix
120/240 — 00S01■ A01■ A02■ 01S01■
— 24 00S07■ A01■ A02■ 01S07■
— 25 00S11■ A01■ A02■ 01S11■
6/19
Molded Case Circuit Breakers
Selection
CQD 100A Frame
Type CQD (Cable In - Cable Out) DIN Rail Mount Shipping Weights
1-Pole 2-Pole 3-Pole Number of Number per Shipping
277V AC 480Y/277V AC Poles Carton Weight lbs. (kg)
Continuous 125V DC 125/250V DC 480Y/277V AC 1 1 0.5 (0)
Current Rating Catalog Catalog Catalog 2 1 1.0 (0)
@ 40°C Number Number Number 3 1 1.5 (1)
115 CQD115 114.00 CQD215 272.00 CQD315485.00
120 CQD120 114.00 CQD220 272.00 CQD320485.00
125 CQD125 114.00 CQD225 272.00 CQD325485.00 Lugs For 60/75°C Wire
130 CQD130 114.00 CQD230 272.00 CQD330485.00 Amps Wire Size
135 CQD135■114.00 CQD235■272.00 CQD335485.00 15–40 #14–#6 AWG Cu
140 CQD140■114.00 CQD240 272.00 CQD340485.00 #12–#6 AWG Al
145 CQD145■114.00 CQD245■272.00 CQD345■485.00
150 CQD150■114.00 CQD250 272.00 CQD350485.00 45–100 #8–#1 AWG Cu
160 CQD160■114.00 CQD260 272.00 CQD360485.00 #6–#1/0 AWG Al
170 CQD170■229.00 CQD270 542.00 CQD370657.00
180 CQD180■229.00 CQD280 542.00 CQD380657.00
190 CQD190■229.00 CQD290■542.00 CQD390657.00
100 CQD1100■229.00 CQD2100 542.00 CQD3100657.00
Interrupting Ratings
6
CQD
1
2
65
—
—
65
14
14
—
—
14
—
—
14
Shunt Trip and Auxiliary Switch
(UL)
3 — 65 14 — — — Shunt Trip Voltage CQD, CQD6, NGG
1 65 — — 14 14 — AC DC Catalog Number
CQD6
2 — 65 — 14 — 14
(CSA) 120 — CQDST120AAS▲
BREAKERS
CIRCUIT
3 — 65 — 14 — —
240 — CQDST240AAS▲
277 — CQDST277AAS▲
Shunt Trip Auxiliary Switch 480 — CQDST480AAS▲
Control Voltage CQD, CQD6, NGG Maximum Number 600 — CQDST600AAS▲
V AC V DC Catalog Number Voltage ofCQD, CQD6, NGG — 012 CQDST12DAS▲
120 — CQDST120569.00 AC DC Contacts Catalog Number
— 024 CQDST24DAS▲
240 — CQDST240▲ 240 125 1A–1B CQDA1
277 — CQDST277▲0 240 125 2A–2B CQDA2 — 048 CQDST48DAS▲
480 — CQDST480▲00 — 125 CQDST125DAS▲
600 — CQDST600 Alarm Switch
— 012 CQDST12 Maximum
— 024 CQDST24 Voltage Alarm and Auxillary Switch Combinations
— 048 CQDST48 CQD, CQD6, NGG
— 125 CQDST125 AC DC Catalog Number For Breaker Catalog #
240 125 CQDBA CQD, CQD6, NGG CQDA1BA▲
6/20
Sentron Thermal Magnetic
and
Electronic Circuit Breakers
6
BREAKERS
CIRCUIT
6/21
Molded Case Circuit Breakers
Selection
ED 125A Frame Sentron Series
Ordering Instructions
All ED Frame Sentron circuit breakers are supplied with load side lugs. If line side lugs are required, add “L” suffix to catalog number, and
breaker will be supplied with line lugs installed at no charge.
50°C Calibration, 400HZ - see page 6-72. All ED frame circuit breakers may be reverse connected.
6/22
Molded Case Circuit Breakers
Selection
ED 125A Frame Sentron Series
Type HED4 Black Label FIGURE1 - ED, HED
1-Pole 2-Pole 3-Pole
277V AC 125V DC 480V AC 250V DC 480V AC D
Continuous
Current Rating Catalog Catalog Catalog
@ 40° C Number Number Number
D1
015 HED41B015 355.00 HED42B015 831.00 HED43B015 1020.00
020 HED41B020 355.00 HED42B020 831.00 HED43B020 1020.00 H
025 HED41B025 355.00 HED42B025■ 831.00 HED43B025 1020.00
030 HED41B030 355.00 HED42B030 831.00 HED43B030 1020.00
035 HED41B035■ 355.00 HED42B035■ 831.00 HED43B035 1020.00
040 HED41B040 355.00 HED42B040 831.00 HED43B040 1020.00
045 HED41B045■ 355.00 HED42B045■ 831.00 HED43B045 1020.00
W3
050 HED41B050■ 355.00 HED42B050 831.00 HED43B050 1020.00 W1 W2
060 HED41B060■ 355.00 HED42B060■ 831.00 HED43B060 1020.00
1 POLE 2 POLE 3 POLE
070 HED41B070■ 402.00 HED42B070■ 957.00 HED43B070 1098.00
080 HED41B080■ 402.00 HED42B080■ 957.00 HED43B080 1098.00 FIGURE 2 - CED (3 Pole shown)
090 HED41B090■ 402.00 HED42B090■ 957.00 HED43B090 1098.00
100 HED41B100■ 402.00 HED42B100■ 957.00 HED43B100 1098.00
D
110 — HED42B110■ 1946.00 HED43B110 2244.00
125 — HED42B125■ 1946.00 HED43B125 2244.00
D1
Fuseless Current Limiting
Type CED6 Red Label H
2-Pole 3-Pole
Continuous
600V AC, 250V DC 600V AC, 500V DC
Current
Rating Catalog Catalog
@ 40°C Number Number
015 CED62B015 2465.00 CED63B015 2862.00
020 CED62B020■ 2465.00 CED63B020 2862.00
025 — — — W2, W3
030 CED62B030■ 2465.00 CED63B030 2862.00
035 — — —
040 CED62B040■ 2465.00 CED63B040 2862.00
045 — — — — Dimensions (in inches)
050 CED62B050■ 2465.00 CED63B050 2862.00 Breaker Type W1 W2 W3 H D D1
060 CED62B060■ 2465.00 CED63B060 2862.00
Figure 1
070 CED62B070■ 2465.00 CED63B070 2862.00 ED2, ED4, ED6, HED4, 1 2 3 6.35 3.92 4.56
080 CED62B080■ 2465.00 CED63B080 2862.00 ED6 ETI
090 CED62B090■ 2465.00 CED63B090 2862.00 Figure 2
100 CED62B100■ 2465.00 CED63B100 2862.00 — 2 3 9.58 3.92 4.56
CED6, CED6 ETI
110 — CED63B110■ 4368.00
6
125 CED62B125■ 3698.00 CED63B125 4368.00
Interrupting Ratings
CSA C22.2 / UL 489 AIR (File #E10848) IEC 947-2
RMS Symmetrical Amperes (KA) Volts AC (50/60Hz)
Breaker Volts AC Volts DC 220/240 380/415 500
BREAKERS
Type 120 240 277 347 480 600 125 250 500 lcu lcs lcu lcs lcu lcs
CIRCUIT
ED2 (1-P) 010 — — — — — 05 — — — — — — — —
ED2 (2, 3-P) — 010 — — — — — 05 (2-P) — — — — — — —
ED4 (1-P) 065 — 22 — — — 30 — — — — — — — —
ED4 (2, 3-P) — 065 — — 018 — — 30 (2-P) — — — — — — —
ED6 (1P) — — — 30 — — — — — — — — — — —
ED6 (2, 3-P) — 065 — — 025 018 — 30 (2-P) 18 (3-P) 65 17 35 9 18 5
HED4 (1-P)
(15–30A) 100 — 65 — — — 30 — — — — — — — —
HED4 (1-P)
(35–100A) 100 — 25 — — — 30 — — — — — — — —
HED4 (2, 3-P) — 100 — — 042 — 30 (2-P) — — — — — —
CED6 (2, 3-P) — 200 — — 200 100 — 30 (2-P) 50 (3-P) — — — — — —
■ Built to order. Allow 2–3 weeks for delivery. HED4 type circuit breakers meet the CSA / UL criteria for Single Pole 15-30A 30KA @ 347V
“current limiting” at 240V AC. 35-100A 18KA @ 347V
SWD rated. ED6-ETI,
CED6-ETI, see page 6-56 for ordering HACR
rated.
When wired as shown on page 6-2, this circuit breaker information.
is CSA Certified / UL listed and rated for use on 500V DC
ungrounded UPS systems.
6/23
Molded Case Circuit Breakers
Selection
SELECTION
Internal Accessories
Accessories for: Shunt Trip Combinations
1 Shunt Trip
ED 125A Frame Control 1 Shunt Trip and 1 Auxiliary Switch 1 Shunt Trip and 1 Shunt Trip and 2
Voltage 1 Shunt Trip 1 Auxiliary Switch and 1 Alarm Switch 1 Alarm Switch Auxiliary Switches
AC DC Catalog Number Catalog Number Catalog Number Catalog Number Catalog Number
024 — S17ED60 — — — —
048 — S18ED60 — — — —
120 — S01ED60 S01ED62A S01ED62AB S01ED62B S01ED62AA
208 — — S02ED62A▲ S02ED62AB▲ S02ED62B▲ S02ED62AA▲
240 — S03ED60 S03ED62A S03ED62AB S03ED62B▲ S03ED62AA▲
277 — S15ED60▲ S15ED64A▲ S15ED64AB▲ S15ED64B▲ —
480 — S04ED60 S04ED64A▲ S04ED64AB▲ S04ED64B▲ —
— 012 S16ED60▲ S16ED62A▲ — — —
— 024 S07ED60 S07ED62A S07ED62AB▲ S07ED62B▲ S07ED62AA▲
— 048 S09ED60▲ S09ED62A▲ S09ED62AB▲ S09ED62B▲ S09ED62AA▲
— 125 S11ED60▲ S11ED62A▲ S11ED62AB▲ S11ED62B▲ S11ED62AA▲
— 250 S13ED60▲ S13ED62A▲ S13ED62AB▲ S13ED62B▲ S13ED62AA▲
Combinations
Available only when ordered together.
Only one module can be added to a Undervoltage Trip Combinations
breaker. Additional accessories, which
1 Undervoltage Trip
always attach to the left pole, cannot be
1 Undervoltage and 1 Auxiliary 1 Undervoltage 1 Undervoltage
added to the combination later. Control 1 Undervoltage Trip and Switch and Trip and Trip and 2
Voltage Trip 1 Auxiliary Switch 1 Alarm Switch 1 Alarm Switch Auxiliary Switches
AC DC Catalog Number Catalog Number Catalog Number Catalog Number Catalog Number
Equipment 120 — U01ED60 U01ED62A U01ED62AB▲ U01ED62B▲ U01ED62AA▲
Ground Sensing 208 — U02ED60▲ U02ED62A▲ U02ED62AB▲ U02ED62B▲ U02ED62AA▲
240 — U03ED60 U03ED62A▲ U03ED62AB▲ U03ED62B▲ U03ED62AA▲
A field addable kit containing 30mA or 277 — U16ED60▲ U16ED64A▲ U16ED64AB▲ U16ED64B▲ —
5 mA ground fault accessory module, 480 — U06ED60▲ U06ED64A▲ U06ED64AB▲ U06ED64B▲ —
current transformer with 24 inch leads, 600 — U08ED60▲ — — — —
and current transformer mounting — 024 U13ED60 U13ED62A▲ U13ED62AB▲ U13ED62B▲ U13ED62AA▲
equipment. Current transformer to — 048 U14ED60▲ U14ED62A▲ U14ED62AB▲ U14ED62B▲ U14ED62AA▲
— 125 U10ED60▲ U10ED62A▲ U10ED62AB▲ U10ED62B▲ U10ED62AA▲
mount in gutter of lighting panel or any — 250 U12ED60▲ U12ED62A▲ — — U12ED62AA▲
control panel. Accessory module
operates from separate 120V control
power source. Auxiliary and Alarm Switch Combinations
Both 30MA and 5MA devices are Maximum 1 Auxiliary 1 Alarm Switch Alarm Switch and 2 Auxiliary 1 Alarm Switch and
equipment protection devices only. Do Voltage Switch* 1 Auxiliary Switch Switches 2 Auxiliary Switches
6
not use for personnel protection. AC DC Catalog Number Catalog Number Catalog Number Catalog Number Catalog Number
240 250 A01ED62 B00ED62 A01ED62B A02ED62 A02ED62B
480 — A01ED64 B00ED64 A01ED64B — —
— 12 A01EDLV* 306.00 Gold Plated Contacts—for PLC use
6/24
Molded Case Circuit Breakers
Selection
FD 250A Frame Sentron Series
Type FXD6-A Blue Label Ordering Information
Non-Interchangeable Trip (Assembled Circuit Breaker – Without Lugs) Complete Breaker Unassembled with
Continuous 2-Pole 3-Pole Lugs
Current Rating Catalog Catalog Prices of FD6, HFD6, and HHFD6
@ 40°C Number Number breakers includes frame, trip and
70 FXD62B070■ 1610.00 FXD63B0702036 both line and load lugs (TA1FD350).
80 FXD62B080■ 1610.00 FXD63B0802036.
90 FXD62B090■ 1610.00 FXD63B0902036. When ordered by these catalog
100 FXD62B100 1610.00 FXD63B1002036. numbers, the customer will receive
110 FXD62B110■ 1610.00 FXD63B1102036.
125 FXD62B125 1610.00 FXD63B1252036. the frame, trip, and lugs separately
150 FXD62B150 1610.00 FXD63B1502036.00 packaged. For applications requiring
175 FXD62B175 1610.00 FXD63B175236.00 different lugs, order individual items
200 FXD62B200 1610.00 FXD63B200203
225 FXD62B225 1610.00 FXD63B225 .00 as needed.
250 FXD62B250 2738.00 FXD63B250 Complete Breaker Assembled
without Lugs
Type FD6-A Blue Label
Prices of FXD6, HFXD6, HHFXD6,
Interchangeable Trip and CFD6 includes frame with non-
Complete Breaker interchangeable trip unit installed
Continuous Unassembled with Lugs Frame Only Trip Unit Only only. Order required lugs separately.
Current Rating Catalog Catalog Catalog
@ 40°C Number Number Number For line and load lugs (TA1FD350A)
installed, add suffix “L” to catalog
2-Pole 600V AC, 250V DC number (add 2 times list price of
70 FD62B070■1695.20 FD62T070■ 839.00 lugs for each pole).
80 FD62B080■1695.20 FD62T080■ 839.00
90 FD62B090■1695.20 FD62T090■ 839.00 50°C Applications see page 6-72.
100 FD62B100■1695.20 FD62T100■ 839.00
110 FD62B110■1695.20 FD62T110■ 839.00 400 Hz Applications see page 6-72.
125 FD62B125■1695.20 FD62F250 777.00 FD62T125■ 839.00
150 FD62B150■1695.20 FD62T150■ 839.00
175
200
FD62B175■1695.20
FD62B200■1695.20
FD62T175■ 839.00
FD62T200■ 839.00
Lugs For 75°C Wire
225 FD62B225■1695.20 FD62T225■ 839.00 Catalog Wire
250 FD62B250■2824.20 FD62T250■1968.00 Number Range
3-Pole 600V AC, 500V DC TA1FD350A
#6—350 kcmil Cu
19.80
70 FD63B070■2159.80 FD63T070■1035.00 #4—350 kcmil Al
80 FD63B080■2159.80 FD63T080■1035.00 TC1FD350 #6—350 kcmil Cu 31.00
90 FD63B090■2159.80 FD63T090■1035.00 Compression Lug
100 FD63B100 2159.80 FD63T100 1035.00
110 FD63B110■2159.80 FD63T110■1035.00 CCF250 350 kcmil Cu/Al 45.50
125 FD63B125 2159.80 FD63F2501006.00 FD63T125 1035.00
Enclosures
6
150 FD63B150 2159.80 FD63T150 1035.00
175 FD63B175 2159.80 FD63T175 1035.00
200 FD63B200 2159.80 FD63T200 1035.00 Catalog
225 FD63B225 2159.80 FD63T225 1035.00 Type Number
250 FD63B250 3320.80 FD63T250 2196.00 1 F6N1S(F) 164.00
Interrupting Ratings 3R
4-4X
F6N3R
FD6SS4
542.00
4221.00
RMS Symmetrical Amperes (KA) 7-9 EC2 4306.00
12 F6N12 366.00
CSA / UL 489 AIR (File E10848) IEC 947-2
BREAKERS
Neutral N250 128.00
CIRCUIT
Volts AC (50/60Hz) Volts DC Volts AC (50/60Hz)
Breaker 240 480 600 250 500 220/240 380/415 500
Type lcu lcs lcu lcs lcu lcs
FXD6-A, FD6-A 65 35 22 30 (2-P) 18 (3-P) 65 33 35 9 20 10
HFXD6 , HFD6 100 65 25 30 (2-P) 25 (3-P) 100 50 65 33 42 21
HHFD6 , HHFXD6 200 100 25 — — 200 100 100 50 65 33
CFD6 200 200 100 50 (2-P) 50 (3-P) — — — — — —
6/25
Molded Case Circuit Breakers
SELECTION / DIMENSIONS
FD 250A Frame Sentron Series
Type HFD6 , Type HFXD6 Black Label
Interchangeable Trip
Complete Breaker
D1
Continuous Unassembled with Lugs Frame Only Trip Unit Only
Current Rating Catalog Catalog Catalog
@ 40°C Number Number Number
L
2-Pole 600V AC, 250V DC (3 Pole Width)
070 HFD62B070■3716.20 FD62T070■839.00 L
080 HFD62B080■3716.20 FD62T080■839.00
090 HFD62B090■3716.20 FD62T090■839.00
100 HFD62B100■3716.20 FD62T100■839.00
110 HFD62B110■3716.20 FD62T110■ 839.00
125 HFD62B125■3716.20 HFD62F250 2798.00 FD62T125■839.00
150 HFD62B150■3716.20 FD62T150■839.00
175 HFD62B175■3716.20 FD62T175■839.00 W
D
D
W
200 HFD62B200■3716.20 FD62T200■839.00
225 HFD62B225■3716.20 FD62T225■839.00 Figure 1 Figure 2
250 HFD62B250■4845.20 FD62T250■
3-Pole 600V AC, 500V DC Dimensions (in inches)
070 HFD63B070■4519.80 FD63T070■ 1035 Breaker D1
080 HFD63B080■4519.80 FD63T080■ 1035 Type W L D (to
090 HFD63B090■4519.80 FD63T090■ 1035 handle)
100 HFD63B100 4519.80 FD63T100 1035 Figure 1
110 HFD63B110■4519.80 FD63T110■ 1035 FXD6-A, FD6-A,
125 HFD63B125 4519.80 HFD63F250 3366.00 FD63T125 1035 HFD6, HFXD6, 4.50 09.50 4 5.25
150 HFD63B150 4519.80 FD63T150 103 HHFD6, FD6-ETI
175 HFD63B175 4519.80 FD63T175 103
Figure 2
200 HFD63B200 4519.80 FD63T200 103
CFD6,
225 HFD63B225 4519.80 FD63T225 1035 4.50 14.25 4 5.25
CFD6-ETI
250 HFD63B250 5680.80 FD63T250
■ Built to order. Allow 3–4 weeks for delivery. breaker, change prefix identifier from HFD6 to HFXD6. Type HFXD6, HFD6, HHFD6, HHFXD6 meet the CSA
Price equals frame and trip prices combined, e.g. price Certified / UL criteria for “Current Limiting” at 240 VAC
When
wired as shown on page 6-3, this circuit breaker of HFXD63B250 equals price of HFD63F250 plus price of and 480V AC.
is CSA Certified / UL listed and rated for use on 500V DC FD63T250. Order lugs separately. FXD6, ETI, CFD6, ETI — See page 6-55 for
ungrounded UPS systems. Type HFXD6, HHFXD6, CFD6 are CSA Certified / UL ordering information.
For non-interchangeable trip 3-pole HFD6 type circuit Listed for reverse feed applications. HACR rated.
6/26
Molded Case Circuit Breakers
SELECTION
Selection
Internal Accessories
Shunt Trip Combinations
Accessories for: Control Voltage 1 Shunt Trip
FD 250A Frame AC DC Catalog Number
024 — S17FD60
120 — S01FD60
240 — S03FD60
277 — S15FD60▲
480 — S04FD60
600 — S06FD60▲
— 012 S16FD60▲
— 024 S07FD60
— 048 S09FD60▲
— 125 S11FD60
— 250 S13FD60▲
6
Alarm Switch Combinations
Maximum 1 Alarm Switch and
Voltage 1 Alarm Switch 1 Auxiliary Switch
AC DC Catalog Number Catalog Number
480 250 B00FD64 242.00C01FD64 483.00
BREAKERS
CIRCUIT
6/27
Molded Case Circuit Breakers
Selection
JD 400A Frame Sentron Series
Type JXD2-A Ordering Information
240V AC, 250V DC Blue Label
Complete Breaker Unassembled
Non-Interchangeable Trip (Assembled Circuit Breaker without Lugs) with Lugs
Continuous 2-Pole (3 Pole Width) 3-Pole Prices of JD6, HJD6, and HHJD6
Current Rating Catalog Catalog breakers include frame, trip and
@ 40°C Number Number both line and load lugs (TA2J6500).
200 JXD22B200■2277.00 JXD23B200 2767.00 When ordered by these catalog
225 JXD22B225■2277.00 JXD23B225 2767.00 numbers, the customer will receive
250 JXD22B250■2277.00 JXD23B250 2767.00
300 JXD22B3002277.00 JXD23B300 2767.00 the frame, trip, and lugs separately
350 JXD22B350■2277.00 JXD23B350 2767.00 packaged. For applications
400 JXD22B4002277.00 JXD23B400 2767.00 requiring different lugs, order
individual items as needed.
Type JXD6-A Complete Breaker Assembled
600V AC, 500V DC Blue Label without Lugs
Non-Interchangeable Trip (Assembled Circuit Breaker without Lugs) Prices of JXD6, HJXD6, HHJXD6,
200 JXD62B200■2847.00 JXD63B2003366.00
and CJD6 include frame with non-
225 JXD62B225■2847.00 JXD63B2253366.00 interchangeable trip unit installed
250 JXD62B250■2847.00 JXD63B2503366.00 only. Order required lugs separately.
300 JXD62B3002847.00 JXD63B3003366.00 For line and load lugs (TA2J6500)
350 JXD62B350■2847.00 JXD63B3503366.00 installed, add suffix “L” to catalog
400 JXD62B4002847.00 JXD63B4003366.00
number (add 2 times list price of
Type JD6-A Blue Label lugs for each pole).
100% Rated
Interchangeable Trip Types JXD6 and HJXD6 breakers
Complete Breaker are available with 100% ratings.
Continuous Unassembled with Lugs Frame Only Trip Unit Only To order add suffix “H” to catalog
Current Rating Catalog Catalog Catalog number, and 10% to list price.■
@ 40°C Number Number Number
100% rated JD breakers require
2-Pole 600V AC, 250V DC (3 Pole Width) the use of 90°C Cu cable and lugs
200 JD62B200■2958.00 JD62T200■1662.00 TC1J6600 or TC2J6500.
225 JD62B225■2958.00 JD62T225■1662.00 50°C Applications see page 6-72.
250 JD62B250■2958.00 JD62T250■1662.00
300 JD62B300■2958.00 JD62F400 1184.00 JD62T300■1662.00 400Hz Applications see page 6-70.
350 JD62B350■2958.00 JD62T350■1662.00
400 JD62B400 2958.00 JD62T400 1662.00
3-Pole 600V AC, 500V DC
200 JD63B200 3534.00 JD63T200 1851.00
225 JD63B225 3534.00 JD63T225 1851.00
250 JD63B250 3534.00 JD63T250 1851.00
6
■ Built to order. Allow 3-4 weeks for delivery. HHJD6 type circuit breakers meet the CSA / UL criteria
for “current limiting” at 240 and 480V AC.
Type
JXD6 circuit breakers are UL Listed for reverse HACR rated.
feed applications. Note: J
D frame qualified to UL489 supplement B “NAVAL.” Modifications page 6-72
Whenwired as shown on page 6-3, this circuit breaker See page 6-72 for additional information. Accessories pages 6-32 and 6-75 to 6-80
is CSA Certified / UL listed and rated for use on 500V DC
ungrounded UPS systems only.
See Note: A, page 6-69.
6/28
Molded Case Circuit Breakers
Selection
JD 400A Frame Sentron Series
Type HJD6-A, HJXD6-A Black Label
Interchangeable Trip
Complete Breaker
D1
Continuous Unassembled with Lugs Frame Only Trip Unit Only
@ 40°C Number Number Number
L
2-Pole 600V AC, 250V DC (3 Pole Width)
200 HJD62B200■4851.00 JD62T200■1662.0 L
225 HJD62B225■4851.00 JD62T225■1662.0
250 HJD62B250■4851.00 HJD62F400■3077.00 JD62T250■1662.0
300 HJD62B300■4851.00 JD62T300■1662.0
350 HJD62B350■4851.00 JD62T350■1662.0
400 HJD62B400■4851.00 JD62T400 1662.00
W
D
W
D
3-Pole 600V AC, 500V DC
Figure 1 Figure 2
200 HJD63B200 5845.00 JD63T200 1851.00
225
250
HJD63B225 5845.00
HJD63B250 5845.00
JD63T225 1851.00
Dimensions (in inches)
HJD63F400 3826.00 JD63T250 1851.00
300 HJD63B300 5845.00 JD63T300 1851.00 To
350 HJD63B350 5845.00 JD63T350 1851.00 Breaker Handle
400 HJD63B400 5845.00 JD63T400 1851.00 Type W L D D1
6
Neutral W60992 348.00
Fuseless Current Limiting Red Label
Shipping Weights
Non-Interchangeable Trip (Assembled Circuit Breakers Without Lugs)
Number of Number per Shipping
2-Pole 3-Pole Poles Carton Weight (lbs.)
Continuous 600V AC/250V DC 600V AC/500V DC JXD2, JXD6, JD6, HJD6, HHJD6
Current Rating Catalog Assembled Breaker (less terminals)
@ 40°C Number 2 1 17.5
BREAKERS
3 1 19.5
200 CJD63B200■7303.
CIRCUIT
225 CJD63B225■7303. JD6, HJD6, HHJD6 Frame Only
250 For 2-pole application CJD63B250■7303. 2 1 14
300 use outside poles of CJD63B300■7303. 3 1 15.5
350 3-pole circuit breaker CJD63B350■7303. JD6 Trip Unit Only
400 CJD63B4007303.00 2 1 03.5
3 1 04
CJD6 Complete Assembled Breaker
(less terminals)
2 1 29.5
3 1 31.5
For inches / millimeters conversion, Fornon-interchangeable 3-pole HJD6 or HHJD6 type JXD6-ETI, CJD6-ETI see page 6-55 for ordering information.
see Application Data section. circuit breaker change the prefix identifier to HJXD6 Type HJXD6, HHJXD6 Circuit Breakers are CSA Certified /
or HHJXD6. Order lugs separately. UL listed for reverse fed applications.
■ Built to order. Allow 3-4 weeks for delivery.
CE applies to non-interchangeable type HJXD only.
2-pole units available in 3-pole construction. HACR rated.
When wired as shown on page 6-2, this circuit breaker
is CSA Certified / UL listed and rated for use on 500V DC
ungrounded UPS systems only.
6/29
Molded Case Circuit Breakers
SJD 400A Frame Digital Solid State Sentron Sensitrip III
Current Limiting
Ordering Information
Type SJD6(A) Type SHJD6(A) Type SCJD6
Required lugs for Digital Sentron
Blue Label Black Label Red Label Series SJD and SLD frames are sold
as separate items. Separate items –
3-Pole, 600V AC 3-Pole, 600V AC 3-Pole, 600V AC
lugs are suitable for 75° C wire.
Max Max Max
Catalog Current Catalog Current Catalog Current SJD6, SCJD6, SLD6, SCLD6 are
Number Rating Number Rating Number Rating acceptable for reverse connection
SJD69200■ 200 4082.00 SHJD69200■ 200 5812.00 SCJD69200■ 200 7734.00 application.
SJD69300■ 300 4082.00 SHJD69300■ 300 5812.00 SCJD69300■ 300 7734.00 SHJD6 and SHLD6 are not
SJD69400■ 400 4082.00 SHJD69400■ 400 5812.00 SCJD69400■ 400 7734.00
acceptable for reverse connection
SJD69200G■ 200 6530.00 SHJD69200G■ 200 8195.00 SCJD69200G■ 200 10498.00 application.
SJD69300G■ 300 6530.00 SHJD69300G■ 300 8195.00 SCJD69300G■ 300 10498.00
SJD69400G■ 400 6530.00 SHJD69400G■ 400 8195.00 SCJD69400G■ 400 10498.00
SJD69200NT■ 200 5545.00 SHJD69200NT■ 200 7197.00 SCJD69200NT■ 200 9290.00
SJD69300NT■ 300 5545.00 SHJD69300NT■ 300 7197.00 SCJD69300NT■ 300 9290.00
SJD69400NT■ 400 5545.00 SHJD69400NT■ 400 7197.00 SCJD69400NT■ 400 9290.00
SJD69200NGT■ 200 8195.00 SHJD69200NGT■ 200 9941.00 SCJD69200NGT■ 200 12818.00 Shipping Weights
SJD69300NGT■ 300 8195.00 SHJD69300NGT■ 300 9941.00 SCJD69300NGT■ 300 12818.00
SJD69400NGT■ 400 8195.00 SHJD69400NGT■ 400 9941.00 SCJD69400NGT■ 400 12818.00 Breaker Number per Shipping
Type Carton Weight (lbs)
SJD6(A), SLD6(A) 1 20
SHJD6(A),
SJD 400A Frame – 100% Rated
SHLD6(A)
SCJD6, SCLD6
1
1
20
33
Type SJD6A-H Type SJD6(A)-H
Blue Label Black Label Lugs for 75° C Wire
Suffix Cont Long Instan- Short Short Time Ground Ground 400 N04SJD 354.00
Letter Trip Current Time taneous Time Time l2t Fault Fault 500 N05SLD 354.00
Code Type Setting Delay Setting Pick Up Delay Pick Up Pick Up Delay 600 N06SLD 354.00
None LI — — — — —
G LIG — — — Enclosures
NT LSI — —
(For JD frame, excluding SCJD6)
NGT LSIG
Catalog
Interrupting Ratings Type Number
1 J6N1 231.00
Breaker RMS Symmetrical kA CSA / UL 489 (File E10848) 3R J6N3R 1246.00
Type 240V AC 480V AC 600V AC 4–4X LD6SS4 6211.00
SJD6 – SLD6 065 035 025 7, 9 (200–250A) EC4 4306.00
SHJD6 – SHLD6 100 065 035 7, 9 (300–400A) EE 5958.00
SCJD6 – SCLD6 200 150 100 12 J6N12 648.00
Neutral W60992 348.00
6/30
Molded Case Circuit Breakers
Selection
Internal Accessories
Accessories for:
Shunt Trip Combinations
JD 400A Frame 1 Shunt Trip and
LD 600A Frame Control Voltage 1 Shunt Trip 1 Auxiliary Switch
LMD 800A Frame AC DC Catalog Number Catalog Number
6
Maximum 1 Alarm Switch and 1 Alarm Switch and
battery back-up for maintaining trip Voltage 1 Alarm Switch 1 Auxiliary Switch 2 Auxiliary Switches
and max logs. Catalog Catalog Catalog
The SADU reads currents, current AC DC Number Number Number
imbalance, current demand, and trip 480 250 B01JLD64 242.00 A01JLD64B 483.00 A02JLD64B
status.
BREAKERS
CIRCUIT
Breaker Type Desc. Catalog Number
The Ammeter may also be panel or Display Unit SADU
SJD, SLD
door mounted using the SADURMK18 Remote Mounting Kit SADURMK18
remote mounting kit.
Note: Accessory modules can only be added to right ▲ Built to order. Allow 7-9 weeks for delivery.
side pole of solid state SJD and SLD frame circuit
breakers. All accessories on this page are useable
on superseded JD2, JJ6, JL6, HJ6, SJL, LJ6, LL6,
HL6 and SLL circuit breakers.
6/31
Molded Case Circuit Breakers
Selection
LD 600A Frame Sentron Series
Type LXD6-A Blue Label Ordering Information
Non-Interchangeable Trip (Assembled Circuit Breaker without Lugs) Complete Breaker Unassembled
2-Pole (3 Pole Width) 3-Pole with Lugs
Continuous 600V AC 250V DC 600V AC 500V DC Prices of LD6, HLD6, and HHLD6
Current Rating Catalog Catalog breakers include frame, trip, and
@ 40°C Number Number both line and load lugs (TA2J6500).
450 LXD62B450■4376.00 LXD63B4505456.00 When ordered by these catalog
500 LXD62B500■4376.00 LXD63B5005456.00 numbers, the customer will receive
600 LXD62B6004376.00 LXD63B6005456.00 the frame, trip and lugs separately
packaged. For applications requiring
Type LD6-A Blue Label different lugs, order individual items
as needed.
Interchangeable Trip
Complete Breaker Complete Breaker Assembled
Continuous Unassembled w/Lugs Frame Only Trip Unit Only without Lugs
Current Rating Catalog Catalog Catalog Prices of LXD6, HLXD6, HHLXD6,
@ 40°C Number Number Number and CLD6 include frame with non-
2-Pole 600V AC, 250V DC (3 Pole Width) interchangeable trip unit installed
only. Order required lugs separately.
250 LD62B250■4488.00 JD62T250■1662.00 For line and load lugs (TA2J6500)
300 LD62B300■4488.00 JD62T300■1662.00
350 LD62B350■4488.00 JD62T350■1662.00 installed, add suffix “L” to catalog
400 LD62B4004488.00 LD62F600 JD62T400 1662.00 number (add 2 times list price of
450 LD62B450■4488.00 LD62T450■1662.00 lugs for each pole).
500 LD62B500■4488.00 LD62T500■1662.00
600 LD62B6004488.00 LD62T600 1662.00 100% Rated
Types, LXD6 and HLXD6 breakers
3-Pole 600V AC, 500V DC are available with 100% ratings.
250 LD63B2505624.00 JD63T250 1851.00 To order add suffix “H” to catalog
300 LD63B3005624.00 JD63T300 1851.00
350 LD63B3505624.00 JD63T350 1851.00
number, and 10% to list price. 100%
400 LD63B4005624.00 LD63F600 JD63T400 1851.00 rated LD breakers require the use of
450 LD63B4505624.00 LD63T450 1851.00 90°C Cu cable and lugs TC1J6600 or
500 LD63B5005624.00 LD63T500 1851.00 TC2J6500.
600 LD63B6005624.00 LD63T600 1851.00
50°C Applications see page 6-72.
Interrupting Ratings 400Hz Applications see page 6-72.
RMS Symmetrical Amperes (KA)
CSA / UL 489 AIR (File E10848) IEC 947-2 Shipping Weights
Breaker Volts AC (50/60Hz) Volts DC Volts AC (50/60Hz) Number of Number per Shipping
Type 240 480 600 250 500 c 220/240 380/415 500 Poles Carton Weight (lbs.)
(lcu) (lcs) (lcu) (lcs) (lcu) (lcs) LXD6, LD6, HLD6, HHLD6
6
LXD6, LD6 065 035 025 30 (2-P) 25 (3-P) 065 033 040 20 30 15 Assembled Breaker (less terminals)
HLD6, HLXD6 100 065 035 30 (2-P) 35 (3-P) 100 050 065 33 42 21 2 1 17.5
3 1 19.5
HHLD6, HHLXD6 200 100 050 — — 200 100 100 50 65 33
LD6, HLD6, HHLD6 Frame Only
CLD6 200 150 100 30 (2-P) 50 (3-P) — — — — — —
2 1 14
3 1 15.5
Instantaneous Adjustment Trip Range LD6, HHLD6 Trip Unit Only
Breaker Ampere Nominal Instantaneous Values
BREAKERS
CIRCUIT
2 1 03.5
Rating Low 2 3 4 5 6 7 High 3 1 04
250-300 1250 1430 1610 1790 1960 2140 2320 2500 CLD6 Complete Assembled Breaker
350-450 2000 2290 2570 2860 3140 3430 3710 4000 (less terminals)
500-600 3000 3430 3800 4290 4710 5140 5570 6000 2 1 29.5
3 1 31.5
6/32
Molded Case Circuit Breakers
Selection
LD 600A Frame Sentron Series
Type HLD6-A, HLXD6 Black Label
Interchangeable Trip
Complete Breaker
Continuous Unassembled w/Lugs Frame Only Trip Unit Only D1
Current Rating Catalog Catalog Catalog
@ 40°C Number Number Number
L
2-Pole 600V AC, 250V DC (3 Pole Width)
250 HLD62B250■ 5868.00 JD62T250■1662.0
300 HLD62B300■ 5868.00 JD62T300■1662.0 L
350 HLD62B350■ 5868.00 JD62T350■1662.0
400 HLD62B400■ 5868.00 HLD62F600■ JD62T400 1662.0
450 HLD62B450■ 5868.00 LD62T450■1662.0
500 HLD62B500■ 5868.00 LD62T500■1662.0
600 HLD62B600■ 5868.00 LD62T600 1662.00 W
D
3-Pole 600V AC, 500V DC
W
D
250 HLD63B250 7465.00 JD63T250 1851.0
300 HLD63B300 7465.00 JD63T300 1851. Figure 1 Figure 2
350 HLD63B350 7465.00 JD63T350 1851.0
400 HLD63B400 7465.00 HLD63F600 JD63T400 1851.0 Dimensions (in inches)
450 HLD63B450 7465.00 LD63T450 0
500 HLD63B500 7465.00 LD63T500 0 To
600 HLD63B600 7465.00 LD63T600 1851.00 Handle
Breaker
Type HHLD6, HHLXD6 Type W L D D1
6
600 HHLD63B600■8864.00 HHLD63T600■ 7,9 ED6 10131.00
Neutral W60993 308.00
Type CLD6 f
Fuseless Current Limiting Red Label
Non-Interchangeable Trip (Assembled Circuit Breaker)
2-Pole 3-Pole
BREAKERS
Continuous 600V AC/250V DC 600V AC/500V DC
CIRCUIT
Current Rating Catalog
@ 40°C Number
450 For 2-pole application CLD63B450■11666
500 use outside poles of CLD63B500 11666
600 3-pole circuit breaker CLD63B600
For inches / millimeters conversion, Type HLXD6, HHLXD6 Circuit Breakers are CSA Certified /
see Application Data section For complete assembled 3 pole HLD6 or HHLD6 type UL Listed for reverse feed applications.
circuit breaker change the prefix identifier HLD6 or LXD6-ETI, CLD6-ETI see page 6-55 for ordering information.
■ Built to order. Allow 3-4 weeks for delivery. HHLD6 to HLXD6 or HHLXD6. Price is sum of frame and CE Applies to non-interchangable type HLXD only.
When wired as shown on page 6-2, this circuit breaker trip units prices, e.g. price of HLXD63B400 is the price HACR rated.
of HLD63F600 plus the price of LD63T600. Order the
is CSA Certified / UL listed and rated for use on 500V DC terminal connectors separately.■
ungrounded UPS systems only.
6/33
Molded Case Circuit Breakers
Selection
SLD 600A Frame Digital Solid State Sentron Sensitrip III Series
Current Limiting
Type SLD6(A) Type SHLD6(A) Type SCLD6
Blue Label Black Label Red Label
3-Pole, 600V AC 3-Pole, 600V AC 3-Pole, 600V AC
Max Max Max
Catalog Current Catalog Current Catalog Current
Number Rating Number Rating Number Rating
SLD69300■ 300 5576.00 SHLD69300■ 300 6790.00 SCLD69300■ 300 12024.00
SLD69400■ 400 5576.00 SHLD69400■ 400 6790.00 SCLD69400■ 400 12024.00
SLD69500■ 500 5576.00 SHLD69500■ 500 6790.00 SCLD69500■ 500 12024.00
SLD69600■ 600 5576.00 SHLD69600■ 600 6790.00 SCLD69600■ 600 12024.00
SLD69300G■ 300 7912.00 SHLD69300G■ 300 9574.00 SCLD69300G■ 300 15880.00
SLD69400G■ 400 7912.00 SHLD69400G■ 400 9574.00 SCLD69400G■ 400 15880.00
SLD69500G■ 500 7912.00 SHLD69500G■ 500 9574.00 SCLD69500G■ 500 15880.00 SJD6, SLD6
SLD69600G■ 600 7912.00 SHLD69600G■ 600 9574.00 SCLD69600G■ 600 15880.00
SLD69300NT■ 300 7006.00 SHLD69300NT■ 300 8407.00 SCLD69300NT■ 300 14231.00
SLD69400NT■ 400 7006.00 SHLD69400NT■ 400 8407.00 SCLD69400NT■ 400 14231.00
SLD69500NT■ 500 7006.00 SHLD69500NT■ 500 8407.00 SCLD69500NT■ 500 14231.00
SLD69600NT■ 600 7006.00 SHLD69600NT■ 600 8343.00 SCLD69600NT■ 600 14231.00
SLD69300NGT■ 300 9738.00 SHLD69300NGT■ 300 11615.00 SCLD69300NGT■ 300 18726.00
SLD69400NGT■ 400 9738.00 SHLD69400NGT■ 400 11615.00 SCLD69400NGT■ 400 18726.00
SLD69500NGT■ 500 9738.00 SHLD69500NGT■ 500 11615.00 SCLD69500NGT■ 500 18726.00
SLD69600NGT■ 600 9738.00 SHLD69600NGT■ 600 11615.00 SCLD69600NGT■ 600 18726.00
H
Trip Unit Adjustable Functions
Short
Suffix Cont Long Instan- Short Short Time Ground Ground
Letter Trip Current Time taneous Time Time l2t Fault Fault
Code Type Setting Delay Setting Pick Up Delay Pick Up Pick Up Delay SJD6, SHJD6, SLD6, SHLD6
None LI — — — — —
G LIG — — —
NT LSI — —
NGT LSIG
H
6
BREAKERS
CIRCUIT
SCJD6, SCLD6
Dimensions (Inches)
Breaker
Type W H D D1
SJD6(A), SHJD6(A)
SLD6(A), SHLD6(A) 7.5 11 4 5.44
SLD6, SHLD6
SCJD6 7.5 17.86 4 5.44
SCLD6
Enclosures
(For LD frame, excluding SCLD6)
Catalog
Type Number
1 LD6N1
3R LD6N3R
4–4X LD6SS4
7, 9 ED6
12 LD6N12
Note: “
G” suffix in catalog number denotes circuit breaker For ordering information and terminal connectors, neutral
Neutral W60993
for 3 phase, 3 wire circuits. transformers and enclosures, see page 6-31.
For 3 phase, 4 wire, order correct 4th wire (neutral) 100% Rated – N ot available in SLD6 Frame.
transformer as separate and additional item. ■ Built to order. Allow 3-4 weeks for delivery.
6/34
Molded Case Circuit Breakers
Selection
Internal Accessories
Accessories for: Shunt Trip Combinations
JD 400A Frame 1 Shunt Trip and
Control Voltage 1 Shunt Trip 1 Auxiliary Switch
LD 600A Frame
LMD 800A Frame AC DC Catalog Number Catalog Number
SJD 400A Frame 024 — S17JLD6 569.00 — --
048 — S18JLD6▲ 569.00 — --
SLD 600A Frame 120 — S01JLD6 569.00 S01JLD62A 802.00
240 — S03JLD6 569.00 S03JLD62A 802.00
277 — S15JLD6▲ 569.00 S15JLD64A▲ 802.00
480 — S04JLD6 569.00 — -
— 012 S16JLD6▲ 569.00 S16JLD62A▲ 802.00
— 024 S07JLD6 569.00 S07JLD62A 802.00
— 048 S09JLD6▲ 569.00 S09JLD62A 802.00
— 125 S11JLD6 569.00 S11JLD62A▲ 802.00
— 250 S13JLD6▲ 569.00 S13JLD62A▲ 802.00
6
Maximum 1 Alarm Switch and 1 Alarm Switch and
battery back-up for maintaining trip Voltage 1 Alarm Switch 1 Auxiliary Switch 2 Auxiliary Switches
and max logs. Catalog Catalog Catalog
The SADU reads currents, current AC DC Number Number Number
imbalance, current demand, and trip 480 250 B01JLD64 242.00 A01JLD64B A02JLD64B
status.
BREAKERS
CIRCUIT
Breaker Type Desc. Catalog Number
The Ammeter may also be panel or Display Unit SADU 1588.00
SJD, SLD
door mounted using the SADURMK18 Remote Mounting Kit SADURMK18 306.00
remote mounting kit.
Note: Accessory modules can only be added to right ▲ Built to order. Allow 4-9 weeks for delivery.
side pole of solid state SJD and SLD frame circuit
breakers. All accessories on this page are useable
on superseded JD2, JJ6, JL6, HJ6, SJL, LJ6, LL6,
HL6 and SLL circuit breakers.
6/35
Molded Case Circuit Breakers
Selection
LMD 800A Frame Sentron Series
Type LMXD6 Blue Label Ordering Information
Non-Interchangeable Trip (Assembled Circuit Breaker without Lugs) Complete Breaker Unassembled
Continuous 2-Pole (3 Pole Width) 3-Pole with Lugs
Current Rating Catalog Catalog Prices of LMD6 and HLMD6 breakers
@ 40°C Number Number include frame, trip, and both line and
500 — LMXD63B500■7 load lugs (TA3K500). These catalog
600 LMXD62B600■ 5582.00 LMXD63B600 7067
700 LMXD62B700■ 5582.00 LMXD63B700 7067 numbers include the frame, trip
800 LMXD62B800 5582.00 LMXD63B800 and lugs separately packaged. For
applications requiring different lugs,
Type LMD6 Blue Label order individual items as needed.
Interchangeable Trip Complete Breaker Assembled
Complete Breaker without Lugs
Continuous Unassembled w/Lugs Frame Only Trip Unit Only Prices of LMXD6 and HLMXD6
Current Rating Catalog Catalog Catalog
@ 40°C Number Number Number include frame with non-
interchangeable trip unit installed
2-Pole 600V AC, 250V DC (3 Pole Width) only. Order required lugs separately.
500 LMD62B500■5928.00 LMD62T500■2671.0
600 LMD62B600■5928.00 LMD62F800■2909.00 LMD62T600■2671.0
For line and load lugs (TA3K500)
700 LMD62B700■5928.00 LMD62T700■2671.0 installed, add suffix “L” to catalog
800 LMD62B800■5928.00 LMD62T800■ number (add 2 times list price of
lugs for each pole).
3-Pole 600V AC, 500V DC
500 LMD63B500■7589.00 LMD63T500■3351.0 50°C Applications see page 6-72.
600 LMD63B600■7589.00 LMD63F8003716.00 LMD63T600■3351.0 400Hz Applications see page 6-72.
700 LMD63B700■7589.00 LMD63T700■3351.0
800 LMD63B8007589.00 LMD63T8003351.00
2 1 4.5
3 1 6.5
6/36
Molded Case Circuit Breakers
SELECTION / DIMENSIONS
LMD 800A Frame Sentron Series
Type HLMXD6 Black Label
Non-Interchangeable Trip (Assembled Circuit Breaker without Lugs)
600V AC 600V AC
2-Pole 3-Pole
Continuous 250V DC 500V DC
Current Rating Catalog
@ 40°C Number
500 For 2-Pole application use HLMXD63B500■ 8553.0
600 outside poles of 3-Pole HLMXD63B600■ 8553.0
700 circuit breaker. HLMXD63B700■ 85
800 HLMXD63B800
6
Type Number
HLMD6, HLMXD6 100 065 050 30 (2-P) 50 (3-P) 100 050 065 33 42 21
1 LMD1 802.00
3R LMD3R 1969.00
12 LMD12■ 2578.00
Neutral W63623 428.00
BREAKERS
CIRCUIT
For inches / millimeters conversion, LMXD6-ETI, see page 6-55 for catalog information.
see Application Data section. When
wired as shown on page 6-2, this circuit breaker is
UL listed and rated for use on 500VDC ungrounded UPS
■ Built to order. Allow 3-4 weeks for delivery. systems only.
HLMXD6 circuit breakers are UL Listed for reverse HACR
rated.
connection applications.
6/37
Molded Case Circuit Breakers
Selection
Internal Accessories
Accessories for: Shunt Trip Combinations
JD 400A Frame Control Voltage 1 Shunt Trip
1 Shunt Trip and
1 Auxiliary Switch
LD 600A Frame
AC DC Catalog Number Catalog Number
LMD 800A Frame
024 — S17JLD6 569.00— --
SJD 400A Frame 048 — S18JLD6▲ 569.00— --
SLD 600A Frame 120 — S01JLD6 569.00S01JLD62A 802.00
240 — S03JLD6 569.00S03JLD62A 802.00
277 — S15JLD6▲ 569.00S15JLD64A▲ 802.00
480 — S04JLD6 569.00— --
— 012 S16JLD6▲ 569.00S16JLD62A▲ 802.00
— 024 S07JLD6 569.00S07JLD62A
— 048 S09JLD6▲ 569.00S09JLD62A
— 125 S11JLD6 569.00S11JLD62A▲
— 250 S13JLD6▲ 569.00S13JLD62A▲ 802.00
Note: Accessory modules can only be added to right ▲ Built to order. Allow 7-9 weeks for delivery.
side pole of solid state SJD and SLD frame circuit
breakers. All accessories on this page are useable
on superseded JD2, JJ6, JL6, HJ6, SJL, LJ6, LL6,
HL6 and SLL circuit breakers.
6/38
Molded Case Circuit Breakers
Selection
MD 800A Frame Sentron Series
Type MXD6 Blue Label Ordering Information
Non-Interchangeable Trip (Assembled Circuit Breaker Without Lugs) Complete Breaker Unassembled
Continuous 2-Pole 3-Pole with Lugs
Current Rating Catalog Catalog
Pricing information for MD6 and
@ 40°C Number Number HMD6 breakers includes frame,
500 MXD62B500■5582.00 MXD63B500■ 7067.00
trip, and both line and load lugs
600 MXD62B600■5582.00 MXD63B600 7067.00 (TA3K500). When ordered by these
700 MXD62B700■5582.00 MXD63B700 7067.00 catalog numbers, the customer
800 MXD62B800■5582.00 MXD63B800 7067.00 will receive the frame, trip and
lugs separately packaged. For
Type MD6 Blue Label applications requiring different lugs,
order individual items as needed.
Interchangeable Trip Complete Breaker Assembled
Complete Breaker without Lugs
Continuous Unassembled with Lugs Frame Only Trip Unit Only Prices of MXD6, HMXD6 and
Current Setting Catalog Catalog Catalog CMD6 include frame with non-
@ 40°C Number Number Number interchangeable trip units installed
only. Order required lugs separately.
2-Pole 600V AC, 250V DC
For line and load lugs (TA3K500)
500 MD62B500■5928.00 MD62T500■2671.0 installed, add suffix “L” to catalog
600 MD62B600■5928.00 MD62F800■2909.00 MD62T600■2671.0 number (add 2 times list price of
700 MD62B700■5928.00 MD62T700■ 26
800 MD62B800■5928.00 MD62T800■
lugs for each pole).
100% Ratedf
3-Pole 600V AC, 500V DC Types MXD6, HMXD6 and CMD6
500 MD63B500 7589.00 MD63T5003351.00 breakers are available with 100%
600 MD63B600 7589.00 MD63F800 3716.00 MD63T6003351.00 ratings. To order add suffix “H” to
700 MD63B700 7589.00 MD63T7003351.00 catalog number, and 10% to list
800 MD63B800 7589.00 MD63T8003351.00 price. 100% rated MD breakers
require the use of 90°C Cu cable and
Lugs lugs 2TA4P8500 or 2TA2N8750 for
Catalog Cables Lugs Wire 2-pole; 3TA4P8500 or 3TA2N8750 for
Number Per Lug Per Kit Range 3-pole.
TA2K500 1-2 1 #1-500 kcmil Cu/Al 64.00
TA3K500 1-3 1 1/0-500 kcmil Cu/Al 87.00 50°C Applications see page 6-72.
TC2K500 1-2 1 #1-500 kcmil Cu 107.00 400Hz Applications see page 6-72.
TC3K350 1-3 1 #1-350 kcmil Cu 135.00
Kits
6
2TA2N8750 2 327.00
3TA2N8750 1-2 3 600-750 kcmil Cu/Al 459.00
2TA3N8750
1-3
2
500-750 kcmil Cu/Al
517.00 Shipping Weights
3TA3N8750 3 744.00
Number of Number per Shipping
2TA4N8500 2 526.00 Poles Carton Weight (lbs.)
3TA4N8500 1-4 3 250-500 kcmil Cu/Al 762.00
MD6, HMD6, HMXD6, CMD6
2TA4P8500 2 522.00 Complete Breaker Assembled
1-4 250-500 kcmil Cu/Al
BREAKERS
3TA4P8500 3 754.00 (less lugs)
CIRCUIT
2 1 53
Instantaneous Adjustment Trip Range 3 1 61.5
Ampere Nominal Instantaneous Values MD6, HMD6 Frame Only
Rating Low 2 3 4 5 6 7 High 2 1 42.25
500–600 3000 3430 3860 4280 4710 5140 5570 6000 3 1 46
700–800 4000 4570 5140 5710 6280 6850 7420 8000 MD6, HMD6 Trip Unit Only
2 1 4.5
3 1 6.5
Enclosures
Catalog List
Type Number Price $
1 MND61 802.00
3R MND63 1969.00
12 MND612■ 2578.00
■ Built to order. Allow 3-4 weeks for delivery. See Note: A, page 6-69.
80%
Neutral W63623 428.00
MXD6 circuit breakers are CSA Certified / UL Listed for rated breakers with the CE mark will also be marked
reverse connection applications. in the 100% rated version.
HACR rated.
2-pole units available in 3-pole width only.
Use 6 connectors for 3-pole, use 4 connectors for 2-pole. Note: M
D frame qualified to UL489 supplement B “NAVAL”. Modifications page 6/73
When wired as shown on page 6-3, this circuit breaker See page 6-72 for additional information. Accessories pages 6/43 and 6/72 to 6/86
is CSA Certified / UL listed and rated for use on 500V DC
ungrounded UPS systems.
6/39
Molded Case Circuit Breakers
Selection / DIMENSIONS
MD 800A Frame Sentron Series
Type HMXD6 Black Label
Non-Interchangeable Trip (Assembled Circuit Breaker Without Lugs)
2-Pole 600V AC 3-Pole 600V AC
Continuous 250V DC 500V DC
Current Rating Catalog
@ 40°C Number
500 HMXD63B500■ 8555.00
600 For 2-pole application use outside HMXD63B600■ 8555.00
700 poles of 3-pole circuit breaker HMXD63B700■ 8555.00
800 HMXD63B800 8555.00
Type CMD6
Fuseless Current Limiting Red Label
Non-Interchangeable Trip (Assembled Circuit Breaker Without Lugs)
2-Pole 3-Pole Lug
Continuous 600V AC/250V DC 600V AC/500V DC
When wire lug shield NDTS is used.
Current Rating Catalog
6
Note: N
DTS lug shields are required when oversized lugs
@ 40°C Number
are used. The kits include the NDTS shield.
500 CMD63B500■ 12599.00
600 For 2-pole application use CMD63B600■ 12599.00
700
800
outside poles of 3-pole
circuit breaker
CMD63B700■
CMD63B800■
12599.00
12599.00
Dimensions (in inches)
(To
Interrupting Ratings Breaker
Type W L D
Handle)
D1
BREAKERS
CIRCUIT
For inches / millimeters conversion, 2-pole units available in 3-pole width only.
see Application Data section. MXD6-ETI, CMD6-ETI see page 6-56 for catalog information.
When wired as shown on page 6-3, this circuit breaker
■ Built to order. Allow 3-4 weeks for delivery. is CSA Certified / UL listed and rated for use on 500V DC
HMXD6 circuit breakers are CSA Certified / UL listed for ungrounded UPS systems only.
HACR rated.
reverse connection applications.
6/40
Molded Case Circuit Breakers
SELECTION
Selection
SMD 800A Frame Digital Solid State Sentron Sensitrip III Series
Current Limiting Ordering Information
Type SMD6 Type SHMD6 Type SCMD6 Pricing information for all Digital Sentron
Series MD and ND frames is for complete
Blue Label Black Label Red Label breaker only. Price requires lugs or lug
3-Pole, 600V AC 3-Pole, 600V AC 3-Pole, 600V AC
kits as separate items. Lugs are suitable
for 75°C wire or as noted. Connector
Max Max Max wire ranges and cavities are established
Catalog Current Catalog Current Catalog Current
Number Rating Number Rating Number Rating
in conjunction with Table 8.1 of UL 489
standards. Choose actual connector
SMD69600A■ 600 7686.00 SHMD69600A■ 600 9370.00 SCMD69600A■ 600 13914.00 for circuit breakers based on customer
SMD69700A■ 700 7686.00 SHMD69700A■ 700 9370.00 SCMD69700A■ 700 13914.00
SMD69800A■ 800 7686.00 SHMD69800A■ 800 9370.00 SCMD69800A■ 800 13914.00
requirements.
Recommended Terminal Connectors
SMD69600AG■ 600 9134.00 SHMD69600AG■ 600 10785.00 SCMD69600AG■ 600 16582.00
SMD69700AG■ 700 9134.00 SHMD69700AG■ 700 10785.00 SCMD69700AG■ 700 16582.00 Breaker Ampere Connector or
SMD69800AG■ 800 9134.00 SHMD69800AG■ 800 10785.00 SCMD69800AG■ 800 16582.00 Frame Rating Connector Kit
SMD69600ANT■ 600 7955.00 SHMD69600ANT■ 600 9658.00 SCMD69600ANT■ 600 15056.00 MD 500–600 TA2K500
SMD69700ANT■ 700 7955.00 SHMD69700ANT■ 700 9658.00 SCMD69700ANT■ 700 15056.00 MD 700–800 TA3K500
SMD69800ANT■ 800 7955.00 SHMD69800ANT■ 800 9658.00 SCMD69800ANT■ 800 15056.00 ND 800 TA3K500
ND 900–1200 (kit) 3TA4N8500
SMD69600ANGT■ 600 10575.00 SHMD69600ANGT■ 600 12418.00 SCMD69600ANGT■ 600 19201.00
SMD69700ANGT■ 700 10575.00 SHMD69700ANGT■ 700 12418.00 SCMD69700ANGT■ 700 19201.00 ypes SMD6, SHMD6, SND6, SHND6 are
T
SMD69800ANGT■ 800 10217.00 SHMD69800ANGT■ 800 12418.00 SCMD69800ANGT■ 800 19201.00 acceptable for reverse connection applications.
Shipping Weights
SMD 800A Frame – 100% Rated
Current Limiting
Breaker Number per Shipping
Type Carton Weight (lbs)
Type SMD6-H Type SHMD6-H Type SCMD6-H All types 1 61.5
6
SMD69700ANTH■ 700 8818.00 SHMD69700ANTH■ 700 10641.00 SCMD69700ANTH■ 700 16549.00
SMD69800ANTH■ 800 8818.00 SHMD69800ANTH■ 800 10641.00 SCMD69800ANTH■ 800 16549.00 Each kit contains the following:
3TA4P8500—3 connectors plus 1 NDTS end barrier
SMD69600ANGTH■ 600 11647.00 SHMD69600ANGTH■ 600 13674.00 SCMD69600ANGTH■ 600 21139.00 3TA3N8750—3 connectors plus 1 NDTS end barrier
SMD69700ANGTH■ 700 11647.00 SHMD69700ANGTH■ 700 13674.00 SCMD69700ANGTH■ 700 21139.00 3TA2N8750—3 connectors plus 1 NDTS end barrier
SMD69800ANGTH■ 800 11647.00 SHMD69800ANGTH■ 800 13674.00 SCMD69800ANGTH■ 800 21139.00
BREAKERS
Letter Trip Current Time taneous Time Time Fault Fault
CIRCUIT
Code Type Setting Delay Setting Pick Up Delay Pick Up Delay 0600 N06SMDA 378.00
0700 N07SMDA 378.00
A LI — — — — 0800 N08SMDA 378.00
AG LIG — — 1000 N10SNDA 378.00
1200 N12SNDA 378.00
ANT LSI — —
ANGT LSIG Enclosures
Catalog
Interrupting Ratings Type Number
RMS Symmetrical kA UL 489 (File E10848) 1 MND61 802.00
Breaker
3R MND63 1969.00
Type 240V AC 480V AC 600V AC
12 MND612 2578.00
SMD6 – SND6 065 050 25
Neutral W63623 428.00
SHMD6 – SHND6 100 065 50
SCMD6 – SCND6 200 100 65
6/41
Molded Case Circuit Breakers
Selection
Internal Accessories
Accessories for: Shunt Trip Combinations
MD/SMD 800A Frame 1 Shunt Trip and
ND/SND 1200A Frame Control Voltage 1 Shunt Trip 1 Auxiliary Switch
PD/SPD 1600A Frame AC DC Catalog Number Catalog Number
RD 2000A Frame 120 — S01MN6 569.00 S01MN64A 802.00
208 — S02MN6▲ 569.00 S02MN64A▲802.00
240 — S03MN6 569.00 S03MN64A▲802.00
277 — S15MN6▲ 569.00 S15MN64A▲802.00
480 — S04MN6▲ 569.00 S04MN64A▲802.00
600 — S06MN6▲ 569.00 — -
— 012 S16MN6▲ 569.00 S16MN64A▲802.00
— 024 S07MN6 569.00 S07MN64A 802.00
— 048 S09MN6▲ 569.00 —
— 125 S11MN6 569.00 S11MN64A▲802.00
— 250 S13MN6▲ 569.00 S13MN64A▲802.00
6/42
Molded Case Circuit Breakers
Selection
ND 1200A Frame Sentron Series
Type NXD6 Blue Label Ordering Information
Non-Interchangeable Trip (Assembled Circuit Breaker Without Lugs) Complete Breaker Unassembled
with Lugs
2-Pole 600V AC 3-Pole 600V AC Prices of ND6 and HND6 breakers
Continuous 250V DC 500V DC
Current Rating Catalog Catalog include frame, trip, and both line
@ 40°C Number Number and load lugs (3TA4N8500). These
0900 NXD62B900■9388.00 NXD63B900 11775.00 catalog numbers are the frame, trip
1000 NXD62B100■9388.00 NXD63B100 11775.00 and lugs separately packaged. For
1200 NXD62B120■9388.00 NXD63B120 11775.00 applications requiring different lugs,
order individual items as needed.
Type ND6 Blue Label Complete Breaker Assembled
Interchangeable Trip without Lugs
Prices of NXD6, HNXD6, and
Complete Breaker
Unassembled with Lugs Frame Only Trip Unit Only
CND6 include frame with non-
Continuous interchangeable trip units installed
Current Rating Catalog Catalog Catalog
@ 40°C Number Number Number
only. Order required terminal
connectors separately.
2-Pole 600V AC, 250V DC For line and load lugs (3TA4N8500)
installed, add suffix “L” to catalog
0800 ND62B800■8574.00 MD62T800■2671.00
0900 ND62B900■10441.00 ND62T900■4538.00 number (add 2 times list price of
ND62F1204851.00 lug kit).
1000 ND62B100■10441.00 ND62T100■4538.00
1200 ND62B12010441.00 ND62T120 4538.00
100% Ratedh
3-Pole 600V AC, 500V DC Types NXD6, HNXD6 and CND6
breakers are available with 100%
0800 ND63B80010961.00 MD63T8003351.00 ratings. To order, suffix “H” to catalog
0900 ND63B90013299.00 ND63T9005689.00
1000 ND63B10013299.00
ND63F1206086.00
ND63T1005689.00
number, and add 10% to list price.
1200 ND63B12013299.00 ND63T1205689.00 100% rated ND breakers require
90°C Cu cable and lug kit 3TA4P8500
Interrupting Ratings or 3TA3N8750.
RMS Symmetrical Amperes (KA)
CSA / UL 489 A IR IEC 947-2 50°C Applications see page 6-72.
Breaker Volts AC Volts DC Volts AC (50/60HZ)
Type 240 480 600 250 500 c 220/240 380/415 500
400Hz Applications see page 6-72.
(lcu) (lcs) (lcu) (lcs) (lcu) (lcs)
ND6, NXD6 65 50 25 30 (2-P) 25 (3-P) 65 33 40 20 30 15 Lugs
HND6, HNXD6 100 65 50 30 (2-P) 50 (3-P) 100 50 65 33 42 21
6
Catalog Cables Wire
CND6 200 100 65 30 (2-P) 50 (3-P) 200 100 100 50 65 33 Number per Lug Range
TA2K500 2 #1-500 kcmil Cu/Al 64.00
Instantaneous Adjustment Trip Range TA3K500 3 #1-500 kcmil Cu/Al 87.00
TC2K500 2 #1-500 kcmil Cu 107.00
Breaker Ampere Nominal Instantaneous Values TC3K350 3 #1-350 kcmil Cu 135.
Rating Low 2 3 4 5 6 7 High Kits (2 Kits required per breaker)
800 4000 4570 5140 5710 6280 6850 7420 08000 2TA4P8500
3TA4P8500 4 250-500 kcmil Cu/Al
900-1200 5000 5715 6430 7145 7860 8575 9290 10000
BREAKERS
2TA4N8500
3TA4N8500 4 250-500 kcmil Cu/Al 762.00
CIRCUIT
2TA2N8750 2 600-750 kcmil Cu/Al
3TA2N8750
2TA3N8750 3 500-750 kcmil Cu/Al
3TA3N8750 744.00
Enclosures
Catalog
Type Number
1 MND61 802.00
3R MND63 1969.00
12 MND612 ■ 2578.00
Neutral W63623 428.00
6/43
Molded Case Circuit Breakers
selection / dimensions
ND 1200A Frame Sentron Series
Type HNXD6 Black Label
Non-Interchangeable Trip (Assembled Circuit Breaker Without Lugs)
2-Pole 600V AC 3-Pole 600V AC
Continuous 250V DC 500V DC
Current Rating Catalog
@ 40°C Number
0900 HNXD63B900 13229.00
For 2-pole application use outside
1000 HNXD63B100 13229.00
poles of 3-pole circuit breaker
1200 HNXD63B120 13229.00
Type CND6
Fuseless Current Limiting Red Label
Non-Interchangeable Trip (Assembled Circuit Breaker)
2-Pole 3-Pole Lugs
Continuous
Current Rating Catalog When lugs shield NDTS is used.
@ 40°C Number
6
For inches / millimeters conversion, 2-pole units available in 3-pole width only.
see Application Data section. Whenwired as shown on page 6-3, this circuit breaker is
UL listed and rated for use on 500V DC ungrounded UPS
■ Built to order. Allow 3-4 weeks for delivery. systems only.
HNXD6 circuit breakers are CSA Certified / UL Listed for HACR rated.
6/44
Molded Case Circuit Breakers
SELECTION
SND 1200A Frame Digital Solid State Sentron Sensitrip III Series
Current Limiting
Type SND6 Type SHND6 Type SCND6
Blue Label Black Label Red Label
3-Pole, 600V AC 3-Pole, 600V AC 3-Pole, 600V AC
Max Max Max
Catalog Current Catalog Current Catalog Current
Number Rating Number Rating Number Rating
SND69800A■ 800 13548.00 SHND69800A■ 800 13548.00 SCND69800A■ 800 18650.00
SND69100A■ 1000 13548.00 SHND69100A■ 1000 13548.00 SCND69100A■ 1000 18650.00
SND69120A■ 1200 13548.00 SHND69120A■ 1200 13548.00 SCND69120A■ 1200 18650.00
SND69800AG■ 800 14963.00 SHND69800AG■ 800 14963.00 SCND69800AG■ 800 20540.00
SND69100AG■ 1000 14963.00 SHND69100AG■ 1000 14963.00 SCND69100AG■ 1000 20540.00
SND69120AG■ 1200 14963.00 SHND69120AG■ 1200 14963.00 SCND69120AG■ 1200 20540.00
SND69800ANT■ 800 14104.00 SHND69800ANT■ 800 14104.00 SCND69800ANT■ 800 19406.00
SND69100ANT■ 1000 14104.00 SHND69100ANT■ 1000 14104.00 SCND69100ANT■ 1000 19406.00
SND69120ANT■ 1200 14104.00 SHND69120ANT■ 1200 14104.00 SCND69120ANT■ 1200 19406.00
SND69800ANGT■ 800 16757.00 SHND69800ANGT■ 800 16757.00 SCND69800ANGT■ 800 23038.00
SND69100ANGT■ 1000 16757.00 SHND69100ANGT■ 1000 16757.00 SCND69100ANGT■ 1000 23038.00
SND69120ANGT■ 1200 16757.00 SHND69120ANGT■ 1200 16757.00 SCND69120ANGT■ 1200 23038.00
Current Limiting
Type SND6-H Type SHND6H Type SCND6-H
H
Blue Label Black Label Red Label
3-Pole, 600V AC 3-Pole, 600V AC 3-Pole, 600V AC
Max Max Max
Catalog Current Catalog Current Catalog Current
Number Rating Number Rating Number Rating SMD6, SHMD6, SCMD6, SND6, SHND6,
SND69800AH■ 800 13374.00 SHND69800AH■ 800 14896.00 SCND69800AH■ 800 20512.00 SCND6
SND69100AH■ 1000 13374.00 SHND69100AH■ 1000 14896.00 SCND69100AH■ 1000 21538.00
SND69120AH■ 1200 13374.00 SHND69120AH■ 1200 14896.00 SCND69120AH■ 1200 21538.00
SND69800AGH■ 800 14993.00 SHND69800AGH■ 800 16470.00 SCND69800AGH■ 800 22613.00
SND69100AGH■ 1000 14993.00 SHND69100AGH■ 1000 16470.00 SCND69100AGH■ 1000 23744.00
SND69120AGH■ 1200 14993.00 SHND69120AGH■ 1200 16470.00 SCND69120AGH■ 1200 23744.00
6
SND69800ANTH■ 800 13976.00 SHND69800ANTH■ 800 15501.00 SCND69800ANTH■ 800 21343.00
SND69100ANTH■ 1000 13976.00 SHND69100ANTH■ 1000 15501.00 SCND69100ANTH■ 1000 22410.00
SND69120ANTH■ 1200 13976.00 SHND69120ANTH■ 1200 15501.00 SCND69120ANTH■ 1200 22410.00
SND69800ANGTH■ 800 16835.00 SHND69800ANGTH■ 800 18439.00 SCND69800ANGTH■ 800 25337.00
SND69100ANGTH■ 1000 16835.00 SHND69100ANGTH■ 1000 18439.00 SCND69100ANGTH■ 1000 26604.00
SND69120ANGTH■ 1200 16835.00 SHND69120ANGTH■ 1200 18439.00 SCND69120ANGTH■ 1200 26604.00
H
Trip Unit Adjustable Functions
BREAKERS
Short
CIRCUIT
Suffix Cont Long Instan- Short Short Time Ground Ground
Letter Trip Current Time taneous Time Time l2t Fault Fault
Code Type Setting Delay Setting Pick Up Delay Pick Up Pick Up Delay
A LI — — — — —
AG LIG — — —
ANT LSI — —
When wire connector shield NDTS is used.
ANGT LSIG
Dimensions (in Inches)
Breaker
Type W H D D1
SMD6, SHMD6, SCMD6
9 16 6 8.25
SND6, SHND6, SCND6
With NDTS shields 9 24 6 8.25
6/45
Molded Case Circuit Breakers
Selection / Dimensions
Internal Accessories
Accessories for: Shunt Trip Combinations
MD/SMD 800A Frame 1 Shunt Trip and
ND/SND 1200A Frame Control Voltage 1 Shunt Trip 1 Auxiliary Switch
PD/SPD 1600A Frame AC DC Catalog Number Catalog Number
RD 2000A Frame 120 — S01MN6 569.00 S01MN64A 802.00
208 — S02MN6▲ 569.00 S02MN64A▲802.00
240 — S03MN6 569.00 S03MN64A▲802.00
277 — S15MN6▲ 569.00 S15MN64A▲802.00
480 — S04MN6▲ 569.00 S04MN64A▲802.00
600 — S06MN6▲ 569.00 —-
— 012 S16MN6▲ 569.00 S16MN64A▲802.00
— 024 S07MN6 569.00 S07MN64A 802.00
— 048 S09MN6▲ 569.00 —
— 125 S11MN6 569.00 S11MN64A▲802.00
— 250 S13MN6▲ 569.00 S13MN64A▲802.00
6/46
Molded Case Circuit Breakers
Selection
PD 1600A Frame Sentron Series
Type PXD6 Non-Interchangeable Trip Ordering Instructions
3-Pole 600V AC, 250-500V DC Blue Label
Complete Breaker Unassembled
Complete Breaker Assembled Mounting
Continuous
(Frame/Trip Unit Only) Assembly Lugs (6 required)
with Lugs
Current Rating
40˚C Catalog Number Catalog Number Catalog Number Prices of PD6, HPD6, RD6, and
1200 PXD63B120■ 15086.00 MB9301
HRD6 type breakers include frame,
1400 PXD63B140■ 15086.00 -or- TA5P600 trip, mounting base (MB9301), and
1600 PXD63B160 15086.00 MBR9302 both line and load lugs (PD Frame –
TA5P600, RD Frame – TC5R600). When
Type PD6 Interchangeable Trip ordered by these catalog numbers,
3-Pole 600V AC, 250-500V DC Blue Label the customer will receive the frame,
trip, mounting assembly and lugs
Complete Breaker Mounting
Unassembled Frame Only Trip Unit Only Assembly Lugs (6 required)
separately packaged. For applications
Continuous requiring different mounting base or
Current Catalog Catalog Catalog Catalog Catalog Rating lugs, order individual items as needed.
40°C Number Number Number Number Number
1200 PD63B120■ 17900.00 PD63T120■0 MB9301
Complete Breaker Assembled
1400 PD63B14017900.00 PD63F160 7754.00 PD63T140 7332.00 -or- TA5P600 86.00 without Lugs
1600 PD63B16017900.00 PD63T160 7332.00 MBR9302 Prices of PXD6, HPXD6, RXD6, HRXD6
and CPD6 type breakers include frame
Type HPXD6 Non-Interchangeable Trip with non-interchangeable trip unit
Blue Label installed only. Order required mounting
3-Pole 600V AC, 250-500V DC
Continuous Current Complete BreakerAssembled (Frame/Trip Unit Only) base and lugs separately.
Rating 40°C Catalog Number 100% Rated
1200 HPXD63B120■ 17017.00 Types PXD6, HPXD6 breakers are
1400 HPXD63B140■ 7017.00 available with 100% ratings. To order
1600 HPXD63B160 17017.00 add suffix “H” to catalog number, and
10% to list price. RD 2000A Frames not
Type HPD6 Interchangeable Trip available with 100% ratings.
3-Pole 600V AC, 250-500V DC Black Label
50°C Applications see page 6-72.
Complete Breaker Mounting 400HZ Applications see page 6-72.
Continuous Unassembled Frame Only Trip Unit Only Assembly Lugs (6 required)
Current Catalog Catalog Catalog Catalog Catalog Rating
40°C Number Number Number Number Number
1200 HPD63B120■ 19829.00 PD63T120■ 7332.00 MB9301 1400 Lugs
HPD63B140 19829.00 HPD63F160 PD63T140 -or- TA5P600 286.00 No of Cables
1600 HPD63B160 19829.00 PD63T160 7332.00 MBR9302 Catalog per
Number Connector Wire Range
Type CPD6 Non-Interchangeable Trip TA5P600
TC5R600
1-5 Pcs.
1-5 Pcs.
300-600 kcmil Cu/Al
300-600 kcmil Cu only
286.00
381.00
6
Fuseless Current Limiting TC4P750▲ 1-4 Pcs. 500-750 kcmil Cu/Al 260.00
3-Pole 600V AC, 250-500V DC Red Label TA6R600 1-6 Pcs. 300-600 kcmil Cu/Al 302.00
BREAKERS
CIRCUIT
Mounting Bases for PD & RD
6.19
6.00 2.00 6.19
6.00 2.00
2.00
2.00
16.00
16.00
25.50
18.73
16.00
16.00
25.50
18.73
MBR9302 MB9301
MBR9302 MB9301
MB9301 MB9301 MB9301 MBR9302 MBR9302
■ Built to order. Allow 3-4 weeks for delivery. When wired as shown on page 6-2, this circuit breaker Foradditional information See Note: A, page 6-69.
▲ Built to order. Allow 7-9 weeks for delivery. is CSA Certified / UL listed and rated for use on 500V DC HACR rated.
Use two outside poles of a 3-pole circuit breaker for ungrounded UPS systems only. Note: PD frame qualified to UL489 supplement B “NAVAL”.
PXD6, HPXD6 type circuit breakers are UL Listed for
See page 6-72 for additional information.
250V
reverse feed applications.
6/47
Molded Case Circuit Breakers
SELECTION / DIMENSIONS
SPD 1600A Frame Digital Solid State Sentron Sensitrip III Series
Ordering Information
Pricing information for all Digital Sentron Series PD frame unit is for breaker
only. Price required mounting block assembly and necessary terminal connectors
as separate items.
SPD6 and SHPD6 are acceptable for reverse connection applications.
Short
Neutral Transformers
Suffix Cont Long Instan- Short Short Time Ground Ground Ampere Catalog
Letter Trip Current Time taneous Time Time l2t Fault Fault Rating Number
Code Type Setting Delay Setting Pick Up Delay Pick Up Pick Up Delay 1400 N14SPD 378.00
None LI — — — — — 1600 N16SPD 378.00
G LIG — — — Enclosure
NT LSI — —
Catalog
NGT LSIG Type Number
1 PRD6N1 5655.00
Interrupting Ratings Mounting Block (Required)
RMS Symmetrical kA CSA / UL 489 Catalog
Breaker
Type 240V AC 480V AC 600V AC Number
MB9301 1098.00
6
2.00
16.00
16.00
25.50
18.73
16.00
16.00
25.50
18.73
MBR9302 MB9301
MBR9302 MB9301
MB9301 (shown)
MBR9302 MBR9301 MB9301 MBR9302 MBR9302
For inches / millimeters conversion, Foradditional information, see Note: A, page 6-69. for 3 phase, 3 wire circuits.
see Application Data section. Note: T
he PD frame circuit breaker requires the use of a For 3 phase, 4 wire, order correct 4th wire (neutral)
connect-all mounting assembly to allow for placing transformer as separate and additional item.
■ Built to order. Allow 3-4 weeks for delivery. into service.
Note: “
G” suffix in catalog number denotes circuit breaker
6/48
Molded Case Circuit Breakers
Selection / Dimensions
Internal Accessories
Accessories for: Shunt Trip Combinations
MD/SMD 800A Frame 1 Shunt Trip and
ND/SND 1200A Frame Control Voltage 1 Shunt Trip 1 Auxiliary Switch
PD/SPD 1600A Frame AC DC Catalog Number Catalog Number
RD 2000A Frame 120 — S01MN6 569.00 S01MN64A 802.00
208 — S02MN6▲ 569.00 S02MN64A▲ 802.00
240 — S03MN6 569.00 S03MN64A▲ 802.00
277 — S15MN6▲ 569.00 S15MN64A▲ 802.00
480 — S04MN6▲ 569.00 S04MN64A▲ 802.00
600 — S06MN6▲ 569.00 — —--
— 012 S16MN6▲ 569.00 S16MN64A▲ 802.00
— 024 S07MN6 569.00 S07MN64A 802.00
— 048 S09MN6▲ 569.00 — —-
— 125 S11MN6 569.00 S11MN64A▲ 802.00
— 250 S13MN6▲ 569.00 S13MN64A▲ 802.00
6
Maximum 1 Alarm Switch and 1 Alarm Switch and
Voltage 1 Alarm Switch 1 Auxiliary Switch 2 Auxiliary Switches
AC DC Catalog Number Catalog Number Catalog Number
The Ammeter Display Units plug into 480 250 B00MN64 242.00 A01MN64B A02MN64B
the Sensitrip Trip Unit and displays
the phrase current flowing in the Plug-in Ammeter Display Units
SADU breaker. They are powered by Breaker Type Desc. Catalog Number
BREAKERS
the breaker’s CT’s with replaceable Display Unit SADU 1588.00
SMD, SND, SPD
CIRCUIT
battery back-up for maintaining trip Remote Mounting Kit SADURMK18 306.00
and max logs.
The SADU reads currents, current
imbalance, current demand, and trip
status.
Ammeter Mounting Kit
The Ammeter may also be panel or
door mounted using the SADURMK18
remote mounting kit.
6/49
Molded Case Circuit Breakers
Selection
RD 2000A Frame Sentron Series
Type RXD6 Blue Label
Non-Interchangeable Trip (Assembled Circuit Breaker Only Without Lugs)
3-Pole 600V AC, 250-500V DC
Complete Breaker
Assembled Mounting
Continuous (Frame/Trip Unit Only) Assembly Lugs (6 required)
Current Catalog Catalog Catalog
Rating 40°C Number Number Number
1600 RXD63B160 16723.00 MB9301 1098.00
1800 RXD63B180 16723.00 -or- TC5R600 381.00
2000 RXD63B200 16723.00 MBR9302 1098.00
Interrupting Ratings
BREAKERS
CIRCUIT
■ Built to order. Allow 3-4 weeks for delivery. RXD6 and HRXD6 type circuit breakers are CSA Certified
Use two outside poles of a 3-pole circuit breaker for / UL Listed for reverse feed applications.
250V DC applications. HACR rated.
When wired as shown on page 6-3, this circuit breaker Note: RD frame qualified to UL489 supplement B “NAVAL”.
is CSA Certified / UL listed and rated for use on 500V DC See page 6-72-+ for additional information.
ungrounded UPS systems only.
6/50
Molded Case Circuit Breakers
Selection / DIMENSIONS
Internal Accessories
Accessories for: Shunt Trip Combinations
MD/SMD 800A Frame 1 Shunt Trip and
ND/SND 1200A Frame Control Voltage 1 Shunt Trip 1 Auxiliary Switch
PD/SPD 1600A Frame AC DC Catalog Number Catalog Number
RD 2000A Frame 120 — S01MN6 S01MN64A 802.00
208 — S02MN6▲ S02MN64A▲ 802.00
240 — S03MN6 S03MN64A▲ 802.00
277 — S15MN6▲ S15MN64A▲ 802.00
480 — S04MN6▲ S04MN64A▲ 802.00
600 — S06MN6▲ —
— 012 S16MN6▲ S16MN64A▲ 802.00
— 024 S07MN6 S07MN64A 802.00
— 048 S09MN6▲ —-
— 125 S11MN6 S11MN64A▲ 802.00
— 250 S13MN6▲ S13MN64A▲ 802.00
6
Voltage 1 Alarm Switch 1 Auxiliary Switch 2 Auxiliary Switches
AC DC Catalog Number Catalog Number Catalog Number
The Ammeter Display Units plug into 480 250 B00MN64 242.00 A01MN64B 483.00 A02MN64B
the Sensitrip Trip Unit and displays
the phrase current flowing in the Plug-in Ammeter Display Units
SADU breaker. They are powered by Breaker Type Desc. Catalog Number
the breaker’s CT’s with replaceable
BREAKERS
Display Unit SADU 1588.00
SMD, SND, SPD
battery back-up for maintaining trip
CIRCUIT
Remote Mounting Kit SADURMK18 306.00
and max logs.
The SADU reads currents, current
imbalance, current demand, and trip
status.
Ammeter Mounting Kit
The Ammeter may also be panel or
door mounted using the SADURMK18
remote mounting kit.
6/51
Molded Case Circuit Breakers
Selection
STD 3200A Frame Digital Solid State Sentron Sensitrip III Series
Type STD6 Type SHTD6 Type SHHTD6 Ordering Information
Blue Label Black Label Red Label TD Breakers are ordered by
S
component - Frame, Trip Unit Rating
3-Pole, 600V AC, 80% Rated 3-Pole, 600V AC, 80% Rated 3-Pole, 600V AC, 80% Rated
Plug & Accessories. Contact Sales
Max Max Max Office for instructions.
Catalog Current Catalog Current Catalog Current
Number Rating Number Rating Number Rating
STD63F2000■ 2000 22 SHTD63F2000■ 2000 SHHTD63F2000■ 2000
STD63F2500■ 2500 SHTD63F2500■ 2500 SHHTD63F2500■ 2500
STD63F3200■ 3200 SHTD63F3200■ 3200 SHHTD63F3200■ 3200
3-Pole, 600V AC, 100% Rated 3-Pole, 600V AC, 100% Rated 3-Pole, 600V AC, 100% Rated
Max Max Max
Catalog Current Catalog Current Catalog Current
Number Rating Number Rating Number Rating H H1
STD63F2000H■ 2000 SHTD63F2000H■ 2000 266 SHHTD63F2000H■ 2000
STD63F2500H■ 2500 SHTD63F2500H■ 2500 SHHTD63F2500H■ 2500
STD63F3200H■ 3200 SHTD63F3200H■ 3200 SHHTD63F3200H■ 3200
Trip Unit
Fits Breaker Frame with Continuous Rating
2000 Amp 2500 Amp 3200 Amp
Function Catalog Numbers
W D
MLI STD20TMLI STD25TMLI STD32TMLI 921.00
LS STD20TLS STD25TLS STD32TLS 2021.00
Dimensions (in Inches)
LI STD20TLI STD25TLI STD32TLI 1440.00 Breaker Type H H1 W D
Cables
1600 20STD1600 25STD1600 32STD1600 Catalog per Con- Wire
Number nector Range
2000 20STD2000 25STD2000 32STD2000
TA6R600STD (1–6 pcs.) 250-600 289.00
2500 — 25STD2500 32STD2500 kcmil Cu/Al
3000 — — 32STD3000
3200 — — 32STD3200 T. Connector
(For Bus Connector)
BREAKERS
CIRCUIT
■ Built to order. Allow 3-4 weeks for delivery. b Dimensions for reference, not for construction. cD
imensions for reference, not for construction.
a Dimensions for reference, not for construction.
6/52
Molded Case Circuit Breakers
Selection
Internal Accessories
Accessories for: Shunt Trip / Undervoltage Release
STD 3200A Frame Control Voltage Shunt Trip Under Voltage Release
STD Breakers are built to order. It is AC DC Catalog Number Catalog Number
recommended that accessories be ordered 120 — STDST120▲ STDUV120▲ 694.00
installed in the breaker. They may also be 240 — STDST240▲ STDUV240▲ 694.00
field added. 480 — STDST480▲ STDUV480▲ 694.00
600 — STDST600▲ STDUV600▲ 694.00
Ammeter Dispay Module — 012 STDST12▲ STDUV12▲ 694.00
— 024 STDST24▲ STDUV24▲ 694.00
The STDDM plugs into the trip unit of the — 048 STDST48▲ STDUV48▲ 694.00
— 125 STDST125▲ STDUV125▲ 694.00
STD 3200 Amp breaker. It provides readout
of currents as well as load current alarm (in Auxiliary Switches
conjunction with the display module relay).
Control Voltage Quantity Contacts
Ground Fault Monitor AC DC NO NC Catalog Number
1 1 STDAS2▲ 355.00
The Ground Fault Monitor for the STD 2 2 STDAS4▲ 584.00
3200 Amp breaker family plugs into the Trip 600 300 3 3 STDAS6▲ 876.00
Unit and reads the ground current. This is 4 4 STDAS8▲ 1170.00
either the residual current calculated from 5 5 STDAS10▲ 1468.00
the measured three phases and neutral (if 6 6 STDAS12▲ 1739.00
present) or the directly measured ground
return current in the ground lead of the
Alarm Switch Auxiliary Power Module
supply transformer, depending on the Control Voltage Catalog
Power Source Catalog Number
configuration of the the trip unit. In addition AC DC Number 120V AC STDAPM▲ 642.00
to displaying the ground current, the display 600 300 STDAS▲ 686.00
module provides an alarm on ground
overcurrent, settable at three pickup levels Electronic Bell Alarm / Display Relay
with three delays (in conjunction with the
Control Voltage Bell Alarm Display Module Relay
display module relay).
AC DC Catalog Number Catalog Number
120 — STDBA120▲ STDDMR120▲ 694.00
— 24 STDBA24▲ STDDMR24▲ 694.00
— 48 STDBA48▲ STDDMR48▲ 694.00
— 60 STDBA125▲ STDDMR125▲ 694.00
6
STDGFM▲ 3669.00
BREAKERS
24V DC STDDMR24▲
Mounting Bracket for
CIRCUIT
48V DC STDDMR48▲
125V DC STDDMR125▲ Terminal Block
For mounting Control Terminal Blocks to
breakers. One per each side as required.
Catalog Number
STDTBM▲ 87.00
Secondary Terminal Blocks
The appropriate number and location of terminal blocks should be selected from the table below based on the features and accessories ordered on
each circuit breaker. Control Terminal Blocks also require separate mounting brackets for the left and right sides.
Accessory
Zone Auxiliary Switches
Contact Under- Remote Interlock Bell Alarm 1A and 1B 4A and 4B
Block Catalog Shunt voltage Neutral Indication and or Display 2A and 2B 5A and 5B
Position Number Trip Release Sensor Panel ACCESS Module Relay 3A and 3B 6A and 6B
LEFT TOP STDTBLT▲ 145.00 — — — — —
LEFT BOTTOM STDTBLB▲ 145.00 — — — — — —
RIGHT TOP STDTBRT▲ 145.00 — — — — — —
RIGHT BOTTOM STDTBRB▲ 145.00 — — — — — —
▲ Built to order. Allow 7-9 weeks for delivery. is required at location remote from the trip unit in
The STD trip unit has built in trip status indication. addition to the intrinsic trip unit capability.
Use the STDRIP120 when display of the cause of trip
6/53
Molded Case Circuit Breakers
Selection
Magnetic Trip Only — ETI Motor Circuit
Instantaneous Trip Range Complete Circuit Breaker Without Lugs
Catalog Catalog
Breaker Ampere Number Number
Type Rating Minimum Maximum 2-Pole 3-Pole
001 002.6 00009 — ED63A001 737.00
002 007 00022 — ED63A002 737.00
003 010 00035 — ED63A003 737.00
005 016 00054 — ED63A005 737.00
010 030 00100 — ED63A010 737.00
ED6-A 025 055 00180 — ED63A025 737.00
600V AC 030 080 00270 — ED63A030 737.00
250V DC 040 115 00375 — ED63A040 737.00
050 180 00600 — ED63A050 886.00
100 315 01000 — ED63A100 941.00
125 500 01250 — ED63A125 1786.0
SHIPPING: 3.8 lbs. each
001 002.6 00009 — CED63A001■2514.0
002 007 00022 — CED63A002■ 2514.0
003 010 00035 — CED63A003■ 2514.0
005 016 00054 — CED63A005■ 2514.0
010 030 00100 — CED63A010■2514.00
CED6-A 025 055 00180 — CED63A025■2514.00
600V AC 030 080 00270 — CED63A030■2514.00
250V DC 040 115 00375 — CED63A040■2514.00
050 180 00600 — CED63A050■3005.00
100 315 01000 — CED63A100■3226.00
125 500 01250 — CED63A125■ 4837.00
SHIPPING: 6 lbs. each
150 0400 00800 — FXD63L150■3084.00
FXD6 150
150
0800
1100
01500
02500
—
—
FXD63A1503084.00
FXD63H1503084.00
600V AC
250V DC 250 1100 02500 — FXD63A2503084.00
SHIPPING: 0 9 lbs. each
150 0400 00800 — CFD63L150■5960.00
CFD6 150
150
0800
1100
01500
02500
—
—
CFD63A150■5960.00
CFD63H150■5960.00
600V AC
250 1100 02500 — CFD63A250■5960.00
250V DC
SHIPPING: 12 lbs. each 12 lbs. each
JXD6(A) 400
400
1250
2000
02500
04000
—
JXD62H400■
JXD63L4003226.00
JXD63H4003226.00
600V AC
250V DC SHIPPING: 16 lbs. each 20 lbs. each
CJD6 400
400
1250
2000
02500
04000
CJD62L400■
CJD62H400■
CJD63L400■6923.00
CJD63H400■6923.00
600V AC
6
LXD6(A) 600
600
2000
3000
04000
06000
LXD62L600■
—
LXD63L600■
LXD63H600
4710
40.00
600V AC
250V DC SHIPPING: 16 lbs. each 20 lbs. each
CLD6 600
600
2000
3000
04000
06000
CLD62L600■
CLD62H600■
CLD63L600■
CLD63H600■
1108200
11082.0
600V AC
250V DC SHIPPING: 31.5 lbs. each
LMXD6
BREAKERS
CIRCUIT
Important Information
ETI interrupting ratings are determined through combination tests with properly sized overload relays and contactors.
Connectors included when ordering by circuit breaker catalog number for
ED6 and CED6 ETI’s. Order ETI circuit breaker and lugs (2 per pole) separately
for the FXD6, CFD6, MXD6, CMD6, JXD6, CJD6, LXD6 and CLD6 ETI’s.
Lug Information pages 6/69 to 6/71
Accessories pages 6/73 to 6/86
Application data pages 6/55 to 6/59
6/54
Molded Case Circuit Breakers
application
Motor Circuits
General continuous-current ratings of at least circuit protection for the motor branch
115% of motor full-load currents. The circuit. The adjustable instantaneous-trip
Protection of Motor Circuits trip-setting positions are approximately feature of the Siemens ETI motor circuit
Molded case circuit breakers are used in 11 times motor full-load currents. The protector provides for a trip setting slightly
motor circuits as a disconnecting means suggested trip settings may have to be above the peak motor-inrush current.
and for short-circuit protection. They adjusted upward to no higher than 1300% With this setting, no delay is introduced
should be used in conjunction with motor- of full-load current for non-design E type in opening the circuit when a fault occurs.
running, over-current-protection devices, motors, and no greater than 1700% of This circuit breaker has no time-delay
and should permit the motor to start full load current for design B & E energy trip element. Therefore it must be used
without nuisance tripping from motor- efficient motors, to allow for motor start- in conjunction with, and immediately
inrush current. The circuit breaker should up due to inrush currents. ahead of, the motor-running overcurrent
have a continuous-current rating of Breaker Mounted Immediately Ahead protective device.
not less than 115% of the motor of Motor Starter Important: The information below does
full-load current. not apply to all motor applications: it
Siemens ETI motor circuit protectors are
The recommended motor circuit is recommended that the user refer to
recommended for use in combination
protectors (Siemens ETI instantaneous the National Electrical Code (NEC) for
motor starters to provide selective short-
only circuit breakers) listed have specific needs.
Motor ETI Trip Setting ETI Trip Setting ETI Trip Setting
Full Load Catalog Adjust- Motor Full Catalog Adjust- Motor Full Catalog Adjust-
Amperes Number ment Amperes Load Amperes Number ment Amperes Load Amperes Number ment Amperes
.20 – .33 Low 2.6 38.46 – 55.37 Low 500 231.00 – 264.00 Low 3000
.34 – .45 2 4.5 55.38 – 70.75 2 720 264.00 – 292.00 2 3430
.46 – .56 ED63A001 3 6 70.76 – 84.60 ed63a125 3 920 330.00 – 362.00 lxd63h600 4 4290
.57 – .68 CED63A001 4 7.5 84.61 – 96.14 ced63a125 4 1100 395.00 – 428.00 cld63h600 6 5140
.69 – .81 High 9 96.15 – 113.60 High 1250 428.99 – 462.00 7 5570
.53 – .83 Low 7 30.76 – 35.37 Low 400 462.00 – 490.00 High 6000
.84 – 1.14 2 11 35.38 – 39.99 2 460 215.00 – 238.00 Low 2800
1.15 – 1.45 ed63a002 3 15 44.51 – 49.23 fxd63l150 4 580 238.00 – 261.00 2 3100
1.46 – 1.68 ced63a002 4 19 53.84 – 58.45 cfd63l150 6 700 261.00 – 284.00 3 3400
1.69 – 2.00 High 22 58.46 – 63.06 7 760 308.00 – 369.00 lmxd63l800 5 4000
.76 – 1.29 Low 10 63.07 – 74.50 High 820 369.00 – 423.00 6 4800
1.30 – 1.75 2 17 61.53 – 69.22 Low 800 423.00 – 462.00 7 5500
1.76 – 2.29 ed63a003 3 23 69.23 – 76.91 2 900 462.00 – 490.00 High 6000
2.30 – 2.68 ced63a003 4 30 84.61 – 92.29 fxd63a150 4 1100 246.00 – 269.00 Low 3200
2.69 – 3.18 High 35 100.00 – 108.00 cfd63a150 6 1300 269.00 – 284.00 2 3500
1.23 – 1.99 Low 16 108.00 – 115.00 7 1400 284.00 – 323.00 3 3700
2.00 – 2.75 2 26 115.00 – 136.00 High 1500 362.00 – 492.00 lmxd63a800 5 4700
6
2.76 – 3.52 ed63a005 3 36 85.00 – 100.00 Low 1100 492.00 – 562.00 6 6400
3.53 – 4.14 ced63a005 4 46 100.00 – 115.00 2 1300 562.00 – 616.00 7 7300
4.15 – 4.90 High 54 131.00 – 146.00 fxd63a250 4 1700 616.00 – 660.00 High 8000
2.30 – 3.83 Low 30 162.00 – 177.00 cfd63a250 6 2100 231.00 – 264.00 Low 3000
3.84 – 5.37 2 50 177.00 – 192.00 7 2300 264.00 – 292.00 2 3430
5.38 – 6.52 ed63a010 3 70 192.00 – 227.00 High 2500 292.00 – 330.00 3 3800
6.53 – 7.68 ced63a010 4 85 95.00 – 110.00 Low 1250 362.00 – 395.00 mxd63l800 5 4710
7.69 – 9.10 High 100 110.00 – 124.00 2 1430 428.00 – 462.00 cmd63l800 7 5570
138.00 – 151.00 jxd63l400 4 1790 462.00 – 490.00 High 6000
BREAKERS
4.23 – 6.91 Low 55
6.92 – 9.61 2 90 165.00 – 178.00 cjd63l400 6 2140 308.00 – 352.00 Low 4000
CIRCUIT
9.62 – 11.91 ed63a025 3 125 178.00 – 192.00 7 2320 352.00 – 442.00 2 4570
11.92 – 13.83 ced63a025 4 155 192.00 – 227.00 High 2500 442.00 – 447.00 3 5740
13.84 – 16.40 High 180 154.00 – 176.00 Low 2000 483.00 – 527.00 mxd63a800 5 6280
176.00 – 198.00 2 2290 571.00 – 616.00 cmd63a800 7 7240
6.15 – 10.37 Low 80 616.00 – 660.00 High 8000
10.38 – 14.22 2 135 220.00 – 242.00 jxd63h400 4 2860
14.23 – 18.06 ed63a030 3 185 264.00 – 285.00 cjd63h400 6 3430 385.00 – 440.00 Low 5000
18.07 – 20.75 ced63a030 4 235 285.00 – 308.00 7 3710 495.00 – 550.00 mxd63h800 3 6430
20.76 – 24.50 High 270 308.00 – 326.00 High 4000 605.00 – 660.00 cmd63h800 5 7860
155.00 – 176.00 Low 2000 660.00 – 695.00 6 8575
8.84 – 14.22 Low 115
14.23 – 19.60 2 185 176.00 – 198.00 2 2290
19.61 – 24.99 ed63a040 3 255 220.00 – 242.00 lxd63l600 4 2860
25.00 – 28.83 ced63a040 4 325 264.00 – 285.00 cld63l600 6 3430
28.84 – 34.00 High 375 285.00 – 308.00 7 3710
308.00 – 326.00 High 4000
13.84 – 23.06 Low 180
23.07 – 31.52 2 300
31.53 – 39.99 ed63a050 3 410
40.00 – 46.14 ced63a050 4 520
46.15 – 54.50 High 600
24.23 – 41.52 Low 315
41.53 – 56.91 2 540
56.92 – 68.45 ed63a100 3 740
68.46 – 76.91 ced63a100 4 890
76.92 – 90.90 High 1000
6/55
Molded Case Circuit Breakers
APPLICATION
Motor Circuits
Breaker Mounted at a Distance From circuit-breaker ratings in Table 2 provide Interrupt Ratings
Motor Starter adequate time delay for starting the For normal commercial purposes, available
ET thermal-magnetic circuit breakers majority of three-phase induction motors. fault current can conveniently be obtained
conform to the National Electrical Code To determine the ampere ratings of the in the Interrupting Selector Tables.
(2002) table 430-52 requirements for ET breaker to protect a motor feeder,
motor branch and feeder circuit protection add the rating of the ET breaker used to
when properly applied in conjunction protect the largest motor branch circuit in
with motor-running overcurrent protective the group to the full-load currents of the
devices. The recommended remaining motors in the group.
200 and 208V Motors 230V Motors 460V Motors 575V Motors
Motor 240V Circuit Breaker Data 240V Circuit Breaker Data 480V Circuit Breaker Data 600V Circuit Breaker Data
Horse-
power Breaker Catalog Ampere Breaker Catalog Ampere Breaker Catalog Ampere Breaker Catalog Ampere
Rating Type Number Rating Type Number Rating Type Number Rating Type Number Rating
0001⁄2 BQ3B015 015 BQ3B015 015 ED43B015 015 ED63B015 015
0003⁄4 BQ3B015 015 BQ3B015 015 ED43B015 015 ED63B015 015
001 BQ3B015 015 BQ3B015 015 ED43B015 015 ED63B015 015
BQ
BQ
ED4 ED6
0011⁄2 BQ3B015 015 BQ3B015 015 ED43B015 015 ED63B015 015
002 BQ3B020 020 BQ3B015 015 ED43B015 015 ED63B015 015
003 BQ3B030 030 BQ3B020 020 ED43B015 015 ED63B015 015
005 BQ3B040 040 BQ3B030 030 ED43B015 015 ED63B015 015
0071⁄2 BQ3B060 060 BQ3B050 050 ED43B030 030 ED63B020 020
010 BQ
BQ3B070 070 BQ
BQ3B070 070 ED4 ED43B030 030 ED6 ED63B030 030
015 BQ3B100 100 BQ3B090 090 ED43B040 040 ED63B035 035
020 — — BQ3B100 100 ED43B050 050 ED63B050 050
025 FXD63B125 125 FXD63B125 125 FXD63B090 090 FXD63B060 060
030 FXD63B150 150 FXD63B150 150 FXD63B100 100 FXD63B070 070
FXD6
040 FXD6 FXD63B175 175 FXD6 FXD63B175 175 FXD6 FXD63B125 125 FXD63B090 090
050 FXD63B200 200 FXD63B200 200 FXD63B150 150 FDX63B100 100
FXD63B225 225
060 JXD2 JXD23B300 300 — — — FXD6, FD6 FXD63B150 150 FXD6 FXD63B100 100
075 JXD2 JXD23B400 400 JXD2 JXD23B350 350 FXD6, FD6 FXD63B200 200 FXD6, FD6 FXD63B125 125
FD6 FD63B250 250
100 JXD2 JXD23B400 400 JXD2 JXD23B400 400 FXD6, FD6 FD63B175 175
JD6 JD63B250 250
LD6 or LD63B600 LD6 or LD63B500 or FXD6, FD6 FXD63B200 200
125 600 500 JD6
JD63B300 300
LMD6 LMD63B600 LMD6 LMD63B500 OR JD6 JD63B200 200
LD6 or LD63B600 or LD63B600 or FXD6 or FXD63B225 225
150 600 LMD6 600 JD6 JD63B300 300
LMD6 LMD63B600 LMD63B600 JD6 JD63B225 225
6
200 LMD6 LMD63B800 800 LMD6 LMD63B800 800 JD6 JD63B350 350 JD6 JD63B300 300
250 — — — — — — JD6 JD63B400 400 JD6 JD63B400 400
LD6 or LD63B600 or
300 — — — — — — 600 JD6 JD63B400 400
LMD6 LMD63B600
LD6 or LD63B500 or 500
350 — — — — — — LMD6 LMD63B700 700
LMD6 LMD63B500
400 — — — — — — LMD6 LMD63B800 800 LD6 or LD63B600 or 600
LMD6 LMD63B600
500 — — — — — — — — — LMD6 LMD63B800 800
BREAKERS
CIRCUIT
The selection of breakers for this table is in accordance reduced voltage starting. For non-interchangeable trip applications, substitute the FXD6
with Article 430, 2002 National Electric Code. The Canadian for the FD6, the JXD6 for the JD6, or the LXD6 for
electrical code should also be referred to for rating For panelboard applications, substitute the BL breaker for the the LD6.
information. Recommended circuit breakers are for full BQ, ED2 circuit breakers may also be used.
voltage starting, special consideration is necessary for
6/56
Molded Case Circuit Breakers
Application
Adjustable Instantaneous Magnetic Trip Settings
Maximum Nominal ETI Motor Circuit Protector Thermal Magnetic
Breaker Continuous AC Adjustable Trip Range Catalog Number Catalog Number
Type Amperes Low 2 3 4 5 6 7 High 3-Pole 2-Pole 3-Pole
1 2.6 4.5 6 7.5 — — — 9 ED63A001 — —
2 7 11 15 19 — — — 22 ED63A002 — —
3 10 17 23 30 — — — 35 ED63A003 — —
5 16 26 36 46 — — — 54 ED63A005 — —
10 30 50 70 85 — — — 100 ED63A010 — —
ED6 25 55 90 125 155 — — — 180 ED63A025 — —
30 80 135 185 235 — — — 270 ED63A030 — —
40 115 185 255 325 — — — 375 ED63A040 — —
50 180 300 410 520 — — — 600 ED63A050 — —
100 315 540 740 890 — — — 1000 ED63A100 — —
125 500 720 920 1100 — — — 1250 ED63A125 — —
1 2.6 4.5 6 7.5 — — — 9 CED63A001 — —
2 7 11 15 19 — — — 22 CED63A002 — —
3 10 17 23 30 — — — 35 CED63A003 — —
5 16 26 36 46 — — — 54 CED63A005 — —
10 30 50 70 85 — — — 100 CED63A010 — —
CED6 25 55 90 125 155 — — — 180 CED63A025 — —
30 80 135 185 235 — — — 270 CED63A030 — —
40 115 185 255 325 — — — 375 CED63A040 — —
50 180 300 410 520 — — — 600 CED63A050 — —
100 315 540 740 890 — — — 1000 CED63A100 — —
125 500 720 920 1100 — — — 1250 CED63A125 — —
70 600 640 690 730 770 810 850 900 — FXD62B070 FXD63B070
80 600 640 690 730 770 810 850 900 — FXD62B080 FXD63B080
90 600 640 690 730 770 810 850 900 — FXD62B090 FXD63B090
100 700 770 840 920 990 1060 1140 1200 — FXD62B100 FXD63B100
110 700 770 840 920 990 1060 1140 1200 — FXD62B110 FXD63B110
125 800 900 1000 1100 1200 1300 1400 1500 — FXD62B125 FXD63B125
150 400 460 520 580 640 700 760 820 FXD63L150 — —
FXD6-A 150 800 900 1000 1100 1200 1300 1400 1500 FXD63A150 FXD62B150 FXD63B150
150 1100 1300 1500 1700 1900 2100 2300 2500 FXD63H150 — —
175 900 1060 1210 1370 1520 1780 1930 2000 — FXD62B175 FXD63B175
200 900 1060 1210 1370 1520 1780 1930 2000 — FXD62B200 FXD63B200
225 1100 1300 1500 1700 1900 2100 2300 2500 — FXD62B225 FXD63B225
250 1100 1300 1500 1700 1900 2100 2300 2500 FXD63A250 FXD62B250 FXD63B250
70 600 640 690 730 770 810 850 900 — FD62B070 FD63B070
80 600 640 690 730 770 810 850 900 — FD62B080 FD63B080
90 600 640 690 730 770 810 850 900 — FD62B090 FD63B090
100 700 770 840 920 990 1060 1140 1200 — FD62B100 FD63B100
110 700 770 840 920 990 1060 1140 1200 — FD62B110 FD63B110
FD6-A 125 800 900 1000 1100 1200 1300 1400 1500 — FD62B125 FD63B125
150 800 900 1000 1100 1200 1300 1400 1500 — FD62B150 FD63B150
175 900 1060 1210 1370 1520 1780 1930 2000 — FD62B175 FD63B175
200 900 1060 1210 1370 1520 1780 1930 2000 — FD62B200 FD63B200
225 1100 1300 1500 1700 1900 2100 2300 2500 — FD62B225 FD63B225
250 1100 1300 1500 1700 1900 2100 2300 2500 — FD62B250 FD63B250
70 600 640 690 730 770 810 850 900 — HFD62B070 HFD63B070
6
80 600 640 690 730 770 810 850 900 — HFD62B080 HFD63B080
90 600 640 690 730 770 810 850 900 — HFD62B090 HFD63B090
100 700 770 840 920 990 1060 1140 1200 — HFD62B100 HFD63B100
110 700 770 840 920 990 1060 1140 1200 — HFD62B110 HFD63B110
HFD6 125 800 900 1000 1100 1200 1300 1400 1500 — HFD62B125 HFD63B125
150 800 900 1000 1100 1200 1300 1400 1500 — HFD62B150 HFD63B150
175 900 1060 1210 1370 1520 1780 1930 2000 — HFD62B175 HFD63B175
200 900 1060 1210 1370 1520 1780 1930 2000 — HFD62B200 HFD63B200
225 1100 1300 1500 1700 1900 2100 2300 2500 — HFD62B225 HFD63B225
250 1100 1300 1500 1700 1900 2100 2300 2500 — HFD62B250 HFD63B250
BREAKERS
70 600 640 690 730 770 810 850 900 — — HHFD63B070
CIRCUIT
80 600 640 690 730 770 810 850 900 — — HHFD63B080
90 600 640 690 730 770 810 850 900 — — HHFD63B090
100 700 770 840 920 990 1060 1140 1200 — — HHFD63B100
110 700 770 840 920 990 1060 1140 1200 — — HHFD63B110
HHFD6 125 800 900 1000 1100 1200 1300 1400 1500 — — HHFD63B125
150 800 900 1000 1100 1200 1300 1400 1500 — — HHFD63B150
175 900 1060 1210 1370 1520 1780 1930 2000 — — HHFD63B175
200 900 1060 1210 1370 1520 1780 1930 2000 — — HHFD63B200
225 1100 1300 1500 1700 1900 2100 2300 2500 — — HHFD63B225
250 1100 1300 1500 1700 1900 2100 2300 2500 — — HHFD63B250
70 600 640 690 730 770 810 850 900 — CFD62B070 CFD63B070
80 600 640 690 730 770 810 850 900 — CFD62B080 CFD63B080
90 600 640 690 730 770 810 850 900 — CFD62B090 CFD63B090
100 700 770 840 920 990 1060 1140 1200 — CFD62B100 CFD63B100
110 700 770 840 920 990 1060 1140 1200 — CFD62B110 CFD63B110
125 800 900 1000 1100 1200 1300 1400 1500 — CFD62B125 CFD63B125
CFD6 150 400 460 520 580 640 700 760 820 CFD63L150 — —
150 800 900 1000 1100 1200 1300 1400 1500 CFD63A150 CFD62B150 CFD63B150
150 1100 1300 1500 1700 1900 2100 2300 2500 CFD63H150 — —
175 900 1060 1210 1370 1520 1780 1930 2000 — CFD62B175 CFD63B175
200 900 1060 1210 1370 1520 1780 1930 2000 — CFD62B200 CFD63B200
225 1100 1300 1500 1700 1900 2100 2300 2500 — CFD62B225 CFD63B225
250 1100 1300 1500 1700 1900 2100 2300 2500 CFD63A250 CFD62B250 CFD63B250
Note: For DC instantaneous trip points, add 15% to nominal values. on circuit breaker, depress indicating knob, then rotate to
Tolerances for instantaneous trip points meet UL 489 (15.3). Instantaneous trip adjustment is made through the breaker desired position.
Nominal AC instantaneous trip points are given in the tables. cover on all frame breakers. To change instantaneous trip point
6/57
Molded Case Circuit Breakers
Application
Adjustable Instantaneous Magnetic Trip Settings
Maximum Nominal ETI Motor Circuit Protector Thermal Magnetic
Breaker Continuous AC Adjustable Trip Range Catalog Number Catalog Number
Type Amperes Low 2 3 4 5 6 7 High 3-Pole 2-Pole 3-Pole
200 1250 1430 1610 1790 1960 2140 2320 2500 — JXD22B200 JXD23B200
225 1250 1430 1610 1790 1960 2140 2320 2500 — JXD22B225 JXD23B225
JXD2(A) 250 1250 1430 1610 1790 1960 2140 2320 2500 — JXD22B250 JXD23B250
300 1250 1430 1610 1790 1960 2140 2320 2500 — JXD22B300 JXD23B300
350 2000 2290 2570 2860 3140 3430 3710 4000 — JXD22B350 JXD23B350
400 2000 2290 2570 2860 3140 3430 3710 4000 — JXD22B400 JXD23B400
200 1250 1430 1610 1790 1960 2140 2320 2500 — JXD62B200 JXD63B200
225 1250 1430 1610 1790 1960 2140 2320 2500 — JXD62B225 JXD63B225
250 1250 1430 1610 1790 1960 2140 2320 2500 — JXD62B250 JXD63B250
JXD6(A)
300 1250 1430 1610 1790 1960 2140 2320 2500 — JXD62B300 JXD62B300
350 2000 2290 2570 2860 3140 3430 3710 4000 — JXD62B350 JXD23B350
400 2000 2290 2570 2860 3140 3430 3710 4000 — JXD62B400 JXD23B400
200 1250 1430 1610 1790 1960 2140 2320 2500 — JD62B200 JD63B200
225 1250 1430 1610 1790 1960 2140 2320 2500 — JD62B225 JD63B225
250 1250 1430 1610 1790 1960 2140 2320 2500 — JD62B250 JD63B250
JD6(A) 300 1250 1430 1610 1790 1960 2140 2320 2500 — JD62B300 JD63B300
350 2000 2290 2570 2860 3140 3430 3710 4000 — JD62B350 JD63B350
400 1250 1430 1610 1790 1960 2140 2320 2500 JXD63L400 — —
400 2000 2290 2570 2860 3140 3430 3710 4000 JXD63H400 JD62B400 JD63B400
200 1250 1430 1610 1790 1960 2140 2320 2500 — HJD62B200 HJD63B200
225 1250 1430 1610 1790 1960 2140 2320 2500 — HJD62B225 HJD63B225
HJD6(A) 250 1250 1430 1610 1790 1960 2140 2320 2500 — HJD62B250 HJD63H250
300 1250 1430 1610 1790 1960 2140 2320 2500 — hjd62b300 hjd63b300
350 2000 2290 2570 2860 3140 3430 3710 4000 — hjd62b350 hjd63b350
400 2000 2290 2570 2860 3140 3430 3710 4000 — hjd62h400 hjd63b400
200 1250 1430 1610 1790 1960 2140 2320 2500 — hhjd62b200 hhjd63b200
225 1250 1430 1610 1790 1960 2140 2320 2500 — hhjd62b225 hhjd63b225
HHJD6 250 1250 1430 1610 1790 1960 2140 2320 2500 — hhjd62b250 hhjd63b250
300 1250 1430 1610 1790 1960 2140 2320 2500 — hhjd62b300 hhjd63b300
350 2000 2290 2570 2860 3140 3430 3710 4000 — hhjd62b350 hhjd63b350
400 2000 2290 2570 2860 3140 3430 3710 4000 — hhjd62b400 hhjd63b400
200 1250 1430 1610 1790 1960 2140 2320 2500 — — cjd63b200
225 1250 1430 1610 1790 1960 2140 2320 2500 — — cjd63b225
250 1250 1430 1610 1790 1960 2140 2320 2500 — — cjd63b250
cjd6 300 1250 1430 1610 1790 1960 2140 2320 2500 — — cjd63b300
350 2000 2290 2570 2860 3140 3430 3710 4000 — — cjd63b350
400 2000 2290 2570 2860 3140 3430 3710 4000 cjd63h400 — chd63b400
400 1250 1450 1610 1790 1960 2140 2320 2500 cjd63l400 — —
450 2000 2290 2570 2860 3140 3430 3710 4000 — lxd62b450 lxd63b450
lxd6(A) 500 3000 3430 3860 4290 4710 5140 5570 6000 — lxd62b500 lxd63b500
600 3000 3430 3860 4290 4710 5140 5570 6000 — lxd62b600 lxd63b600
250 1250 1430 1610 1790 1960 2140 2320 2500 — ld62b250 ld63b250
300 1250 1430 1610 1790 1960 2140 2320 2500 — ld62b300 ld63b300
350 2000 2290 2570 2860 3140 3430 3710 4000 — ld62b350 ld63b350
6
LD6(A) 400 2000 2290 2570 2860 3140 3430 3710 4000 — ld62b400 ld63b400
450 2000 2290 2570 2860 3140 3430 3710 4000 — ld62b450 ld63b450
500 3000 3430 3800 4290 4710 5140 5570 6000 — ld62b500 ld63b500
600 2000 2290 2570 2860 3140 3430 3710 4000 lxd63l600 — —
600 3000 3430 3800 4290 4710 5140 5570 6000 lxd63h600 ld62b600 ld63b600
250 1250 1430 1610 1790 1960 2140 2320 2500 — hld62b250 hld63b250
300 1250 1430 1610 1790 1960 2140 2320 2500 — hld62b300 hld63b300
350 2000 2290 2570 2860 3140 3430 3710 4000 — hld62b350 hld63b350
hld6(A) 400 2000 2290 2570 2860 3140 3430 3710 4000 — hld62b400 hld63b400
BREAKERS
CIRCUIT
450 2000 2290 2570 2860 3140 3430 3710 4000 — hld62b450 hld63b450
500 3000 3430 3860 4290 4710 5140 5570 6000 — hld62b500 hld63b500
600 3000 3430 3860 4290 4710 5140 5570 6000 — hld62b600 hld63b600
250 1250 1430 1610 1790 1960 2140 2320 2500 — hhld62b250 hhld63b250
300 1250 1430 1610 1790 1960 2140 2320 2500 — hhld62b300 hhld63b300
350 2000 2290 2570 2860 3140 3430 3710 4000 — hhld62b350 hhld63b350
hhld6 400 2000 2290 2570 2860 3140 3430 3710 4000 — hhld62b400 hhld63b400
450 2000 2290 2570 2860 3140 3430 3710 4000 — hhld62b450 hhld63b450
500 3000 3430 3860 4290 4710 5140 5570 6000 — hhld62b500 hhld63b500
600 3000 3430 3860 4290 4710 5140 5570 6000 — hhld62b600 hhld63b600
250 1250 1430 1610 1790 1960 2140 2320 2500 — — cld63b250
300 1250 1430 1610 1790 1960 2140 2320 2500 — — cld63b300
350 2000 2290 2570 2860 3140 3430 3710 4000 — — cld63b359
400 2000 2290 2570 2860 3140 3430 3710 4000 — — CLD63b400
CLD6
450 2000 2290 2570 2860 3140 3430 3710 4000 — — cld63b450
500 3000 3430 3860 4290 4710 5140 5570 6000 — — cld63b500
600 2000 2290 2570 2860 3140 3430 3710 4000 cld63l600 — —
600 3000 3430 3860 4290 4710 5140 5570 6000 cld63h600 — cld63b600
500 3000 3430 3860 4290 4710 5140 5570 6000 — — lmxd63b500
600 3000 3430 3860 4290 4710 5140 5570 6000 — lmxd62b600 lmxd63b600
lmxd6 700 3200 3500 3700 4200 4700 6400 7300 8000 — lmxd62b700 lmxd63b700
800 2800 3100 3400 3700 4000 4800 5500 6000 lmxd63l800 — —
800 3200 3500 3700 4200 4700 6400 7300 8000 lmxd63A800 lmxd62b800 lmxd63b800
500 3000 3430 3860 4290 4710 5140 5570 6000 — lmd62b500 lmd63b500
600 3000 3430 3860 4290 4710 5140 5570 6000 — lmd62b600 lmd63b600
lmd6
700 3200 3500 3700 4200 4700 6400 7300 8000 — lmd62b700 lmd63b700
800 3200 3500 3700 4200 4700 6400 7300 8000 — lmd62b800 lmd63b800
6/58
Molded Case Circuit Breakers
Application
Adjustable Instantaneous Magnetic Trip Settings
Maximum Nominal ETI Motor Circuit Protector Thermal Magnetic
Breaker Continuous AC Adjustable Trip Range Catalog Number Catalog Number
Type Amperes Low 2 3 4 5 6 7 High 3-Pole 2-Pole 3-Pole
500 3000 3430 3860 4290 4710 5140 5570 6000 — — HLMXD63B500
600 3000 3430 3860 4290 4710 5140 5570 6000 — — HLMXD63B600
HLMXD6 700 3200 3500 3700 4200 4700 6400 7300 8000 — — HLMXD63B700
800 3200 3500 3700 4200 4700 6400 7300 8000 — — HLMXD63B800
500 3000 3430 3860 4290 4710 5140 5570 6000 — HLMD62B500 HLMD63B500
600 3000 3430 3860 4290 4710 5140 5570 6000 — HLMD62B600 HLMD63B600
HLMD6 700 3200 3500 3700 4200 4700 6400 7300 8000 — HLMD62B700 HLMD63B700
800 3200 3500 3700 4200 4700 6400 7300 8000 — HLMD62B800 HLMD63B800
500 3000 3430 3860 4290 4710 5140 5570 6000 — MD62B500 MD63B500
600 3000 3430 3860 4290 4710 5140 5570 6000 — MD62B600 MD63B600
700 4000 4570 5140 5710 6280 6850 7420 8000 — MD62B700 MD63B700
MD6 800 3000 3430 3860 4280 4710 5140 5570 6000 MXD63L800 — —
800 4000 4570 5140 5710 6280 6850 7420 8000 MXD63A800 MD62B800 MD63B800
800 5000 5715 6430 7145 7860 8575 9290 10000 MXD63H800 — —
500 3000 3430 3860 4280 4710 5140 5570 6000 — MXD62B500 MXD63B500
600 3000 3430 3860 4280 4710 5140 5570 6000 — MXD62B600 MXD63B600
700 4000 4570 5140 5710 6280 6850 7420 8000 — MXD62B700 MXD63B700
MXD6 800 3000 3430 3860 4280 4710 5140 5570 6000 MXD63L800 — —
800 4000 4570 5140 5710 6280 6850 7420 8000 MXD63A800 MXD62B800 MXD63B800
800 5000 5715 6430 7145 7860 8575 9290 10000 MXD63H800 — —
500 3000 3430 3860 4280 4710 5140 5570 6000 — HMD62B500 HMD63B500
600 3000 3430 3860 4280 4710 5140 5570 6000 — HMD62B500 HMD63B600
HMD6 700 4000 4570 5140 5710 6280 6850 7420 8000 — HMD62B700 HMD63B700
800 4000 4570 5140 5710 6280 6850 7420 8000 — HMD62B800 HMD63B800
500 3000 3430 3860 4280 4710 5140 5570 6000 — — HMXD63B500
600 3000 3430 3860 4280 4710 5140 5570 6000 — — HMXD63B600
HMXD6 700 4000 4570 5140 5710 6280 6850 7420 8000 — — HMXD63B700
800 4000 4570 5140 5710 6280 6850 7420 8000 — — HMXD63B800
400 3000 3430 3860 4280 4710 5140 5570 6000 — — CMD63B400
500 3000 3430 3860 4280 4710 5140 5570 6000 — — CMD63B500
600 3000 3430 3860 4280 4710 5140 5570 6000 — — CMD63B600
CMD6 700 4000 4570 5140 5710 6280 6850 7420 8000 — — CMD63B700
800 3000 3430 3860 4280 4710 5140 5570 6000 CMD63L800 — —
800 4000 4570 5140 5710 6280 6850 7420 8000 CMD63A800 — CMD63B800
800 5000 5715 6430 7145 7860 8575 9290 10000 CMD63H800 — —
800 4000 4570 5140 5710 6280 6850 7420 8000 — ND62B800 ND63B800
900 5000 5715 6430 7145 7860 8575 9290 10000 — ND62B900 ND63B900
ND6 1000 5000 5715 6430 7145 7860 8575 9290 10000 — ND62B100 ND63B100
1200 5000 5715 6430 7145 7860 8575 9290 10000 — ND62B120 ND63B120
900 5000 5715 6430 7145 7860 8575 9290 10000 — NXD62B900 NXD63B900
NXD6 1000 5000 5715 6430 7145 7860 8575 9290 10000 — NXD62B100 NXD63B100
1200 5000 5715 6430 7145 7860 8575 9290 10000 — NXD62B120 NXD63B120
800 4000 4570 5140 5710 6280 6850 7420 8000 — HND62B800 HND63B800
6
900 5000 5715 6430 7145 7860 8575 9290 10000 — HND62B900 HND63B900
HND6 1000 5000 5715 6430 7145 7860 8575 9290 10000 — HND62B100 HND63B100
1200 5000 5715 6430 7145 7860 8575 9290 10000 — HND62B120 HND63B120
900 5000 5715 6430 7145 7860 8575 9290 10000 — — HNXD63B900
HNXD6 1000 5000 5715 6430 7145 7860 8575 9290 10000 — — HNXD63B100
1200 5000 5715 6430 7145 7860 8575 9290 10000 — — HNXD63B120
800 4000 4570 5140 5710 6280 6850 7420 8000 — — CND63B800
900 5000 5715 6430 7145 7860 8575 9290 10000 — — CND63B900
CND6 1000 5000 5715 6430 7145 7860 8575 9290 10000 — — CND63B100
BREAKERS
1200 5000 5715 6430 7145 7860 8575 9290 10000 — — CND63B120
CIRCUIT
1200 5000 5715 6430 7145 7860 8575 9290 10000 — — PD63B120
PD6 1400 5000 5715 6430 7145 7860 8575 9290 10000 — — PD63B140
1600 5000 5715 6430 7145 7860 8575 9290 10000 — — PD63B160
1200 5000 5715 6430 7145 7860 8575 9290 10000 — — PXD63B120
PXD6 1400 5000 5715 6430 7145 7860 8575 9290 10000 — — PXD63B140
1600 5000 5715 6430 7145 7860 8575 9290 10000 — — PXD63B160
1200 5000 5715 6430 7145 7860 8575 9290 10000 — — HPD63B120
HPD6 1400 5000 5715 6430 7145 7860 8575 9290 10000 — — HPD63B140
1600 5000 5715 6430 7145 7860 8575 9290 10000 — — HPD63B160
1200 5000 5715 6430 7145 7860 8575 9290 10000 — — HPXD63B120
HPXD6 1400 5000 5715 6430 7145 7860 8575 9290 10000 — — HPXD63B140
1600 5000 5715 6430 7145 7860 8575 9290 10000 — — HPXD63B160
1200 5000 5715 6430 7145 7860 8575 9290 10000 — — CPD63B120
CPD6 1400 5000 5715 6430 7145 7860 8575 9290 10000 — — CPD63B140
1600 5000 5715 6430 7145 7860 8575 9290 10000 — — CPD63B160
1800 5000 5715 6430 7145 7860 8575 9290 10000 — — RD63B180
RD6 2000 5000 5715 6430 7145 7860 8575 9290 10000 — — RD63B200
1800 5000 5715 6430 7145 7860 8575 9290 10000 — — RXD63B180
RXD6 2000 5000 5715 6430 7145 7860 8575 9290 10000 — — RXD63B200
1800 5000 5715 6430 7145 7860 8575 9290 10000 — — HRD63B180
HRD6 2000 5000 5715 6430 7145 7860 8575 9290 10000 — — HRD63B200
6/59 6/59
Molded Case Circuit Breakers
selection
Molded Case Switch — Circuit Disconnect
2-Pole 3-Pole
Maximum Self-Protective Ordering Information
Frame Catalog Catalog Instantaneous
Rating Number Number Override±20% Order by catalog number. Switches
BQ2S060 ■ 68.00 BQ3S060■ 314.00 11000A include frame and self protective
1100A (except TD) trip unit only. Order lugs
BQ2S100■ 181.00 BQ3S100■ 314.00 11000A
1125A ED22S100A■ 257.00 ED23S100A 437.00 11000A separately from pages 6-70 to 6-72.
ED42S100A■ 541.00 ED43S100A 664.00 11000A
ED42S125A■1035.00 ED43S125A 1337.00 11000A
ED62S100A■ 624.00 ED63S100A 800.00 11000A
— — ED63S125A 1527.00 11000A
CED62S100A■2325.00 CED63S100A■2907.00 11000A
CED62S125A■3509.00 CED63S125A■4172.00 11000A
1225A QJ22S225A■ 273.00 QJ23S225A 886.00 12000A
1250 FXD62S250A 1451.00 FXD63S250A 1758.00 13200A
HFXD62S250A■ HFXD63S250A■3060.00 13200A
— CFD63S250A■5644.00 13200A
1400 JXD22S400A■1833.00 JXD23S400A2262.00 16000A
— —2539.00 JXD63S400A 3087.00 16000A
— HJXD63S400A■5208.00 16000A
CJD63S400A■6434.00 16000A
1600 — LXD63S600A4442.00 18000A
— HLXD63S600A■5942.00 18000A
CLD63S600A■10450.00 18000A
1800 — LMXD63S800A■5104.00 10000A
— MXD63S800A5104.00 10000A
CMD63S800A11857.00 10000A
1200 — NXD63S120A9016.00 10000A
CND63S120A■16930.00 10000A
1600
PXD63S160A13326.00 10000A
2000
RXD63S200A■14762.00 10000A
Non Automatic Molded Case Switch
2000
TD63S2000■19413.00 —
2500
TD63S2500■21856.00 —
3200
TD63S3200■24053.00 —
4000-5000 See “SB” Type Insulated Case Breakers
6
BREAKERS
CIRCUIT
6/60
Molded Case Circuit Breakers
technical
Digital Solid State Sentron Sensitrip III Series
The Sentron Sensitrip III circuit Functions available in Sentron Sensitrip circuit breakers.
breaker is a true RMS current sensing Short
device. Digital microprocessor Cont Long Instan- Short Short Time Ground Ground
circuitry within the electronic trip unit Catalog Number Trip Current Time taneous Time Time l2t Fault Fault
provides more precise control over the (Description + Suffix) Type Setting Delay Setting Pick Up Delay Pick Up Pick Up Delay
circuit breaker functions. This control Basic Unit + (A) LI — — — — —
allows circuit coordination flexibility Basic Unit + (A)G LIG — — —
not available with thermal magnetic Basic Unit + (A)NT LSI — —
circuit breakers. Basic Unit + (A)NGT LSIG
Letter “A” is used for MD and ND Solid State frame types only.
Typical Trip Unit Labeling and Adjustment Positions for the Sentron Sensitrip Circuit Breaker.
6/61
Molded Case Circuit Breakers
technical
Digital Solid State Sentron Sensitrip III Series
A. Adjustable “Continuous D. Adjustable “Short Time
Amps” Rating Switch Pick-Up” Switch (Optional)
ll Sensitrip III solid
A ensitrip III circuit breakers
S
state molded case with an adjustable short
circuit breakers have an time pick-up switch allow for
adjustable ampere rating selection of short time
switch. Adjustments made pick-up in a range from 1.5
to this switch change the to 10 times the setting of the
continuous current rating of maximum current rating.
the breaker from 20% to E. Adjustable “Short Time
100% of its maximum trip Delay” Switch (Optional)
unit rating depending on the
circuit breaker frame. ensitrip III circuit breakers
S
with an adjustable short time
B. Adjustable “Long Time pick-up switch also contain a
Delay” Switch switch for adjustment in time
ll Sensitrip III circuit
A delay. The adjustable short
breakers have an adjustable time delay switch allows for
long time delay switch to either of two modes of short
allow for selection of long time delays. One range of
time delays of fixed time settings enables the breaker
intervals at six times the to be set for fixed time
setting of the adjustable delays and the other range of
“continuous amps” rating settings enables the breaker
switch. to be set for short time
delays based on l2t curves.
C. Adjustable “Instantaneous
Pick-Up” Switch
ensitrip III circuit breakers
S
with an adjustable
instantaneous trip switch
allow selection of a tripping
point from related to the
adjusted circuit breaker
Rating (lr).
djustable “Ground Fault Pick-Up”
A
Switch
ensitrip III circuit breakers
S
containing the optional equipment
ground fault protection cover the
ground fault pick-up range of 20% to
70% of the circuit breaker frame
rating. The ground fault pick-up
settings also allow for one of three
time delays based on 12t curves.
For 3-phase, 4-wire systems, an
external neutral transformer is
required with an ampere rating equal
to the trip unit ampere rating.
6
ln = 800 amperes. Instantaneous set at 10 x lr = 10 x 560 = 5600 l2t switch on .28 seconds @ 6 x 560 = 3360 amperes.
lr
amperes. (Inverse time)
= 560 amperes (70% of 800).
Short
Time Pick-Up On — Set at 8 = 8 x 560 = 4480 Ground Fault Pick-Up set at 40 = 40% of ln = 320
Delay =2
0 seconds at 3360 amps (6 x lr).
amperes. amperes. (Definite Time)
Breaker will trip in 20 seconds with 3360
amperes. Short Time Delay = .5 seconds. (Definite Time) Ground Fault Delay set at .2 seconds. Breaker will trip in
Note: & are mutually exclusive. 200 milliseconds with a 400 ampere ground fault.
Short Time Pick-Up Off — Instantaneous can be used.
6/62
SB Encased System Breakers
WL Power Circuit Breakers — Insulated Case general
3-pole,
800 up to
to 5000 5000A Frame Rating
Ampere General
Breaker Description
Description CSA / UL / IEC Symmetrical RMS Amperes Interrupting Ratings
The ever-increasing use of plant and
® SB Breakers
Trip Units ▪ Manual operating mechanism with
Siemens
energySENTRON
management systems has
SB Encased Systems Breaker
mechanical and electrically
provide maximum flexibility, The electronic, micro processor-based Frame Amperage Rating c
forwith
Voltage
intensified the demand circuit trip unit Measurement
Standard is auxiliary voltage-independent
AC 400 800 interlocked
1200 2000 closing
3200 4000 5000
four principal frame size envelopes:
breakers supporting multiple open for all protective functions and enables A.I.R. (KA):▪ Motorized
Blue Label operating mechanism with
1200, 2000, 3200, and 5000 amperes. Type SBA–Alternate
protocols to monitor and control the flow adaptation to the different240 protection mechanical
085 and—electrically
— interlocked
Applications include mains, ties, feeders, 065 065 065 —
of energy in the power system. The closing.065
Operating
and emergency source breakers in requirements of distribution
480 systems,
065 065 065 — mechanisms
— —with
extensive and modular WL family of motors, transformers and electrically interlocked closing are
industrial plants, commercial installations, 600 generators.
042 042 042 050 — — —
circuit breakers and accessories provides suitable for synchronizing tasks
and health care facilities. SB Breakers Non-Automatic Switch
Type SBS–Standard A.I.R. (KA): Black Label
this
combine forhigh
applications from
interrupting 200A to 5000A.
ability Interrupting
A specialRatings–
version of the240 100
circuit breaker 100
is Auxiliary
100 Contacts
100 150 150 150
withApplications
extended short time tripping for Symmetrical
successful application used as RMS
CSA/UL a non-automatic 480 switch.100 100 Auxiliary switches100
100 100 can be100added accord-
100
WL breakers can beinapplied
fully-rated
as main, tie, (489) Amperes
ing
050to the065
type of085
installation.
085 They085are
systems, The non-automatic switch 600 is constructed
050 050
feeder while providingbreakers
or distribution completein
easily mounted via front, top mounted
selectivity through the applied without a trip unit andType has SBH–High
no protective
A.I.R. (KA): Red Label
low-voltage electrical powerbreaker’s
systems. terminal blocks.
short time rating. This assures the highest function. A possible application
240 is for use
N/A N/A N/A 200 200 200 200
Versions
possible reliability and availability from as a tie in systems with 480parallelN/A
feeds. N/A N/A 150 150 150 150
Modularity
Framedistribution
the▪ power ratings: 800A to5000A
system. Main Bus Connectors600 N/A N/A N/A 100 100
Common guide frames for the draw-out
100 100
The▪ circuit breaker
3 physical mechanism
frame sizes is a true Short Time Ratings 0 0 0 0 0 0 0
Breakers(KA)tare =equipped
.5 secondswith standard
25 25 version
25 make
35 them 50 completely
65 inter-
65
two-step stored energy system that
▪ Rated nominal operating voltage upvertical main bus connections. Horizontal changeable between the UL 489 / CSA and
allows for a maximum five cycle closing lcu
to 600VAC bus connections are available 100 100 100 / UL
ANSI 100 100 circuit
1066 rated 100 breakers.
100
for distribution bus paralleling. IEC Interrupting 415 lcs as an
▪ Seven interrupting classes from 50kA option inRatings-
947-2 Frame Size 1 andlcw 2 up025to 025 Components,
025 035 such 050as auxiliary
065 releases,
065
SB Breakers
to 200kAExceed
at 480VUL Requirements (For SBS Symmetrical
2000A. lcu 0 0 motorized
0 0 operating0 mechanisms,
0 0 trip
Breakers RMS Amperes 65 65 65 current
units, 65 sensors, 65 65
auxiliary 65
SB▪ Breakers complyor
Circuit breaker with worldwide switch
non-automatic Communication
Only) (50HZ) Capability
690 lcs
industry standards and are UL Listed lcw 025 025 signal
025 switches,
035 automatic
050 065reset devices
065
WL Circuit Breakers aredelivered MODBUS or PROFIBUS communica-
as or interlocks can be used to modify or
and▪ CSA certified for enclosed operation
complete assembled breakers or
at 100% in both fixed and drawout
SBtions
Frame transmitSizes, Ratings,
the acquired and Rating
metered Plugs & Dimensions
retrofit any circuit breaker to meet
individual frames, guide frames, and data, such as current values, breaker
Frame changing requirements. The main con-
Moveable
mounting configurations. The robust,
accessories status, trip
Frame log, etc. Rating
Ampere to a central
Plugs Fixed
tacts canMounting
be replacedDrawoutto extend Mounting
the life
self-cooling SB Breaker design requires Sizes
Rating
(Amperes) (H x W x D) (H x W x D)
no Installation Types even when
additional ventilation, monitoring computer. When the optional of the circuit breaker and feature inte-
operated at 100% or of the Frameversion.
Ampere metering function is200,
0400 installed,
225, 250, the WL
300, 350, 400
grated contact wear indicators.
Fixed-mounted Draw-out
Rating. acquires0800
1200A data useful400, for 450,
power500, 600, 700, 800 12.0 x 15.5 x 12.5 13.75 x 20.5 x 16.0
Standards management 1200 and can 600,contribute to a 1200
700, 800, 1000, Electronic Trip Unit Modularity
CIRCUIT BREAKERS
MOLDED CASE
Internal Accessories significant1200savings in600, energy costs.
700, 800, 1000,A1200 Modularity is the outstanding feature of
▪ WL ANSI / UL 1066 Circuit Breakers 2000A 16.75 x 15.5 x 12.5 19.8 x 20.5 x 16.0
Electric Motor C37.13,
will satisfy: OperatorC37.16, C37.17, new, internal
2000 circuit 1000, breaker1200,bus enables
1600, 2000 the new WL Circuit Breakers. The trip
C37.50, NEMA SG3 the expansion
2500 of breaker functionality
1600, 2000, 2500 units themselves can be retrofitted with
Local Electric Close 3200A 27.5 x 15.5 x 12.5 35.0 x 21.5 x 16.0
through 3200the integration 1600,of2000,
many 2500, 3000, 3200 special LCDs, ground fault modules,
6
▪ WL UL&489
Auxiliary AlarmCircuit Breakers will
Switches secondary functions which were rating plugs and communication
satisfy: UL 489 / CSA C22.2 NO.5 2500 1600, 2000, 2500
Undervoltage Release (UVR) previously separate, including: modules.100% Rated Circuit Breaker WL
3200 1600, 2000, 2500, 3000, 3200
▪ WL Trip
Circuit Breakers are suitable for 5000A circuit
27.5 xbreakers
23.5 x 12.5are designed
35.0 x 29.5for
x 16.0
Shunt
use in UL 1558 LV Switchgear and UL ▪ Control of analog 2000,
4000 displays2500, 3000, 3200, 4000
continuous operation at 100% of their
Remote
891 LVOpen/Close
Switchboards & Alarm Relay ▪ Options 5000for testing2500,the3000, 3200, 4000, 5000
current rating without the need for
communication setup
Conditions
External of Application
Accessories external heat sinks.
▪ Display of breaker status and reason
BREAKERS
WL Circuit
Ground Breakers
Fault Sensingare
anddesigned
Relaying to for trip Conditions of Application
CIRCUIT
meet
Key standard
Interlock andIndustrial
Padlock and Commercial
Features Input modules for reading other WL Circuit Breakers are designed to
application requirements. ▪
Drawout Padlock and Close Blocking external signals and transmitting meet standard Industrial and Commercial
Uniform Dimensions these signalsvia PROFIBUS or application requirements.
Cell Switches
WL Circuit Breaker dimensions differ MODBUS communication
Drawout Safety Shutters
only in the device width, which varies by
Secondary ▪ A selection of output modules to
frame size.Disconnect & TerminalofBlock
With the exception the provide contact closures based on
T200kA
Connectors
ANSI Frame Size II which has an events or measured-value setpoints.
additional
Neutral 5" in depth
Sensing to accommodate
Transformers It is not only possible to monitor the
integral fuses. breaker remotely, it is also possible
Lifting Device Jacket
to open and close the breaker as well
Auxiliary PowerRequirements
Minimal Space Supply
as setting parameters remotely
Dead
The WL Front Shield
design is extremely compact
without Operating Mechanisms
Trip Unit sacrificing
Retrofit Kitsperformance and does
not use energy-wasting heat sinks. Circuit breakers can be optionally
PC and Network Communications
delivered with different operating
mechanisms, including:
▪ Manual
Consult Siemensoperating mechanism
Sales Office for with
pricing and production Breaker Frame Size refers to the physical breaker
mechanical
schedule. SB Price andclosing
Selection (standard)
Guide IPPS-2209 is also envelope size.
available. Breaker Frame Ampere Rating is determined by the
current sensors in the breaker.
6/63
SB Encased System Breakers
WL Power Circuit Breakers GENERAL
Electronic Trip
Electronic TripUnits
Units General
Selection criteria for WL Circuit
Two types of interchangeable trip units displays. Both units offer unique models Advanced True RMS Current Sensing
forBreakers
the SB Encased Systems Breakers to provide an efficient combination of Both the basic type “TL” and the
are
The available. The basic
basic criteria type “TL”circuit
for selecting Trip options versus cost for every application. premium SB-EC Trip Unit feature
Unit features
breakers is: a full range of industry advanced digital-processing techniques to
standard protective settings Interchangeable Rating Plugs
▪ MaximumSystems Available Shortand the high-
Circuit measure the true heating content of the
performance Breaker SB Breaker trip units use field
at the installation point. ThisEnergy
value current waveform. This True RMS value of
Communicating Trip short
Unit (SB-EC Trip Unit) interchangeable rating plugs allowing current measurement virtually eliminates
determines the circuit current
offers advanced rating
metering, protective the effective ampere rating of the circuit nuisance tripping due to the presence of
interrupting or short circuit
relaying, time-stamped logs, and power breaker to be field-modified and provides harmonics on the distribution bus.
current withstand rating of the circuit
quality monitoring functions, including an security against indiscriminate changes in
breaker
integral keypad and LCD graphical display the breaker’s ampere rating.
Rated Current
for▪ menu-driven In which
system is to flow and
configuration
through the respective circuit
real-time voltage and current waveform breaker
continuously. This value may not be
greater than the maximum rated
current of the circuit breaker. The rated
Communications
the rating plug, up to the maximum
All frame
SB Circuit
ratingBreaker trip units control, including peak demand, trend that allows data exchange to
feature two levels of communication: analysis,
Trip waveform
Unit Functions analysis, and other Windows software such as
▪ Ambient
Zone Selective
Temperature
Interlocking
of the circuit
and harmonic calculations and displays. spreadsheets and word-processors.
breaker. This is usually the
ACCESS ™ System Open-protocol TheseBfunctions
asic Protecthelp ive Fupinpoint
nctions energy ETU72are
Protocol Converters 5 available
ETU7from
27
temperature inside the cubicle L o n g - t im e o v e rc u rr ent proissues,
tection L
communications, allowing integration consumption, power quality Siemens for connection to a variety
Short-time delayed overcurrent protection S
▪ Design
into Siemens of the
WinPMcircuit breaker.
™ V4.0 and the energy cost of any process. of open and proprietary automation
Protectivesoftware,
Functionsalongof the circuit Instantaneous overcurrent protection I
supervisory with Outages and potential outages can
Neutral conductor protection
protocols,
N
including
—
Profibus DP,
breaker. These
thirdare determined
energy by the be quickly
other popular party Groundiagnosed
d fault proteand ction plans can LonWorks,
G the Siemens
— S7 PLC,
selectionnetworks
monitoring of the appropriate trip unit
and components. be generated for expansion and and many other third party PLCs and
Additional Functions
WinPM™ V4.0 delivers a powerful preventative plant maintenance. associated networks. The SB-EC Trip
Selectable neutral protection —
energy management system providing Communications is accomplished via Unit’s EIA-232 communications
Defeatable short-time protection
sophisticated monitoring capability to a EIA-485 twisted pair wire or modem,
Defeatable instantaneous protection
port provides additional
—
local PC—
host computer and other components providing
Selecommunications
ctable thermal memto orya remote communications for — available trip— unit
in the electrical distribution system site and
Zonallowing
e selective access
interloctokinmultiple
g data displays and — trip unit configuration
—
at an affordable cost. It also provides electable™I2utilizes
plants.SWinPM t or fixeda sWindows
hort-time delay via Siemens SBWin — ™ software. —
process DDE (dynamic
Adjustabledata instaexchange)
ntaneous piserver
ck-up — —
Selectable I2t or I4t long-time delay — —
Adjustable short-time delay and pick-up
Selectable and adjustable neutral protection — —
Dual protective setting capability — —
Dynamic arc-flash sentry — —
6
PC Grasp,hD Ce
alvLic
ice DN — —
nWork
S DP, Lo
PROFIBU Metering Function
Metering function — —
Data Transfer Link
Metering function Plus — —
Communication Win PM
CubicleBUS Power Meters — —
Communication via PROFIBUS-DP — —
Access Communication via the MODBUS — —
MT Communication via the Ethernet (BDA) — —
SB
Breaker
MCCBs
6/64
SB Encased System Breakers
WL Power Circuit Breakers general
ElectronicTrip
Electronic Trip Units
Units General
SB-EC Trip Unit Frame Rating Indication:
indicates the frrame
rating of the circuit
Features by Model Type breaker with which the
trip unit is used
Feature SBxxTP01 SBxxTP01G SBxxTP02 SBxxTP02G
Integral Keypad & Display System Status System Check Indicators:
Voltage/Current Waveform Displays Indicators: Two green LEDs blink to
Yellow LED indicates indicate that protective
Protective Functions an alarm condition, and metering systems
Long Time, Short Time, Instantaneous red LED indicates a trip are working correctly
Metering Functions condition
Volts, Amps, PF, Frequency, Watts, VARs,
VA, Crest Factor, Ampand Watt Demand, LCD Display:
Voltage and Current Waveforms, Voltage provides fast,
and Current Unbalance convenient
Communications display of
menu options
PC (RS-232), ACCESS (RS-485) and device
Counters status
Breaker Test (Trip/No Trip), Mechanical
Counter, Interruption Level Fault Counter
Security
Password Protection
Trip Unit Functions
Event Log
Basic ProtectiveMost
FunctRecent
ions Events ETU745 ETU748 ETU755 ETU776
Time-stamped—10
Trip Long-time
Log overcurrent protection L
Time-stamped—5
Short-time delayedMost overcurrent
Recent Eventsprotection S
Instantaneous overcurrent protection
Alarms I
ESC Key:
(Alarm
NeuOnly)
tral coOvercurrent,
nductor protGnd.
ection N used to exit
Overcurrent,
Ground faOver
ult pAmp
rotectDemand,
ion Over G menus
kW Over kW Demand, Phase Sequence,
OverAdditional
KVAR, Over Functions
KVA, Under/Over P.F.
Selectable
Advanced neutral protection
Alarms — —
TotalDefeatable
Harmonicsshort-time protection —
Defeatable
Min./Max. Logs instantaneous protection — Enter Key:
Selectable thermal memory — — for selection
Volt/Amp, Power, PF, Freq., %THD of choices
Zone selective interlocking or moving
Harmonic Analysis — —
Up toSelectable I2t or fixed
19th Per Phase, THD short-time delay
Up and Down Arrows: between
Adjustable instantaneous pick-up — for convenient selections
Protective Relay Functions scrolling through
Selectable I2t or I4t long-time delay choices on LCD
(Alarm and/or Trip)
Adjustable
Neutral short-time
Overcurrent, delay
Current and pick-up
Balance,
Selectable
Under/Over and adjustable
Voltage, neutral protection —
Voltage Unbalance, — EIA232 Serial Port: Test Connector:
Dual Power,
Reverse protectUnder/Over
ive setting cFrequency,
apability — — for direct connection easy connection to
Phase to a personal portable TS-31 test
DyLoss
6
namic arc-flash sentry — —
computer set for functional
Extended
Ground instantaneous protection
Fault Protection — testing
—
Residual or Ground Return
Parameterization and Displays
Parameterization by rotary switches (10 steps) — —
WaveParameterization
Form Displays by communication (absolute values)
Siemens WinPM—™ Version 4.0 or later via the trip unit’s EIA-232 or EIA-485
Parameterization by menu/keypad (absolute values) —
or SBWin™ Software to display the— —
communication ports or a hard-wire
The SB-EC
RemoteTrip Unit offers digital
parameterization of the basic functions — —
waveform sampling as a standard waveforms and automatically perform
feature functions input. For remote operation via a
BREAKERS
Remote parameterization of the additional — —
that allows a real-time harmonic analysis using Fast Fourier communication port, WinPM Version 4.0
LCD graphical view
CIRCUIT
Alphanumeric — —
of a complete
Graphical Lcycle
CD of line and neutral transformation techniques.
—
Both the—
or later,—Shunt Trip and Remote Open/
currents or phase voltages, including resident trip unit and the PC-based Close Relay accessories are required
Metering Function
voltage and current phase relationships harmonic analysis functions provide for the remote open function, and an
Metering function the value of Total Harmonic Distortion Electrical Operator accessory is required
and harmonic distortion.
Metering function Plus
On-board
harmonic analysis functions are available (THD) of the waveforms and are useful in addition for both remote open and
Communication
on premium units, allowing harmonic in locating the source and severity of close operations.
up to the 19th multiple and
CubicleBUS
analysis harmonics and developing corrective For remote operation via a hard-wire
Communication via PROFIBUS-DP
permitting the data to be viewed and strategies. input, only a Shunt Trip accessory is
Communication via the MODBUS necessary for the remote open function,
examined on the integral LCD graphical
Communication via the Ethernet (BDA) Remote Operation
panel. Sampled data can also be stored and an Electrical Operator is additionally
Standard — Not available Optional Remote, automatic open and close required for both remote open and
in memory and transmitted to a PC via
the serial communications port, using operation of the breaker is possible close operations.
Further Information
Refer to SB Encased Systems Breaker Bulletin IPPS-2209E
for additional price and catalog information. SB-EC Trip
Unit Product Bulletins are also available (IPPS-2208B,
IPFL-2207A).
6/65
SB Encased
WL SystemBreakers
Power Circuit Breakers
GENERAL
3-Pole, up to Trip
Electronic 5000AUnits General
Rating Plug a wide range of locking devices can be ▪ Spring charge indicator Rating Plug
ItBasic Type necessary
is no longer “TL” TriptoUnit replace the installed or retrofit, including:
▪ Rear vertical main contacts
current transformer to change the rated ▪ Lockable drawout version to protect
Available
current of Type “TL” Features
the breaker. Instead,by youModel ▪ Main contact replacement flag
against unauthorized removal
simply replace the rating plug which is Catalog Number (standard) ▪ Auxiliary plug system with bare wire
easily accessible
Trip Unit Function on the front of the tripSB T pressure screw terminals. Delivery
unit. The circuit breaker is set to the new
Adjustable Continuous Current ▪
High
degree
of protection
through includes all auxiliary plugs necessary for
rated current quickly and is already Plexiglas cover
Adjustable
correctly Long Time Delay
labeled. both factory installed and future field
Adjustable
Long TimeShort Time PickupProtection —
Overcurrent ▪ Mechanical
— reclosing
lockout after installed accessories
2 long-time, short-time or instantaneous
with Switchable I2t/I4t Characteristics
Adjustable Short Time Delay (l T) — —
trip (optional)
▪ Mechanical trip indicator Curveof the
The long time
Adjustable Shortovercurrent
Time Delay (Fixed) — — overcurrent releaseAdjustments
system
protection
Adjustable in the ETU745,
Instantaneous ETU755 and
Pickup ▪ Devices
— with —trip unit ETU745 or ▪ Automatic reset after trip
ETU776 trip units can be switched
Adjustable Ground Fault Pickup — —
higher
—
are equipped with temperature
▪ The front panel cannot be removed if
between an I2t and I4t characteristic to sensors on the BSS and
Adjustable
improve Ground Faultbetween
coordination (l2T) —
Time Delayupstream — — the circuit breaker closed
COM15/COM16 (standard)
circuit breakers
Adjustable GF TimeandDelay
fuses.
(Fixed) — — —
Lock provision for locking the breaker ▪ Laminated main contact fingers as part
Front
Fixed Panel
Instantaneous Override ▪ of the breaker contact strip on
in the OPEN position
The frontWatchdog
Internal panel is designed so that it can the drawout circuit breaker
beIntegral
accessed
Testing through
Functions a cutout in the ▪ Lockable
covers for
the CLOSE button
door, which means that all controls and ▪ Breaker position display in the
Local Trip Indication:
displays are accessible even when the ▪ Lockable racking handle prevents operator’s panel
Overload moving the breaker
cubicle door is closed. The front panels
of all Frame
Short TimeSize II and Frame Size III ▪ Lockable
— charging
handle prevents
▪ Captive crank handle Fault forindicators
racking out
circuit breakers the breaker
Short Circuit are identical, and allow charging
thesprings
for two different through-door access
Ground Fault — Standard
Version
Features ▪ Guide frame withBuilt-in guide rails for easy
designs: Trip unit and front panel controls handling of draw-out Testversion
Functions
orAccess
front Communications
panel controls only. The degree
Compatibility
WL Circuit Breakers
have the following
ofCatalog
protection
Number of Suffix
the front
panel is IP 20.LI standard
LSI LS equipment:
LIG LSG LSIG ▪ Breaker cannot be moved in the
Environmental Protection CLOSED state Plug-in
▪ Mechanical CLOSE and mechanical
The plastics used are halogen-free and OPEN push buttons ▪ Rated current coding between
Display Module the
recyclable. guide frame and the breaker
▪ Manual operating mechanism with
Safety and Reliability mechanical closing ▪ Suitable for reverse feed applications
In order to help protect the electrical ▪ The breaker is always equipped with
distribution system and circuit breaker ▪ Contact position indicator
the required number of secondary
against unauthorized trip
The interchangeable breaker operations,
unit system of Front panel ready-to-close
All▪ standard trip units feature: indicator Choose the appropriate
disconnect blocks function
the SB breaker showcases the latest Integral Testing Functions
package and catalog number as shown
Exclusive
advancementsFeatures in microprocessor below:
Built-in Trip Indicators
controlled circuit protection technology.
Generator/Utility Dynamic Arc-Flash Sentry (DAS) employs Example: breakerSwith B 2 an0 T'LS'
L S trip
G unit, or when
6
Protection
Using the speed Sets and power of its Instantaneous
the unique dual“Override”
protective setting capa- the instantaneous function is switched
microprocessor
24/7/365 power to drive sophisticated
availability is critical for bility of the 755 and 776 trip units, cou-
Continuous Self-Diagnostic
off on an 'LSI' trip unit, can only be
digital systems.
some sampling On-site
techniques, the SBcapa-
generation trip pled with
“Watchdog” the ability to easily toggle to a applied up to it's short-time rating,
unit measures
bility is growingthe trueand
more heating
morecontent
common lower arc flash parameter set. A normal commonly 85kA or less. For application
System LED
operation on frontset
parameter covercan be opti- on systems with Breaker levels of Catalog
available fault
in
of many systems.
the current All of the
waveform (RMS WLcurrent)
digital
electronic trip units allow the system mized for selective trip coordination, current above the
Frame short-timeNumberrating, the
hundreds of times each second, typical 'LS' power circuit
designer to precisely tailor trip
effectively eliminating nuisance tripping settings while the second set is optimized for
Available protective function Ampere Suffix cannot
breaker
for the most demanding requirements. lower arc flash energy levels. The be applied or must employ an instanta-
BREAKERS
CIRCUIT
6-78
6/66
Molded Case Circuit Breakers
selection
Electronic and Communications Accessories
Electronic & Display Devices
Trip Unit Test Set SADU Ammeter Display Unit
Type Catalog Number
Portable TS31 12372.00
Spare TS-31 Test Set Interconnecting Cable TS31CABLE 168.00
The TS-31 test set is used to test the operation of the fault protection functions of the
circuit breaker’s trip unit, including long-time, short-time, instaneous, and ground fault
by means of secondary current injections.
Sensitrip Ammeter Display Unit
Breaker Type Catalog Number
SJD, SLD, SMD, SADU 1588.00
SND, SPD SADURMK18 306.00
The Sensitrip Ammeter Display Unit (SADU) provides real-time metering for all Sentron-
Sensitrip III Molded Case Circuit Breakers. The unit plugs directly onto the front of the
trip unit and provides displays for individual phase currents flowing through the breaker.
Additional features include Average, Demand, Ground and Unbalance Current displays,
along with impending Trip Status. Current Metering Logs, and a unique diagnostic Trip
Log that records the date, time and type of fault for the previous five breaker trips. The • Direct plug-in or Panel Mounting*
device is UL and CSA certified. • Trip Unit Powered & Battery back-up
The optional panel mount accessory (SADURMK18) allows easy device mounting • 2 x 16 LCD Alphanumeric Display*
external from the circuit breaker, in panelboard and switchboard spaces or gutters, with • Ammeter Diplay Functions
the flexibility of interior panel exterior panel, or wall mounting capability. — RMS Phase Currents
The 2 x 16 alphanumeric LCD display provides easy viewing of data, such as viewing all — Average Current*
three phase currents simultaneously. — Current Demand*
— Ground Current
Plug-in Mounting
— Current Unbalance (%)*
• Breaker Status
— Normal
— Impending Trip*
• Time Stamped Trip Log (last 5)
6
— Time & Date*
— Trip Cause: LT, ST, GF, SC
• Max Log (with date & time)
— Max Phase Current*
— Max Average Current*
— Max Ground Current*
BREAKERS
— Max Unbalance Current*
CIRCUIT
— Max Current Demand*
* Unique Features
6/67
Molded Case Circuit Breakers
Selection
Communications Accessories
Multiplexor Translator
Breaker Type Features Cat No
SJD, SLD Zone Interlocking Only MTZ 1740.00
SMD, SND
SPD, STD Full Communications
MTA 3876.00
SBA, SBS, SBH with Zone Interlocking
Telephone Cables
Breaker Type Length Cat No
08˝ MTCSB08 ▲ 70.00
SB 15˝ MTCSB15 ▲ 105.00
STD 25˝ MTCSB25 ▲ 139.00
50˝ MTCSB50 ▲ 139.00
ACCESS™ Communicationsa SJD, SLD 8˝ MTC08 70.00
SMD, SND, 15˝ MTC15 105.00
All SB Circuit Breaker trip units feature two levels of SPD, 25˝ MTC25 139.00
communication: Zone Selective Interlocking and ACCESS™ SBA, SBS, SBH 50˝ MTC50 139.00
System Open-protocol communications. The SB-EC Trip Unit is The Expansion Plug EP is a required isolating device to connect the breaker
fully equipped for direct integration into ACCESS™ or compatible with the Multiplexor Translator. It is connected to the trip unit on the
communication systems. breaker with a “Ribbon Cable”, EPC08 e.g., and the Multiplexor Translator
with the “Telephone Cable” (an RJ-11 cable) MTCSB08 e.g.
A multiplex/Translator (MTA) and Expansion Plug area required
for the TYPE “TL” trip unit when full Access™ communications is Expansion Plug Selection Guide
specified. The MTA also has Zone Selective Interlocking capability.
Breaker Frame Mounting Cat.
Refer to Bulletin IPIM-2211A and Instruction Sheet Pc. No. Type Size Type No
411152A00 for additional information.
SB ICCB and 1200A, Fixed EPSBFMK■ 187.00
Siemens WinPM™ V4.0 supervisory software delivers a powerful STD 2000A Draw out EPSBDMK■ 187.00
6
6/68
Lug Information
Selection
Mechanical Lug
For Use Circuit Breaker Cables Per Catalog
With Type(s) Ampere Rating Lug Lug Wire Range Number
Line Side
1 #14–#6 AWG Cu
15–40 TC1Q1 (Pkg. of 6) 13.90
1 #12–#6 AWG Al
1 #8–#1 AWG Cu
50–100 TA1Q1 (Pkg. of 6) 12.20
1 #6–#1/0 AWG Al
BQ, BQH, Load Side
BQHF, 1 #14–#10 AWG Cu
15–20
BQE, 1 #12–#10 AWG Al
BQF, 1 #14–#6 AWG Cu
25–35
BL, BLH, 1 #12–#6 AWG Al
HBL, 1 #8–#6 AWG Cu Lugs are integral to
40–50
HBQ 1 #8–#4 AWG Al Circuit Breaker
Switching 1 #8–#4 AWG Cu
55–70
Neutrals 1 #8–#2 AWG Al
BG 1 #4–#1/0 AWG Cu
80–100
BLG 1 #2–#1/0 AWG Al
1 #2–#1/0 AWG Cu
110–125
1 #1/0–#2/0 AWG Al
Line Side (CQD, CQD6) & Load Side
BQD, CQD #14–#6 AWG Cu
15–40 1 Integral
BQD6, CQD6 #12–#6 AWG Al
#8–#1 AWG Cu
45–100 1 Integral
#6–#1/0 AWG Al
#14–#6 AWG Cu
15–40 1 TC1Q1 (pkg. of 6) 13.90
#12–#6 AWG Al
#8–#1 AWG Cu
50–100 1 TA1Q1 (pkg. of 6) 12.20
NGG #6–#1/0 AWG Al
#6–#1/0 AWG Cu
110–125 1 3TA1GG20 (pkg. of 3) 12.00
#4–#2/0 AWG Al
15–125 — NUT KEEPER PLATE TNKG3 (Pkg. of 3)
16.00
6
BREAKERS
CIRCUIT
Note:
(A) M
olded case circuit breakers having a rated ampacity Lug
is steel.
of 125 amperes or less are to be connected with 60 or Sold
in package of six.
75°C wire. Circuit breakers having a rated ampacity Use on load side only.
greater than 125 amperes shall only be cabled with One nut keeper plate is required with each lug on the
75°C cable unless otherwise indicated on the circuit NGG breaker.
breaker label. Exceptions to this rule are outlined in the
2002 National Electrical Code and Canadian Electrical
Code.
6/69
Lug Information
Selection
Aluminum Body Lugs for Copper or Aluminum Wire
For Use Circuit Breaker Cables Per Catalog
With Type(s) Ampere Rating Lug Lug Wire Range Number
QJ2, QJH2 #6 AWG–300 kcmil (Cu)
60–225 1 TA1Q300 (pkg of 3) 12.00
QJ2H, HQJ2H #4 AWG–300 kcmil (Al)
#14–#10 AWG (Cu)
15–25 1
All 2, 3 pole #12–#10 AWG (Al) SA1E025 3.50
ED2, ED4, ED6,
ED6 ETI,
HED4, 30–100 1 #10–#1/0 (Cu or Al) LN1E100 3.50
#3-3/0 (Cu) 10.90
110–125 1 TA1E6125
#1-2/0 (Al)
CED6 LD1E060
30–60 1 #10–4 (Cu or Al) 3.60
All 1 pole (Load Side)
ED, HED
LD1E100
70–100 1 #4–#1/0 (Cu or Al) 3.50
(Load Side)
FXD6-A, FD6-A,
HFD6, #6 AWG–350 kcmil (Cu)
70–250 1 TA1FD350A 19.80
cfd6 #4 AWG–350 kcmil (Al)
HHFD6
SJD6(A),
SHJD6(A) 65-200 1–2 #4 AWG–310 kcmil (Cu or Al) TA2J630 19.80
SCJD6
JXD2(A), JXD6(A),
JD6(A), SJD6(A),
HJD6(A), 3/0–500 kcmil (Cu)
200–400 1–2 TA2J6500 28.00
HHJXD6, HHJD6, 4/0–500 kcmil (Al)
SHJD6(A), CJD6,
SCJD6
LXD6(A), LD6(A),
SLD6(A), HLD6(A),
3/0–500 kcmil (Cu)
HHLXD6, HHLD6, 250–600 1–2 TA2J6500 28.00
4/0–500 kcmil (Al)
SHLD6(A), CLD6,
SCLD6
LMD6, LMXD6,
HLMD6, 500–600 1–2 250–500 kcmil (Cu or Al) TA2K500 64.00
HLMXD6, MD6,
MXD6, SMD6,
HMD6, HMXD6, 1/0–500 kcmil (Cu or Al) TA3K500
SHMD6, CMD6, 700–800 1–3 500–750 kcmil (Cu or Al) TA2N750 87.00
6
SCMD6
ND6, 2TA4P8500 522.00
250–500 kcmil (Cu or Al)
NXD6, SND6, 3TA4P8500 754.00
HND6, HNXD6, 800–1200 1–4
SHND6, CND6, 2TA4N8500 526.00
250–500 kcmil (Cu or Al)
SCND6 3TA4N8500 762.00
PD6, HPD6,
CPD6
PXD6,
BREAKERS
CIRCUIT
Use TA2K500 or TA3K500 only. Contains 2 connectors plus 1 NDTS end barrier.
Used for 100% rated MD/ND frame breakers. Contains 3 connectors plus 1 NDTS end barrier.
6/70
Lug Information
Selection
Optional Mechanical Lugs
For Use Circuit Breaker Cables Per Lug Qty per Catalog
With Type Ampere Rating Lug Material Lug Wire Range Cat. # Number
QJ2, QJH2,
60–225 1 Cu #6 AWG–250 kcmil (Cu) 1 TC1Q250 28.50
QJ2H, HQJ2H
ED, HED 2&3 pole 2–3 pole 30-125 1 Cu #10–#1/0 (Cu) 1 TC1ED6150 30.00
HFD6, HHFD6,
70–250 1 Cu #6 AWG–350 kcmil (Cu) 1 TC1FD350 31.00
CFD6, F(X)D6-A
J(X)D2(A), J(X)D6(A),
1 Cu 3/0–600 kcmil (Cu) 1 TC1J6600 69.00
HJD6(A), HHJD6,
1–2 3/0–500 kcmil (Cu) 1 TC2J6500 68.00
SHJD6(A), L(X)D6(A),
HHLD6, SCD6, 250–600
HLD6(A), SHLD6(A), 1 500–750 kcmil (Al)
CJD6, CLD6, SCJD6, Al 1 TA1L6750 68.00
1 500–600 kcmil (Cu)
SCLD6
SMD6, M(X)D6, 500–600 1–2 Cu #1 AWG–500 kcmil (Cu) 1 TC2K500 107.00
HM(X)D6, HMD6, 1–3 Cu #1 AWG–350 kcmil (Cu) 1 TC3K350 135.00
CMD6, SCMD6, SND6, 700–800 500–750 kcmil (Cu) 2 2TA2N8750 327.00
1–2 Al
N(X)D6, HN(X)D6, 500–750 kcmil (Al) 3 3TA2N8750 459.00
SHND6, CND6, SCND6 500–750 kcmil (Cu) 2 2TA3N8750 517.00
800–1200 1–3 Al 500–750 kcmil (Al) 3 3TA3N8750 744.00
R(X)D6, HR(X)D6 1600–2000 1–5 Cu 300–600 kcmil (Cu) 1 TC5R600 381.00
P(X)D6, HP(X)D6,
1200–1600 1–4 Al 600–750 kcmil (Cu/Al) 1 TA4P750 216.00
CPD6, SPD6, SHPD6
Compression Lugs
Ampere Lugs Lug Wire Catalog
For Circuit Breaker Types Rating Poles Per Kit Size Number
Lugs (contains indicated number of lugs and necessary hardware per kit)
ED2, ED4, ED6, HED4, CED4 15–125 1, 2, 3 1 #2/0 CCE125 24.00
QJ2, QJH2, QJ2-H 125–225 2, 3 1 350 kcmil CCQ225 45.50
F(X)D6-A, HF(X)D6, HHF(X)D6, CFD6 125–250 2, 3 1 350 kcmil CCF250 45.50
JXD2-A, J(X)D6-A, HJ(X)D6-A, HHJ(X)D6-A, CJD6, SJD6-A, SHJD6-A,
200–600 2, 3 1 500 kcmil CCL600 134.00
SCJD6, L(X)D6-A, HL(X)D6-A, CLD6, SLD6-A, SHLD6-A, SCLD6
Kits (contain lugs and hardware for complete line or load end of 2 or 3 pole breaker)
2 6 CCM800K2 649.00
M(X)D6, HM(X)D6, CMD6, SMD6, SHMD6, SCMD6 500–800
3 9 CCM800K3 945.00
6
500 kcmil
2 8 CCN1200K2 851.00
N(X)D6, HN(X)D6, CND6, SND6, SHND6, SCND6 900–1200
3 12 CCN1200K3 1246.00
BREAKERS
CIRCUIT
6/71
Molded Case Circuit Breakers
Selection / general
Modifications
A variety of internal and external Modifications
accessories, as well as modifications, 50°C Ambient Calibration — Not UL listed and not available for solid state, 100% rated breakers or
are available to adapt Siemens circuit 400HZ calibrated breakers.
breakers to special installation or BL Type Circuit Breakers
F
requirements. UL listed internal — Add suffix ‘M’ to catalog number (Example: B120M)
accessories for 100 through 2000A For BQ, QJ2, and ED Frame Circuit Breakers
circuit breakers are field-addable. — Replace ‘B’ in catalog number with ‘M’ (Example: BQ3M060, QJ23M200, ED63M060)
Internal accessories fine tune an For FD, JD, LD, LMD, MD, ND, PD, and RD Frame Circuit Breakers
Non-Interchangeable Trip (3–pole only)
electrical distribution system, — Replace ‘B’ in catalog number with ‘M’ (Example: FXD63M225, JXD63M400)
allowing control of the circuit breakers to Interchangeable Trip (trip unit only, 3–pole only)
meet special application requirements. — Replace ‘T’ in catalog number with ‘W’ (Example: FD63W200, JD63W400)
For example, emergency situations may 400 HZ Calibration
dictate tripping critically placed circuit L Listed (5KA IR)
U
breakers quickly. Shunt trips accomplish for BQ, BL, and QJ Type Circuit Breakers (200A max.)
this conveniently and efficiently. — Add suffix ‘Y’ to catalog number
Or, when voltage drops are a concern, Not UL Listed
undervoltage trips automatically open for all other Circuit Breakers — Add suffix ‘Y’ to catalog number
the circuit breaker at a predetermined Fungus Proofing — In accordance with MIL-T-152.
voltage level. ll BQD, CQD, NGG, ED, FD, JD, LD, LMD, MD, ND, PD, and RD, Frame Circuit Breakers are
A
inherently fungus resistant and do not require special treatment.
A wide range of external operating and
Fungus proofing in accordance with MIL-T-152
mounting accessories is also available. For BL, and BQ Type Circuit Breakers
For example, face, shallow, and back — Order must be placed directly with the factory by the sales office.
mounting plates are ideal for tailoring BQ or all other Circuit Breaker Types
F
circuit breakers to OEM applications. — Order must be placed directly with the factory by the sales office.
A complete line of operating handles Certificate of Compliance
and handle-blocking devices meet Certificate of compliance testing must be performed on the actual device being shipped. The
switchboard, enclosure and safety needs. certificate cannot be provided after initial shipment. Order for devices with COC requirement must
be placed directly with the factory by the sales office.
Plug-in mounting assemblies, which
simplify switchboard mounting of circuit
breakers and permit breaker removal
without disconnecting bus or cable
connections, are available.
to subject the breaker to extreme testing at each resonant CED6 E10848, Vol 4, Sec 13
frequency. The second is a swept frequency test, in which the FD6, FXD6, HFD6, HFXD6 E10848, Vol 4, Sec 17
frequency of excitation is changed in intervals of 1Hz, and held at CFD6 E10848, Vol 4, Sec 18
each frequency for five minutes. The excitation frequencies run JXD2, JD6, JXD6, LXD6, LD6, E10848, Vol 4, Sec 8
from 4 to 33Hz, and the test is conducted in each of the three HJD6, HJXD6, HLD6, HLXD6
orthogonal axes of the breaker. HHJD6, HHJXD6, HHLD6, HHLXD6 E10848, Vol 4, Sec 20
During these tests, the breaker must not trip from the closed CJD6, CLD6 E10848, Vol 4, Sec 14
position, nor may the contacts touch from the open position. MD6, MXD6, HMD6, HMXD6, CMD6, E10848, Vol 4, Sec 15
Calibration and insulation resistance are also verified during the test. ND6, NXD6, HND6, HNXD6, CND6
PD6, PXD6, HPD6, HPXD6, CPD6, E10848, Vol 4, Sec 19
For detailed information, refer to UL 489, Supplement SB. RD6, RXD6, HRD6, HRXD6
SBA400, SBS400, SBA800, E9896, Vol 15, Sec 1
SBS800, SBA1200, SBS1200,
SBA1600, SBS1600, SBA2000, SBS2000
6/72
Molded Case Circuit Breakers
general / selection
Internal Accessories
Feature Combinations
The available feature combinations are shown in the chart below. For applications requiring combinations of features not listed in this
chart, consult the sales office for availability.
Shunt Trip (ST) voltage returns to 85% of line voltage. The Alarm Switch (ALSW)
undervoltage trip, which is continuously
One or all critical circuit breakers may energized, must be energized before the The alarm switch contact is closed when
be tripped from a distant control point circuit breaker can be closed. the circuit breaker is opened automatically
by use of a shunt trip device. A shunt by an overload, short circuit, shunt trip or
trip operates through an auxiliary switch Auxiliary Switch (AUX) undervoltage trip. The alarm switch contact
contact; when the breaker opens, current For applications requiring remote “on” or is open when the circuit breaker is reset.
is not maintained on the shunt trip coil.
6
“off” indication (or electrical interlocking),
Undervoltage Trip (UVT) auxiliary switches are available. Each
switch comprises an “A” (open when
When voltage drops to a value below 35% circuit breaker is open) and a “B” (closed
of the nominal coil rating, the undervoltage when circuit breaker is open) contact with
trip device automatically opens the breaker. a common connection. (Form C)
The operation is instantaneous, and the
circuit breaker cannot be reclosed until the
BREAKERS
CIRCUIT
Factory assembled only If mechanical interlock is installed, no accessory module One module per column.
I f
mechanical interlock is installed, no accessory module can be installed.
can be installed in the right pocket. I f mechanical interlock is installed, no accessory module
can be installed in the left pocket.
6/73
Molded Case Circuit Breakers
selection
External Accessories
Handle Ties
Provide simultaneous switching of 2 adjacent handles. Do not provide common trip.
For Use With Catalog Standard Wt Lb/
Breaker Frame(s) Number Package Std Pkg
BQ, BQH, HBQ, B6, BLH, HBL (2 Pole) QTH3 50 1
⁄4
Padlocking Devices
For locking breaker in “OFF” position.
ECQTH3
BQXD,
ECQLD3 10 1
⁄4
BQ, BQH, HBQ, BL, BLH, HBL
One pole BL, BLF, BE, BAF ECPLD1 3 1
⁄4
Two-pole BL, BLF and BE ECPLD2 3 1
⁄4
All QJ HL9419 10 1
⁄4
All BQD, CQD BQDPLD 1 1
⁄8
All ED ED2HPL 1 1
⁄4
All FD FD6PL1 1 1
⁄4
All JD, LD, LMD JD6HPL 1 1
⁄4
1
All MD, ND, PD, RD MN6PLD 1 ⁄4
STD STDPLD ■ 1 1
FD Padlocking Padlocking
Device Device
Filler Plates FD6PLI ECQLD3
BQ, BQH, HBQ, BL, BLH, HBL QF3-UL 1 1
⁄4
Handle Extensions
For replacement. One extension shipped with breaker.
All MD, ND, PD, RD EX11 1 2
STD EXSTD■ — —.00
BREAKERS
CIRCUIT
Handle
Extension
EX11
6/74
Molded Case Circuit Breakers
Selection
External Accessories
Mounting Clips
For Use With Number of Catalog Standard Wt Lb
Breaker Frame(s) Poles Number Package Std Pkg
BQ, BQH 1 MB120 20 ⁄4
1
MB120
6
All QJ MSQJ
1 1
MSF6 1 ⁄4
1
All FD (CFD6 requires 2 kits)
MSF650 50 1
1
All JD, LD MSJ6 1 ⁄4
All LMD MSLMD 1 1
⁄4
1
All MD, ND, MSMN 1 ⁄4
All PD, RD MSPR6 1 2
BREAKERS
Mounting Screw Kit
CIRCUIT
MSE6
“MI” Mechanical Interlocks
For Use With Panel Plug-in Standard Wt Lb
Breaker Type(s) Mounted Mounted Package Std Pkg
BQ — ECQML12 10 1
⁄4
All QJ CSO — 1 1
All FD MI5444 MI5444 Complete with —
two breakers
All JD, LD MI5413 — 1 1
All LMD MI5406 — 1 1
All MD MI5404 ■ — 1 3
All ND MI5404 ■ — 1 3 Mechanical Interlock
All PD, RD MI5405▲ MI5405▲ — — MI5444
STD STDMIF32▲ — — —
■ Built to order. Allow 2–3 weeks for delivery. installed into circuit breaker right pole. Each
package contains 5 strips of 6 each. Each strip can
Addition of the mechanical interlock will prevent be broken at perforations for 1, 2 or 3-pole use.
▲ Built to order. Allow 6–8 weeks for delivery.
Note: C SO = Consult Sales Office accessory installation in the left pole. Mechanical interlock is not designed for use within
Sold only in standard package quantities. Multiply List Siemens panelboards.
K it consists of 4 screws and washers.
Price Each times package quantity for full price.
C onsists of 1 screw and washers (order 100).
C onsists of 1 screw and washers (order 50).
With mechanical interlock in place, no accessory can be
6/75
Molded Case Circuit Breakers
Selection
External Accessories
Rotary Door Mounted Operating Handles
Types 1, 3, 3R , 12, 4 4X
Complete Mechanism Handle Only Breaker Operator Shaft Only
For Use
With Catalog Number
Breaker Standard Variable Catalog Catalog Length Catalog
Frames Depth Depth Number Number (inches) Number
ED CRHOESD CRHOEVD RHOEBO 68.00
2 RHOSSD 28.00
FD CRHOFSD CRHOFVD RHOFBO 117.00
CRHOH 12 RHOSVD 28.00
JD, LD CRHOJSD CRHOJVD RHOJBO
16 RHOSXD 28.00
LMD CRHOLMSD CRHOLMVD RHOLMBO
3 RHONSSD▲ 86.00
MD, ND RHONSD RHONVD RHOH RHONBO214.00 12 RHONSVD 86.00 CRHOH
PD, RD 24 RHONSXD 114.00 RHOH
For 3 or 3R, order shaft and breaker operator as shown, and handle RHOH. For 4 & 4X, order handle RHOH4.
F6RH1
6/76
Molded Case Circuit Breakers
Selection
External Accessories
Max-Flex™, Flange Mounted Variable Depth Operators
Complete Kit Handle Only Breaker Operator 36˝ Cable Cable
6
For use with Max-Flex and Rotary Door operators (FHOH and RHOH). 1 NO and 1 NC contact.
For Use With Catalog Number
ED, JD, LD, LMD, ND, PD, RD, SD, Max Flex HAS1 167.00
BREAKERS
CIRCUIT
Minimum Left Hand Mount Right Hand Mount
Enclosure NEMA
Frames Depth Type Catalog Number Catalog Number
1, 3R, 12 FDFBEL▲ 246.00 FDFBER▲ 246.00
ED 6.44
4, 4X FDFBEL4▲ 329.00 FDFBER4▲ 329.00
1, 3R, 12 FDFBFL▲ 263.00 FDFBFR▲ 263.00
FD 6.44
4, 4X FDFBFL4▲ 349.00 FDFBFR4▲ 349.00
Max-Flex™ handles are available with solid black handles instead of the customary “Red for On” flange handle. These are
preferred for use in IECmarkets, where red handles have specific meaning. Order componenets separately, apppending the
letter “i” to the catalog number (e.g. FHOHI).
FDFBFR
▲ Built to order. Allow 7–9 weeks for delivery. 48inch cable is standard length for M through R frame
For 1- or 2-pole breaker order FHOED036 complete kit or Max-Flex operators.
FHOEDBO breaker operator only.
6/77
Molded Case Circuit Breakers
Selection
External Accessories
Telemand® Motor Operator
AC Hinged to List
Breaker Frame Voltage Open Down Price $
ED except CED 120 MOE6120 3018.00
240 MOE6240 ▲ 3284.00
ED motor operator opens downward.
Operating Currents
On Off
Catalog In-Rush Running Time In-Rush Running Time Reset
Number (Amps) (Amps) (msec) (Amps) (Amps) (msec) (Amps)
MOE6120 10.25 2.3 550 10.0 2.3 400 2.3
MOE6240 5.2 1.1 500 5.0 1.0 330 1.1
MOF6120/L 10.0 5.5 200 10.0 5.5 175 5.5
6
Bottom View
For inches / millimeters conversion, see Application Data section.
▲ Built to order. Allow 7–9 weeks for delivery.
6/78
Molded Case Circuit Breakers
Selection / dimensions
External Accessories
Plug-In Mounting Assemblies, Including Base and Tulip Assemblies
Line Side Load Side Base
Steel Switchboard
For Use With Catalog Catalog Mounting Plate
Breaker Frames Poles Number Number Catalog Number ➝
All ED 2 PC2637▲ 98.00 PC2638▲98.00
PL2616
except CED 3 PC2657 158.00 PC2658 158.00
2 PC2637▲ 98.00 PC2638▲98.00
CED PL2617
3 PC2657 158.00 PC2658 158.00
All FD 2 PC4753▲237.00 PC4753▲237.00
PL4762
except CFD 3 PC4754 309.00 PC4754 309.00
2 PC4753▲237.00 PC4753▲237.00
CFD PL4763
3 PC4754 309.00 PC4754 309.00
All JD 2 PC5777▲318.00 PC5777▲318.00
PL5796
except CJD 3 PC5778 527.00 PC5778 527.00
Kit CJD, SCJD 3 PCCJD 570.00 PCCJD 570.00 PL5797
➝
➝
➝
All LD 2 PC5660▲596.00 PC5660▲596.00 Tulip
PL5696 Assemblies
except CLD 3 PC5661 835.00 PC5661 835.00 Switchboard
Kit CLD, SCLD 3 PCCLD 769.00 PCCLD 769.00 PL5797 Mounting
Plate
2 PC5662▲1098.00 PC5662▲1098.00
All MD PL9698
3 PC56631341.00 PC56631341.00
2 PC5664▲1516.00 PC5664c▲1516.00
All ND PL9699
3 PC5666 1748.00 PC5666 1748.00 ➝
➝ ➝
Tulip Assemblies Separately
2 Pole 3 Pole
RS4755
For Catalog Catalog
Frame Number Number RS4756
ED TCE2▲ TCE3▲ 184.00
FD TCF2▲ TCF3▲ 275.00 ➝
JD TCJ2▲ TCJ3▲ 309.00 ➝ ➝
LD TCL2▲ TCL3▲ 366.00
MD TCM2▲ TCM3▲ 408.00
ND TCN2▲ TCN3▲ 428.00
6
Rear-Connecting Studs
Circuit Breaker
For Use Extension With Rear-Connecting Studs
With Behind Line Side Load Side
Breaker Ampere Breaker Catalog Catalog
Frames Rating Description (inches) Number Number
100 Line Side (Short) 2.38 RS2643▲ 40.50 — 40.50
BREAKERS
100 Load Side (Short) 2.38 — RS2644▲40.50
All ED
100 Line Side (Long) 4.88 RS2641▲ 47.50 — 47.50
CIRCUIT
100 Load Side (Long) 4.88 — RS2642▲47.50
250 Short 3.12 RS4756▲ 58.00 RS4756▲58.00
All FD
250 Long 7.06 RS4755▲ 91.00 RS4755▲91.00
400 Short 5.85 RS5774▲ 161.00 RS5774▲161.00
All JD
400 Long 11.20 RS5773▲ 161.00 RS5773▲161.00
600 Short 5.85 RS5784▲ 158.00 RS5784▲192.00
All LD
600 Long 11.20 RS5783▲ 181.00 RS5783▲181.00
CJD, SCJD —
Add required shield kit. CLRSJL3 45.50
CLD, SCLD
LM(X)D6, Short 5.85 RS5788▲ 280.00 RS5788▲280.00
800
HLM(X)D6 Long 11.20 RS5787▲ 297.00 RS5787▲297.00
All MD, 1200 Short 5.50 RS5786▲ 231.00 RS5786▲231.00
ND 1200 Long 8.00 RS5785▲ 291.00 RS5785▲291.00
▲ Built to order. Allow 7–9 weeks for delivery. For vertical bus mounting — for horizontal, substitute Forproper electrical clearance, studs must alternate
Furnished at no extra charge when ordered with plug-in PC5665 for PC5664 and PC5667 for PC5666. between short and long stud lengths on circuit breaker
mounting assembly. Price includes one current stud, insulating tube, stud poles (e.g. SLSLSL or LSLSLS).
Each piece catalog number consists of (1) mounting nuts and terminal shields, when required.
block assembly and required tulip assemblies (2) for
2-pole, (3) for 3-pole
6/79
Enclosed Circuit Breakers
GENERAL
Enclosures
Type 3R
Type 1
6
Types 5, 12
BREAKERS
ENCLOSED CIRCUIT
6/80
Enclosed Circuit Breakers
SELECTION/ dimensions
Enclosures — Type 1
Dimensions
Type 1
K.O. Dimensions
Number Maximum Weight
Fig. Breaker of Current Catalog Lb./Ship. Dimensions (inches) 6 Plcs. 2 Plcs.
No. Type Poles Rating Number Package A B C D E F G H
BQ, BQH, 0 0 0 0 0
1 3 100 EB3100S
32 17 ⁄8
1
7 ⁄8
1
4 ⁄4
3
14 ⁄8
1
4 ⁄2
1
1 ⁄16
5
— —
HBQ
ED2, ED4, ED6, 0 E2N1S 008 1623⁄32 071⁄2 051⁄16 1345⁄64 051⁄4 1
2 2–3 100 ⁄8, 11⁄8,
7 7
⁄8, 11⁄8,
HED4, HED6 E2N1F 008 171⁄2 081⁄2 051⁄16 1345⁄64 051⁄4 1
13⁄8, 13⁄8,
ED4, ED6, HED4, HED6, 0 CED6N1S 014 2115⁄32 0719⁄32 057⁄64 181⁄4 051⁄4 1
2 2–3 125 13⁄4, 2 13⁄4, 2
CED6 CED6N1F 014 221⁄4 081⁄2 057⁄64 181⁄4 051⁄4 1
FXD6, FD6, FXD6-A, 11⁄8, 13⁄8, 11⁄8, 13⁄8,
2 FD6-A, HFD6, HFXD6, 2–3 0250 F6N1S 033 38 13
⁄32 1115
⁄32 051
⁄16 33 08 1 33
⁄64 13⁄4, 2, 13⁄4, 20,
HHFD6, CFD6 F6N1F 21⁄2, 3 21⁄2, 3
JXD2(A), JD6(A),
JXD6(A), HJD6(A),
3 HJXD6(A), HHJD6, 2–3 0400 J6N1 120 4013⁄64 2227⁄64 1045⁄64 36 181⁄4 25⁄64 — —
HHJXD6, SJD6(A),
SHJD6(A), SXD6H
6
LD6(A), LXD6(A),
HLD6(A), HLXD6(A),
3 HHLD6, HHLXD6, 2–3 0600 LD6N1 101 46 2227⁄64 1045⁄64 42 181⁄4 25⁄64 — —
SLD6(A), SHLD6(A), (L6N1 )
SCJD6, SCLD6, LXD6H
MD6, MXD6, SMD6,
HMD6, HMXD6,
ENCLOSED CIRCUIT
SHMD6, ND6, NXD6,
3 2–3 1200 MND61 132 60 2227⁄64 10 557⁄8 181⁄4 25⁄64 — —
SND6, HND6, HNXD6,
SHND6, CMD6,
SCMD6, CND6, SCND6
BREAKERS
PD6, PXD6, HPD6,
HPXD6, CPD6, RD6,
— 3 2000 PRD6N1 — 90 32 28 — — — — —
SPD6, SHPD6, RXD6,
HRD6, HRXD6
For inches / millimeters conversion, see page 15/6. Neutral not included. Order as separate item from table Will not accept breaker with shunt trip.
on next page. Will not accept 2-pole GFCI or breaker with shunt trip.
Surface mounted, indoor. If flush mounting is required, Neutral included in enclosure.
replace suffix “S” in catalog number with suffix “F”. Also, Surface mounted, indoor. If outdoor model is required,
if outdoor model required, use prefix “W” use prefix “W” instead of “E”. Not available in flush (“F”)
instead of “E”. model.
Does not include circuit breaker. Order circuit Use for 110-125 ampere ED4, ED6, HED4 or HED6
Built to order. Consult sales office for factory lead time
and prices.
breaker separately. circuit breakers.
6/81
Enclosed Circuit Breakers
SELECTION / DIMENSIONS
Enclosures — Type 1
Dimensions
Figure 4
Neutrals
Enclosure Neutral
Catalog Catalog Neutral Cable Capacity List
Number Number and Wire Range Price $
E2N1(S)(F) (1 pc.) #14–2 Cu/Al
W53045 246.
CED6N1(S)(F) Grd. Lug (1 pc.) #14–8 Cu/Al
(1 pc.) #6–350 kcmil
F6N1(S)(F) N250 (NFD) 259.
Grd. Lug (1 pc.) #14–2/0 Cu/Al
(1 pc.) #1/0–750 kcmil Cu/Al or
J6N1 W60992 (NJD) (2 pcs.) #1/0–300 kcmil Cu/Al 259.
Grd. Lug (1 pc.) #6–250 kcmil Cu/Al
6
Does
not include circuit breaker. Order circuit
breaker separately.
Neutral
included in enclosure.
6/82
Enclosed Circuit Breakers
SELECTION / DIMENSIONS
Enclosures — Type 3R
Dimensions
Type 3R
Number Maximum Weight
Figure Breaker of Current Catalog Lb./Ship. Dimensions (inches)
Number Type Poles Rating Number Package A B C D E F G H
BQ, BQH, 3 0050 00 0 0 0 0
2 WB3100 9 171⁄8 73⁄8 45⁄16 141⁄8 41⁄2 11⁄8 311⁄16 —
HBQ 3 0100
ED2, ED4, ED6, 0 0 0 0 0 0
5 2–3 100 E2N3R 12 179⁄16 71⁄4 51⁄4 1239⁄64 51⁄4 1 3 —
HED4, HED6
5 CED6 2–3 0125 CED6N3R
016 22 ⁄64 07 ⁄4
21 1
05 ⁄4
1
17 ⁄8
3
05 ⁄4
1
1 03 —
FXD6, FD6, FXD6-A,
1 FD6-A, HFD6, HFXD6, 2–3 0250 F6N3R 045 381⁄8 141⁄16 073⁄4 339⁄32 08 513⁄16 131⁄2 513⁄16
HHFD6, CFD6
JXD2(A), JD6(A),
JXD6(A), HJD6(A),
1 HJXD6(A), HHJD6, 2–3 0400 J6N3R 126 4063⁄64 263⁄4 1123⁄32 353⁄4 181⁄4 21⁄8 241⁄2 11⁄8
HHJXD6, SJD6(A),
SHJD6(A), SXD6H
LD6(A), LXD6(A),
LXD6H, HLD6(A),
HLXD6(A), HHLD6, 0
1 2–3 600 LD6N3R 137 4563⁄64 263⁄4 1123⁄32 403⁄4 181⁄4 21⁄8 241⁄2 11⁄8
6
HHLXD6, CJD6, (L6N3R)
CLD6, SCJD6(A),
SLD6(A), SHLD6(A)
MD6, MXD6, SMD6,
HMD6, HMXD6,
SHMD6, ND6, NXD6,
1 SND6, HND6, HNXD6, 2–3 1200 MND63 210 619⁄64 263⁄4 1123⁄32 5717⁄32 181⁄4 21⁄8 245⁄8 11⁄16
SHND6, CMD6, SCMD6,
ENCLOSED CIRCUIT
CND6,
SCND6
BREAKERS
For inches / millimeters conversion, see page 15/6. Neutral not included. Order as separate item from table
on next page.
Does not include circuit breaker. Neutral included in enclosure.
Order circuit breaker separately. Will not accept breaker with shunt trip.
6/83
Enclosed Circuit Breakers
SELECTION / dimensions
Enclosures — Type 3R
Dimensions
Neutrals
Enclosure Neutral
Catalog Catalog Neutral Cable Capacity List
Number Number and Wire Range Price $
E2N3R (1 pc.) #14–2 Cu/Al
W53045 Grd. Lug (1 pc.) #14–8 Cu/Al 246.
CED6N3R
(1 pc.) #6–350 kcmil
F6N3R N250 (NFD) 259.
Grd. Lug (1 pc.) #14–2/0 Cu/Al
6
For inches / millimeters conversion, see page 15/6. Neutralnot included. Order as separate item from table Use CED enclosure for all ED-frame 110-125
on next page. ampere units.
Does not include circuit breaker. Order circuit
Neutral included in enclosure.
breaker separately.
6/84
Enclosed Circuit Breakers
SELECTION / dimensions
Enclosures — Type 12
Types 5, 12
Number Maximum Weight
Figure Breaker of Current Catalog Lb./Ship . Dimensions (inches)
Number Type Poles Rating Number Package A B C D E F
ED2, ED4, ED6,
2 2–3 0100 E2N12
012 18 ⁄8
5
08 ⁄32 07 ⁄16
11 1
18 06 ⁄16
1
01⁄2
HED4, HED6
1 CED6 2–3 0125 CED6N12 016 225⁄8 0811⁄32 071⁄16 22 061⁄16 05⁄8
FXD6, FD6, FXD6-A,
2 2–3 0250 F6N12
040 38 ⁄32 14 ⁄64 08 ⁄8
19 29 1
34 13 023⁄32
FD6-A, HFD6, CFD.6
JXD2(A), JD6(A), JXD6(A),
HJD6(A), HJXD6(A),
3 2–3 0400 J6N12 104 40 2535⁄64 117⁄8 36 2435⁄64 —
HHJD6, HHJXD6, SJD6(A),
SHJD6(A)
LD6(A), LXD6(A), HLD6(A),
HLXD6(A), HHLD6,
3 HHLXD6, SLD6(A), 2–3 0600 LD6N12 104 45 2535⁄64 117⁄8 41 2435⁄64 —
SHLD6(A), CJD6, CLD6, (L6N12)
SCJD6(A), SCLD6(A)
MD6, MXD6, SMD6,
HMD6, HMXD6, SHMD6,
ND6, NXD6, SND6, HND6,
4 2–3 1200 MND612 220 60 373⁄8 10 005⁄8 03 2
HNXD6, SHND6,
CMD6, SCMD6,
CND6, SCND6
Dimensions
6
Figure 2 Figure 3
ENCLOSED CIRCUIT
Figure 1
BREAKERS
Neutrals
Enclosure Neutral
Catalog Catalog Neutral Cable Capacity List
Number Number and Wire Range Price $
E2N12 (1 pc.) #14–2 Cu/Al
W53045 246.
CED6N12 (1 pc.) #14–2 Cu/Al
(1 pc.) #6–350 kcmil
F6N12 N250 (NFD) 259.
Grd. Lug (1 pc.) #14–2/0 Cu/Al
(1 pc.) #1/0–750 kcmil Cu/Al or
J6N12 W60992 (NJD) (2 pc.) #1/0–300 kcmil Cu/Al 259.
Grd. Lug (1 pc.) #6–250 kcmil Cu/Al
(2 pcs.) #1/0–600 kcmil
L6N12 W60993 (NLD) 393.
Grd. Lug (1 pc.) #6–250 kcmil Cu/Al
(8 pcs.) 250 kcmil–500 kcmil Cu/Al Figure 4
MND612 W63623 (NMND) 802.
Grd. Lug (1 pc.) #6–300 kcmil Cu/Al
6/85
Enclosed Circuit Breakers
SELECTION / dimensions
Enclosures — Knockout and Hub Data
Knockouts & Wire Bending Space
Types 1, 12 Type 3R
Number of Knockouts Per Panel (type 12 have no KO’s)
Conduit Range Maximum Maximum Cable Sizes
Per Knockout Hub Size Recommended (Cu/Al)
Breaker Outside Dimensions (inches) for Type 1, 3R, 4, 4X,
Type (inches) Top Bottom Side Back Bottom Side Back Type 3R 12 & 12K Enclosures
BQ, BQH, HBQ
3
⁄4, 1, 11⁄4 1 1 2 2 8 1 3 2
70–100A
QJ 11⁄2, 2, 21⁄2, 3 2 2 2 2 3 1 1 21⁄2
For inches / millimeters conversion, see page 15/6. Sufficientwire bending space is provided for all The
use of compression type connectors will violate NEC
available mechanical type CB lugs. and CSA wire bending space requirements.
171⁄8"
high enclosure provides sufficient wire bending The use of cables larger than those listed below may
space for all available CB lugs. violate NEC & CSA wire bending space requirements.
6/86
Notes
6/87
ENCLOSED CIRCUIT
BREAKERS 6
Molded Case Circuit Breakers
GENERAL
Series Rated Combination Guide
6
BREAKERS
CIRCUIT
6/88
Molded Case Circuit Breakers
GENERAL
Series Rated Combination Guide
Example:
The application voltage is 208V, 3phase, the available short circuit current is 19,000 Amps. The Main breaker
is 200A rated and the Branch breaker is 3 Pole, 100A rated.
From the tables select the voltage greater than and closest to the application voltage. ( 240 )
From the IC column select the current rating greater than and closest to the application short circuit current. ( 22 )
From the Main Breaker column select the type based on the required ampere rating and number of poles.
( QJH2, 200A, 3P ) The Maximum current tested for this type of breaker is 225A.
From the Branch Breaker column select the type based on the required ampere rating and number of poles. In
some cases more than one option may be available. ( QP, BQ, BL )
1 15 - 70 120/240
6
QP, BQ, BL 2 15 - 125 240
22 QJH2 60 - 225 (2 & 3) 3 60 - 100 240
QPF, BQF BLF, QE, BE, BLE 1 15 - 30 120
QT 1, 2 15, 20, 40 120/240
This information is of a general nature and is intended for reference purposes only. Although every effort to ensure correctness of the material,
Siemens Canada Limited cannot assume any responsibility for actions taken on the basis of the content herein.
BREAKERS
CIRCUIT
Diagram for the above example:
QJH2
MAIN BREAKER
AVAILABLE FAULT
CURRENT AT Figure 3
208V
(10K AMPS)
(19K Amps)
QP, BQ, BL
FEEDER
BREAKERS
6/89
Molded Case Circuit Breakers
GENERAL
Series Rated Combination Guide
100
100
100
65 Max
Main Breaker / Disjoncteur principal Branch Breaker / Disjoncteur de branchement
IC/CI KA Voltage
Type Ams (Poles) Type # Poles Amps (AC/CA)
1 15 -70 120/240
QP, BQ, BL 2 15 -125 120/240
15-70 (1), 15-125 (2), 3 15-100 240
22 QPH, BQH, BLH
15-100 (3) QE, BLE, QPF, BLF 1 15 - 60 120/240
QE, BLE, QPF, BQF, BLF 2 15 - 30 120
QT 1, 2 15, 20, 40 120/240
1 15 -70 120/240
QP, BQ, BL
2 15 -125 120/240
QE, BLE, BE, QPF, BQF, BLF 1 15 - 30 120
22 QPPH 125 - 225 (2)
QE, BLE, BE, QPF, BLF 2 15 - 60 120/240
QPP 2 125 - 200 120/240
QT 1, 2 15, 20, 40 120/240
1 15 - 70 120/240
QP, BQ, BL 2 15 - 125 240
22 QJH2 60 - 225 (2 & 3) 3 60 - 100 240
QPF, BQF BLF, QE, BE, BLE 1 15 - 30 120
QT 1, 2 15, 20, 40 120/240
1 15 - 70 120/240
QP, BQ, BL 2 15 - 125 120/240
3 60 - 100 240
1 15 - 70 120/240
42 QJ2H 60 - 225 (2 & 3)
QPH, BQH, BLH 2 15 - 125 120/240
3 15 - 100 240
QE, BLE, BE, QPF, BLF 2 15 - 60 120/240
QJH2 2, 3 60 - 225 240
1 15 - 70 120/240
QP, BQ, BL, QPH, BQH, BLH 2 15 - 100 120/240
3 15 - 100 240
15-70 (1), 15-125 (2),
65 HQP, HBQ, HBL QPF, BQF, BLF, BE, QFHF, BQHF, BLHF, QEH,
15-100 (3) 1 15 - 30 120
BLEH, QE, BLE
QEH, BLEH, QE, QPHF, BLHF, BLE, QPF, BLF 2 15 - 60 120/240
QT 1, 2 15 - 40 120/240
1 15 - 70 120/240
QP, BQ, BL, QPH, BQH, BLH
2 15 - 125 120/240
QPF, BQF, BLF, QPHF, BQHF, BLHF, QEH, BLEH,
1 15 - 30 120
6
6/90
Molded Case Circuit Breakers
GENERAL
Series Rated Combination Guide
100
100
100
65 Max
Main Breaker / Disjoncteur principal Branch Breaker / Disjoncteur de branchement
IC/CI KA Voltage
Type Ams (Poles) Type # Poles Amps (AC/CA)
6
3 15 - 100 240
100 HQJ2H 60 - 225 (2 & 3) 1 15 - 70 120/240
QPH, BQH, BLH, HQP, HBQ, HBL 2 15 - 125 120/240
3 15 - 100 240
QEH, BLEH, QE, BE, QPHF, BQHF, BLHF, QPF,
1 15 - 30 120
BQF, BLF, BLE
QEH, BLEH, QPHF, BLHF,QE, BLE, QPF, BLF 2 15 - 60 120/240
QT 1 15 - 50 120/240
BREAKERS
1 15 - 70 120/240
CIRCUIT
QP, BQ, BL, QPH, BQH, BLH, HQP, HBQ, HBL 2 15 - 125 120/240
3 15 - 100 240
QE, BE, BLE, QPHF, BQHF, BLHF, QPF, BQF, BLF,
1 15 - 30 120
QEH, BLEH
QPF, BLF, QE, BLE, QPHF, BLHF, QEH, BLEH 2 15 - 60 120
100 HFD6, HFXD6 70 - 250 (2 & 3)
ED4 1 15 - 100 120
ED4, ED6 2, 3 15 - 125 240
FD6-A, FXD6-A 2, 3 70 -250 240
QJ2, QJH2, QJ2H 2, 3 60 - 225 240
HQPP, QPPH, QPP 2 125 - 225 120/240
QT 1, 2 15 - 30 120/240
ED4 1 15 - 100 120/240
HJD6-A, HJXD6-A, ED4, ED6 2, 3 15 - 125 120/240
100 200 - 400 (2 & 3)
SHJD6-A FD6-A, FXD6-A 2, 3 70 - 250 120/240
JD6-A, JXD6-A, JXD2-A, SJD6-A 2, 3 200 - 400 120/240
ED4 1 15 - 100 120
ED4, ED6 2, 3 15 - 125 240
100 HLD6-A 200 - 600 (2 & 3)
FD6-A, FXD6-A 2, 3 70 - 250 240
JD6-A, JXD6-A, JXD2-A, SJD6-A 2, 3 200 - 400 240
6/91
Molded Case Circuit Breakers
GENERAL
Series Rated Combination Guide
100
100
100
65 Max
Main Breaker / Disjoncteur principal Branch Breaker / Disjoncteur de branchement
IC/CI KA Voltage
Type Ams (Poles) Type # Poles Amps (AC/CA)
LD6-A 2, 3 200 - 600 240
100 HLD6-A 200 - 600 (2 & 3) LXD6-A 2, 3 450 - 600 240
SLD6-A 3 300 - 600 240
ED4 1 15 - 100 120
ED4, ED6 2, 3 15 - 125 240
FD6-A, FXD6-A 2, 3 70 - 250 240
100 HLXD6-A 450 - 600 (2 & 3) JD6-A, JXD6-A, JXD2-A, SJD6-A 2, 3 200 - 400 240
LD6-A 2, 3 200 - 600 240
LXD6-A 2, 3 450 - 600 240
SLD6-A 3 300 - 600 240
ED4 1 15 - 100 120
ED4, ED6 2, 3 15 - 125 240
FD6-A, FXD6-A 2, 3 70 - 250 240
100 SHLD6-A 300 - 600 (3) JD6-A, JXD6-A, JXD2-A, SJD6-A 2, 3 200 - 400 240
LD6-A 2, 3 200 - 600 240
LXD6-A 2, 3 450 - 600 240
SLD6-A 3 300 - 600 240
ED4 1 15 - 100 120
ED4, ED6 2, 3 15 - 125 240
FD6-A, FXD6-A 2, 3 70 - 250 240
JD6-A, JXD6-A, JXD2-A, SJD6-A 2, 3 200 -400 240
100 HMD6, HMXD6 500 - 800 (2 & 3)
LD6-A 2, 3 200 - 600 240
LXD6-A 2, 3 450 - 600 240
SLD6-A 3 300 - 600 240
MD6, MXD6, SMD6 2, 3 500 -800 240
ED4 1 15 - 100 120
ED4, ED6 2, 3 15 - 125 240
FD6-A, FXD6-A 2, 3 70 - 250 240
JD6-A, JXD6-A, JXD2-A, SJD6-A 2, 3 200 - 400 240
100 SHMD6 500 - 800 (3)
LD6-A 2, 3 200 - 600 240
LXD6-A 2, 3 450 - 600 240
SLD6-A 3 300 - 600 240
MD6, MXD6, SMD6 2, 3 500 - 800 240
FD6-A, FXD6-A 2, 3 70 - 250 240
6
6/92
Molded Case Circuit Breakers
GENERAL
Series Rated Combination Guide
100
100
100
65 Max
Main Breaker / Disjoncteur principal Branch Breaker / Disjoncteur de branchement
IC/CI KA Voltage
Type Ams (Poles) Type # Poles Amps (AC/CA)
ED4 1 15 -100 120
ED4, ED6 2, 3 15 - 125 240
FD6-A, FXD6-A 2, 3 70 - 250 240
JD6-A, JXD6-A, JXD2-A, SJD6-A 2, 3 200 - 400 240
LD6-A 2, 3 200 - 600 240
100 HRD6, HRXD6 1600 - 2000 (3) LXD6-A 2, 3 450 - 600 240
SLD6-A 3 300 - 600 240
MD6, MXD6, SMD6 2, 3 500 - 800 240
ND6, NXD6, SND6 2, 3 500 - 1200 240
PD6, PXD6, SPD6 2, 3 1200 - 1600 240
RD6, RXD6 2, 3 1600 - 2000 240
1 15 - 70 120/240
QP, BQ, BL, QPH, BQH, BLH, HQP, HBQ, HBL 2 15 - 125 120/240
3 15 - 100 240
QPHF, BQHF, BLHF, QPF, BQF, BLF, QEH, QE,
1 15 - 30 120
200 CED6 15 - 125 (2 & 3) BE, BLEH
QEH, BLEH, QPHF, BLHF, QPF, BLF, QE, BLE 2 15 - 60 120/240
ED4, HED4 1 15 - 100 120
ED4, ED6, HED4, HED6 2, 3 15 - 125 240
QT 1, 2 15 - 40 120/240
1 15 - 70 120/240
QP, BQ, BL, QPH, BQH, BLH, HQP, HBQ, HBL 2 15 - 125 120/240
3 15 - 100 240
QPHF, BQHF, BLHF, QE, BE, BLE, QPF, BQF, BLF,
1 15 - 30 120
QEH, BLEH
QPHF, BLHF, QE, BLE, QPF, BLF, QEH, BLEH 2 15 - 60 120/240
200 CFD6 70 - 250 (2 & 3) ED2 1, 2, 3 15 - 100 120/240
HED4, ED4 1 15 - 100 120
ED4, ED6, HED4, HED6 2, 3 15 - 125 240
FD6-A, FXD6-A, HFD6, HFXD6 2, 3 70 - 250 240
QJ2H, QJH2, QJ2 2, 3 60 - 225 240
QPPH, QPP 2 125 - 225 120/240
QT 1, 2 15 - 40 120/240
HHJD6, HHJXD6,
200 200 - 600 (2 & 3) FD6-A, FXD6-A, HFD6, HFXD6 2, 3 70 - 250 240
HHLD6, HHLXD6
6
2 100 - 125 120/240
QPH, BQH, BLH, HQP, HBQ, HBL
3 100 240
ED4, ED6 2, 3 15 - 125 240
200 CJD6 200 - 400 (2 & 3)
FD6-A, FXD6-A, HFD6, HFXD6 2, 3 70 - 250 240
JXD2-A, JD6-A, JXD6-A, HJD6-A, HJXD6-A 2, 3 200 - 400 240
QT 1, 2 15 - 30 120/240
2 100 - 125 120/240
QPH, BQH, BLH, HQP, HBQ, HBL
3 100 240
BREAKERS
ED4, ED6 2, 3 15 - 25 120/240
CIRCUIT
FD6-A, FXD6-A, HFD6, HFXD6 2, 3 70 - 250 240
200 CLD6 450 - 600 (2 & 3)
JXD2-A, JD6-A, JXD6-A, HJD6-A, HJXD6-A 2, 3 200 - 400 240
LD6-A, HLD6-A 2, 3 200 - 600 240
LXD6-A, HJXD6-A 2, 3 450 - 600 240
QT 1,2 15 - 30 120/240
ED4, ED6, HED4, HED6 2, 3 15 - 125 240
FD6-A, FXD6-A, HFD6, HFXD6 2, 3 70 - 250 240
JXD2-A, JD6-A, JXD6-A, HJD6-A, HJXD6-A 2, 3 200 - 400 240
200 CMD6 500 - 800 (2 & 3)
LD6-A, HLD6-A 2, 3 200 - 600 240
LXD6-A, HLXD6-A 2, 3 450 - 600 240
MD6, MXD6, HMD6, HMXD6 2, 3 500 - 800 240
200 SCMD6 500 - 800 (3) MD6, MXD6, HMD6, HMXD6 2, 3 500 - 800 240
ED4, ED6, HED4, HED6 2, 3 15 - 125 240
200 CND6 900 - 1200 (2 & 3) FD6-A, FXD6-A, HFD6, HFXD6 2, 3 70 - 250 240
JXD2-A, JD6-A, JXD6-A, HJD6-A, HJXD6-A 2, 3 200 - 400 240
LD6-A, HLD6-A 2, 3 200 - 600 240
LXD6-A, HLXD6-A 2, 3 450 - 600 240
200 CND6 900 - 1200 (2 & 3)
MD6, MXD6, HMD6, HMXD6 2, 3 500 - 800 240
ND6, NXD6, SND6, HND6, HNXD6 2, 3 500 - 1200 240
4
6/93
Molded Case Circuit Breakers
GENERAL
Series Rated Combination Guide
100
100
100
65 Max
Main Breaker / Disjoncteur principal Branch Breaker / Disjoncteur de branchement
IC/CI KA Voltage
Type Ams (Poles) Type # Poles Amps (AC/CA)
MD6, HMD6, HMXD6, MXD6, SHMD6, SMD6 2, 3 500 - 800 240
200 SCND6 900 - 1200 (3)
ND6, HND6, SHND6, NXD6, HNXD6, SND6 2, 3 500 - 1200 240
FD6-A, FXD6-A, HFD6, HFXD6 2, 3 70 - 250 240
JXD2-A, JD6-A, JXD6-A, HJD6-A, HJXD6-A 2, 3 200 - 400 240
LD6-A, HLD6-A 2, 3 200 - 600 240
200 CPD6 1200 - 1600 (3)
LXD6-A, HLXD6-A 2, 3 450 - 600 240
MD6, MXD6, HMD6, HMXD6 2, 3 500 - 800 240
ND6, NXD6, SND6, HND6, HNXD6 2, 3 500 - 1200 240
1 15-70 120/240
65 J, R 15 - 600 (1, 2, 3) QPH, BQH, BLH 2 15-125 120/240
3 15 - 100 240
1 15-70 120/240
65 T 15 - 1200 (1, 2, 3) QPH, BQH, BLH 2 15-125 120/240
3 15 - 100 240
1 15-70 120/240
65 L 601 - 6000 (1, 2, 3) QPH, BQH, BLH 2 15-125 120/240
3 15 - 100 240
QP, BQ, BL 1, 2, 3 15 - 125 120/240
HQP, HBQ, HBL, QPH, BQH, BLH 3 15 - 100 240
QPF, BQF, BLF, QE, BE, BLE, QEH, BLEH, BLHF,
15-200 (1, 2, 3) 1 15 - 30 120
100 T (300 V) QPHF, BQHF,
QEH, BLEH, QE, QPHF, BLHF, BLE, QPF, BLF 2 15 - 60 120/240
QT 1, 2 15 - 50 120/240
15 - 600 (1, 2, 3) QPH, BQH, BLH, HQP, HBQ, HBL 1, 2 15 - 125 120/240
ED4, HED4 1 15 - 100 120
15 - 600 (2, 3)
ED4, ED6, HED4, HED6 2, 3 15 - 125 240
70 - 600 (2, 3) FD6-A, FXD6-A 2, 3 70 - 250 240
100 J, R JD6-A, JXD6-A, JXD2-A, SJD6-A 2, 3 200 - 400 240
200 - 600 (2, 3)
LD6-A 2, 3 200 - 600 240
300 - 600 (3) SLD6-A 3 300 - 600 240
450 - 600 (2, 3) LXD6-A 2, 3 450 - 600 240
ED4, HED4 1 15 - 100 120/240
15 - 1200 (2, 3)
6
6/94
Molded Case Circuit Breakers
GENERAL
Series Rated Combination Guide
100
100
100
65 Max
Main Breaker / Disjoncteur principal Branch Breaker / Disjoncteur de branchement
IC/CI KA Voltage
Type Ams (Poles) Type # Poles Amps (AC/CA)
HFD6, HFXD6 2, 3 70 - 250 240
200 L 601 - 6000 (2, 3) MD6, MXD6, HMD6, HMXD6 2, 3 500 - 800 240
ND6, NXD6, HND6, HNXD6 2, 3 500 - 1200 240
BQD, CQD 1, 2, 3 15 - 100 277
30 HED6 15 - 125 (2 & 3) ED4 1 15 - 100 277
ED4, ED6 2, 3 15 - 125 480
JD6, JXD6 200-400 (2 & 3) 277
35 LD6 200-600 (2 & 3) ED4 2,3 15-100 277
LXD6 450-600 (2 & 3) 277
BQD, CQD 1, 2, 3 15,100 277
42 HED4 15 - 125 (2 & 3) ED4 1 15 - 100 480
ED4, ED6 2, 3 15 - 125 480
50 HJD6-A, HJXD6-A 200-400 (2 & 3)
HED4 2, 3 15 - 50 480
50 HLD6-A, HLXD6-A 200-600 (2 & 3)
FD6-A, FXD6-A 2, 3 70 - 250 480
JD6-A, JXD6-A, SJD6-A 2, 3 200 - 400 480
50 MD6, MXD6 500-800 (2 & 3) LD6-A 2, 3 200 - 600 480
LXD6-A 2, 3 450 - 600 480
SLD6-A 3 400 - 600 480
FD6-A, FXD6-A 2, 3 70 - 250 480
JD6-A, JXD6-A, 2, 3 200 - 400 480
LD6-A 2, 3 200 - 600 480
50 ND6, NXD6 500-1200 (2 & 3)
LXD6-A 2, 3 450 - 600 480
SJD6-A 3 200 - 400 480
SLD6-A 3 400 - 600 480
JD6-A, JXD6-A 2, 3 200 - 400 480
LD6-A 2, 3 200 - 600 480
50 SMD6 500 - 800 (3) LXD6-A 2, 3 450 - 600 480
SJD6-A 3 200 - 400 480
SLD6-A 3 400 - 600 480
JD6-A, JXD6-A 2, 3 200 - 400 480
LD6-A 2, 3 200 - 600 480
50 SND6 500 - 1200 (3) LXD6-A 2, 3 450 - 600 480
6
SJD6-A 3 200 - 400 480
SLD6-A 3 400 - 600 480
JD6-A, JXD6-A 2, 3 200 - 400 480
LD6-A 2, 3 200 - 600 480
50 SPD6 1200 - 1600 (3) LXD6-A 2, 3 450 - 600 480
SJD6-A 3 200 - 400 480
SLD6-A 3 400 - 600 480
1400 - 1600 (3) FD6-A, FXD6-A 2, 3 70 - 250 480
BREAKERS
JD6-A, JXD6-A, SJD6-A 2, 3 200 - 400 480
CIRCUIT
LD6-A 2, 3 200 - 600 480
50 PD6, PXD6
1200 - 1600 (3) LXD6-A 2, 3 450 - 600 480
SJD6-A 3 200 - 400 480
SLD6-A 3 400 - 600 480
FD6-A, FXD6-A 2, 3 70 - 250 480
JD6-A, JXD6-A, SJD6-A 2, 3 200 - 400 480
LD6-A 2, 3 200 - 600 480
50 RD6, RXD6 1800 - 2000 (3)
LXD6-A 2, 3 450 - 600 480
SJD6-A 3 200 - 400 480
SLD6-A 3 400 - 600 480
BQD, CQD 1, 2, 3 15 - 100 480
65 HFD6, HFXD6 70 - 250 (2 & 3) ED4, HED4 1 15 - 100 277
ED4, ED6, HED4, HED6 2, 3 15 - 125 480
HED4, ED4 1 15 - 100 480
65 HJD6-A, HJXD6-A 200 - 400 (2 & 3) FD6-A, FXD6-A 2, 3 70 - 250 480
JD6-A, JXD6-A 2, 3 200 - 400 480
6/95
Molded Case Circuit Breakers
GENERAL
Series Rated Combination Guide
100
100
100
65 Max
Main Breaker / Disjoncteur principal Branch Breaker / Disjoncteur de branchement
IC/CI KA Voltage
Type Ams (Poles) Type # Poles Amps (AC/CA)
ED4, HED4 1 15 - 100 277
FD6-A, FXD6-A 2, 3 70 - 250 480
65 HLD6-A 200 - 600 (2 & 3) JD6-A, JXD6-A 2, 3 200 - 400 480
LD6-A 2, 3 200 - 600 480
LXD6-A 2, 3 450 - 600 480
ED4, HED4 1 15 - 100 277
FD6-A, FXD6-A 2, 3 70 - 250 480
65 HLXD6-A 450 - 600 (2 & 3) JD6-A, JXD6-A 2, 3 200 - 400 480
LD6-A 2, 3 200 - 600 480
LXD6-A 2, 3 450 - 600 480
FD6-A, FXD6-A 2, 3 70 - 250 480
JD6-A, JXD6-A 2, 3 200 - 400 480
65 HMD6, HMXD6 500 - 800 (2 & 3)
LD6-A 2, 3 200 - 600 480
LXD6-A 2, 3 450 - 600 480
FD6-A, FXD6-A 2, 3 70 - 250 480
JD6-A, JXD6-A 2, 3 200 - 400 480
65 HND6, HNXD6 500 - 1200 (2 & 3) LD6-A 2, 3 200 - 600 480
LXD6-A 2, 3 450 - 600 480
MD6, MXD6, SMD6 2, 3 500 - 800 480
FD6-A, FXD6-A 2, 3 70 - 250 480
JD6-A, JXD6-A 2, 3 200 - 400 480
65 HRD6, HRXD6 1800 - 2000 (3)
LD6-A 2, 3 200 - 600 480
LXD6-A 2, 3 450-600 480
HHJXD6, HHJD6, ED4, ED6, HED4, HED6 1 15 - 100 277
100 200 - 600 (2 & 3)
HHLD6, HHLXD6 FD6-A, FXD6-A, HFD6, HFXD6 2, 3 70 - 250 480
FD6-A, FXD6-A, HFD6, HFXD6 2, 3 70 - 250 480
JD6-A, HJD6-A, JXD6-A, HJXD6-A 2, 3 200 - 400 480
100 CMD6 500 - 800 (3) LD6-A, HLD6-A 2, 3 200 - 600 480
LXD6-A, HLXD6-A 2, 3 450 - 600 480
MD6, MXD6, HMD6, HMXD6 2, 3 500 - 800 480
100 SCMD 500 - 800 (3) HFXD6 2, 3 70 - 250 480
100 SCND6 900 - 1200 (3) HFD6, HFXD6 2, 3 70 - 250 480
FD6-A, FXD6-A, HFD6, HFXD6 2, 3 70 - 250 480
JD6-A, JXD6-A, HJD6-A, HJXD6-A 2, 3 200 - 400 480
LD6-A, HLD6-A 2, 3 200 - 600 480
100 CND6 1200 (3)
LXD6-A, HLXD6-A 2, 3 450 - 600 480
6
6/96
Molded Case Circuit Breakers
GENERAL
Series Rated Combination Guide
100
100
100
65 Max
Main Breaker / Disjoncteur principal Branch Breaker / Disjoncteur de branchement
IC/CI KA Voltage
Type Ams (Poles) Type # Poles Amps (AC/CA)
JD6-A, JXD6-A, HJD6-A, HJXD6-A 2, 3 200 - 400 480
200 - 600 (2, 3)
100 T, J, R LD6-A, HLD6-A, HLXD6-A 2, 3 200 - 600 480
450 - 600 (2, 3) LXD6-A, 2, 3 450 - 600 480
100 T 70 - 1200 (2, 3) HFD6, HFXD6 2, 3 70 - 250 480
JD6-A, JXD6-A, HJD6-A, HJXD6-A 2, 3 200 - 400 480
100 T, L 601 - 1200 (2, 3) LD6-A, HLD6-A 2, 3 200 - 600 480
LXD6-A, HLXD6-A 2, 3 450 - 600 480
HFD6, HFXD6 2, 3 70 - 250 480
MD6, MXD6, HMD6, HMXD6 2, 3 500 - 800 480
100 L 601 - 6000 (2, 3)
ND6, NXD6, HND6, HNXD6 2, 3 500 - 1200 480
PD6, HPD6, HPXD6 3 1200 - 1600 480
1 15 - 100 480
R 15 - 100 (1, 2, 3) BQD, CQD
2, 3 20 - 30 480
200
1 15 - 100 480
T, J 15 - 200 (1, 2, 3) BQD, CQD
2,3 20 - 30 480
ED6, HED6 15 -125 (1, 2, 3) BQD6,CQD6 1 15 - 70 347
18
ED6, HED6 15 -125 (2, 3) BQD6,CQD6 2, 3 15 - 70 347/600
BQD6, CQD6 1 15 - 70 347
25 HFD6 70 - 250 (2, 3) BQD6, CQD6, ED6, HED6 2, 3 15 - 70 347/600
ED6, HED6 2, 3 15 - 125 347/600
HJD6, HJXD6 200 - 400 (2, 3)
35 HFD6 2, 3 70 - 250 347/600
HLD6, HLXD6 450 - 600 (2, 3)
HFD6 70 600
HMD6, HMXD6 500 - 800 (2, 3) JD6, JXD6 200 - 400 600
50 HND6 500 - 1200 (2, 3) HJD6, HJXD6 2, 3 200 - 400 600
HNXD6 900 - 1200 (2, 3) LD6, HLD6 200 - 600 600
LXD6, HLXD6 450 - 600 600
BQD6,CQD6 15 - 70 347/600
65 CFD6 70 - 250 (2, 3) 2, 3
ED6, HED6 15 - 125 600
HFD6 70 600
CMD6 500 - 800 (2, 3) JD6, JXD6 200 - 400 600
65 CND6 900 - 1200 (2,3) HJD6, HJXD6 2, 3 200 - 400 600
CPD6 1200 - 1600 (2,3) LD6, HLD6 200 - 600 600
LXD6, HLXD6 450 - 600 600
6
HFD6 70 600
JD6, JXD6 200 - 400 600
65 HPD6, HPXD6 1200 - 1600 (2, 3) HJD6, HJXD6 2, 3 200 - 400 600
LD6, HLD6 200 - 600 600
LXD6, HLXD6 450 - 600 600
1 15 - 70 347
BQD6,CQD6 2 15 - 70 347/600
100 CED6 15 - 125 (2, 3)
BREAKERS
3 15 - 70 347/600
CIRCUIT
ED6, HED6 2, 3 15 - 125 600
BQD6,CQD6 1 15 - 70 347
100 CFD6 70 -250 (2, 3) ED6, HED6 15 - 125 600
2, 3
HFD6 70 - 250 600
JD6, JXD6 200 - 400 600
HJD6, HJXD6
100 J,R,T 200 - 600 (2, 3) 2, 3 200 - 600 600
LD6, HLD6
LXD6, HLXD6 450 - 600 600
2001.10.01
6/97
Molded Case Circuit Breakers
REFERENCE
Unusual Operating Conditions
Note: The information provided on this and the next page is intended for reference and recommendation only. Because several
variables can act on a circuit breaker’s performance at the same time, the data below is based less on controlled testing, than on
experience and engineering judgment. Contact Siemens for further information on special conditions and treatment.
High Ambient Temperatures Table 1 — Temperature Derating Data for Thermal-Magnetic Breakers
Because thermal-magnetic trip breakers Reference
are temperature sensitive and calibrated Ampere Ampere Rating at:
for a specific ambient of 40° C (104° F) Rating at 25° C 50° C 60° C
(average enclosure temperature), 40° C (104° F) (77° F) (122° F) (140° F) Siemens Breaker Frames
a higher ambient will cause the 0015 0017 0013 0011
breaker to trip at lower current than 0020 0022 0018 0016
its nameplate rating, in other words, 0025 0028 0023 0021
causing the breaker to “derate” (see 0030 0033 0028 0026
Table 1). Similarly, the current carrying 0035 0039 0030 0025
capacity of a circuit conductor is based 0040 0044 0037 0034
ED
upon a certain ambient temperature, a 0050 0055 0046 0042
higher ambient will reduce its current 0060 0066 0056 0052
carrying capacity, causing it to “derate.” 0070 0077 0065 0060
Thus, with a fluctuating temperature, 0090 0099 0084 0078
a thermal-magnetic breaker will derate 0100 0110 0094 0087
nearly parallel with its connected circuit 0125 0137 0114 0100 QJ
conductors and maintain close circuit 0150 0165 0136 0120 FD
protection. If the application temperature 0175 0192 0159 0140
exceeds 40° C (104° F) and is known, 0200 0220 0182 0160
either a breaker specially calibrated for
0225 0247 0205 0180
the higher ambient or one oversized
0250 0275 0235 0220
according to Table 1 may be selected. In a JD
0300 0330 0276 0252
case such as this, the circuit conductors
should be oversized as well. 0350 0385 0325 0301
LD
0400 0440 0372 0340
Siemens Sensitrip® III and Type 0500 0550 0468 0435
SB Encased Systems Breakers are
0600 0660 0564 0525
insensitive to temperature changes. MD
0700 0770 0658 0613
However, they do include circuitry to
protect the components from abnormally 0800 0880 0754 0704
high temperatures. 0900 0990 0828 0749
ND
1000 1100 0900 0825
Moisture — Corrosion
1200 1320 1090 1000
For atmospheres having high moisture 1400 1540 1304 1148 PD
content and / or where fungus growth is 1600 1760 1500 1320
6
6,000 (1,800)
6/98
Molded Case Circuit Breakers
REFERENCE
Unusual Operating Conditions
400 Hz Systems a
Siemens molded case circuit breakers ambient temperature exceeds 40° C are usually the hottest terminals with a
can be applied for overcurrent protection (104° F). balanced load. A maximum temperature
on 400Hz systems, commonly used to Cable and Bus Sizing of 75° C (35° C over a maximum ambient
power computer installations, aircraft, of 40° C) would verify the particular
military and other specialty equipment. The cable and bus sizes to be utilized application. Temperature profiles taken
Below are basic guidelines. at 400Hz are not based on standard on these breakers can be correlated to
National Electric Codes tables for 60Hz ensure that the hottest points within
Circuit Breaker Derating Required application. Larger cross sections the breaker are within the required
This table lists the maximum continuous are necessary at 400Hz. All bus bars temperature limits.
current carrying capacity for Siemens specified are based upon mounting
breakers at 400Hz. Due to the increased the bars in the vertical plane to allow Factory Configuration
resistance of the copper sections maximum air flow. All bus bars are When required, molded case circuit
resulting from the skin effect produced spaced at a minimum of 0.25 in. breakers may be factory calibrated for
by eddy currents at these frequencies, (6mm) apart. Mounting of bus bars in 400Hz application. These breakers are
circuit breakers in many cases require the horizontal plane will necessitate specially labeled for 400Hz usage and
derating. The thermal derating on these additional drafting. Edgewise orientation their nameplate current rating will
devices is based upon 100%, three-phase of the bus may change the maximum include the necessary derating factory.
application in open air in a maximum of ratings indicated. If additional information The highest “Maximum Continuous
40° C (104° F) with 48 in. (1219 mm) of is required for other connections of cable Amperes” rating at 400Hz, found in the
the specified cable or bus at the line and or bus, contact Siemens for information. table below approximates the highest
load side. Additional derating of not less Application Recommendations specially calibrated 400Hz nameplate
than 20% will be required if the circuit ampere rating available for a given frame
breaker is to be utilized in an enclosure. It is recommended that temperatures be
measured on the line and load terminals size. Contact Siemens for ordering
Further derating may be required if the information on other breakers applied in
enclosure or T-connectors of the center pole. These
400Hz systems.
400Hz Breakers
Maximum Continuous Ampere Rating 75°C (167° F) Maximum Continuous Ampere Rating 75° C (167° F)
At 40°C (104°F) b Copper At 40° C (104° F) b Copper
Siemens 60HZ 400HZ Cable per Pole Siemens 60HZ 400/415HZ Cable per Pole
Breaker Enclosed No of Wire Breaker Enclosed No of Wire
Type Open Air Open Air c After Derating Pieces Size Type Open Air Open Air c After Derating Pieces Size
015 015 012 1 #14 0250 0210 168 1 250 kcmil
020 020 016 1 #12 0300 0240 192 1 350 kcmil
025 025 020 1 #10 LD6, LXD6, 0350 0260 208 1 500 kcmil
HLD6, HLXD6,
030 030 024 1 #10 HHLD6, 0400 0300 240 2 #3/0
035 035 028 1 #10 HHLXD6, 0450 0340 272 2 #4/0
CLD6
040 040 032 1 #8 0500 0375 300 2 250 kcmil
ED2, ED4, 045 043 034 1 #8 0600 0420 336 2 350 kcmil
ED6, HED4, 050 048 038 1 #8 0250 0210 210 1 250 kcmil
6
CED6 060 057 046 1 #6 0300 0240 240 1 350 kcmil
070 067 054 1 #4 LD6, LXD6, 0350 0260 260 1 500 kcmil
080 076 061 1 #4 HLD6, HLXD6, 0400 0300 300 2 #3/0
090 086 069 1 #3 100% Rated 0450 0340 340 2 #4/0
100 095 076 1 #3 0500 0375 375 2 250 kcmil
110 105 084 1 #2 0600 0420 420 2 350 kcmil
125 119 095 1 #1 0500 0400 320 2 250 kcmil
070 063 050 1 #4 MD6, MXD6, 0600 0430 360 2 350 kcmil
HMD6,
080 072 058 1 #4 HMXD6, CMD6 0700 0500 400 3 250 kcmil
BREAKERS
090 080 064 1 #3 0800 0560 448 3 300 kcmil
CIRCUIT
100 090 072 1 #3 0500 0400 400 2 250 kcmil
MD6, MXD6,
FD6, FXD6, 110 095 075 1 #2 HMD6, 0600 0430 430 2 350 kcmil
HFD6, HFXD6, 125 105 084 1 #1 HMXD6, CMD6 0700 0500 500 3 250 kcmil
CFD6 100% Rated
150 125 100 1 #1/0 0800 0560 560 3 300 kcmil
175 140 112 1 #2/0 0800 0560 448 3 300 kcmil
200 160 128 1 #3/0 ND6, NXD6 0900 0600 480 3 350 kcmil
HND6, HNXD6,
225 180 144 1 #4/0 CND6 1000 0650 520 3 400 kcmil
250 200 160 1 250 kcmil 1200 0780 624 4 350 kcmil
200 170 136 1 #3/0 ND6, NXD6 0900 0600 600 3 350 kcmil
JXD2, JD6, 225 190 152 1 #4/0 HND6, HNXD6, 1000 0650 650 3 400 kcmil
250 210 168 1 250 kcmil CND6 1200 0780 780 4 350 kcmil
JXD6, HJD6,
HJXD6, HHJD6, 300 240 192 1 350 kcmil PD6, PXD6, 1200 0780 624 4 400 kcmil
HHJXD6, CJD6 HPD6, HPXD6,
350 260 208 1 500 kcmil CPD6, 1400 0850 680 4 500 kcmil
400 300 240 2 #3/0 100% Rated 1600 0960 768 5 500 kcmil
200 170 170 2 #3/0 PD6, PXD6, 1200 0780 780 4 400 kcmil
225 190 190 2 #4/0 HPD6, HPXD6, 1400 0850 850 4 500 kcmil
JD6, JXD6, CPD6
HJD6, HJXD6 250 210 210 1 250 kcmil 1600 0960 960 5 500 kcmil
100% Rated 300 240 240 1 350 kcmil RD6, RXD6, 1600 0960 768 5 500 kcmil
350 260 260 1 500 kcmil HRD6, HRXD6 1800 1080 864 5 500 kcmil
400 300 300 2 #3/0 80% Rated 2000 1200 960 6 500 kcmil
aThe information provided on this page is intended for controlled testing, than on experience and engineering cCalculated after derating to compensate for the heating
reference and recommendation only. Because several judgment. Contact Siemens for further information on of the copper conductor, caused by the skin effect
variables can act on a circuit breaker’s performance at special conditions and treatment. generated by eddy currents produced at 400/415HZ.
the same time, the data above is based less on bAdditional derating may be required if the ambient
temperature is greater than 40°C (104°F).
6/99
Molded Case Circuit Breakers
REFERENCE
Typical Specifications
General Specifications
Molded case circuit breakers shall provide circuit overcurrent protection with inverse
time and instantaneous tripping characteristics and shall be Siemens Sentron,
Sensitrip or approved equal.
All circuit breakers shall be CSA Certified and conform to applicable requirements of
NEMA Standard Publication No. AB1.
Solid State Sensing Specifications
As indicated on the drawings, circuit breaker frames 400
Ampere through 3200-Ampere shall have microprocessor-
based RMS sensing trip units, with the capability to
All circuit breakers shall have a quick-make, quick-break over center toggle type measure through to the 21st harmonic. Automatic
mechanism and the handle mechanism shall be trip free to prevent holding contacts operation of all circuit breaker frames 400A and larger shall
closed against a short circuit or sustained overload. All circuit breaker handles shall be obtained by means of solid state tripping elements
assume a position between “ON” and “OFF” when tripped automatically. Multi- providing inverse time delay and (instantaneous) and/or
pole circuit breakers shall be common-trip such that an overload or short circuit (short-time delay) circuit protection. Continuous current
on any one pole will result in all poles opening simultaneously. Arc extinction is to ratings shall be adjustable from 20% to 100% of the trip
be accomplished by magnetic arc chutes. All ratings are to be clearly visible. When unit rating, without the need for a rating plug. Long-time
reverse feed is indicated on the drawings, in accordance with CSA, circuit breakers delay and instantaneous trip shall be adjustable. The
with sealed trip units shall be supplied. optional short-time trip function shall have adjustable
pick-up settings, three fixed times, and I2t ramp. Circuit
breaker frames 400A and larger, and where indicated on
the drawings, shall be 100% equipment rated.
Thermal Magnetic Specifications
Unless otherwise noted on the drawings, all Circuit breakers 2000 Ampere
and below shall have thermal-magnetic trip units, with inverse time-current
Integral Ground
characteristics. Automatic operation of these circuit breakers shall be obtained Fault Option
by means of thermal-magnetic tripping devices located in each pole providing Main and feeder circuit breakers, as indicated on the
inverse time delay and instantaneous circuit protection. Circuit breakers shall be drawings, shall be provided with integral ground fault
ambient compensating in that, as the ambient temperature increases over 40°C, protection. Ground fault pick-up shall be adjustable from
the circuit breaker automatically derates itself so as to better protect its associated 20% to 70% of the circuit breakers maximum continuous
conductor. Thermal magnetic breakers from 250 to 2000A frames shall have thermal current rating. Ground fault time delay shall be adjustable
interchangeable trip units, with instantaneous magnetic trip settings that are with three 12t ramps.
adjustable and accessible from the front of all circuit breakers on frame sizes 250
Amperes and above. Where indicated, provide circuit breakers CSA Certified for
application at 100% of their continuous ampere rating in their intended enclosure. Metering Option
When indicated on the drawings, solid state trip breakers
shall be furnished with a plug-in or panel mounted
Motor Circuit Protectors metering device. This device shall simultaneously display
all three phase currents, as well as average current, ground
Where indicated on the drawings and in the combination motor starter/motor current, and phase unbalance. In addition it shall display
6
control center schedule, furnish instantaneous magnetic trip only circuit breakers for breaker status, a max log, and a trip log. The trip log will
motor short circuit protection. The magnetic trips shall be adjustable and accessible retain and display date, time and type of trip (overload,
from the front of all circuit breakers frames. The continuous current rating shall be short circuit or ground fault) for the most recent 5 trip
between 1 and 800 Amperes as indicated on the drawing. events.
Connection Accessories
Unless otherwise noted, Mechanical lugs shall be provided with all Molded Case
Breakers. Where indicated on the drawings, compression lugs shall be provided
on 1200 Ampere frame and below circuit breakers. All compression lugs shall be
supplied by the Circuit Breaker Manufacturer. Where indicated on the drawings, CSA
Certified plug-in or rear connectors shall be supplied.
6/100
Molded Case Circuit Breakers
General
Superseded Breakers
Sentron Series Note Superseded Note Superseded
CED62B015-CED62B125
CLE62B015-CLE62B100
CE2B015-CE2B100
CED62S100A
CLE62S100
CE2S100
CED63A001-CED63A125
CLE63A001-CLE63A125 -
CED63B015-CED63B125
CLE63B015-CLE63B100
CE3B015-CEB100
CED63S100A
CLE63S100
CE3S100
-
HHED62B015-HHED62B125
HED62B015-HED62B125
-
HHED63B015-HHED63B125
HED63B015-HED63B125
CFD62A150, CFD62L150, CFD62A250
CLF62A150, CLF62A250 -
CFD62B070-CFD62B250
CLF62B070-CLF62B240
CJ2B125-CJ2B250
CFD62S250A
CLF62S250 -
CFD63A150, CFD63L150, CFD63A250
CLF63A150, CLF63A250 -
CFD63B070-CFD63B250
CLF63B070-CLF63B250
CJ3B125-CJ3B250
CFD63S250A
CLF63S250
CJD62B200-CJD62B400
CLJ62B100-CLJ62B400
CJ2B300-CJ2B400
CJD62H400, CJD62L400
CLJ62L400, CLJ62H400 -
CJD62S400A
CLJ62S400
CJ2S400
CJD63B200-CJD63B400
CLJ63B200-CLJ63B400
CJ3B300-CJ3B400
CJD63H400, CJD63L400
CLJ63L400, CLJ63H400 -
CJD63S400A
CLJ63S400
CJ3S400
CPD63B120-CPD63B160
CP3B120-CP3B160 -
ED21B015-ED21B100
E21B015-E21B100
EE1B015-EE1B100
ED22B015-ED22B100
E22B015-E22B100
EE2B015-EE2B100
ED22S100A
E22S100A
EE2S100
ED23B015-ED23B100
E23B015-E23B100
EE3B015-EE3B100
ED23S100A
E23S100A
EE3S100
ED41B015-ED41B100
E41B015-E41B100
EH1B015-EH1B100
ED42B015-ED42B125
E42B015-E42B100
EH2B015-ED2B125
ED42S100A
E42S100
EH2S100
ED43B015-ED43B125
E43B015-E43B100
EH3B015-EH3B100
ED43S100A
E43S100
EH3S100
ED61B015-ED61B100
E61B015-E61B100
EF1B015-EF1B020
ED62B015-ED62B125
E62B015-E62B100
EF2B015-EF2B100
ED62S100A
E62S100A
EF2S100
ED63A001-ED63A125
E63A001-E63A125
EF3A003, EF3J050, EF3L050-EF3A100, EF3H1
ED63B015-ED63B125
E63B015-E63B100
EF3B015-EF3B100
ED63S100A
E63S100A
EF3S100
CED62B015-CED62B125
HHED62B015-HHED62B125 HED62B015-HED62B125
CED62B015-CED62B125
HHED63B015-HHED63B125 HED63B015-HED63B125
FD62B070-FD62B250 ,
F62B070, F62B250 -
FD63B070-FD63B250 ,
F63B070-F63B250 -
FXD62A150, FXD62L150, FXD62A250
FJ62A150, FJ62L150-FJ62A250 -
6
FXD62B070-FXD62B250 ,
FJ62B070-FJ62B250
FJ2B070-FJ2B225
FXD62S250A
FJ62S250
FJ2S225
FXD63A150, FXD63L150, FXD63A250
FJ63A150, FJ63L150-FJ63A250
FJ3A225
FXD63B070-FXD63B250 ,
FJ63B070-FJ63B250
FJ3B070-FJ3B225
FXD63S250A
FJ63S250
FJ3S225
HED41B015-HED41B100
HE41B015-HE41B100 -
HED42B015-HED42B125
HE42B015-HE42B100 -
HED43B015-HED43B125
HE43B015-HE43B100 -
-
HED61B015-HED61B100 HE61B015-HE61B100
BREAKERS
CED62B015-CED62B125
HED62B015-HED62B125
HE62B015-HE62B110 or (HE2B015-HE2B100)
CIRCUIT
CED63B015-CED63B125
HED63B015-HED63B125
HE63B015-HE63B100 or (HE3B015-HE3B100)
HFD62B070-HFD62B250
HF62B070-HF62B250 -
HFD63B070-HFD63B250
HF63B070-HF63B250 -
CED62B015-CED62B125
HHED62B015-HHED62B125 HED62B015-HED62B125
CED63B015-CED63B125
HHED63B015-HHED63B125 HED63B015-HED63B125
HJD63B200-HJD63B400
HJ63B200-HJ63B400
HJ3B125-HJ3B400
HLD63B250-HLD63B600
HL63B450-HL63B600
HL3B450-HL3B600
HMD63B500-HMD63B800
HN3B500-HN3B800 -
HND63B100-HND63B120
HK3B100-HK3B120 -
HPD63B120-HPD63B160
HP3B120-HP3B160 -
HRD63B160-HRD63B200
HR3B160-HR3B200 -
6/101
Molded Case Circuit Breakers
general
Superseded Breakers
Sentron Series Note Superseded Note Superseded
JD62B200-JD62B400
JLB200-JL62B400
JL2B070-JL2B400
JD63B200-JD63B400
JL63B200-JL63B400
JL3B0L0-JL3B400
JXD22B200-JXD22B400
JD22B200-JD22B400
JD2B250-JD2B400
JXD22S400A
JD22S400
JD2S400
JXD23B200-JXD23B400
JD23B200-JD23B400
JD3B250-JD3B400
JXD23S400A
JD23S400
JD3S400
JXD62B200-JXD62B400
JJ62B200-JJ62B400
JJ2B250-JJ2B400
JXD62H400, JXD62L400
JL62L400, JL62H400
JL2L400-JL2H400
JXD62S400A
JJ62S400A -
JXD63B200-JXD63B400
JJ63B200-JJ63B400
JJ3B200-JJ3B400
JXD63H400, JXD63L400
JL63A400, JL63H400, JL63L400
JL3H400, JL3L400, JL3A225
JXD63S400A
JJ63S400A -
LD62B250-LD62B500
LL63B250-LL62B600
LL2B450-LL2B600
LD62B250-LD63B600
LL63B250-LL63B600
LL3B450-LL3B600
LXD62B450-LXD62B600
LJ62B450-LJ62B600 -
LXD62J600, LXD62L600
LL2H600, LL2U600, LL2X600 -
LXD62S600A
LJ62S600 -
LXD63B450-LXD63B600
LJ63B450-LJ63B600 -
LXD64H600, LXD63L600
LL63H600, LL63L600
LL3A450, LL3H600
LXD63S600A
LJ63S600A
LL3S600
MD62B500-MD62B800
KM2B500-KM2B800 -
MD63B500-MD63B800
KM3B500-KM3B800 -
MXD62A800, MXD62H800, MXD62L800
KM2A800, KM2H800, KM2L800 -
MXD62S800A
KM2S800 -
MXD63A800, MXD63H800, MXD63L800
KM3A600, KM3H800, KM3L800 -
MXD63S800A
KM3S800 -
ND63B100-ND63B900
KP3B100-KP3B900 -
NXD63A120A
KP3S120 -
PD63B120-PD63B160
HP3B120-HP3B160 -
PXD63S160A
HP3S160 -
RD63B160-RD63B200
HR3B160-HR3B200 -
QJ22B060-QJ22B225
QJ2B125-QJ2B225 -
QJ22B060H-QJ22B225H - -
QJ22S225
QJS225 -
QJ23B060-QJ23B225
QJ3B125-QJ3B225 -
QJ23B060H-QJ23B225H - -
QJH22B060-QJH22B225
QJ2H125-QJ2B225 -
QJH23B060-QJH23B225
QJ3H125-QJ3H225 -
QJH23S225
QJ3S225 -
RD63B160-RD63B200
HR3B160-HR3B200 -
6
RXD63S200A
HR3S200 -
SHJD69200-SHJD69400
SHJ63B200-SHJ63B400G -
SHJD69200G-SHJD69400G
SHJ63B200G-SHJ63B400G -
SHJD69200NGT-SHJD69400NGT
SHJ63N200G-SHJ63N400G -
SHJD69200NT-SHJD69400NT
SHJ63N200-SHJ63N400 -
SHLD69300-SHLD69600
SHL63B300-SHL63B600 -
SHLD69300G-SHLD69600G
SHL63B300G-SHL63B600G -
SHLD69300NGT-SHLD69600NG
SHL63N300G-SHL63N600G -
BREAKERS
CIRCUIT
SHLD69300NT-SHLD69600NT
SHL63N300-SHL63N600 -
SHND69100A-SHND69120A
SHND69100-SHND69800
SHKF3B100-SHKF3B800
SHND69100AG-SHND69120AG
SHND69100G-SHND69800G
SHKF3B100G-SHKF3B800G
SHPD69120-SHPD69160
SHPF3B120-SHPF3B160 -
SHPD69120G-SHPD69160G
SHPF3B120G-SHPF3B160G -
1 Mechanically and electrically interchangeable. 3 Electrically interchangeable only if the system 4 Electrically interchangeable only if the system
2 Electrically interchangeable only, refer to sales office for interrupting capacity is less than or equal to: interrupting capacity is less than or equal to:
further details. 200 kA at 240V AC 200 kA at 240V AC
200 kA at 480V AC 150 kA at 480V AC
100 kA at 600V AC 100 kA at 600V AC
5 Refer to local sales office for replacement information.
6/102
Molded Case Circuit Breakers
general
Superseded Breakers
New Sentron Series Note Superseded Note Superseded
SHND69100NGT-SHND69800NGT
SHKF3N100G-SHKF3N800G
SHK3N100G-SHK3N600G
SHND69100NT-SHND69800NT
SHKF3N100-SHKF3N800
SHK3N100-SHK3N600
SHPF3B120-SHPF3B160
SHP3B120-SHP3B800 —
SHPF3B120G-SHPF3B160G
SHP3B120G-SHP3B800G —
SHPF3N120-SHPF3N160
SHP3N120-SHP3N800 —
SHPF3N120G-SHPF3N160G
SHP3N120G-SHP3N800G —
SJD69200-SJ369400
SJL63B200-SJL63B400 —
SJD69200G-SJD69400G
SJL63B200G-SJL63B400G —
SJD69200NGT-SJD69400NGT
SJL63N200G-SJL63N400G —
SJD69200NT-SJD69400NT
SJL63N200-SJL63N400 —
SLD69300-SLD69600
SLL63B300-SLL63B600 —
SLD69300G-SLD69600G
SLL63B300G-SLL63B600G —
SLD69300NGT-SLD69600NGT
SLL63N300G-SLL63N600G —
SLD69300NT-SLD69600NT
SLL63N300-SLL63N600 —
SMD69600A-SMD69800A
SMD69600-SMD69800
SKMF3B600-SKMF3B800
SMD69600AG-SMD69800AG
SMD69600G-SMD69800G
SKMF3B600G-SKMF3B800G
SMD69600ANGT-SMD69800ANGT
SMD69600NGT-SMD69800NGT
SKMF3N600G-SKMF3N800G
SMD69600ANT-SMD69800ANT
SMD69600NT-SMD69800NT
SKMF3N600-SKMF3N800
SND69800A-SND69120A
SND69100-SND69800
SKPF3B100-SKPF3B600
SND69800AG-SND69120AG
SND69100G-SND69800G
SKPF3B100G-SKPF3B600G
SND69800ANGT-SND69120ANGT
SND69100NGT-SND69800NGT
SKPF3N100G-SKPF3N600G
SND69800ANT-SND69120ANT
SND69100NT-SND69800NT
SKPF3N100-SKPF3N600
SPD69120-SPD69160
SHPF3B120-SHPF3B160 —
SPD69120G-SPD69160G
SHPF3B120G-SHPF3B160G —
SPD69120NGT-SPD69160NGT
SHPF3N120-SHPF3N160G —
SPD69120NT-SPD69160NT
SHPF3N120G-SHPF3N160G —
—
BQCC1B015-BQC1B030 —
—
CC1B015-CC1B030 —
—
CC2B015-CC2B030 —
—
CC3B015-CC3B030 —
—
EF2A003, EF2H050, EF2L050, EF2A100, —
EF2H150, EF2L150 —
—
EH1B015-EH1B100 —
—
EH2B015-EH2B100 —
—
EH3B015-EH3B100 —
—
HE2A003, HE2H050, HE2L050-HE2A100 —
—
HE3A003, HE3H050, HE3L050-HE3A100 —
—
HE3B015-HE3B100 —
6
BREAKERS
CIRCUIT
1 Mechanically and electrically interchangeable. 4 Electrically interchangeable only if the system 6 These units are no longer manufactured, and no
2 Electrically interchangeable only, refer to sales office interrupting capacity is less than or equal to: replacement is available.
for further details. 200 kA at 240V AC
3 Electrically interchangeable only if the system 150 kA at 480V AC
interrupting capacity is less than or equal to: 100 kA at 600V AC
200 kA at 240V AC 5 These units are for replacement purposes only. Consult
200 kA at 480V AC sales office for availability.
100 kA at 600V AC
6/103
Siemens VL Circuit Breakers
Reference Guide Selection/Application
Breakers
50°C CalibratedA
Auxiliary Switch
CASE
BREAKERS
MOLDEDCASE
CIRCUITBREAKERS
Alarm Switch
Shunt Trip
MOLDED
Undervoltage Release
Accessories & Mechanical Interlocks
CIRCUIT
6
6-16
6/104
Siemens VL Circuit Breakers
Reference Guide Selection/Application
6
Modifications Electric Motor or Stored Energy Operator
Rear Connecting Studs
Plug-In Mounting Assy. w/Trip Interlock
Draw-Out Assembly
Handle Mechanism Options
Fungus Proofing
NEMA 1 – Indoor, Surface Mount
NEMA 1 – Indoor, Flush Mount
BREAKERS
NEMA 3R – Outdoor, Rain Proof
CIRCUIT
EnclosuresA NEMA 4, 4X – Stainless Steel
NEMA 7, 9 – Hazardous Locations
NEMA 12 – Lint, Fine Dust, Oils, Coolant
Terminal Shields
Distribution Lugs
Ground Sensor (Neutral Transformer)
Communications available via COMPRO or COMMOD modules using Profibus or Modbus protocol.
500Vdc nominal, 600Vdc max. for ungrounded DC UPS systems.
DC Interrupting Ratings are not applicable to electronic circuit breakers.
# - Consult Siemens for these applications.
A - Consult Siemens for availability.
6/105
Molded Case Circuit Breakers
Selection
NGG 125A Frame
Type NGG (Cable In - Cable Out)
1-Pole 2-Pole 3-Pole
Continuous
Ampere Rating Catalog Catalog Catalog
@ 40°C Number Number Number
15 NGG1B015L 177.00 NGG2B015L473.00 NGG3B015L591.00
20 NGG1B020L 177.00 NGG2B020L473.00 NGG3B020L591.00
25 NGG1B025L177.00 NGG2B025L473.00 NGG3B025L591.00
30 NGG1B030L177.00 NGG2B030L473.00 NGG3B030L591.00
35 NGG1B035L177.00 NGG2B035L473.00 NGG3B035L591.00
40 NGG1B040L177.00 NGG2B040L473.00 NGG3B040L591.00 NGG
50 NGG1B050L177.00 NGG2B050L473.00 NGG3B050L591.00
60 NGG1B060L177.00 NGG2B060L473.00 NGG3B060L591.00
70 NGG1B070L209.00 NGG2B070L557.00 NGG3B070L695.00
2.9
80 NGG1B080L209.00 NGG2B080L557.00 NGG3B080L695.00
90 NGG1B090L209.00 NGG2B090L557.00 NGG3B090L695.00
100 NGG1B100L209.00 NGG2B100L557.00 NGG3B100L695.00
110 — NGG2B110L1023.00 NGG3B110L1279.00 5.4
125 — NGG2B125L1023.00 NGG3B125L1279.00
Line and load lugs are included as standard. If only load side lugs are needed, change “L” suffix to “B”.
HACR rated.
Suitable for screws or DIN rail mounting.
Shipping Weights
NGG
Number of Number per Shipping
Poles Carton Weight lbs. (kg)
1 1 .75 (0.34)
2 1 1.3 (0.59)
3 1 2.0 (0.98)
Interrupting Ratings
CSA / UL 489 AIR IEC 947-2
Number RMS Symmetrical Amperes (KA) Volts AC (50/60Hz)
Breaker of Volts AC(50/60Hz) Volts DC 220/240 380/415 Volts DC
BREAKERS
CIRCUIT
Type Poles 120 240 277 347 480 600/347 125 250 lcu lcs lcu lcs 250
01 65 — 25 18 — 0— 14 — 25 12.5 — — —
NGG
2, 3 0— 65 — — 25 TBD 0— 14 25 12.5 25 12.5 10
SWD rated.
HID rated at 277 VAC.
6/106
Molded Case Circuit Breakers
SELECTION
Internal Accessories for NGG and NGB 125A Frame
Shunt Trip
Control Voltage CQD, CQD6, NGG
V AC V DC Catalog Number List Price $
120 — CQDST120
240 — CQDST240
277 — CQDST277
480 — CQDST480
600 — CQDST600
— 012 CQDST12
— 024 CQDST24
— 048 CQDST48
— 125 CQDST125
Auxiliary Switch
Maximum Number
Voltage of CQD, CQD6, NGG
AC DC Contacts Catalog Number List Price $
240 125 1A–1B CQDA1
240 125 2A–2B CQDA2
Alarm Switch
Maximum
Voltage CQD, CQD6, NGG
AC DC Catalog Number List Price $
240 125 CQDBA
Shunt Trip
Voltage CQD, CQD6, NGG
AC DC Catalog Number List Price $
120 — CQDST120AAS
240 — CQDST240AAS
277 — CQDST277AAS
480 — CQDST480AAS
6
600 — CQDST600AAS
— 12 CQDST12DAS
— 24 CQDST24DAS
— 48 CQDST48DAS
— 125 CQDST125DAS
BREAKERS
CIRCUIT
For Breaker Catalog Number List Price $
CQD, CQD6, NGG CQDA1BA
Padlocking Devices
for locking breaker in “off” position Terminal Shields Breaker type
NGG HPLG NGG TSSG3A
6/107
6
3-Pole 15 HEM3M015L
100 HES3S100L 30 HEM3M030L
125 HES3S125L 50 HEM3M050L
160 HES3S160L 70 HEM3M070L
4-Pole 100 HEM3M100L
125 HES4S125L 125 HEM3M125L
6/108
Molded Case Circuit Breakers
Internal Accessories for NEG and HEG 125A Frame Selection
Shunt Trip Handle Operators
Control Voltage NEG, HEG
Description NEMA Type Catalog Number
V AC V DC Catalog Number List PriceRotary
$ Handle Operator
1 RHFESD
(black handle, breaker mounted)
110-240 125 STRER240 636.00 Rotary Handle Operator with Door Interlock
380-600 — STREV600 636.00 (black handle, breaker mounted)
1 RHFESDL
24-60 24-60 STREM60D 636.00 Rotary Handle Operator
1 RHFESDEM
(red handle, breaker mounted)
Variable Depth Rotary Operator Kit
(black handle, 6 inch shaft)
1, 12, 3R, 4X RHVE64X RHFESDEM
Variable Depth Rotary Operator Kit RHVE124X
(black handle, 12 inch shaft)
1, 12, 3R, 4X
Auxiliary Switch Variable Depth Rotary Operator Kit
1, 12, 3R, 4X RHVE244X
(black handle, 24 inch shaft)
Maximum Number Variable Depth Rotary Operator Kit
1, 12, 3R, 4X RHVEEM64X
Voltage of NEG, HEG
(red handle, 6 inch shaft)
Variable Depth Rotary Operator Kit RHVEEM124X
AC DC Contacts Catalog Number List Price $ 12 inch shaft)
(red handle,
1, 12, 3R, 4X
240 125 1A–1B ASKE2 271.00
Variable Depth Rotary Operator Kit
1, 12, 3R, 4X RHVEEM244X
240 125 2A–2B ASKE3 (red handle, 24 inch shaft)
540.00 RHVE64X
Flex Operator Kit
(Flange Mounted Variable Depth, 24 in. cable)
1, 12 MFKE2
Flex Operator Kit
(Flange Mounted Variable Depth, 36 in. cable)
1, 12 MFKE3
6
48 UVREC48D 636.00 Flex Operator Kit 4X MFKE4X9
(Flange Mounted Variable Depth, 108 in. cable)
125 UVRED125D 636.00 Flex Operator Kit
4X MFKE4X10
(Flange Mounted Variable Depth, 120 in. cable)
250 UVREE250D 636.00
All operators are for use on 3-pole and 4-pole breakers.
BREAKERS
For Breaker Catalog Number List Price $
CIRCUIT
NEG, HEG ASKE6 540.00
Miscellaneous Accessories
Breaker Amp Catalog
Rating (A) Description Number
Mounting Screw Kit, 1-pole MSKE1
Mounting Screw Kit, 2-pole MSKE2
Mounting Screw Kit, 3 or 4-pole MSKE4
DIN Rail Adapter, 3 or 4-pole DRAE3
6/109
VL Circuit Breakers
Trip Unit Overview Selection
The interchangeability of the VL circuit mation menus. With precise control frame and do not overlap with the set-
breaker trip units allow for easy conver- over the circuit beaker functions and tings on the other frames. Therefore,
sion from any of 3 types of protection. access to system status, diagnostics, when VL breakers are used together in
They are thermal-magnetic, electronic, and information, these trip units allow a system the GF protection is automati-
or electronic with a built-in LCD display. for unsurpassed flexibility in circuit cally coordinated. The user also has the
The thermal-magnetic trip unit features coordination. ability to program a custom coordina-
an adjustable magnetic trip setting. The tion scheme with the high level of
electronic trip units are microprocessor An example of coordination is the out adjustability available on the Model
based true RMS sensing devices and of the box Ground Fault function on the 576 trip units.
are available with a variety of adjustable Model 545 trip units. The pick-up and
trip settings, configurations, and infor- time delay settings are fixed for each
VL Trip Units
Trip Unit Functions Model 525 Model 545 Model 576
Thermal- Electronic Electronic Electronic Electronic Electronic with LCD Electronic with LCD
Magnetic LI LIG LSI LSIG LSI LSIG
Continuous Current
Fixed
Setting (Ir)
Long Time Delay (tr) Fixed Fixed
Instantaneous
Fixed Fixed
Overcurrent Setting (Ii)
Short Time Pick-up (Isd) (ON/OFF) (ON/OFF)
– Adjustable setting.
– This feature is included.
“fixed” – Non-Adjustable setting.
– Feature is not included.
– Requires the trip unit to be connected to a PC (via a COMPRO or COMMOD communications module) for access or programming.
Continuous Amps Rating (Ir) ting is fixed on LSI and LSIG trip units used with the Short Time Pick-up to
This setting is the continuous current and adjustable on LI and LIG trip units. achieve selectivity and better system
BREAKERS
CIRCUIT
that the breaker will carry without trip- These features are fully adjustable on coordination.
ping. It can be set up to 100% of the trip Model 576 trip units. Ground Fault Pick-Up (Ig)
unit’s nominal rating (In). Short Time Pick-Up (lsd) This setting controls the level of ground
This function controls the level of fault fault current that will cause the breaker
Long Time Delay (tr) current the breaker will carry for a short to trip. Model 545 Electronic Trip Units
Sometimes referred to as the “overload” time without tripping, thus allowing act on the residual current to sense
position, this function controls the break- downstream devices to clear short cir- ground current. The Model 576
er‘s “pause-in-tripping” time. It allows cuits ahead of up-stream protection. Electronic Trip Unit is programmable
low level, temporary inrush currents It may be defeated (turned-off) on and allows the user to select either
such as those encountered when start- Model 576 trip units. the residual current method or direct
ing a motor to pass without tripping. The detection (via a separate current trans-
time delay begins when the current Short Time Delay (tsd) former) to detect ground current.
reaches 6 x Ir. This controls the interval of time the
breaker will remain closed against a fault Ground Fault Time Delay (tg)
Instantaneous Pick-up (Ii) (at the Short Time Pick-up current level) This controls the interval of time the
This function sets the breaker to trip without tripping. The time delay may be breaker will remain closed after a ground
instantaneously during high fault condi- set at fixed points or at short time inter- fault is detected (at the Ground Fault
tions. On Model 545 trip units this set- vals based on l2t curves. This function is Pick-up current level) without tripping.
6/110
VL Circuit Breakers
General Information Selection
Thermal-Magnetic trip units, Model 525, combine the inverse time element design for low level overloads, and instantaneous
magnetic action for short circuit protection. The standard unit has preset overload protection and an adjustable instantaneous trip
setting, with 6 set points. Thermal-Magnetic trip units are available throughout the VL family, from 15 to 1600A.
Type/Tipo CLT3
M4-PAN-TORX
Ii M4-PAN-TORX
I n = 600A
3850 4400
40 C
3300 4950
TM ~
2750 5500
Trip Unit/Disparador 525 Cat. No. CLT3B600
6
has an LCD display
BREAKERS
CIRCUIT
6/111
VL Circuit Breakers
DG 150A Frame, VL Series Selection
Ordering Information
Complete Assembled Breaker
Prices for a complete factory assembled DG breaker include the frame, trip unit,
and standard line and load connectors, all factory installed and shipped as a
complete breaker. Assembled breakers are only available with standard
connectors.
For any other configuration, order the frame, trip unit, and terminals as
separate items.
For DC applications, use thermal magnetic trip unit only.
For reverse feed applications, select non-interchangeable trip breakers only. For
non-interchangeable trip breakers, change the third digit of the catalog number
to “X” for standard breakers.
For 50˚C and special applications, refer to page 6-144.A
Mounting hardware is included with each frame or complete breaker.
Interrupting Ratings
RMS Symmetrical Amperes (KA)
UL 489 IEC 60947-2
Volts AC (50/60 Hz) Volts DC Volts AC (50/60 Hz)
Breaker 220/240 380/415 690
Type 240 480 600 250 500 ICU ICS ICU ICS ICU ICS
NDG 65 35 18 30 18 65 65 40 40 12 6
HDG 100 65 20 30 18 100 75 70 70 12 6
LDG 200 100 25 30 18 200 150 100 75 12 6
Dimensions, inches (mm)
Number To Handle
of Poles Width Length Depth D1
Connectors for 75°C Wire 2, 3 4.1 (105)
Ampere Wire No. of cables Catalog List 6.9 (175) 3.4 (81) 4.2(107)
4 5.5 (139)
Construction Rating Range per connector Number Price $
Steel 50-150 #8–1/0 Cu 1 3TW1DG20 22.00
Aluminum 50-150 #6–3/0 Al/Cu 1 3TA1DG30 22.00
Copper 50-150 #6–3/0 Cu 1 3TC1DG30 101.00 Approx. Shipping Weight, lbs. (kg)
Distribution Lugs
Trip Unit Complete
50-150 #14–#2 Cu (3pcs. Max) 3 3TA3DG02 110.00
Poles Frame Thermal-Mag. Electronic Breaker
50-150 #14–#4 Cu 6 3TA6DG04 110.00
Compression Lugs 2, 3 3.7 (1.7) 2.2 (1.0) 2.6 (1.2) 5.9 (2.7)
6
50-150 #14–2/0 kcmil Al/Cu – 2CLD20 54.00 4 4.9 (2.2) 2.6 (1.2) 3.3 (1.5) 7.5 (3.4)
50-150 #14–2/0 kcmil Al/Cu – 3CLD20 81.00
Standard connector supplied with complete breakers.
Kit consists of 3 terminal connectors.
2 Lugs for 2-pole breakers.
3 Lugs for 3-pole breakers.
DG Thermal-Magnetic,
BREAKERS
CIRCUIT
Instantaneous Trip
Adjustment Range
Instantaneous
Trip Unit Continuous Overcurrent Setting (Ii)
Amp Rating (In) Min. Max.
50 450 700
60 450 700
70 450 700
80 450 800
90 500 1000
100 500 1000
110 550 1100
125 625 1250
150 800 1600
Note: Each breaker has 6 trip settings in this range.
6/112
VL Case Circuit Breakers
DG 150A Thermal-Magnetic Trip Unit Selection
AMPS I n =150A
1120 1280 40? C
TM ~
960 1440
6
90 NDG3B090L 1344.00 HDG3B090L 2372.00 LDG3B090L 3524.00 CDT3B090 533.00
100 NDG3B100L 1344.00 HDG3B100L 2372.00 LDG3B100L 3524.00 CDT3B100 533.00
110 NDG3B110L 2793.00 HDG3B110L 3821.00 LDG3B110L 4973.00 CDT3B110 1982.00
125 NDG3B125L 2793.00 HDG3B125L 3821.00 LDG3B125L 4973.00 CDT3B125 1982.00
150 NDG3B150L 2793.00 HDG3B150L 3821.00 LDG3B150L 4973.00 CDT3B150 1982.00
BREAKERS
N-Interrupting Class H-Interrupting Class L-Interrupting Class
CIRCUIT
Catalog List Catalog List Catalog List Catalog List
Number Price $ Number Price $ Number Price $ Number Price $
FRAME ONLY
Continuous NDG4F150 998.00 HDG4F150 2335.00 LDG4F150 3833.00
Ampere Rating COMPLETE FACTORY ASSEMBLED CIRCUIT BREAKER TRIP UNIT ONLY
50 NDG4B050L 1597.00 HDG4B050L 2934.00 LDG4B050L 4432.00 CDT4B050 541.00
60 NDG4B060L 1597.00 HDG4B060L 2934.00 LDG4B060L 4432.00 CDT4B060 541.00
70 NDG4B070L 1750.00 HDG4B070L 3087.00 LDG4B070L 4585.00 CDT4B070 694.00
80 NDG4B080L 1750.00 HDG4B080L 3087.00 LDG4B080L 4585.00 CDT4B080 694.00
90 NDG4B090L 1750.00 HDG4B090L 3087.00 LDG4B090L 4585.00 CDT4B090 694.00
100 NDG4B100L 1750.00 HDG4B100L 3087.00 LDG4B100L 4585.00 CDT4B100 694.00
110 NDG4B110L 3634.00 HDG4B110L 4971.00 LDG4B110L 6469.00 CDT4B110 2578.00
125 NDG4B125L 3634.00 HDG4B125L 4971.00 LDG4B125L 6469.00 CDT4B125 2578.00
150 NDG4B150L 3634.00 HDG4B150L 4971.00 LDG4B150L 6469.00 CDT4B150 2578.00
6/113
VL Circuit Breakers
DG 150A Electronic 3-Knob & LCD Trip Units Selection
6/114
VL Circuit Breakers
Internal Accessories for DG 150A and FG 250A Frames Selection
Auxiliary Switch and Alarm Switch Combination Kits
Description Mounting Pocket Catalog Number List Price $
1 Alarm Switch
1A/B Left, Right ASKL1
Bases AMBL2 & AMBL3
2 Aux. Switches
1A + 1B Left, Right, Neutral ASKL2
Bases AMBL1
2 Aux. + 1 Alarm Switch
1A + 1B, 1A/B Left, Right ASKL3
Bases AMBL2 & AMBL3
Shunt Trips
Description Mounting Pocket Catalog Number List Price $
24 VDC STRLB24DC
48-60 VDC STRLC60DC
STRLD125DC
6
110-127 VDC
220-250 VDC Right Pocket Only STRLE250DC
48-60 VAC STRLM60
CIRCUIT BREAKERS
MOLDED CASE
110-127 VAC STRLN120
208-277 VAC STRLS277
380-600 VAC STRLV600
6
Undervoltage Release
Description Mounting Pocket Catalog Number List Price $
12 VDC UVRLA12DC
24 VDC UVRLB24DC
48 VDC UVRLC48DC
60 VDC UVRLG60DC
110-127 VDC UVRLD125DC
BREAKERS
220-250 VDC UVRLE250DC
CIRCUIT
110-127 VAC Right Pocket Only UVRLN120
220-240 VAC UVRLR240
208 VAC UVRLP208
277 VAC UVRLS277
380-415 VAC UVRLT415
440-480 VAC UVRLU480
600 VAC UVRLV600
‘A’ refers to a normally open contact (open when the breaker contacts are open).
‘B’ refers to a normally closed contact (closed when the breaker contacts are open).
Refer to the “Accessory Locations” chart for guidelines and limitations about which pockets may be used for accessory
combinations.
These kits include two bases, one for mounting switches in the left pocket and another for mounting in the right. External Accessories pages 6-142 through 6-155
Includes 1A and 1B contact for alarm purposes, only one of which may be installed at any time.
6/115
VL Circuit Breakers
FG 250A Frame, VL Series Selection/Dimensions
Ordering Information
Complete Assembled Breaker
Prices for a complete factory assembled FG breaker include the frame, trip
unit, and standard line and load connectors, all factory installed and shipped
as a complete breaker. Assembled breakers are available only with standard
connectors.
For any other configuration, order the frame, trip unit, and terminals as
separate items.
For DC applications, use thermal magnetic trip unit only.
For reverse feed applications, select non-interchangeable trip breakers only.
For non-interchangeable trip breakers, change the third digit of the catalog
number to “X” for standard breakers.
For 50˚C and special applications, refer to page 6-160.A
Mounting hardware is included with each frame or complete breaker. Dimensions, inches (mm)
Number To Handle
of Poles Width Length Depth D1
Interrupting Ratings 2, 3 4.1 (105)
6.9 (175) 3.4 (81) 4.2 (107)
RMS Symmetrical Amperes (KA) 4 5.5 (139)
UL 489 IEC 60947-2
Breaker
Volts AC (50/60 Hz) Volts DC
220/240
Volts AC (50/60 Hz)
380/415 690
Shipping Weight, lbs. (kg)
Type 240 480 600 250 500 ICU ICS ICU ICS ICU ICS Trip Unit Complete
NFG 65 35 18 30 18 65 65 40 40 12 6 Poles Frame Thermal-Mag. Electronic Breaker
HFG 100 65 20 30 25 100 75 70 70 12 6 2, 3 4.0 (1.8) 2.2 (1.0) 2.6 (1.2) 6.2 (2.8)
LFG 200 100 25 30 30 200 150 100 75 12 6 4 5.3 (2.4) 2.6 (1.2) 3.3 (1.5) 7.9 (3.6)
FG Thermal-Magnetic,
Instantaneous Trip
Adjustment Range
Instantaneous
Trip Unit Continuous Overcurrent Setting (Ii)
Amp Rating (In) Min. Max.
100 625 1250
110 800 1600
125 800 1600
150 800 1600
175 1000 2000
200 1000 2000
225 1250 2500
250 1250 2500
Note: Each breaker has 6 trip settings in this range.
6/116
VL Circuit Breakers
FG 250A Thermal-Magnetic Trip Unit Selection
AMPS I n =250A
1750 2000 40? C
TM ~
1500 2250
6
200 NFG3B200L HFG3B200L LFG3B200L CFT3B200
225 NFG3B225L HFG3B225L LFG3B225L CFT3B225
250 NFG3B250L HFG3B250L LFG3B250L CFT3B250
BREAKERS
Catalog List Catalog List Catalog List Catalog List
CIRCUIT
Number Price $ Number Price $ Number Price $ Number Price $
FRAME ONLY
Continuous NFG4F250 HFG4F250 LFG4F250
Ampere Rating COMPLETE FACTORY ASSEMBLED CIRCUIT BREAKER TRIP UNIT ONLY
100 NFG4B100L HFG4B100L LFG4B100L CFT4B100
110 NFG4B110L HFG4B110L LFG4B110L CFT4B110
125 NFG4B125L HFG4B125L LFG4B125L CFT4B125
150 NFG4B150L HFG4B150L LFG4B150L CFT4B150
175 NFG4B175L HFG4B175L LFG4B175L CFT4B175
200 NFG4B200L HFG4B200L LFG4B200L CFT4B200
225 NFG4B225L HFG4B225L LFG4B225L CFT4B225
250 NFG4B250L HFG4B250L LFG4B250L CFT4B250
6/117
VL Circuit Breakers
FG 250A Electronic 3-Knob & LCD Trip Units Selection
6/118
VL Circuit Breakers
Internal Accessories for DG 150A and FG 250A Frames Selection
Auxiliary Switch and Alarm Switch Combination Kits
Description Mounting Pocket Catalog Number List Price $
1 Alarm Switch
1A/B Left, Right ASKL1
Bases AMBL2 & AMBL3
2 Aux. Switches
1A + 1B Left, Right, Neutral ASKL2
Bases AMBL1
2 Aux. + 1 Alarm Switches
1A + 1B, 1A/B Left, Right ASKL3
Bases AMBL2 & AMBL3
Shunt Trips
Description Mounting Pocket Catalog Number List Price $
24 VDC STRLB24DC
6
48-60 VDC STRLC60DC
110-127 VDC STRLD125DC
STRLE250DC
CIRCUIT BREAKERS
MOLDED CASE
220-250 VDC Right Pocket Only
48-60 VAC STRLM60
110-127 VAC STRLN120
208-277 VAC STRLS277
380-600 VAC STRLV600
6
Undervoltage Release
Description Mounting Pocket Catalog Number List Price $
12 VDC UVRLA12DC
24 VDC UVRLB24DC
48 VDC UVRLC48DC
60 VDC UVRLG60DC
BREAKERS
UVRLD125DC
CIRCUIT
110-127 VDC
220-250 VDC UVRLE250
110-127 VAC Right Pocket Only UVRLN120
220-240 VAC UVRLR240
208 VAC UVRLP208
277 VAC UVRLS277
380-415 VAC UVRLT415
440-480 VAC UVRLU480
600 VAC UVRLV600
‘A’ refers to a normally open contact (open when the breaker contacts are open).
‘B’ refers to a normally closed contact (closed when the breaker contacts are open).
Refer to the “Accessory Locations” chart for guidelines and limitations about which pockets may be used for accessory
combinations.
These kits include two bases, one for mounting switches in the left pocket and another for mounting in the right. External Accessories pages 6-142 through 6-155
Includes 1A and 1B contact for alarm purposes, only one of which may be installed at any time.
6/119
VL Circuit Breakers
JG 400A Frame, VL Series Selection/Dimensions
Ordering Information
Complete Assembled Breaker
Prices for a complete factory assembled JG breaker include the frame, trip
unit, and standard line and load connectors, all factory installed and shipped
as a complete breaker. Assembled breakers are available only with
standard connectors.
For any other configuration, order the frame, trip unit, and terminals as
separate items.
For DC applications, use thermal magnetic trip unit only.
For reverse feed applications, select non-interchangeable trip breakers only. For
non-interchangeable trip breakers, change the third digit of the catalog number
to “X” for standard breakers.
100% Rated: For 100% rated breakers (or frames) with an interchangeable trip
unit, change the 3rd character of the catalog name to ”H”.
For 100% rated breakers with a non-interchangeable trip unit, change the 3rd
character of the catalog number to ”Y“. Dimensions, inches (mm)
For 50˚C and special applications, refer to page 6-160.A
Number To Handle
Mounting hardware is included with each frame or complete breaker. of Poles Width Length Depth D1
2, 3 5.5 (139)
11 (279) 4.2 (102) 5.4 (138)
Interrupting Ratings 4 7.2 (183)
EnclosuresA
Connectors for 75°C Wire List
Ampere Wire No. of cables Catalog List NEMA Class Catalog Number Price $
Construction Rating Range per connector Number Price $ 1 JG0401S CSO
Steel 70-400 1/0–600 kcmil Cu 1 3TW1JG600
Aluminum 70-400 3/0–250 kcmil Al/Cu 2 3TA2JG250 1 (Compact) JG0401SC CSO
Aluminum 70-400 250–750 kcmil Al 1 3TA1JG750 3R JG0403R CSO
6
JG Thermal-Magnetic,
Instantaneous
Trip Adjustment Range
Instantaneous
Trip Unit Continuous Overcurrent Setting (Ii)
Amp Rating (In) Min. Max.
250 1250 2500
300 1500 3000
350 1750 3500
400 2000 4000
Note: Each breaker has 6 trip settings in this range.
6/120
VL Circuit Breakers
JG 400A Thermal-Magnetic Trip Unit Selection
M4-PAN-TORX
Ii M4-PAN-TORX
AMPS
I n = 400A
2800 3200
40 C
2400 3600
TM ~
2000 4000
Trip Unit/Disparador 525
6
Ampere Rating COMPLETE FACTORY ASSEMBLED CIRCUIT BREAKER TRIP UNIT ONLY
250 NJG4B250L HJG4B250L LJG4B250L CJT4B250
300 NJG4B300L HJG4B300L LJG4B300L CJT4B300
350 NJG4B350L HJG4B350L LJG4B350L CJT4B350
400 NJG4B400L HJG4B400L LJG4B400L CJT4B400
JJ 400A Frame 240V max., 2-pole with Thermal-Magnetic Non-Interchangeable Trip Unit
N-Interrupting Class
Catalog List
BREAKERS
Continuous Number Price $
CIRCUIT
Ampere Rating COMPLETE BREAKER
250 NJJ2B250L
300 NJJ2B300L
350 NJJ2B350L
400 NJJ2B400L
JJ 400A Frame 240V max., 3-pole with Thermal-Magnetic Non-Interchangeable Trip Unit
N-Interrupting Class
Catalog List
Continuous Number Price $
Ampere Rating COMPLETE BREAKER
250 NJJ3B250L
300 NJJ3B300L
350 NJJ3B350L
400 NJJ3B400L
6/121
VL Circuit Breakers
JG 400A Electronic 3-Knob & LCD Trip Units Selection
6/122
VL Circuit Breakers
Internal Accessories for JG 400A and LG 600A Frames Selection
Auxiliary Switch and Alarm Switch Combination Kits
Description Mounting Pocket Catalog Number List Price $
1 Alarm Switch
1A/B Left, Right ASKL1
Bases AMBL2 & AMBL3
2 Aux. Switches
1A + 1B Left, Right, Neutral ASKL2
Bases AMBL1
2 Aux. + 1 Alarm Switches
1A + 1B, 1A/B Left, Right ASKL3
Bases AMBL2 & AMBL3
Shunt Trips
Description Mounting Pocket Catalog Number List Price $
24 VDC STRLB24DC
48-60 VDC STRLC60DC
110-127 VDC STRLD125DC
220-250 VDC Right Pocket Only STRLE250DC
48-60 VAC STRLM60
110-127 VAC STRLN120
208-277 VAC STRLS277
380-600 VAC STRLV600
Undervoltage Release
6
Description Mounting Pocket Catalog Number List Price $
12 VDC UVRLA12DC
24 VDC UVRLB24DC
48 VDC UVRLC48DC
60 VDC UVRLG60DC
110-127 VDC UVRLD125DC
220-250 VDC UVRLE250DC
BREAKERS
110-127 VAC Right Pocket Only UVRLN120
CIRCUIT
220-240 VAC UVRLR240
208 VAC UVRLP208
277 VAC UVRLS277
380-415 VAC UVRLT415
440-480 VAC UVRLU480
600 VAC UVRLV600
‘A’ refers to a normally open contact (open when the breaker contacts are open).
‘B’ refers to a normally closed contact (closed when the breaker contacts are open).
Refer to the “Accessory Locations” chart for guidelines and limitations about which pockets may be used for accessory
combinations.
Includes 1A and 1B contact for alarm purposes, only one of which may be installed at any time. External Accessories pages 6-142 through 6-155
6/123
VL Circuit Breakers
LG 600A Frame, VL Series Selection/Dimensions
Ordering Information
Complete Assembled Breaker
Prices for a complete factory assembled LG breaker include the frame, trip unit,
and standard line and load lugs, all factory installed and shipped as a complete
breaker. Assembled breakers are available only with standard connectors.
For any other configuration, order the frame, trip unit, and terminals as
separate items.
For DC applications, use thermal magnetic trip unit only.
For reverse feed applications, select non-interchangeable trip breakers only.
Change the third digit of the catalog number to “X” for non-interchangeable
trip unit.
For 50˚C and special applications, refer to page 6-160.A
Mounting hardware is included with each frame or complete breaker.
A Toggle Handle Extension is included with each frame or complete breaker.
LG Thermal-Magnetic,
BREAKERS
CIRCUIT
Instantaneous
Trip Adjustment Range
Instantaneous
Trip Unit Continuous Overcurrent Setting (Ii)
Amp Rating (In) Min. Max.
400 2000 4000
500 2500 5000
600 2750 5500
Note: Each breaker has 6 trip settings.
6/124
VL Circuit Breakers
LG 600A Thermal-Magnetic Trip Unit Selection
Type/Tipo CLT3
M4-PAN-TORX
Ii M4-PAN-TORX
I n = 600A
3850 4400
40 C
3300 4950
TM ~
2750 5500
Trip Unit/Disparador 525 Cat. No. CLT3B600
6
BREAKERS
CIRCUIT
6/125
VL Circuit Breakers
LG 600A Electronic 3-Knob & LCD Trip Units Selection
6/126
VL Circuit Breakers
Internal Accessories for JG 400A and LG 600A Frames Selection
Auxiliary Switch and Alarm Switch Combination Kits
Description Mounting Pocket Catalog Number List Price $
1 Alarm Switch
1A/B Left, Right ASKL1
Bases AMBL2 & AMBL3
2 Aux. Switches
1A + 1B Left, Right, Neutral ASKL2
Bases AMBL1
2 Aux. + 1 Alarm Switches
1A + 1B, 1A/B Left, Right ASKL3
Bases AMBL2 & AMBL3
Shunt Trips
Description Mounting Pocket Catalog Number List Price $
24 VDC STRLB24DC
48-60 VDC STRLC60DC
110-127 VDC STRLD125DC
220-250 VDC Right Pocket Only STRLE250DC
48-60 VAC STRLM60
110-127 VAC STRLN120
208-277 VAC STRLS277
380-600 VAC STRLV600
Undervoltage Release
6
Description Mounting Pocket Catalog Number List Price $
12 VDC UVRLA12DC
24 VDC UVRLB24DC
48 VDC UVRLC48DC
60 VDC UVRLG60DC
110-127 VDC UVRLD125DC
BREAKERS
220-250 VDC UVRLE250DC
CIRCUIT
110-127 VAC Right Pocket Only UVRLN120
220-240 VAC UVRLR240
208 VAC UVRLP208
277 VAC UVRLS277
380-415 VAC UVRLT415
440-480 VAC UVRLU480
600 VAC UVRLV600
‘A’ refers to a normally open contact (open when the breaker contacts are open).
‘B’ refers to a normally closed contact (closed when the breaker contacts are open).
Refer to the “Accessory Locations” chart for guidelines and limitations about which pockets may be used for accessory
combinations.
Includes 1A and 1B contact for alarm purposes, only one of which may be installed at any time. External Accessories pages 6-142 through 6-155
6/127
VL Circuit Breakers
MG 800A Frame, VL Series Selection/Dimensions
Ordering Information
Complete Assembled Breaker
Prices for a complete factory assembled MG breaker include the frame, trip
unit, and standard line and load lugs, all factory installed and shipped as a
complete breaker. Assembled breakers are available only with standard
connectors.
For any other configuration, order the frame, trip unit, and terminals as
separate items.
For DC applications, use thermal magnetic trip unit only.
For reverse feed applications, select non-interchangeable trip breakers only. For
non-interchangeable trip breakers, change the third digit of the catalog number
to “X” for standard breakers.
100% Rated: For 100% rated breakers (or frames) with an interchangeable trip
unit, change the 3rd character of the catalog name to ”H”.
For 100% rated breakers with a non-interchangeable trip unit, change the 3rd
character of the catalog number to ”Y“.
For 50˚C and special applications, refer to page 6-160.A Dimensions, inches (mm)
Mounting hardware is included with each frame or complete breaker. Number To Handle
of Poles Width Length Depth D1
A Toggle Handle Extension is included with each frame or complete breaker.
2, 3 7.5 (190)
16 (406) 4.5 (114) 5.9 (151)
4 10 (253)
Interrupting Ratings
RMS Symmetrical Amperes (KA) Shipping Weight, lbs. (kg)
UL 489 IEC 60947-2 Complete
Volts AC (50/60 Hz) Volts DC Volts AC (50/60 Hz) Poles Frame Trip Unit Breaker
Breaker 220/240 380/415 690
Type 240 480 600 250 500 ICU ICS ICU ICS ICU ICS 2, 3 31.3 (14.2) 4.0 (1.8) 35.3 (16.0)
NMG 65 35 25 22 35 65 65 50 50 20 10 4 40.2 (18.2) 5.0 (2.3) 45.2 (20.5)
HMG 100 65 35 25 50 100 75 70 70 30 15
LMG 200 100 50 42 65 200 150 100 75 35 17 EnclosuresA
List
Connectors for 75°C Wire NEMA Class Catalog Number Price $
Ampere Wire No. of cables Catalog List 1 MG0801S CSO
Construction Rating Range per connector Number Price $ 3R MG0803R CSO
Aluminum 200-800A 1/0–500 kcmil Al/Cu 3 3TA3MG500 Neutral (future) —
6
MG Thermal-Magnetic,
Instantaneous
Trip Adjustment Range
Instantaneous
Trip Unit Continuous Overcurrent Setting (Ii)
Amp Rating (In) Min. Max.
600 3000 6000
700 3250 6500
800 3250 6500
Note: Each breaker has 6 trip settings.
6/128
VL Circuit Breakers
MG 800A Thermal-Magnetic Trip Unit Selection
AMPS Ii
I n = 800A
4550 5200
3900
40 C
5850
TM ~
3250 6500
Trip Unit/Disparador 525
6
800 NMG3B800L HMG3B800L LMG3B800L CMT3B800
CIRCUIT BREAKERS
MOLDED CASE
6BREAKERS
CIRCUIT
6/129
VL Circuit Breakers
MG 800A Electronic 3-Knob & LCD Trip Units Selection
Alarm Ir 315 350 I sd 1.5 2 t sd .2 .3 2 V1.04
>1.05 Sec.
I t
300 400 1.5 2.5 .1 .4 OFF
300 500 1.5 3 0 .5
X3 800 600 7 4 2 .4 .1
700 630 xI r 6 5 I t .3 .2
680HG Amps ON Active
A= 605 B= 612
C= 615 N= 0
X3
680JM
6/130
VL Circuit Breakers
Internal Accessories for MG 800A, NG 1200A and PG 1600A Frames Selection
Auxiliary Switch and Alarm Switch Combination Kits
Description Mounting Pocket Catalog Number List Price $
2 Aux. + 2 Alarm Switches
2A + 2B Left Pocket Only ASKP3
Bases AMBP2
4 Aux. Switches
2A + 2B Left, Right, Neutral ASKP4 x4
Bases AMBP1
Shunt Trips
Description Mounting Pocket Catalog Number List Price $
24 VDC STRPB24DC
48-60 VDC STRPC60DC
110-127 VDC STRPD125DC
220-250 VDC Right Pocket Only STRPE250DC
48-60 VAC STRPM60
110-127 VAC STRPN120
208-277 VAC STRPS277
380-600 VAC STRPV600
Undervoltage Release
Description Mounting Pocket Catalog Number List Price $
12 VDC UVRPA12DC
24 VDC UVRPB24DC
6
48 VDC UVRPC48DC
60 VDC UVRPG60DC
110-127 VDC UVRPD125DC
220-250 VDC UVRPE250DC
110-127 VAC Right Pocket Only UVRPN120
220-240 VAC UVRPR240
208 VAC UVRPP208
277 VAC UVRPS277
BREAKERS
380-415 VAC UVRPT415
CIRCUIT
440-480 VAC UVRPU480
600 VAC UVRPV600
‘A’ refers to a normally open contact (open when the breaker contacts are open).
‘B’ refers to a normally closed contact (closed when the breaker contacts are open).
Refer to the “Accessory Locations” chart for guidelines and limitations about which pockets may be used for accessory
combinations.
6/131
VL Circuit Breakers
NG 1200A Frame, VL Series Selection/Dimensions
Ordering Information
Complete Assembled Breaker with Lugs
Prices for a complete factory assembled NG breaker include the frame, trip unit,
and standard line and load lugs, all factory installed and shipped as a complete
breaker. Assembled breakers are available only with standard connectors.
For any other configuration, order the frame, trip unit, and terminals as
separate items.
For DC applications, use thermal magnetic trip unit only.
For reverse feed applications, select non-interchangeable trip breakers only. For
non-interchangeable trip breakers, change the third digit of the catalog number
to “X” for standard breakers.
100% Rated: For 100% rated breakers (or frames) with an interchangeable trip
unit, change the 3rd character of the catalog name to ”H”.
For 100% rated breakers with a non-interchangeable trip unit, change the 3rd
character of the catalog number to ”Y“.
For 50˚C and special applications, refer to page 6-160.A
Mounting hardware is included with each frame or complete breaker. Dimensions, inches (mm)
Number To Handle
A Toggle Handle Extension is included with each frame or complete breaker. of Poles W L D D1
2, 3 9 (229)
4 12 (305) 16 (406) 6 (152) 8.1 (207)
Interrupting Ratings
UL 489
RMS Symmetrical Amperes (KA)
IEC 60947-2
Shipping Weight, lbs. (kg)
Volts AC (50/60 Hz) Volts DC Volts AC (50/60 Hz) Complete
Breaker 220/240 380/415 690 Poles Frame Trip Unit Breaker
Type 240 480 600 250 500 ICU ICS ICU ICS ICU ICS
2, 3 46.3 (21.0) 8.8 (4.0) 55.1 (25.0)
NNG 65 35 25 22 35 65 35 50 25 20 10
4 60.6 (27.5) 13.2 (6.0) 73.8 (33.5)
HNG 100 65 35 25 50 100 50 70 35 30 15
LNG 200 100 65 42 65 200 100 100 50 35 17
EnclosuresA
Catalog List
Connectors for 75°C Wire Type Number Price $
1 NG1201S CSO
Ampere Wire No. of cables Catalog List
Construction Rating Range per connector Number Price $ 3R NG1203R CSO
Aluminum 300-1200A 1/0–500 kcmil Al/Cu 4 3TA4NG500 12 NG12012 CSO
6
NG Thermal-Magnetic,
Instantaneous
Trip Adjustment Range
Instantaneous
Trip Unit Continuous Overcurrent Setting (Ii)
Amp Rating (In) Min. Max.
800 4000 8000
900 5000 10000
1000 5000 10000
1200 7000 12000
Note: Each breaker has 6 trip settings.
6/132
VL Circuit Breakers
NG 1200A Thermal-Magnetic Trip Unit Selection
Ii I n = 1200A Ii Ii
AMPS AMPS AMPS
40 C
9000 10000 9000 10000 9000 10000
8000
TM ~ 8000 8000
11000 11000 11000
6
BREAKERS
CIRCUIT
6/133
VL Circuit Breakers
NG 1200A Electronic 3-Knob & LCD Trip Units Selection
In = 1200 A ~ Alarm Ir tr Ii
V2.02
>1.05
500 600 6 8 240 360
400 630 4 10 180 480
400 700 2.5 14 150 600
X3 1200 800 30 17 1200 720
1000 900 Sec. 25 20 1200 960
Amps Amps x10 Active
2 4 6
6/134
VL Circuit Breakers
Internal Accessories for MG 800A, NG 1200A, and PG 1600A Frames Selection
Auxiliary Switch and Alarm Switch Combination Kits
Description Mounting Pocket Catalog Number List Price $
2 Aux. + 2 Alarm Switches
2A + 2B Left Pocket Only ASKP3
Base AMBP2
4 Aux. Switches
2A + 2B Left, Right, Neutral ASKP4
Base AMBP1 x4
Shunt Trips
Description Mounting Pocket Catalog Number List Price $
24 VDC STRPB24DC
48-60 VDC STRPC60DC
110-127 VDC STRPD125DC
220-250 VDC Right Pocket Only STRPE250DC
48-60 VAC STRPM60
110-127 VAC STRPN120
208-277 VAC STRPS277
380-600 VAC STRPV600
Undervoltage Release
Description Mounting Pocket Catalog Number List Price $
12 VDC UVRPA12DC
24 VDC UVRPB24DC
6
48 VDC UVRPC48DC
60 VDC UVRPG60DC
110-127 VDC UVRPD125DC
220-250 VDC UVRPE250DC
110-127 VAC Right Pocket Only UVRPN120
220-240 VAC UVRPR240
208 VAC UVRPP208
BREAKERS
CIRCUIT
277 VAC UVRPS277
380-415 VAC UVRPT415
440-480 VAC UVRPU480
600 VAC UVRPV600
‘A’ refers to a normally open contact (open when the breaker contacts are open).
‘B’ refers to a normally closed contact (closed when the breaker contacts are open).
Refer to the “Accessory Locations” chart for guidelines and limitations about which pockets may be used for accessory combinations.
6/135
VL Circuit Breakers
PG 1600A Frame, VL Series & Thermal-Magnetic Trip Unit Selection/Dimensions
Ordering Information
Prices for a complete factory assembled PG breaker include the frame and trip
unit only. The connectors must be ordered as separate items.
For any other configuration, order the frame, trip unit, and connectors as
separate items.
Connectors require a Breaker Lug Mounting Assembly or Breaker Mounting
Base and must be ordered as a seperate item.
For DC applications, use Thermal magnetic trip unit only.
For reverse feed applications select non-interchangeable trip breakers only.
Change the third digit of the catalog number to “X” for non-interchangeable trip
breakers.
100% Rated: For 100% rated breakers (or frames) with an interchangeable trip
unit, change the 3rd character of the catalog name to ”H”.
For 100% rated breakers with a non-interchangeable trip unit, change the 3rd
character of the catalog number to ”Y“.
For 50˚C and special applications, refer to page 6-160.A
Mounting hardware is included with each frame or complete breaker. Dimensions, inches (mm)
Number To Handle
A Toggle Handle Extension is included with each frame or complete breaker. of Poles W L D D1
2, 3 9 (229)
Interrupting Ratings 4 12 (305) 16 (406) 6 (152) 8.1 (207)
RMS Symmetrical Amperes (KA)
UL 489 IEC 60947-2 Shipping Weight, lbs. (kg)
Volts AC (50/60 Hz) Volts DC Volts AC (50/60 Hz) Complete
Breaker 220/240 380/415 690 Poles Frame Trip Unit Breaker
Type 240 480 600 250 500 ICU ICS ICU ICS ICU ICS
NPG 65 35 25 22 35 65 35 50 25 20 10 2, 3 60.2 (27.3) 8.8 (4.0) 69.0 (31.3)
HPG 100 65 35 25 50 100 50 70 35 30 15 4 76.7 (34.8) 13.2 (6.0) 89.9 (40.8)
LPG 200 100 65 42 65 200 100 100 50 35 17
PG Thermal-Magnetic,
Connectors for 75°C Wire Instantaneous
Ampere Wire No. of cables Catalog List Trip Adjustment Range
Construction Rating Range per phase Number Price $
Aluminum 1200-1600A 1/0–750 kcmil Al/Cu 6 3TA6PG750 Instantaneous
Copper 1200-1600A 1/0–750 kcmil Cu 6 3TC6PG750 (future) Trip Unit Continuous Overcurrent Setting (Ii)
Aluminum 1200-1600A 300–600 kcmil 5 TA5P600 Amp Rating (In) Min. Max.
6
Mounting Arrangement
Description Catalog Number List Price $
Lug Mounting Assembly LMAP1600
Breaker Mounting Base (Front Connect) MBPG1600
Breaker Mounting Base (Rear Connect) MBPG1601 Model 525 Trip Unit
6/136
VL Circuit Breakers
PG 1600A Electronic 3-Knob & LCD Trip Units Selection
6
ELECTRONIC LSIG TRIP
1200 NPG4U120 HPG4U120 LPG4U120 CPT4U120
1600 NPG4U160 HPG4U160 LPG4U160 CPT4U160
ELECTRONIC LIG TRIP
1200 NPG4X120 HPG4X120 LPG4X120 CPT4X120
1600 NPG4X160 HPG4X160 LPG4X160 CPT4X160
BREAKERS
Model 576 Trip Unit CIRCUIT
PG 1600A Frame 3-Pole Electronic LCD Trip Unit
N-Interrupting Class H-Interrupting Class L-Interrupting Class
Catalog List Catalog List Catalog List Catalog List
Number Price $ Number Price $ Number Price $ Number Price $
FRAME ONLY
Continuous NPG3F160 HPG3F160 LPG3F160
Ampere Rating COMPLETE FACTORY ASSEMBLED CIRCUIT BREAKER TRIP UNIT ONLY
LCD ELECTRONIC LSI TRIP
1200 NPG3D120 HPG3D120 LPG3D120 CPT3D120
1600 NPG3D160 HPG3D160 LPG3D160 CPT3D160
LCD ELECTRONIC LSIG TRIP
1200 NPG3E120 HPG3E120 LPG3E120 CPT3E120
1600 NPG3E160 HPG3E160 LPG3E160 CPT3E160
A - Consult with Siemens for availability.
6/137
VL Circuit Breakers
Internal Accessories for MG 800A, NG 1200A, and PG 1600A Frames Selection
Auxiliary Switch and Alarm Switch Combination Kits
Description Mounting Pocket Catalog Number List Price $
2 Aux. + 2 Alarm Switches
2A + 2B Left Pocket Only ASKP3
Base AMBP2
4 Aux. Switches
2A + 2B Left, Right, Neutral ASKP4
Base AMBP1 x4
Shunt Trips
Description Mounting Pocket Catalog Number List Price $
24 VDC STRPB24DC
48-60 VDC STRPC60DC
110-127 VDC STRPD125DC
220-250 VDC Right Pocket Only STRPE250DC
48-60 VAC STRPM60
110-127 VAC STRPN120
208-277 VAC STRPS277
380-600 VAC STRPV600
Undervoltage Release
Description Mounting Pocket Catalog Number List Price $
12 VDC UVRPA12DC
24 VDC UVRPB24DC
6
48 VDC UVRPC48DC
60 VDC UVRPG60DC
110-127 VDC UVRPD125DC
220-250 VDC UVRPE250DC
110-127 VAC Right Pocket Only UVRPN120
220-240 VAC UVRPR240
BREAKERS
CIRCUIT
‘A’ refers to a normally open contact (open when the breaker contacts are open).
‘B’ refers to a normally closed contact (closed when the breaker contacts are open).
Refer to the “Accessory Locations” chart for guidelines and limitations about which pockets may be used for accessory combinations.
6/138
Molded Case Circuit Breakers
Molded Case Switch Selection
General switch has a fixed instantaneous self- the molded case switch. Also, the
Typically a molded case switch is used protecting trip element which may short-circuit current rating of the
when a compact load-break switch is open the switch under high fault condi- switch is limited to the interrupting rat-
needed for disconnect purposes. The tions. ing of the upstream protective device
VL line of molded case switches from or the ratings in the table below,
Application Note whichever is less.
Siemens is made of the same materi-
als and components as the VL circuit Overcurrent protection must be provid-
breakers but do not provide overcur- ed by an appropriate overcurrent pro-
rent protection. Each molded case tective device located upstream from
Ordering Information
Each type VL molded case switch accepts the same terminals and accessories as the equivalent VL circuit breakers.
All type VL molded case switches are suitable for reverse feed applications.
Mounting hardware and standard line and load terminals are included on ratings through 250A. For 400 – 1600A ratings,
order the lugs separately.
All ratings are UL listed and CSA certified.
6
Ampere Instantaneous
Rating / Frame 3-Pole 240V 480V 600V Override
250A /FG LFS3S250L 200k 100k 25k 3,500A
400A / JG LJS3S400 200k 100k 42k 4,400A
600A / LG LLS3S600 200k 100k 42k 5,500A
800A / MG LMS3S800 200k 100k 50k 6,500A
1200A / NG LNS3S120 200k 100k 65k 12,000A
1600A / PG LPS3S160 200k 100k 65k 12,000A
BREAKERS
CIRCUIT
* The Short-Circuit Current Rating is the maximum available current of the circuit where the switch is used, when protected by an appropriate overcurrent protective device.
Above 250A, terminals are not included and must be ordered separately. For terminal information and the variety of lugs available for VL breakers.
6/139
Molded Case Circuit Breakers
Motor Circuit Protectors Selection
General
Protection of Motor Circuits
Molded case circuit breakers are used in motor circuits as a disconnecting means and for short-circuit protection. They should be
used in conjunction with motor-running, over-current protection devices, and should permit the motor to start without nuisance trip-
ping from motor-inrush current. The circuit breaker should have a continuous current rating of not less than 115% of the motor full-
load current.
The recommended motor circuit protectors listed have continuous-current ratings of at least 115% of motor full-load currents. The
trip setting positions are approximately 11 times motor full-load current. The suggested trip settings may need to be adjusted
upward to no higher than 1300% of full-load current for non-design E type motors, and no greater than 1700% of full-load current
for design E motors, to allow for motor startup due to in-rush current.
Important: The information below does not apply to all motor applications: it is recommended that the user refer to the National
Electrical Code (NEC) for specific needs.
Motor circuit protectors rated 150A and 250A are supplied with line and load lugs installed. If lugs are required on
400A to 1200A motor circuit breakers, order required lugs separately.
6/140
VL External Accessories
Operating Mechanisms Selection
6
BREAKERS
CIRCUIT
6/141
VL External Accessories
Operating Mechanisms
For DG to FG Frame For JG to LG Frame
150 to 250 A 400 A to 600 A
Catalog List Catalog List
Description Number Price $ Number Price $
Through Door Mounted Rotary Handle Operator KitA
Fixed depth and the handle is mounted
directly on the circuit breaker.
Lockable knob (for up to 3 padlocks).
NEMA 1, 12 RHFF 155.00 RHFL 193.00
Red Handle Version
with red knob, yellow indicator plate
NEMA 1, 12 RHFFEM 168.00 RHFLEM 205.00
Door Mounted Rotary Handle Operator KitA
Variable depth, door mounted handle.
Includes knob with masking frame,
indicator plate, detachable door coupling,
12" shaft, and breaker mounted rotary
operator. Lockable knob (for up to 3
padlocks).
NEMA 1, 12 RHVF12 214.00 RHVL12 295.00
During manual operation, Early Break auxiliary switch contacts open before the breaker opens.
A - Consult with Siemens for availability.
6/142
For MG Frame For NG to PG Frame
800 A 1200 to 1600 A
Catalog List Catalog List
Description Number Price $ Number Price $
Through Door Mounted Rotary Handle Operator KitA
Fixed depth, breaker mounted.
For direct fitting to the circuit breaker.
Lockable with up to 3 padlocks.
NEMA 1, 12 RHFM 210.00 — —
Red Handle version
with red knob, yellow indicator plate
NEMA 1, 12 RHFMEM 226.00 — —
Door Mounted Rotary Handle Operator KitA
Variable depth, door mounted handle. — —
Includes knob with masking frame,
indicator plate, detachable door coupling,
12" shaft, and breaker mounted rotary
operator. Lockable knob (for up to 3
padlocks).
NEMA 1, 12 RHVM12 322.00 — —
6
Extension Shaft Only, for Door Mounted OperatorA
2 inches (50.8mm) RHVMS02 31.50 — —
3 inches (76.2mm) — — RHVPS03 97.00
12 inches (304.8 mm) RHVMS12 31.50 RHVPS12 97.00
16 inches (406.4 mm) RHVMS16 31.50 — —
24 inches (609.6mm) w/ support bracket RHVPS24 127.00 RHVPS24 127.00
BREAKERS
CIRCUIT
6/143
VL External Accessories
Operating Mechanisms
For DG and FG Frame For JG and LG Frame
150 to 250 A 400 to 600 A
Catalog List Catalog List
Description Number Price $ Number Price $
Variable Depth Flange Mounted Operator KitA
Adjustable from 8" to 16"
Complete kit, includes handle and
variable depth operator. NEMA 1, 3R, 12 FHVF3R 275.00 FHVL3R 294.00
NEMA 4X FHVF4X 368.00 FHVL4X 391.00
IEC Black Handle NEMA 1, 3R, 12 FHVF3RB 275.00 FHVL3RB 294.00
Breaker Operator Mechanism Only, for Max-Flex™ A MFMF 194.00 MFML 218.00
Max-Flex™ handles are available with solid gray or black handles instead of the customary “Red for On” flange handle.
The black handle is preferred for IEC markets, where red handles have a specific meaning.
During manual operation, Early Break aux. contacts open before the breaker opens.
A - Consult with Siemens for availability.
6/144
For MG Frame For NG Frame For PG Frame
800 A 1200 A 1600 A
Catalog List Catalog List Catalog List
Description Number Price $ Number Price $ Number Price $
Variable Depth Flange Mounted Operator KitA
Adjustable from 8" to 16"
Complete kit, includes handle and
variable depth operator. NEMA 1, 3R, 12 — — — — — —
NEMA 4X — — — — — —
IEC Black Handle NEMA 1, 3R, 12 — — — — — —
Breaker Operator Mechanism Only, for Max-Flex™ A MFMM 218.00 MFMP 218.00 MFMP 218.00
6
BREAKERS
CIRCUIT
6/145
VL External Accessories
Operating Mechanisms
For DG to FG Frame
150 to 250 A
Catalog List
Description Number Price $
Stored Energy and Motor Operators
Lockable with up to 3 padlocks.
AC Voltage DC Voltage Stored Energy Type
— 24 SEAFB 1915.00
42-48 42-48 SEAFM 1915.00
60 60 SEAFY 1915.00
110–127 110–127 SEAFN 1915.00
220–250 220–250 SEAFR 1915.00
Cylinder Locks for Field Installation CLKF 120.00
Draw-out Assembly
Includes base, position indicator switch, socket, base trip
interlock, crank handle, connectors, and necessary shields.
Rear Connected
3-pole DCADRC3 944.00 DCAFRC3 1194.00
Front Connected
3-pole DCADFC3 944.00 DCAFFC3 1194.00
(Draw-out assembly includes side plates and all hardware)
Hex Wrench for racking draw-out assembly and position indicator DCHP 134.00 DCHP 134.00
6
6/146
For JG to LG Frame For MG Frame For NG to PG Frame
400 to 600 A 800 A 1200 to 1600 A
Catalog List Catalog List Catalog List
Number Price $ Number Price $ Number Price $
For JG Frame For LG Frame For MG Frame For NG Frame For PG Frame
400 A 600 A 800 A 1200 A 1600 A
Catalog List Catalog List Catalog List Catalog List Catalog List
Number Price $ Number Price $ Number Price $ Number Price $ Number Price $
DCAJRC3 1881.00 DCALRC3 2886.00 DCAMRC3 4337.00 DCAPRC3 5566.00 DCAPRC3 5566.00
DCAJFC3 1881.00 DCALFC3 2886.00 DCAMFC3 4337.00 DCAPFC3A 5566.00 DCAPFC3A 5566.00
ASE
REAKERS
DCHP 134.00 DCHP 134.00 DCHP 134.00 DCHP 134.00 DCHP 134.00
DCIP 156.00 DCIP 156.00 DCIP 156.00 DCIP 156.00 DCIP 156.00
6
PCTL83 133.00 PCTL83 133.00 PCTM83 143.00 PCTP83 168.00 PCTP83 168.00
— — — — — — — — — —
BREAKERS
CIRCUIT
PCXJ3 410.00 PCXL3 483.00 PCXM3 1085.00 PCXN3 1344.00 — —
DCXJ3 378.00 DCXL3 452.00 DCXM3 1050.00 DCXN3 1307.00 DCXP3 1307.00
PCXLT 23.00 PCXLT 23.00 PCXMT 58.00 PCXPT 77.00 PCXPT 77.00
6/147
VL External Accessories
Connections
For DG Frame For FG Frame
150 A 250 A
Catalog List Catalog List
Description Number Price $ Number Price $
Front Bus Bar Connections
Includes nut keeper plates and shield.
Standard (straight)
3-Pole Set FBCD3 CSO FBCF3 CSO
Bus Bar Connection Strap Kit — — — —
Includes 6 - Bus Bars, 6 Nut Keepers & Shields
Standard 3-Pole Set
Rear-Connecting Studs
Short length round term. (1piece) RTLDSR 83.00 RTLFSR 83.00
Long length round term. (1piece) RTLDLR 112.00 RTLFLR 112.00
3-Pole round term. kit, 2 short + 1 long SRTDR3 277.00 SRTFR3 277.00
Short length flat term. (1piece) RTLDSF 83.00 RTLFSF 83.00
Long length flat term. (1piece) RTLDLF 112.00 RTLFLF 112.00
Round Terminal 3-Pole flat term. kit, 2 short + 1 long SRTDF3 277.00 SRTFF3 277.00
Flat bus bar type (1 piece) — — — —
3-Pole set of flat bus bar — — — —
Terminal Shields
Includes 1 terminal shield, for line or load.
3-Pole Standard Shield TSSF3 37.00 TSSF3 37.00
Flat Terminal 3-Pole Extended Shield TSLF3 58.00 TSLF3 58.00
Interphase Barriers
Set of 2 barriers IPBF 29.00 IPBF 29.00
Also fits plug-in and draw-out bases.
Terminal Shields
BREAKERS
CIRCUIT
Interphase Barriers
Not UL listed.
A - Consult Siemens for availability.
6/148
For JG Frame For LG Frame For MG Frame For NG Frame For PG Frame
400 A 600 A 800 A 1200 A 1600 A
Catalog List Catalog List Catalog List Catalog List Catalog List
Number Price $ Number Price $ Number Price $ Number Price $ Number Price $
FBCJ3A CSO FBCL3A CSO FBCM3A CSO FBCP3A CSO FBCP3A CSO
— — — — — — — — SSBP 1004.00
SSBPH 1227.00
100% rated applications
RTLJSR 195.00 — — — — — — — —
RTLJLR 208.00 — — — — — — — —
SRTJR3 597.00 — — — — — — — —
RTLJSF 195.00 — — — — — — — —
RTLJLF 208.00 — — — — — — — —
SRTJF3 597.00 — — — — — — — —
— — RTLLSF 224.00 RTLMSF 323.00 RTLNSF 434.00 — —
— — SRTLF3 671.00 SRTMF3 967.00 SRTNF3 1303.00 — —
TSSL3 47.50 TSSL3 47.50 TSSM3 67.00 TSSP3 91.00 TSSP3 91.00
TSLL3 68.00 TSLL3 68.00 TSLM3 97.00 TSLP3 116.00 TSLP3 116.00
IPBM 38.50 IPBM 38.50 IPBM 38.50 IPBP 83.00 IPBP 83.00
— — — — — — — — LMAP1600 968.00
— — — — — — — — MBPG1600 1211.00
— — — — — — — — MBPG1601 1211.00
6
BREAKERS
CIRCUIT
6/149
VL External Accessories
Connections
For DG Frame For FG Frame
150 A 250 A
Catalog List Catalog List
Discription Number Price $ Number Price $
Nut Keeper Plates
For ring/tongue terminal or bus bar connections.
(For metric threads on other than the JG or LG frame,
change ”TNK” to ”TMK”)
1 Nut Keeper Plate TNKD 6.10 TNKF 6.10
Kit of 3 TNKD3 19.40 TNKF3 19.40
Mechanical Lugs
Steel Wrap Around Body (Cu Wire Only)
Cable Size; (cables per phase) #8-1/0; 1-hole #4-350 kcmil; 1-hole
Single Lug TW1DG20 7.20 TW1FG350 22.00
Kit of 3 3TW1DG20 22.00 3TW1FG350 65.00
Aluminum Body (Al or Cu Wire)
Cable Size; (cables per phase) #6-3/0; 1-hole #4-350 kcmil; 1-hole
Single Lug TA1DG30 7.20 TAW1FG350 22.00
Kit of 2 — — — —
Single Lug — — — —
Kit of 2 — — — —
Kit of 3 — — — —
Kit of 3 — — — —
Copper Body (Cu Wire Only)
Cable Size; (cables per phase) #6-3/0; 1-hole #4-350 kcmil; 1-hole
Single Lug TC1DG30 33.50 TCW1FG350 34.50
Kit of 2 — — — —
6/150
For JG Frame For LG Frame For MG Frame For NG Frame For PG Frame
400 A 600 A 800 A 1200 A 1600 A
Catalog List Catalog List Catalog List Catalog List Catalog List
Number Price $ Number Price $ Number Price $ Number Price $ Number Price $
TMKJ 6.10 TNKL 9.80 TNKM 9.80 TNKP 9.80 TNKP 9.80
TMKJ3 19.40 TNKL3 29.00 TNKM3 29.00 TNKP3 29.00 TNKP3 29.00
3/0-250 kcmil; 2-hole #2-600 kcmil; 2-hole 1/0-500 kcmil, 3-hole 1/0-500 kcmil; 4-hole 1/0-750 kcmil; 6-hole
TA2JG250 29.00 — — TA3MG500 67.00 — — — —
— — 2TA2LG600LD 72.00 3TA3MG500 202.00 2TA4NG500 579.00 — —
2TA2LG600LN 72.00
3TA2JG250 87.00 3TA2LG600LD 109.00 3TA4NG500 291.00 3TA6PG750 940.00
3TA2LG600LN 109.00 3TA4NG500H 875.00
3/0-250 kcmil; 2-hole #2-600 kcmil; 2-hole 1/0-500 kcmil; 3-hole 1/0-500 kcmil; 4-hole 1/0-750 kcmil; 6-hole
TC2JG250 77.00 — — TC3MG500 134.00 — — — —
— — 2TC2LG600LD 154.00 — — — — — —
2TC2LG600LN 154.00
— — 3TC2LG600LD 231.00 — — 3TC4NG500 832.00 3TC6PG750 (future) 1342.00
3TC2LG600LN 231.00
3/0-750 kcmil; 1-hole — — — — 1/0-500 kcmil; 3-hole 300-600 kcmil; 5-hole
TC1JG750 77.00 — — — — TC3NG500 CSO TC5R600 426.00
#6-350 kcmil; 1-cable #6-350 kcmil; 2-cable 1/0-500 kcmil; 3-cable 1/0-500 kcmil; 4-cable #2-600 kcmil; 8-cable
— — — — — — — — — —
3CLJ350 449.00 6CLL350 899.00 9CLM500 (future) 1056.00 12CLN500 1393.00 24CLP600 (future) 2787.00
6
3CLJ750 449.00 3CLL750 494.00 — — — — — —
#14-#4; 12-hole — — — — — — — —
TA12JG04 88.00 — — — — — — — —
3TA12JG04 265.00 — — — — — — — —
#14-2/0; 6-hole — — — — — — — —
TA6JG20 88.00 — — — — — — — —
BREAKERS
3TA6JG20 265.00 — — — — — — — —
CIRCUIT
6/151
VL External Accessories
General
For DG Frame For FG Frame
150 A 250 A
Catalog List Catalog List
Description Number Price $ Number Price $
Handle Padlocking Device HPLF 15.80 HPLF 15.80
To padlock breaker toggle in the “OFF” position. Accepts up
to 3 padlocks with 5–8 mm shackles.
HBDL 27.00 HBDL 27.00 HBDM 57.00 HBDP 57.00 HBDP 57.00
WBMLFM 608.00 WBMLFM 608.00 WBMMFM 608.00 WBMPFM 658.00 WBMPFM 658.00
WBMLDP 603.00 WBMLDP 603.00 WBMMDP 603.00 WBMPDP 658.00 WBMPDP 658.00
CBTL 515.00 CBTL 515.00 CBTM 548.00 CBTP 582.00 CBTP 582.00
— — — — — — — — — —
CBCM36 156.00 CBCM36 156.00 CBCM36 156.00 — — — —
CBCP54 190.00 CBCP54 190.00 CBCP54 190.00 CBCP54 190.00 CBCP54 190.00
— — — — — — — — — —
MSKL4 10.90 MSKL4 10.90 MSKM4 15.80 MSKP4 29.00 MSKP4 29.00
TSCPET 15.80 TSCPET 15.80 TSCPET 15.80 TSCPET 15.80 TSCPET 15.80
TSCLTM 38.50 TSCLTM 38.50 TSCMTM 38.50 — — — —
6
BREAKERS
CIRCUIT
6/153
VL External Accessories
Ground Sensors & Electronic Accessories
For DG Frame For FG Frame
150 A 250 A
Catalog List Catalog List
Description Number Price $ Number Price $
Neutral Current Transformer (Ground Sensor, N-pole)
Neutral = 35/60A NGSD060 402.00 — —
Neutral = 100A NGSF100 402.00 NGSF100 402.00
Neutral = 150A NGSF150 402.00 NGSF150 402.00
Neutral = 250A — — NGSJ250 402.00
Neutral = 400A — — — —
Neutral = 600A — — — —
Neutral = 800A — — — —
Neutral = 1000/1200A — — — —
Neutral = 1600A — — — —
Test Kit - Portable power supply for programming, trip test, ELTPHB 3428.00 ELTPHB 3428.00
and checking CT’s plus a port for local communications of
currents flow and trip settings. (Requires two 9V batteries)
Spare Flat
Cable Universal Power Supply - 120/240Vac adapter used in lieu of UPAPELTK 537.00 UPAPELTK 537.00
9V batteries for Test Kit ELTPHB (includes necessary cables)
Power Stick
Power Supply with ZSI (for Model 576 trip units only. COMPS 2013.00 COMPS 2013.00
Includes necessary cables)
Com10 Profibus Communications Module with ZSI COMPRO 2684.00 COMPRO 2684.00
RS232 Cable for LCD trip Model 576 only
Com11 Modbus Communications Module with ZSI COMMOD 2684.00 COMMOD 2684.00
for LCD Trip Model 576 only
Cable for COM10/11 and Model 576 external COMKIT1 179.00 COMKIT1 179.00
power supply……5ft. (1.5m)
Extension cable for COMKIT1 & COMKIT2, adds 5 ft. COMEXT 134.00 COMEXT 134.00
Com10 Profibus &
6
Com11 Modbus
Spare flat cable for Test Kits or Communications Adapters COMPCA 358.00 COMPCA 358.00
Communications
Module
RS232 type cable for Test Kits or Communications Adapters COMP232 179.00 COMP232 179.00
For breakers with stored energy operator. (IP40) BZLFRHSE 224.00 BZLFRHSE 224.00
Toggle Handle
Extension
6/154
For JG Frame For LG Frame For MG Frame For NG Frame For PG Frame
400 A 600 A 800 A 1200 A 1600 A
Catalog List Catalog List Catalog List Catalog List Catalog List
Number Price $ Number Price $ Number Price $ Number Price $ Number Price $
— — — — — — — — — —
— — — — — — — — — —
— — — — — — — — — —
NGSJ250 402.00 — — — — — — — —
NGSL400 402.00 NGSL400 402.00 — — — — — —
— — NGSM600 402.00 NGSM600 402.00 — — — —
— — — — NGSN800 402.00 NGSN800 402.00 — —
— — — — — — NGSP120 402.00 NGSP120 402.00
— — — — — — — — NGSP160 402.00
EPSP18V 582.00 EPSP18V 582.00 EPSP18V 582.00 EPSP18V 582.00 EPSP18V 582.00
ELTPHB 3428.00 ELTPHB 3428.00 ELTPHB 3428.00 ELTPHB 3428.00 ELTPHB 3428.00
UPAPELTK 537.00 UPAPELTK 537.00 UPAPELTK 537.00 UPAPELTK 537.00 UPAPELTK 537.00
COMPS 2013.00 COMPS 2013.00 COMPS 2013.00 COMPS 2013.00 COMPS 2013.00
COMPRO 2684.00 COMPRO 2684.00 COMPRO 2684.00 COMPRO 2684.00 COMPRO 2684.00
COMMOD 2684.00 COMMOD 2684.00 COMMOD 2684.00 COMMOD 2684.00 COMMOD 2684.00
CSAPELTU 911.00 CSAPELTU 911.00 CSAPELTU 911.00 CSAPELTU 911.00 CSAPELTU 911.00
COMKIT2 179.00 COMKIT2 179.00 COMKIT2 179.00 COMKIT1 179.00 COMKIT1 179.00
COMEXT 134.00 COMEXT 134.00 COMEXT 134.00 COMEXT 134.00 COMEXT 134.00
COMPCA 358.00 COMPCA 358.00 COMPCA 358.00 COMPCA 358.00 COMPCA 358.00
6
COMP232 179.00 COMP232 179.00 COMP232 179.00 COMP232 179.00 COMP232 179.00
BZLL3 224.00 BZLL3 224.00 BZLM3 279.00 BZLP3 279.00 BZLP3 279.00
BREAKERS
CIRCUIT
BZLLRHSE 224.00 BZLLRHSE 224.00 BZLMRHSE 279.00 BZLPRHSE 279.00 BZLPRHSE 279.00
BZLLBDC 224.00 BZLLBDC 224.00 BZLMBDC 279.00 BZLPBDC 279.00 BZLPBDC 279.00
THEL 63.00 THEL 63.00 THEM 105.00 THEP 105.00 THEP 105.00
6/155
VL Molded Case Circuit Breakers
Accessory Locations Selection
* Except DG and FG breakers with Electronic Trip Units. Due to the location of the Magnetic Latch, the Left Pocket is not available for accessories.
6/156
VL Molded Case Circuit Breakers
Selection
Suffix for factory mounted Switch Combinations
Then add Device
If the frame is: And you need these functions: this suffix: Catalog Number
1 Alarm Switch
DG, FG, JG or LG 1 NO Alarm A1 ASKL1
1 NC Alarm
2 Aux. Switches
DG, FG, JG or LG A2 ASKL2
1 NO + 1 NC Aux. Contacts
2 Aux. + 1 Alarm Switches
1NO + 1NC Aux. and 1NO Alarm
DG, FG, JG or LG 1NO + 1NC Aux. and 1NC Alarm A3 ASKL3
2NO Aux. and 1NC Alarm
2NC Aux. and 1NO Alarm
2 Aux. + 2 Alarm Switches
1NO + 1NC Aux. and 1NO + 1NC Alarm
MG, NG or PG A3 ASKP3
2NO Aux. and 2NC Alarm
2NC Aux. and 2NO Alarm
4 Aux. Switches
MG, NG or PG A4 ASKP4
2NO + 2NC Aux.
6
Suffix for factory mounted Under Voltage Releases
Then add Device
If the frame is: And you need these functions: this suffix: Catalog Number
12V DC UA UVRLA12DC
24V DC UB UVRLB24DC
48V DC UC UVRLC48DC
60V DC UG UVRLG60DC
BREAKERS
110-127V DC UD UVRLD125DC
CIRCUIT
220-250V DC UE UVRLE250DC
DG, FG, JG or LG 110-127V AC UN UVRLN120
220-240V AC UR UVRLR240
208V AC UP UVRLP208
277V AC US UVRLS277
380-415V AC UT UVRLT415
440-480V AC UU UVRLU480
600V AC UV UVRLV600
12V DC UA UVRPA12DC
24V DC UB UVRPB24DC
48V DC UC UVRPC48DC
60V DC UG UVRPG60DC
110-127V DC UD UVRPD125DC
220-250V DC UE UVRPE250DC
MG, NG or PG 110-127V AC UN UVRPN120
220-240V AC UR UVRPR240
208V AC UP UVRPP208
277V AC US UVRPS277
380-415V AC UT UVRPT415
440-480V AC UU UVRPU480
600V AC UV UVRPV600
6/157
VL Technical Data
DG FG JG LG MG NG PG
Max rated continuous current 150 250 400 600 800 1200 1600
Rated operational voltage
NEMA V AC 600 600 600 600 600 600 600
IEC V AC 690 690 690 690 690 690 690
Rated Impulse Withstand Voltage
Main conducting paths kV 8 8 8 8 8 8 8
Auxiliary circuits kV 4 4 4 4 4 4 4
Ambient Temperature Range ºC -25 to +75 -25 to +75 -25 to +75 -25 to +75 -25 to +75 -25 to +75 -25 to +75
High Ambient Derating (thermal-mag.) 50ºC 93% 93% 93% 93% 95% 95% 95%
60ºC 86% 86% 86% 86% 86% 86% 80%
70ºC 80% 80% 80% 80% 80% 80% 74%
Operating Cycles 20,000 20,000 20,000 10,000 5,000 3,000 3,000
Max switching rate (per hour) 120 120 120 60 60 30 30
Power loss (at max. rated current)
Thermal-magnetic W 15 – 48 32 – 80 60 – 175 85 – 230 170 – 250 150 – 220 200 – 260
Electronic trip unit W 40 60 90 160 250 210 260
IEC
Time constant t = 10 ms
1 current path 2 current paths 3 current paths
in series in series
Up to 250V DC 440V DC 600V DC — — — — — — —
NEMA
Time constant t = 8 ms
2 poles switching 1 current path
250V DC Max. 30 30 30 30 42 42 42
3 poles switching 2 current paths in series
500V DC Max. 18 25 35 35 65 65 65
Accessories
Auxiliary / Alarm Switch
Current rating (1 or 2 switches) 10 10 10 10 10 10 10
Current rating (3 or 4 same switch) A 5 5 5 5 5 5 5
Shunt Trip
Pick-up voltage V 0.7 – 1.1 0.7 – 1.1 0.7 – 1.1 0.7 – 1.1 0.7 – 1.1 0.7 – 1.1 0.7 – 1.1
Power Consumption (short-time) at:
6
48 – 60 V AC VA 401 – 501 401 – 501 401 – 501 401 – 501 401 – 501 401 – 501 401 – 501
110 – 127 V AC VA 424 – 489 424 – 489 424 – 489 424 – 489 424 – 489 424 – 489 424 – 489
208 – 277 V AC VA 533 – 736 533 – 736 533 – 736 533 – 736 533 – 736 533 – 736 533 – 736
380 – 600 V AC VA 408 – 645 408 – 645 408 – 645 408 – 645 408 – 645 408 – 645 408 – 645
24 V DC W 594 594 594 594 594 594 594
48 – 60 V DC W 740 – 925 740 – 925 740 – 925 740 – 925 740 – 925 740 – 925 740 – 925
110 –127 V DC W 559 – 648 559 – 648 559 – 648 559 – 648 559 – 648 559 – 648 559 – 648
BREAKERS
CIRCUIT
220 – 250 V DC W 722 – 820 722 – 820 722 – 820 722 – 820 722 – 820 722 – 820 722 – 820
Max. Operating time ms 50 50 50 50 50 50 50
6/158
VL Technical Data
DG FG JG LG MG NG PG
Undervoltage Trip
Drop voltage (percentage) V 35% – 70% 35% – 70% 35% – 70% 35% – 70% 35% – 70% 35% – 70% 35% – 70%
Pick-up voltage (percentage) V 70% – 85% 70% – 85% 70% – 85% 70% – 85% 70% – 85% 70% – 85% 70% – 85%
Power consumption (continuous) at:
110 – 127 V AC VA 1 1 1 1 1.1 1.1 1.1
220 – 250 V AC VA 2.1 2.1 2.1 2.1 2.1 2.1 2.1
208 V AC VA 1.2 1.2 1.2 1.2 1.2 1.2 1.2
277 V AC VA 1.4 1.4 1.4 1.4 1.4 1.4 1.4
380 – 415 V AC VA 1.9 1.9 1.9 1.9 1.9 1.9 1.9
440 – 480 V AC VA 2.2 2.2 2.2 2.2 2.2 2.2 2.2
500 – 525 V AC VA 2.5 2.5 2.5 2.5 2.5 2.5 2.5
600 V AC VA 2.8 2.8 2.8 2.8 2.8 2.8 2.8
Max. opening time ms 50 50 50 50 50 50 50
Motorized Operating Mechanism
Motor with stored energy mechanism
(synchronizable) X X X X X X X
Motor Operator X X
Max. switching rate (per hour) 120 120 120 60 60 30 30
Command duration ms 20 – 50 20 – 50 20 – 50 20 – 50 20 – 50 — —
Closing time ms <100 <100 <100 <100 <100 <5,000 <5,000
Charging time s <5 <5 <5 <5 <5 <5 <5
Break time s <5 <5 <5 <5 <5 <5 <5
Power consumption VA/W <500
Inrush (A)
Control Voltages 110 – 127 V AC
220 – 250 V AC
24 V DC
48 V DC
60 V DC
Operating Range 85 – 110% of rated control voltage
6
BREAKERS
CIRCUIT
6/159
Molded Case Circuit Breakers
Unusual Operating Conditions Reference
Note: The information provided on this and the next page is intended for reference and recommendation only. Because several
variables can act on a circuit breaker’s performance at the same time, the data below is based less on controlled testing,
than on experience and engineering judgment. Contact Siemens for further information on special conditions and treatment.
High Ambient Temperatures Table 1 — Temperature Derating Data for Thermal-Magnetic Breakers
Because thermal-magnetic trip breakers Reference
are temperature sensitive and calibrated Ampere Ampere Rating at:
for a specific ambient of 40° C (104° F) Rating at 25° C 50° C 60° C
(average enclosure temperature), a 40° C (104° F) (77° F) (122° F) (140° F) Siemens Breaker Frames
higher ambient will cause the breaker to 0015 0017 0013 0011
trip at lower current than its nameplate 0020 0022 0018 0016
BQ,
rating, in other words, causing the 0025 0028 0023 0021
breaker to “derate” (see Table 1). 0030 0033 0028 0026 BL,
Similarly, the current carrying capacity 0035 0039 0030 0025 BQD,
of a circuit conductor is based upon a 0040 0044 0037 0034
CQD,
certain ambient temperature, a higher 0050 0055 0046 0042
ambient will reduce its current carrying 0060 0066 0056 0052 NGG,
capacity, causing it to “derate.” Thus, 0070 0077 0065 0060 NGB,
with a fluctuating temperature, a 0090 0099 0084 0078 DG
ED
thermal-magnetic breaker will derate 0100 0110 0094 0087
nearly parallel with its connected circuit 0125 0137 0114 0100
conductors and maintain close circuit 0150 0165 0136 0120
protection. If the application temperature 0175 0192 0159 0140 FG
exceeds 40° C (104° F) and is known, 0200 0220 0182 0160
either a breaker specially calibrated for
0225 0247 0205 0180
the higher ambient or one oversized
0250 0275 0235 0220
according to Table 1 may be selected.
0300 0330 0276 0252
In a case such as this, the circuit JG
conductors should be oversized as well. 0350 0385 0325 0301
0400 0440 0372 0340
Siemens Electronic Trip Unit Breakers 0500 0550 0468 0435 LG
are insensitive to temperature changes.
0600 0660 0564 0525
However, they do include circuitry to
0700 0770 0658 0613 MG
protect the components from
0800 0880 0754 0704
abnormally high temperatures.
0900 0990 0828 0749
Moisture — Corrosion 1000 1100 0900 0825
NG
Where the air is heavily laden with 2000 2200 1880 1650
corrosive elements, breakers made
with special corrosion-resistant
finishes may be required. 13,000 (4,000)
Altitude 12,000 (3,675)
Altitude in Feet (Meters)
6,000 (1,800)
6/160
VL Molded Case Circuit Breakers
Unusual Operating Conditions Reference
400 Hz Systems
Siemens molded case circuit breakers ambient temperature exceeds 40° C are usually the hottest terminals with a
can be applied for overcurrent protection (104° F). balanced load. A maximum temperature
on 400Hz systems, commonly used to Cable and Bus Sizing of 75° C (35° C over a maximum ambient
power computer installations, aircraft, of 40° C) would verify the particular
military and other specialty equipment. The cable and bus sizes to be utilized application. Temperature profiles taken
Below are basic guidelines. at 400Hz are not based on standard on these breakers can be correlated to
National Electric Codes tables for 60Hz ensure that the hottest points within
Circuit Breaker Derating Required application. Larger cross sections are the breaker are within the required
This table lists the maximum continuous necessary at 400Hz. All bus bars temperature limits.
current carrying capacity for Siemens specified are based upon mounting
breakers at 400Hz. Due to the increased the bars in the vertical plane to allow Factory Configuration
resistance of the copper sections maximum air flow. All bus bars are When required, molded case circuit
resulting from the skin effect produced spaced at a minimum of 0.25 in. (6 mm) breakers may be factory calibrated for
by eddy currents at these frequencies, apart. Mounting of bus bars in the 400Hz application. These breakers are
circuit breakers in many cases require horizontal plane will necessitate specially labeled for 400Hz usage and
derating. The thermal derating on these additional drafting. Edgewise orientation their nameplate current rating will
devices is based upon 100%, of the bus may change the maximum include the necessary derating factory.
three phase application in open air in a ratings indicated. If additional information The highest “Maximum Continuous
maximum of 40° C (104° F) with 48 in. is required for other connections of cable Amperes” rating at 400Hz, found in the
(1219 mm) of the specified cable or bus or bus, contact Siemens for information. table below approximates the highest
at the line and load side. Additional Application Recommendations specially calibrated 400Hz nameplate
derating of not less than 20% will be ampere rating available for a given
required if the circuit breaker is to be It is recommended that temperatures be
measured on the line and load terminals frame size. Contact Siemens for
utilized in an enclosure. Further derating ordering information on other
may be required if the enclosure or T-connectors of the center pole. These
breakers applied in 400Hz systems.
400Hz Breakers
Maximum Continuous Ampere Rating 75° C (167° F) Maximum Continuous Ampere Rating 75° C (167° F)
At 40° C (104° F) Copper At 40° C (104° F) Copper
Siemens 60HZ 400HZ Cable per Pole Siemens 60HZ 400HZ Cable per Pole
Breaker Enclosed No of Wire Breaker Enclosed No of Wire
Type Open Air Open Air After Derating Pieces Size Type Open Air Open Air After Derating Pieces Size
015 015 012 1 #14 250 210 168 1 250 kcmil
020 020 016 1 #12 300 240 192 1 350 kcmil
JG
15 15 12 1 #14 350 260 208 1 500 kcmil
20 20 16 1 #12 400 300 240 2 #2/0
25 25 20 1 #10 250 210 210 1 250 kcmil
30 30 24 1 #10 300 240 240 1 350 kcmil
JG 100% Rated
35 35 28 1 #10 350 260 260 1 500 kcmil
40 40 32 1 #8 400 300 300 2 #3/0
NGG, EG 45 43 34 1 #8 400 300 240 2 #3/0
50 48 38 1 #8 LG 500 375 300 2 250 kcmil
6
60 57 46 1 #6 600 420 336 2 350 kcmil
70 67 54 1 #4 600 430 360 2 350 kcmil
80 76 61 1 #4 MG 700 500 400 3 250 kcmil
90 86 69 1 #3 800 560 448 3 300 kcmil
100 95 76 1 #3 600 430 430 2 350 kcmil
110 105 84 1 #2 MG 100% Rated 700 500 500 3 250 kcmil
125 119 95 1 #1 800 560 560 3 300 kcmil
50 48 38 1 #8 800 560 448 3 300 kcmil
60 57 46 1 #6 900 600 480 3 350 kcmil
BREAKERS
NG
70 63 50 1 #4 1000 650 520 3 400 kcmil
CIRCUIT
80 72 58 1 #4 1200 780 624 4 350 kcmil
DG 90 80 64 1 #3 900 600 600 3 350 kcmil
100 90 72 1 #3 NG 100% Rated 1000 650 650 3 400 kcmil
110 95 75 1 #2 1200 780 780 4 350 kcmil
125 105 84 1 #1 1200 780 624 4 400 kcmil
150 125 100 1 #1/0 PG 1400 850 680 4 500 kcmil
100 90 72 1 #3 1600 960 768 5 500 kcmil
110 95 75 1 #2 1200 780 780 4 400 kcmil
125 105 84 1 #1 PG 100% Rated 1400 850 850 4 500 kcmil
150 125 100 1 #1/0 1600 960 960 5 500 kcmil
FG
175 140 112 1 #2/0
200 160 128 1 #3/0
225 180 144 1 #4/0
250 200 160 1 250 kcmil
The information provided on this page is intended for judgment. Contact Siemens for further information on Calculated after derating to compensate for the heating
reference and recommendation only. Because several special conditions and treatment. of the copper conductor, caused by the skin effect
variables can act on a circuit breaker’s performance Additional derating may be required if the ambient generated by eddy currents produced at 400/415HZ.
at the same time, the data above is based less on temperature is greater than 40°C (104°F).
controlled testing, than on experience and engineering
6/161